March 4, 2022 Mr. Shawn K. Gibby Vice President Nuclear Engineering Duke Energy Corporation 526 South Church Street, EC-07H Charlotte, NC 28202
SUBJECT:
CATAWBA NUCLEAR STATION, UNITS 1 AND 2; MCGUIRE NUCLEAR STATION, UNITS 1 AND 2; AND SHEARON HARRIS NUCLEAR POWER PLANT, UNIT 1 - ISSUANCE OF AMENDMENTS TO ADOPT TSTF-577, REVISION 1, REVISED FREQUENCIES FOR STEAM GENERATOR TUBE INSPECTIONS (EPID L-2021-LLA-0161)
Dear Mr. Gibby:
The U.S. Nuclear Regulatory Commission (NRC) has issued the following enclosed Amendment Nos. 311 and 307 to Renewed Facility Operating License Nos. NPF-35 and NPF-52 for the Catawba Nuclear Station, Units 1 and 2, respectively; Amendment Nos. 321 and 300 to Renewed Facility Operating License Nos. NPF-9 and NPF-17 for the McGuire Nuclear Station, Units 1 and 2, respectively; and Amendment No. 191 to Renewed Facility Operating License No. NPF-63 for the Shearon Harris Nuclear Power Plant, Unit 1.
The amendments revise the technical specifications (TSs) in response to the Duke Energy application dated September 16, 2021. The amendments revise the TSs for each of these facilities based on Technical Specifications Task Force (TSTF) Traveler TSTF-577, Revision 1, Revised Frequencies for Steam Generator Tube Inspections.
A copy of the NRC staffs Safety Evaluation is also enclosed. The Notice of Issuance will be included in the Commissions Federal Register notice.
If you have any questions, please contact me at (301) 415-8480 or by e-mail at Andrew.Hon@nrc.gov.
Sincerely,
/RA/
Andrew Hon, Project Manager Plant Licensing Branch II-2 Division of Operating Reactor Licensing Office of Nuclear Reactor Regulation Docket Nos.
50-413, 50-414, 50-369, 50-370, and 50-400
Enclosures:
- 1.
Amendment No. 311 to NPF-35
- 2.
Amendment No. 307 to NPF-52
- 3.
Amendment No. 321 to NPF-9
- 4.
Amendment No. 300 to NPF-17
- 5.
Amendment No. 191 to NPF-63
- 6.
Safety Evaluations, Notices and Environmental Findings cc: Mr. Robert T. Simril Site Vice President Catawba Nuclear Station Duke Energy Carolinas, LLC 4800 Concord Road York, SC 29745 Mr. Thomas Ray Site Vice President McGuire Nuclear Station Duke Energy Carolinas, LLC 12700 Hagers Ferry Road Huntersville, NC 28078-8985 Ms. Tanya Hamilton Site Vice President Duke Energy Progress, LLC Shearon Harris Nuclear Power Plant, Unit 1 5413 Shearon Harris Road, M/C HNP01 New Hill, NC 27562-0165 Mr. Ernest J. Kapopoulos, Jr.
Site Vice President H. B. Robinson Steam Electric Plant Duke Energy Progress, LLC 3581 West Entrance Road, RNPA01 Hartsville, SC 29550 cc: Listserv
DUKE ENERGY CAROLINAS, LLC DOCKET NO. 50-413 CATAWBA NUCLEAR STATION, UNIT 1 AMENDMENT TO RENEWED FACILITY OPERATING LICENSE Amendment No. 311 Renewed License No. NPF-35
- 1.
The Nuclear Regulatory Commission (the Commission) has found that:
A.
The application for amendment to the Catawba Nuclear Station, Unit 1 (the facility) Renewed Facility Operating License No. NPF-35 filed by the Duke Energy Carolinas, LLC (licensee), dated September 16, 2021, with the standards and requirements of the Atomic Energy Act of 1954, as amended (the Act), and the Commissions rules and regulations as set forth in 10 CFR Chapter I; B.
The facility will operate in conformity with the application, the provisions of the Act, and the rules and regulations of the Commission; C.
There is reasonable assurance (i) that the activities authorized by this amendment can be conducted without endangering the health and safety of the public, and (ii) that such activities will be conducted in compliance with the Commissions regulations set forth in 10 CFR Chapter I; D.
The issuance of this amendment will not be inimical to the common defense and security or to the health and safety of the public; and E.
The issuance of this amendment is in accordance with 10 CFR Part 51 of the Commissions regulations and all applicable requirements have been satisfied.
- 2.
Accordingly, the license is amended by changes to the Technical Specifications, as indicated in the attachment to this license amendment, and Paragraph 2.C.(2) of Renewed Facility Operating License No. NPF-35 is hereby amended to read as follows:
(2)
Technical Specifications The Technical Specifications contained in Appendix A, as revised through Amendment No. 311 which are attached hereto, are hereby incorporated into this renewed operating license. Duke Energy Carolinas, LLC shall operate the facility in accordance with the Technical Specifications.
- 3.
This license amendment is effective as of its date of issuance and shall be implemented within 120 days of issuance.
FOR THE NUCLEAR REGULATORY COMMISSION David J. Wrona, Chief Plant Licensing Branch II-2 Division of Operating Reactor Licensing Office of Nuclear Reactor Regulation
Attachment:
Changes to Renewed Facility Operating License No. NPF-35 and Technical Specifications Date of Issuance: March 4, 2022 David J.
