Search by property
Jump to navigation
Jump to search
This page provides a simple browsing interface for finding entities described by a property and a named value. Other available search interfaces include the page property search, and the ask query builder.
List of results
- 05000029/LER-1980-007, Forwards LER 80-007/03L-0 + (ML19296D421)
- 05000321/LER-1980-018, Forwards LER 80-018/03L-0 + (ML19296D423)
- ML19296D424 + (ML19296D424)
- 05000321/LER-1980-015-03, /03L-0:on 800207,during Normal Operation,Drywell Temp recorder,1T47-RG12,was Stamping Erratically & High. Caused by Microswitch in Recorder Printing Mechanism Being Out of Adjustment.Switch Readjusted + (ML19296D425)
- ML19296D426 + (ML19296D426)
- 05000029/LER-1980-007-03, /03L-0:on 800128,during Cold Shutdown Mode 5,while Performing Operational Check of Safety Injection Accumulator switches,SI-SOV-56 Failed.Caused by Dirt on Valve Internals. Valve Replaced + (ML19296D427)
- ML19296D428 + (ML19296D428)
- 05000321/LER-1980-018-03, /03L-0:on 800207,during Normal,Full Power Operation,Hydraulic Control Unit Accumulator 42-23 Received Low Pressure Alarm.Caused by Failure of Nitrogen Cartridge Valve from Wear Due to Constant Use + (ML19296D429)
- ML19296D430 + (ML19296D430)
- ML19296D431 + (ML19296D431)
- ML19296D432 + (ML19296D432)
- 05000346/LER-1980-012, Forwards LER 80-012/03L-0 + (ML19296D433)
- ML19296D434 + (ML19296D434)
- ML19296D436 + (ML19296D436)
- ML19296D438 + (ML19296D438)
- 05000219/LER-1980-004, Forwards LER 80-004/03L-0 + (ML19296D439)
- ML19296D440 + (ML19296D440)
- 05000346/LER-1980-012-03, /03L-0:on 800201,operator Noticed Loss of Control Room Position Indication for Letdown Cooler Isolation Valve MU2A.Caused by Design Deficiency.Apparently,Someone Brushed Up Against Disconnect Breaker Switch.Switch Reposition + (ML19296D441)
- ML19296D444 + (ML19296D444)
- 05000346/LER-1980-011, Forwards LER 80-011/03L-0 + (ML19296D445)
- ML19296D446 + (ML19296D446)
- 05000219/LER-1980-004-03, /03L-0:on 800125,on 800125,29 & 0213,radioactive Water Discovered Leaking from Severely Pitted Aluminum Piping of Condensate Transfer Sys.Caused by Galvanic Corrosion.Leaks Temporarily Repaired & Piping to Be Replaced + (ML19296D447)
- ML19296D448 + (ML19296D448)
- 05000324/LER-1980-010, Supplemental LER 80-010/03L-1:on 800114,during Normal Plant operation,OD-1 Determined That Max Critical Power Ratio Was Below Tech Specs for Bundle 43-28.Caused by Problems W/Low Power Range Monitor & Core Flow Input.Power Redu + (ML19296D449)
- 05000346/LER-1980-011-03, /03L-0:on 800131,during Normal Operation, Operations Personnel Received Half Trip on Steam & Feedwater Rupture Control Sys Channels 1/3.Caused by Spurious Trip from +25 Volt Dc Power Supply PS03 in Sglic Channel 1 + (ML19296D450)
- ML19296D451 + (ML19296D451)
- 05000259/LER-1980-010, Forwards LER 80-010/03L-0 + (ML19296D452)
- ML19296D453 + (ML19296D453)
- 05000312/LER-1980-007, Forwards LER 80-007/03L-0 + (ML19296D454)
- ML19296D455 + (ML19296D455)
- 05000259/LER-1980-010-03, /03L-0:on 800129,during Scheduled Refueling Outage,Found That Various Instrument Sensing Line Hangers in HPCI Pump Room Were Broken.Caused by Water Hammer While Warming HPCI Sys.Hangers Repaired + (ML19296D457)
- ML19296D458 + (ML19296D458)
- 05000312/LER-1980-007-03, /03L-0:on 800125,refueling Cycle Hydraulic Snubber Testing Program Revealed Seven Failed Units.Caused by Broken Springs,Worn Poppets & Seats & Worn O Rings.Defective Parts Replaced & Retested + (ML19296D460)
- ML19296D461 + (ML19296D461)
- ML19296D462 + (ML19296D462)
- ML19296D463 + (ML19296D463)
- 05000338/LER-1980-020, Forwards LER 80-020/03L-0 + (ML19296D465)
- ML19296D466 + (ML19296D466)
- ML19296D467 + (ML19296D467)
- 05000338/LER-1980-021, Forwards LER 80-021/03L-0 + (ML19296D468)
- ML19296D469 + (ML19296D469)
- 05000338/LER-1980-020-03, /03L-0:on 800129,during Mode 1 Operation,B Casing Cooling Subsystem Rendered Inoperable.Caused by Disconnection of LT-RS-103B Level Transmitter During Design Changes.Level Transmitter Reinstalled + (ML19296D470)
- ML19296D471 + (ML19296D471)
- ML19296D472 + (ML19296D472)
- 05000338/LER-1980-021-03, /03L-0:on 800202,w/unit in Mode 1,emergency Diesel Generator 1H Tripped on High Crankcase Pressure During Manual Start to Verify Diesel Operability.Cause Unknown. Generator Restarted.Vendor Investigating + (ML19296D473)
- ML19296D474 + (ML19296D474)
- ML19296D475 + (ML19296D475)
- ML19296D477 + (ML19296D477)
- ML19296D478 + (ML19296D478)
- ML19296D479 + (ML19296D479)
- ML19296D481 + (ML19296D481)