Search by property
Jump to navigation
Jump to search
This page provides a simple browsing interface for finding entities described by a property and a named value. Other available search interfaces include the page property search, and the ask query builder.
List of results
- ML18024B226 + (ML18024B226)
- 05000296/LER-1979-024-03, /03L-0:on 701208,following Return to Svc After Refueling,Excessive Local Leakage Detected at Southeast Drywell Equipment Hatch Door.Caused by Unevenly Tightened Bolts.Bolts Retightened + (ML18024B227)
- IR 05000296/1979021 + (ML18024B229)
- ML18024B229 + (ML18024B229)
- ML18024B233 + (ML18024B233)
- ML18024B234 + (ML18024B234)
- ML18024B236 + (ML18024B236)
- 05000296/LER-1979-025, Forwards LER 79-025/03L-0 + (ML18024B237)
- ML18024B238 + (ML18024B238)
- 05000296/LER-1979-025-03, /03L-0:on 791212,following Return to Svc After Refueling Outage,Reactor Core Isolation Cooling Failed to Reach Rated Flow.Caused by Short in Reactor Core Isolation Cooling Egm Box.Ground Wire Causing Short Removed + (ML18024B239)
- ML18024B242 + (ML18024B242)
- IR 05000259/1979033 + (ML18024B244)
- ML18024B248 + (ML18024B248)
- IR 05000259/1979035 + (ML18024B250)
- ML18024B251 + (ML18024B251)
- ML18024B254 + (ML18024B254)
- 05000296/LER-1979-027, Forwards LER 79-027/03L-0 + (ML18024B255)
- ML18024B257 + (ML18024B257)
- 05000296/LER-1979-027-03, /03L-0:on 791216,while Performing SI 4.2.C.1A, Average Power Range Monitor B Scram Setting Found to Be Greater than 120% for Simulated Flow of 125%.Caused by Instrument Drift.Trip Channels Adjusted + (ML18024B258)
- 05000296/LER-1979-028, Forwards LER 79-028/03L-0 + (ML18024B259)
- ML18024B260 + (ML18024B260)
- OIG-03-A-15, Status of Recommendations: Audit of NRCs Regulatory Oversight of Special Nuclear Materials, Dated January 24, 2017 + (ML18024B261)
- 05000296/LER-1979-028-03, /03L-0:on 791218,while Performing SI,PS-3-74A & B & PS-68-95 (Reactor Pressure) Did Not Actuate at Correct Setpont.Caused by Drifting of Barton Model 288 & Barksdale B2T-M12SS.Switches Readjusted + (ML18024B262)
- ML18024B263 + (ML18024B263)
- ML18024B265 + (ML18024B265)
- ML18024B266 + (ML18024B266)
- ML18024B267 + (ML18024B267)
- 05000260/LER-1980-002, Forwards LER 80-002/03L-0 + (ML18024B270)
- ML18024B271 + (ML18024B271)
- 05000260/LER-1980-002-03, /03L-0:on 791222,w/unit in Cold Shutdown,Found That Flow Control Valve 2-FCV-68-79 on Recirculation Sys Would Not Operate.Caused by Motor Pinion Gear Being Installed Backwards.Installment Procedures Will Be Revised + (ML18024B272)
- ML18024B273 + (ML18024B273)
- 05000260/LER-1979-026, Forwards LER 79-026/03L-0 + (ML18024B276)
- ML18024B277 + (ML18024B277)
- 05000260/LER-1979-026-03, /03L-0:on 791223,during Startup & Followup PCIS mods,drywell-to-torus Differential Pressure Indicator Not Operating.Caused by Blown Fuse.Fuse Replaced.No Recurrence Control Action Planned + (ML18024B278)
- ML18024B284 + (ML18024B284)
- 05000260/LER-1980-001, Forwards LER 80-001/03L-0 + (ML18024B285)
- ML18024B287 + (ML18024B287)
- 05000260/LER-1980-001-03, /03L-0:on 791229,during Normal Operation,While Performing SI 4.2.B-1,switch 1 on Reactor Water Level LITS-3-58D Failed to Operate.Caused by Rendom Failure of Switch in Yarway Model 4418CE.Switch Replaced + (ML18024B288)
- 05000296/LER-1980-001, Forwards LER 80-001/03L-0 + (ML18024B289)
- ML18024B290 + (ML18024B290)
- 05000296/LER-1980-001-03, /03L-0:on 791230,w/Unit 3 in Shutdown,Bus Tie Board Was de-energized for Startup.Caused by Feeder Cable Failure.Work in Progress to Bypass Bad Cable Sections + (ML18024B291)
- ML18024B292 + (ML18024B292)
- IR 05000259/1979045 + (ML18024B294)
- IR 05000296/1979019 + (ML18024B295)
- ML18024B295 + (ML18024B295)
- ML18024B296 + (ML18024B296)
- ML18024B297 + (ML18024B297)
- ML18024B299 + (ML18024B299)
- ML18024B301 + (ML18024B301)
- ML18024B302 + (ML18024B302)
- ML18024B303 + (ML18024B303)