Wrona Digitally signed by David J. Wrona Date: 2022.03.04 16:02:19 -05'00'
DUKE ENERGY CAROLINAS, LLC DOCKET NO. 50-414 CATAWBA NUCLEAR STATION, UNIT 2 AMENDMENT TO RENEWED FACILITY OPERATING LICENSE Amendment No. 307 Renewed License No. NPF-52
- 1.
The Nuclear Regulatory Commission (the Commission) has found that:
A.
The application for amendment to the Catawba Nuclear Station, Unit 2 (the facility) Renewed Facility Operating License No. NPF-52 filed by the Duke Energy Carolinas, LLC (licensee), dated September 16, 2021, complies with the standards and requirements of the Atomic Energy Act of 1954, as amended (the Act), and the Commissions rules and regulations as set forth in 10 CFR Chapter I; B.
The facility will operate in conformity with the application, the provisions of the Act, and the rules and regulations of the Commission; C.
There is reasonable assurance (i) that the activities authorized by this amendment can be conducted without endangering the health and safety of the public, and (ii) that such activities will be conducted in compliance with the Commissions regulations set forth in 10 CFR Chapter I; D.
The issuance of this amendment will not be inimical to the common defense and security or to the health and safety of the public; and E.
The issuance of this amendment is in accordance with 10 CFR Part 51 of the Commissions regulations and all applicable requirements have been satisfied.
- 2.
Accordingly, the license is amended by changes to the Technical Specifications, as indicated in the attachment to this license amendment, and Paragraph 2.C.(2) of Renewed Facility Operating License No. NPF-52 is hereby amended to read as follows:
(2)
Technical Specifications The Technical Specifications contained in Appendix A, as revised through Amendment No. 307, which are attached hereto, are hereby incorporated into this renewed operating license. Duke Energy Carolinas, LLC shall operate the facility in accordance with the Technical Specifications.
- 3.
This license amendment is effective as of its date of issuance and shall be implemented within 120 days of issuance.
FOR THE NUCLEAR REGULATORY COMMISSION David J. Wrona, Chief Plant Licensing Branch II-2 Division of Operating Reactor Licensing Office of Nuclear Reactor Regulation
Attachment:
Changes to Renewed Facility Operating License No. NPF-52 and the Technical Specifications Date of Issuance: March 4, 2022 David J.
Wrona Digitally signed by David J. Wrona Date: 2022.03.04 16:02:43 -05'00'
ATTACHMENT TO CATAWBA NUCLEAR STATION, UNITS 1 AND 2 LICENSE AMENDMENT NO. 311 RENEWED FACILITY OPERATING LICENSE NO. NPF-35 DOCKET NO. 50-413 AND LICENSE AMENDMENT NO. 307 RENEWED FACILITY OPERATING LICENSE NO. NPF-52 DOCKET NO. 50-414 Replace the following pages of the Renewed Facility Operating Licenses and the Appendix A Technical Specifications with the attached revised pages. The revised pages are identified by amendment number and contain marginal lines indicating the areas of change.
Remove Insert License License NPF-35, page 4 NPF-35, page 4 NPF-52, page 4 NPF-52, page 4 Technical Specifications Technical Specifications 5.5-6 5.5-6 5.5-8 5.5-8 5.5-9 5.5-9 5.5-10 5.5-10 5.5-11 5.5-11 5.6-6 5.6-6 5.6.7
5HQHZHG/LFHQVH1R13)
$PHQGPHQW1R
7(&+1,&$/63(&,),&$7,216 7KH7HFKQLFDO6SHFLILFDWLRQVFRQWDLQHGLQ$SSHQGL[$DVUHYLVHGWKURXJK
$PHQGPHQW1RZKLFKDUHDWWDFKHGKHUHWRDUHKHUHE\\LQFRUSRUDWHGLQWR WKLVUHQHZHGRSHUDWLQJOLFHQVH'XNH(QHUJ\\&DUROLQDV//&VKDOORSHUDWHWKH
IDFLOLW\\LQDFFRUGDQFHZLWKWKH7HFKQLFDO6SHFLILFDWLRQV
