Text
CALLAWAY PLANT 2.0-i CHAPTER TABLE OF CONTENTS CHAPTER 2.0 SAFETY LIMITS (SLs)
Section Page 2.1 SLs........................................................................................................... 2.0-1 2.2 SL Violations............................................................................................ 2.0-1
CALLAWAY PLANT 2.0-1 Amendment 235 l SLs 2.0 2.0 SAFETY LIMITS (SLs) 2.1 SLs 2.1.1 Reactor Core SLs In MODES 1 and 2, the combination of THERMAL POWER, Reactor Coolant System (RCS) highest loop average temperature, and pressurizer pressure shall not exceed the limits specified in the COLR; and the following SLs shall not be exceeded:
2.1.1.1 For Westinghouse fuel, the departure from nucleate boiling ratio (DNBR) shall be maintained 1.17 for the WRB-2 DNB correlation.
2.1.1.2 For Westinghouse fuel, the peak fuel centerline temperature shall be maintained < 5080ºF, decreasing by 58ºF per 10,000 MWd/MTU of burnup.
2.1.1.3 For Framatome GAIA fuel, the DNBR shall be maintained 1.12 for the ORFEO-GAIA DNB correlation.
2.1.1.4 For Framatome GAIA fuel, the peak fuel centerline temperature shall be maintained < 4901ºF, decreasing linearly by 13.7ºF per 10,000 MWd/MTU of burnup.
2.1.2 RCS Pressure SL In MODES 1, 2, 3, 4, and 5, the RCS pressure shall be maintained 2735 psig.
2.2 SL Violations 2.2.1 If SL 2.1.1 is violated, restore compliance and be in MODE 3 within 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br />.
2.2.2 If SL 2.1.2 is violated:
2.2.2.1 In MODE 1 or 2, restore compliance and be in MODE 3 within 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br />.
2.2.2.2 In MODE 3, 4, or 5, restore compliance within 5 minutes.