8SGDWHG)LQDO6DIHW\\$QDO\\VLV5HSRUW 7KH8SGDWHG)LQDO6DIHW\\$QDO\\VLV5HSRUWVXSSOHPHQWVXEPLWWHGSXUVXDQWWR
&)5GDVUHYLVHGRQ'HFHPEHUGHVFULEHVFHUWDLQIXWXUH
DFWLYLWLHVWREHFRPSOHWHGEHIRUHWKHSHULRGRIH[WHQGHGRSHUDWLRQ'XNHVKDOO
FRPSOHWHWKHVHDFWLYLWLHVQRODWHUWKDQ'HFHPEHUDQGVKDOOQRWLI\\WKH15&
LQZULWLQJZKHQLPSOHPHQWDWLRQRIWKHVHDFWLYLWLHVLVFRPSOHWHDQGFDQEHYHULILHGE\\
15&LQVSHFWLRQ
7KH8SGDWHG)LQDO6DIHW\\$QDO\\VLV5HSRUWVXSSOHPHQWDVUHYLVHGRQ
'HFHPEHUGHVFULEHGDERYHVKDOOEHLQFOXGHGLQWKHQH[WVFKHGXOHGXSGDWH
WRWKH8SGDWHG)LQDO6DIHW\\$QDO\\VLV5HSRUWUHTXLUHGE\\&)5HIROORZLQJ
LVVXDQFHRIWKLVUHQHZHGRSHUDWLQJOLFHQVH8QWLOWKDWXSGDWHLVFRPSOHWH'XNHPD\\
PDNHFKDQJHVWRWKHSURJUDPVGHVFULEHGLQVXFKVXSSOHPHQWZLWKRXWSULRU
&RPPLVVLRQDSSURYDOSURYLGHGWKDW'XNHHYDOXDWHVHDFKVXFKFKDQJHSXUVXDQWWRWKH
FULWHULDVHWIRUWKLQ&)5DQGRWKHUZLVHFRPSOLHVZLWKWKHUHTXLUHPHQWVLQWKDW
VHFWLRQ
$QWLWUXVW&RQGLWLRQV
'XNH(QHUJ\\&DUROLQDV//&VKDOOFRPSO\\ZLWKWKHDQWLWUXVWFRQGLWLRQVGHOLQHDWHGLQ
$SSHQGL[&WRWKLVUHQHZHGRSHUDWLQJOLFHQVH
)LUH3URWHFWLRQ3URJUDP
'XNH(QHUJ\\&DUROLQDV//&VKDOOLPSOHPHQWDQGPDLQWDLQLQHIIHFWDOOSURYLVLRQVRI
WKHDSSURYHGILUHSURWHFWLRQSURJUDPWKDWFRPSOLHVZLWK&)5DDQG
&)5FDVVSHFLILHGLQWKHOLFHQVHHDPHQGPHQWUHTXHVWGDWHG
6HSWHPEHUDVVXSSOHPHQWHGE\\OHWWHUVGDWHG-DQXDU\\
-DQXDU\\)HEUXDU\\0DUFK$SULO
-XO\\$XJXVW6HSWHPEHU'HFHPEHU
-DQXDU\\0DUFK-XQH$XJXVW
6HSWHPEHUDQG-DQXDU\\DVDSSURYHGLQWKH6(GDWHG
)HEUXDU\\([FHSWZKHUH15&DSSURYDOIRUFKDQJHVRUGHYLDWLRQVLV
UHTXLUHGE\\&)5FDQGSURYLGHGQRRWKHUUHJXODWLRQWHFKQLFDO
VSHFLILFDWLRQOLFHQVHFRQGLWLRQRUUHTXLUHPHQWZRXOGUHTXLUHSULRU15&DSSURYDO
WKHOLFHQVHHPD\\PDNHFKDQJHVWRWKHILUHSURWHFWLRQSURJUDPZLWKRXWSULRU
DSSURYDORIWKH&RPPLVVLRQLIWKRVHFKDQJHVVDWLVI\\WKHSURYLVLRQVVHWIRUWKLQ
&)5DDQG&)5FWKHFKDQJHGRHVQRWUHTXLUHDFKDQJHWRD
WHFKQLFDOVSHFLILFDWLRQRUDOLFHQVHFRQGLWLRQDQGWKHFULWHULDOLVWHGEHORZDUH
VDWLVILHG
5HQHZHG/LFHQVH1R13)
$PHQGPHQW1R
7(&+1,&$/63(&,),&$7,216 7KH7HFKQLFDO6SHFLILFDWLRQVFRQWDLQHGLQ$SSHQGL[$DVUHYLVHGWKURXJK
$PHQGPHQW1RZKLFKDUHDWWDFKHGKHUHWRDUHKHUHE\\LQFRUSRUDWHGLQWRWKLV
UHQHZHGRSHUDWLQJOLFHQVH'XNH(QHUJ\\&DUROLQDV//&VKDOORSHUDWHWKHIDFLOLW\\
LQDFFRUGDQFHZLWKWKH7HFKQLFDO6SHFLILFDWLRQV
8SGDWHG)LQDO6DIHW\\$QDO\\VLV5HSRUW 7KH8SGDWHG)LQDO6DIHW\\$QDO\\VLV5HSRUWVXSSOHPHQWVXEPLWWHGSXUVXDQWWR
&)5GDVUHYLVHGRQ'HFHPEHUGHVFULEHVFHUWDLQIXWXUH
DFWLYLWLHVWREHFRPSOHWHGEHIRUHWKHSHULRGRIH[WHQGHGRSHUDWLRQ'XNHVKDOO
FRPSOHWHWKHVHDFWLYLWLHVQRODWHUWKDQ'HFHPEHUDQGVKDOOQRWLI\\WKH15&
LQZULWLQJZKHQLPSOHPHQWDWLRQRIWKHVHDFWLYLWLHVLVFRPSOHWHDQGFDQEHYHULILHG
E\\15&LQVSHFWLRQ
7KH8SGDWHG)LQDO6DIHW\\$QDO\\VLV5HSRUWVXSSOHPHQWDVUHYLVHGRQ
'HFHPEHUGHVFULEHGDERYHVKDOOEHLQFOXGHGLQWKHQH[WVFKHGXOHGXSGDWH
WRWKH8SGDWHG)LQDO6DIHW\\$QDO\\VLV5HSRUWUHTXLUHGE\\&)5HIROORZLQJ
LVVXDQFHRIWKLVUHQHZHGRSHUDWLQJOLFHQVH8QWLOWKDWXSGDWHLVFRPSOHWH'XNHPD\\
PDNHFKDQJHVWRWKHSURJUDPVGHVFULEHGLQVXFKVXSSOHPHQWZLWKRXWSULRU
&RPPLVVLRQDSSURYDOSURYLGHGWKDW'XNHHYDOXDWHVHDFKVXFKFKDQJHSXUVXDQWWR
WKHFULWHULDVHWIRUWKLQ&)5DQGRWKHUZLVHFRPSOLHVZLWKWKHUHTXLUHPHQWVLQ
WKDWVHFWLRQ
$QWLWUXVW&RQGLWLRQV
'XNH(QHUJ\\&DUROLQDV//&VKDOOFRPSO\\ZLWKWKHDQWLWUXVWFRQGLWLRQVGHOLQHDWHGLQ
$SSHQGL[&WRWKLVUHQHZHGRSHUDWLQJOLFHQVH
)LUH3URWHFWLRQ3URJUDP
'XNH(QHUJ\\&DUROLQDV//&VKDOOLPSOHPHQWDQGPDLQWDLQLQHIIHFWDOOSURYLVLRQV
RIWKHDSSURYHGILUHSURWHFWLRQSURJUDPWKDWFRPSOLHVZLWK&)5DDQG
&)5FDVVSHFLILHGLQWKHOLFHQVHHDPHQGPHQWUHTXHVWGDWHG
6HSWHPEHUDVVXSSOHPHQWHGE\\OHWWHUVGDWHG-DQXDU\\
-DQXDU\\)HEUXDU\\0DUFK$SULO-XO\\
$XJXVW6HSWHPEHU'HFHPEHU-DQXDU\\
0DUFK-XQH$XJXVW6HSWHPEHUDQG
-DQXDU\\DVDSSURYHGLQWKH6(GDWHG)HEUXDU\\([FHSWZKHUH
15&DSSURYDOIRUFKDQJHVRUGHYLDWLRQVLVUHTXLUHGE\\&)5FDQG
SURYLGHGQRRWKHUUHJXODWLRQWHFKQLFDOVSHFLILFDWLRQOLFHQVHFRQGLWLRQRU
UHTXLUHPHQWZRXOGUHTXLUHSULRU15&DSSURYDOWKHOLFHQVHHPD\\PDNHFKDQJHVWR
WKHILUHSURWHFWLRQSURJUDPZLWKRXWSULRUDSSURYDORIWKH&RPPLVVLRQLIWKRVH
FKDQJHVVDWLVI\\WKHSURYLVLRQVVHWIRUWKLQ&)5DDQG&)5F
WKHFKDQJHGRHVQRWUHTXLUHDFKDQJHWRDWHFKQLFDOVSHFLILFDWLRQRUDOLFHQVH
FRQGLWLRQDQGWKHFULWHULDOLVWHGEHORZDUHVDWLVILHG
Programs and Manuals 5.5 Catawba Units 1 and 2 5.5-6 Amendment Nos.
5.5 Programs and Manuals (continued) 5.5.8 Inservice Testing Program (Deleted)
Note: See Section 1.1 for the definition of INSERVICE TESTING PROGRAM.
5.5.9 Steam Generator (SG) Program An SG Program shall be established and implemented to ensure that SG tube integrity is maintained. In addition, the SG Program shall include the following:
a.
Provisions for condition monitoring assessments. Condition monitoring assessment means an evaluation of the "as found" condition of the tubing with respect to the performance criteria for structural integrity and accident induced leakage. The "as found" condition refers to the (continued)
Programs and Manuals 5.5 Catawba Units 1 and 2 5.5-8 Amendment Nos.
5.5 Programs and Manuals 5.5.9 Steam Generator (SG) Program (continued)
The following SG tube alternate plugging criteria shall be applied as an alternative to the 40% depth based criteria:
1.
For Unit 2 only, tubes with service-induced flaws located greater than 14.01 inches below the top of the tubesheet do not require plugging. Tubes with service-induced flaws located in the portion of the tube from the top of the tubesheet to 14.01 inches below the top of the tubesheet shall be plugged upon detection.
d.
Provisions for SG tube inspections. Periodic SG tube inspections shall be performed. For Unit 1, the number and portions of the tubes inspected and method of inspection shall be performed with the objective of detecting flaws of any type (for example, volumetric flaws, axial and circumferential cracks) that may be present along the length of the tube, from the tube-to-tubesheet weld at the tube inlet to the tube-to-tubesheet weld at the tube outlet, and that may satisfy the applicable tube plugging criteria. The tube-to-tubesheet weld is not part of the tube. For Unit 2, the number and portions of the tubes inspected and method of inspection shall be performed with the objective of detecting flaws of any type (for example, volumetric flaws, axial and circumferential cracks) that may be present along the length of the tube, from the tube-to-tubesheet weld at the tube inlet to the tube-to-tubesheet weld at the tube outlet except for any portions of the tube that are exempt from inspection by alternate repair criteria, and that may satisfy the applicable tube plugging criteria.
In addition to meeting requirements d.1, d.2, d.3, and d.4 below, the inspection scope, inspection methods, and inspection intervals shall be such as to ensure that SG tube integrity is maintained until the next SG inspection. A degradation assessment shall be performed to determine the type and location of flaws to which the tubes may be susceptible and, based on this assessment, to determine which inspection methods need to be employed and at what locations.
(continued)
Programs and Manuals 5.5 Catawba Units 1 and 2 5.5-9 Amendment Nos. XXX/
YYY 5.5 Programs and Manuals 5.5.9 Steam Generator (SG) Program (continued) 1.
Inspect 100% of the tubes in each SG during the first refueling outage following SG installation.
2.
For Unit 1, after the first refueling outage following SG installation, inspect 100% of the tubes in each SG at least every 96 effective full power months, which defines the inspection period.
3.
For Unit 2, after the first refueling outage following SG installation, inspect 100% of the tubes in each SG at least every 54 effective full power months, which defines the inspection period. If none of the SG tubes have ever experienced cracking other than in regions that are exempt from inspection by alternate repair criteria and the SG inspection was performed with enhanced probes, the inspection period may be extended to 72 effective full power months. Enhanced probes have a capability to detect flaws of any type equivalent to or better than array probe technology. The enhanced probes shall be used from the tube-to-tubesheet weld at the tube inlet to the tube-to-tubesheet weld at the tube outlet except any portions of the tube that are exempt from inspection by alternate repair criteria. If there are regions where enhanced probes cannot be used, the tube inspection techniques shall be capable of detecting all forms of existing and potential degradation in that region.
4.
For Unit 1, if crack indications are found in any SG tube, then the next inspection for each affected and potentially affected SG for the degradation mechanism that caused the crack indication shall be at the next refueling outage. For Unit 2, if crack indications are found in any SG tube excluding any region that is exempt from inspection by alternate repair criteria, then the next inspection for each affected and potentially affected SG for the degradation mechanism that caused the crack indication shall be at the next refueling outage, but may be deferred to the following refueling outage if the 100% inspection of all SGs was performed with enhanced probes as described in paragraph d.3. If definitive information, such as from examination of a pulled tube, diagnostic non-destructive testing, or engineering evaluation indicates that a crack-like indication is not associated with crack(s), then the indication need not be treated as a crack.
e.
Provisions for monitoring operational primary to secondary LEAKAGE.
(continued)
Programs and Manuals 5.5 Catawba Units 1 and 2 5.5-10 Amendment Nos.
Page 5.5-10 has been deleted by Amendment Nos. 311/307
Programs and Manuals 5.5 Catawba Units 1 and 2 5.5-11 Amendment Nos.
Page 5.5-11 has been deleted by Amendment Nos. 311/307
Reporting Requirements 5.6 Catawba Units 1 and 2 5.6-6
$PHQGPHQW1RVXXX/YYY 5.6 Reporting Requirements (continued) 5.6.8 Steam Generator (SG) Tube Inspection Report A report shall be submitted within 180 days after the initial entry into MODE 4 following completion of the inspection. The report shall include:
a.
The scope of inspections performed on each SG; b.
The nondestructive examination techniques utilized for tubes with increased degradation susceptibility; c.
For each degradation mechanism found:
- 1. The nondestructive examination techniques utilized;
- 2. The location, orientation (if linear), measured size (if available), and voltage response for each indication. For tube wear at support structures less than 20 percent through-wall, only the total number of indications needs to be reported;
- 3. A description of the condition monitoring assessment and results, including the margin to the tube integrity performance criteria and comparison with the margin predicted to exist at the inspection by the previous forward-looking tube integrity assessment; and
- 4. The number of tubes plugged during the inspection outage.
d.
An analysis summary of the tube integrity conditions predicted to exist at the next scheduled inspection (the forward-looking tube integrity assessment) relative to the applicable performance criteria, including the analysis methodology, inputs, and results; e.
The number and percentage of tubes plugged to date, and the effective plugging percentage in each SG; f.
The results of any SG secondary side inspections; g.
For Unit 2, the primary to secondary LEAKAGE rate observed in each SG (if it is not practical to assign leakage to an individual SG, the entire primary to secondary LEAKAGE should be conservatively assumed to be from one SG) during the cycle preceding the inspection which is the subject of the report; (continued)
Reporting Requirements 5.6 Catawba Units 1 and 2 5.6-7 Amendment Nos.
5.6 Reporting Requirements 5.6.8 Steam Generator (SG) Tube Inspection Report (continued) h.
For Unit 2, the calculated accident leakage rate from the portion of the tubes below 14.01 inches from the top of the tubesheet for the most limiting accident in the most limiting SG. In addition, if the calculated accident leakage rate from the most limiting accident is less than 3.27 times the maximum primary to secondary LEAKAGE rate, the report shall describe how it was determined; and i.
For Unit 2, the results of monitoring for tube axial displacement (slippage). If slippage is discovered, the implications of the discovery and corrective action shall be provided.
DUKE ENERGY CAROLINAS, LLC DOCKET NO. 50-369 MCGUIRE NUCLEAR STATION, UNIT 1 AMENDMENT TO RENEWED FACILITY OPERATING LICENSE Amendment No. 321 Renewed License No. NPF-9
- 1.
The Nuclear Regulatory Commission (the Commission) has found that:
A.
The application for amendment to the McGuire Nuclear Station, Unit 1 (the facility), Renewed Facility Operating License No. NPF-9, filed by the Duke Energy Carolinas, LLC (licensee), dated September 16, 2021, complies with the standards and requirements of the Atomic Energy Act of 1954, as amended (the Act), and the Commissions rules and regulations as set forth in 10 CFR Chapter I; B.
The facility will operate in conformity with the application, the provisions of the Act, and the rules and regulations of the Commission; C.
There is reasonable assurance (i) that the activities authorized by this amendment can be conducted without endangering the health and safety of the public, and (ii) that such activities will be conducted in compliance with the Commissions regulations set forth in 10 CFR Chapter I; D.
The issuance of this amendment will not be inimical to the common defense and security or to the health and safety of the public; and E.
The issuance of this amendment is in accordance with 10 CFR Part 51 of the Commissions regulations and all applicable requirements have been satisfied.
- 2.
Accordingly, the license is amended by changes to the Technical Specifications, as indicated in the attachment to this license amendment, and Paragraph 2.C.(2) of Renewed Facility Operating License No. NPF-9 is hereby amended to read as follows:
(2)
Technical Specifications The Technical Specifications contained in Appendix A, as revised through Amendment No. 321, are hereby incorporated into this renewed operating license. The licensee shall operate the facility in accordance with the Technical Specifications.
- 3.
This license amendment is effective as of its date of issuance and shall be implemented within 120 days of issuance.
FOR THE NUCLEAR REGULATORY COMMISSION David J. Wrona, Chief Plant Licensing Branch II-2 Division of Operating Reactor Licensing Office of Nuclear Reactor Regulation
Attachment:
Changes to Renewed Facility Operating License No. NPF-9 and the Technical Specifications Date of Issuance: March 4, 2022 David J.
Wrona Digitally signed by David J. Wrona Date: 2022.03.04 16:03:30 -05'00'
DUKE ENERGY CAROLINAS, LLC DOCKET NO. 50-370 MCGUIRE NUCLEAR STATION, UNIT 2 AMENDMENT TO RENEWED FACILITY OPERATING LICENSE Amendment No. 300 Renewed License No. NPF-17
- 1.
The Nuclear Regulatory Commission (the Commission) has found that:
A.
The application for amendment to the McGuire Nuclear Station, Unit 2 (the facility), Renewed Facility Operating License No. NPF-17, filed by the Duke Energy Carolinas, LLC (the licensee), dated September 16, 2021, complies with the standards and requirements of the Atomic Energy Act of 1954, as amended (the Act), and the Commissions rules and regulations as set forth in 10 CFR Chapter I; B.
The facility will operate in conformity with the application, the provisions of the Act, and the rules and regulations of the Commission; C.
There is reasonable assurance (i) that the activities authorized by this amendment can be conducted without endangering the health and safety of the public, and (ii) that such activities will be conducted in compliance with the Commissions regulations set forth in 10 CFR Chapter I; D.
The issuance of this amendment will not be inimical to the common defense and security or to the health and safety of the public; and E.
The issuance of this amendment is in accordance with 10 CFR Part 51 of the Commissions regulations and all applicable requirements have been satisfied.
- 2.
Accordingly, the license is amended by changes to the Technical Specifications, as indicated in the attachment to this license amendment, and Paragraph 2.C.(2) of Renewed Facility Operating License No. NPF-17 is hereby amended to read as follows:
(2)
Technical Specifications The Technical Specifications contained in Appendix A, as revised through Amendment No. 300 are hereby incorporated into this renewed operating license. The licensee shall operate the facility in accordance with the Technical Specifications.
- 3.
This license amendment is effective as of its date of issuance and shall be implemented within 120 days of issuance.
FOR THE NUCLEAR REGULATORY COMMISSION David J. Wrona, Chief Plant Licensing Branch II-2 Division of Operating Reactor Licensing Office of Nuclear Reactor Regulation
Attachment:
Changes to Renewed Facility Operating License No. NPF-17 and the Technical Specifications Date of Issuance: March 4, 2022 David J.
Wrona Digitally signed by David J. Wrona Date: 2022.03.04 16:03:56 -05'00'
ATTACHMENT TO MCGUIRE NUCLEAR STATION, UNITS 1 AND 2 LICENSE AMENDMENT NO. 321 RENEWED FACILITY OPERATING LICENSE NO. NPF-9 DOCKET NO. 50-369 AND LICENSE AMENDMENT NO. 300 RENEWED FACILITY OPERATING LICENSE NO. NPF-17 DOCKET NO. 50-370 Replace the following pages of the Renewed Facility Operating Licenses and the Appendix A Technical Specifications with the attached revised pages. The revised pages are identified by amendment number and contain marginal lines indicating the areas of change.
Remove Insert License License NPF-9, page 3 NPF-9, page 3 NPF-17, page 3 NPF-17, page 3 Technical Specifications Technical Specifications 5.5-6 5.5-6 5.5-7 5.5-7 5.5-8 5.5-8 5.6-5 5.6-5
5HQHZHG/LFHQVH1RNPF-9
$PHQGPHQW1R
3XUVXDQWWRWKH$FWDQG&)53DUWVDQGWRUHFHLYHSRVVHVV DQGXVHLQDPRXQWVDVUHTXLUHGDQ\\E\\SURGXFWVRXUFHRUVSHFLDOQXFOHDUPDWHULDO ZLWKRXWUHVWULFWLRQWRFKHPLFDORUSK\\VLFDOIRUPIRUVDPSOH DQDO\\VLVRULQVWUXPHQWFDOLEUDWLRQRUDVVRFLDWHGZLWKUDGLRDFWLYHDSSDUDWXV RUFRPSRQHQWV
3XUVXDQWWRWKH$FWDQG&)53DUWVDQGWRSRVVHVVEXWQRWVHSDUDWH
VXFKE\\SURGXFWVDQGVSHFLDOQXFOHDUPDWHULDOVDVPD\\EH SURGXFHGE\\WKHRSHUDWLRQRI0F*XLUH1XFOHDU6WDWLRQ8QLWVDQGDQG
3XUVXDQWWRWKH$FWDQG&)53DUWVDQGWRUHFHLYHSRVVHVVDQGSURFHVV IRUUHOHDVHRUWUDQVIHUVXFKE\\SURGXFWPDWHULDODVPD\\EH SURGXFHGE\\WKH'XNH7UDLQLQJDQG7HFKQRORJ\\&HQWHU
&
7KLVUHQHZHGRSHUDWLQJOLFHQVHVKDOOEHGHHPHGWRFRQWDLQDQGLVVXEMHFWWRWKH
FRQGLWLRQVVSHFLILHGLQWKH&RPPLVVLRQ VUHJXODWLRQVVHWIRUWKLQ&)5&KDSWHU
,DQGLVVXEMHFWWRDOODSSOLFDEOHSURYLVLRQVRIWKH$FWDQGWRWKHUXOHV
UHJXODWLRQVDQGRUGHUVRIWKH&RPPLVVLRQQRZRUKHUHDIWHULQHIIHFWDQGLV VXEMHFWWRWKHDGGLWLRQDOFRQGLWLRQVVSHFLILHGRULQFRUSRUDWHGEHORZ
0D[LPXP3RZHU/HYHO 7KHOLFHQVHHLVDXWKRUL]HGWRRSHUDWHWKHIDFLOLW\\DWDUHDFWRUFRUHIXOO VWHDG\\VWDWHSRZHUOHYHORIPHJDZDWWVWKHUPDO
7HFKQLFDO6SHFLILFDWLRQV 7KH7HFKQLFDO6SHFLILFDWLRQVFRQWDLQHGLQ$SSHQGL[$DVUHYLVHGWKURXJK
$PHQGPHQW1RDUHKHUHE\\LQFRUSRUDWHGLQWRWKLVUHQHZHGRSHUDWLQJOLFHQVH
7KHOLFHQVHHVKDOORSHUDWHWKHIDFLOLW\\LQDFFRUGDQFHZLWKWKH 7HFKQLFDO6SHFLILFDWLRQV
8SGDWHG)LQDO6DIHW\\$QDO\\VLV5HSRUW 7KH8SGDWHG)LQDO6DIHW\\$QDO\\VLV5HSRUWVXSSOHPHQWVXEPLWWHGSXUVXDQW WR&)5GDVUHYLVHGRQ'HFHPEHUGHVFULEHVFHUWDLQ IXWXUHDFWLYLWLHVWREHFRPSOHWHGEHIRUHWKHSHULRGRIH[WHQGHGRSHUDWLRQ
'XNHVKDOOFRPSOHWHWKHVHDFWLYLWLHVQRODWHUWKDQ-XQHDQGVKDOOQRWLI\\
WKH15&LQZULWLQJZKHQLPSOHPHQWDWLRQRIWKHVHDFWLYLWLHVLV FRPSOHWHDQGFDQEHYHULILHGE\\15&LQVSHFWLRQ
7KH8SGDWHG)LQDO6DIHW\\$QDO\\VLV5HSRUWVXSSOHPHQWDVUHYLVHGRQ
'HFHPEHUGHVFULEHGDERYHVKDOOEHLQFOXGHGLQWKHQH[W VFKHGXOHGXSGDWHWRWKH8SGDWHG)LQDO6DIHW\\$QDO\\VLV5HSRUWUHTXLUHGE\\
&)5HIROORZLQJLVVXDQFHRIWKLVUHQHZHGRSHUDWLQJOLFHQVH
8QWLOWKDWXSGDWHLVFRPSOHWH'XNHPD\\PDNHFKDQJHVWRWKHSURJUDPVGHVFULEHG
LQVXFKVXSSOHPHQWZLWKRXWSULRU&RPPLVVLRQDSSURYDO
SURYLGHGWKDW'XNHHYDOXDWHVHDFKVXFKFKDQJHSXUVXDQWWRWKHFULWHULDVHWIRUWKLQ
&)5DQGRWKHUZLVHFRPSOLHVZLWKWKHUHTXLUHPHQWVLQWKDW VHFWLRQ
5HQHZHG/LFHQVH1RNPF-17
$PHQGPHQW1R
3XUVXDQWWRWKH$FWDQG&)53DUWVDQGWRUHFHLYHSRVVHVV DQGXVHLQDPRXQWVDVUHTXLUHGDQ\\E\\SURGXFWVRXUFHRUVSHFLDOQXFOHDU PDWHULDOZLWKRXWUHVWULFWLRQWRFKHPLFDORUSK\\VLFDOIRUPIRUVDPSOH DQDO\\VLVRULQVWUXPHQWFDOLEUDWLRQRUDVVRFLDWHGZLWKUDGLRDFWLYHDSSDUDWXV RUFRPSRQHQWV
3XUVXDQWWRWKH$FWDQG&)53DUWVDQGWRSRVVHVVEXWQRW VHSDUDWHVXFKE\\SURGXFWVDQGVSHFLDOQXFOHDUPDWHULDOVDVP\\EH SURGXFHGE\\WKHRSHUDWLRQRI0F*XLUH1XFOHDU6WDWLRQ8QLWVDQGDQG
3XUVXDQWWRWKH$FWDQG&)53DUWVDQGWRUHFHLYHSRVVHVVDQG SURFHVVIRUUHOHDVHRUWUDQVIHUVXFKE\\SURGXFWPDWHULDODVPD\\EH SURGXFHGE\\WKH'XNH7UDLQLQJDQG7HFKQRORJ\\&HQWHU
&
7KLVUHQHZHGRSHUDWLQJOLFHQVHVKDOOEHGHHPHGWRFRQWDLQDQGLVVXEMHFWWRWKH
FRQGLWLRQVVSHFLILHGLQWKH&RPPLVVLRQ¶VUHJXODWLRQVVHWIRUWKLQ&)5&KDSWHU,
DQGLVVXEMHFWWRDOODSSOLFDEOHSURYLVLRQVRIWKH$FWDQGWRWKHUXOHVUHJXODWLRQV
DQGRUGHUVRIWKH&RPPLVVLRQQRZRUWKHUHDIWHULQHIIHFWDQGLVVXEMHFWWRWKH
DGGLWLRQDOFRQGLWLRQVVSHFLILHGRULQFRUSRUDWHGEHORZ
0D[LPXP3RZHU/HYHO 7KHOLFHQVHHLVDXWKRUL]HGWRRSHUDWHWKHIDFLOLW\\DWDUHDFWRUFRUHIXOOVWHDG\\
VWDWHSRZHUOHYHORIPHJDZDWWVWKHUPDO
7HFKQLFDO6SHFLILFDWLRQV 7KH7HFKQLFDO6SHFLILFDWLRQVFRQWDLQHGLQ$SSHQGL[$DVUHYLVHGWKURXJK
$PHQGPHQW1RDUHKHUHE\\LQFRUSRUDWHGLQWRWKLVUHQHZHGRSHUDWLQJ
OLFHQVH7KHOLFHQVHHVKDOORSHUDWHWKHIDFLOLW\\LQDFFRUGDQFHZLWKWKH
7HFKQLFDO6SHFLILFDWLRQV
8SGDWHG)LQDO6DIHW\\$QDO\\VLV5HSRUW 7KH8SGDWHG)LQDO6DIHW\\$QDO\\VLV5HSRUWVXSSOHPHQWVXEPLWWHGSXUVXDQW
WR&)5GDVUHYLVHGRQ'HFHPEHUGHVFULEHVFHUWDLQ
IXWXUHDFWLYLWLHVWREHFRPSOHWHGEHIRUHWKHSHULRGRIH[WHQGHGRSHUDWLRQ
'XNHVKDOOFRPSOHWHWKHVHDFWLYLWLHVQRODWHUWKDQ0DUFKDQGVKDOO
QRWLI\\WKH15&LQZULWLQJZKHQLPSOHPHQWDWLRQRIWKHVHDFWLYLWLHVLV
FRPSOHWHDQGFDQEHYHULILHGE\\15&LQVSHFWLRQ
7KH8SGDWHG)LQDO6DIHW\\$QDO\\VLV5HSRUWVXSSOHPHQWDVUHYLVHGRQ
'HFHPEHUGHVFULEHGDERYHVKDOOEHLQFOXGHGLQWKHQH[W
VFKHGXOHGXSGDWHWRWKH8SGDWHG)LQDO6DIHW\\$QDO\\VLV5HSRUWUHTXLUHGE\\
&)5HIROORZLQJLVVXDQFHRIWKLVUHQHZHGRSHUDWLQJOLFHQVH
8QWLOWKDWXSGDWHLVFRPSOHWH'XNHPD\\PDNHFKDQJHVWRWKHSURJUDPV
GHVFULEHGLQVXFKVXSSOHPHQWZLWKRXWSULRU&RPPLVVLRQDSSURYDOSURYLGHG
WKDW'XNHHYDOXDWHVHDFKVXFKFKDQJHSXUVXDQWWRWKHFULWHULDVHWIRUWKLQ
&)5DQGRWKHUZLVHFRPSOLHVZLWKWKHUHTXLUHPHQWVLQWKDW
VHFWLRQ
(continued)
McGuire Units 1 and 2 5.5-6 Amendment No.
5.5 Programs and Manuals (continued) 5.5.8 Inservice Testing Program (Deleted)
Note: See Section 1.1 for the definition of INSERVICE TESTING PROGRAM.
5.5.9 Steam Generator (SG) Program An SG Program shall be established and implemented to ensure that SG tube integrity is maintained. In addition, the SG Program shall include the following:
a.
Provisions for condition monitoring assessments. Condition monitoring assessment means an evaluation of the as found condition of the tubing with respect to the performance criteria for structural integrity and accident induced leakage. The as found condition refers to the condition of the tubing during an SG inspection outage, as determined from the inservice inspection results or by other means, prior to the plugging of tubes. Condition monitoring assessments shall be conducted during each outage during which the SG tubes are inspected or plugged to confirm that the performance criteria are being met.
(continued)
McGuire Units 1 and 2 5.5-7 Amendment No.
5.5 Programs and Manuals (continued) 5.5.9 Steam Generator (SG) Program (continued) b.
Performance criteria for SG tube integrity. SG tube integrity shall be maintained by meeting the performance criteria for tube structural integrity, accident induced leakage, and operational LEAKAGE.
1.
Structural integrity performance criterion: All in-service SG tubes shall retain structural integrity over the full range of normal operating conditions (including startup, operation in the power range, hot standby, and cool down), all anticipated transients included in the design specification, and design basis accidents. This includes retaining a safety factor of 3.0 against burst under normal steady state full power operation primary-to-secondary pressure differential and a safety factor of 1.4 against burst applied to the design basis accident primary-to-secondary pressure differentials. Apart from the above requirements, additional loading conditions associated with the design basis accidents, or combination of accidents in accordance with the design and licensing basis, shall also be evaluated to determine if the associated loads contribute significantly to burst or collapse. In the assessment of tube integrity, those loads that do significantly affect burst or collapse shall be determined and assessed in combination with the loads due to pressure with a safety factor of 1.2 on the combined primary loads and 1.0 on axial secondary loads.
2.
Accident induced leakage performance criterion: The primary to secondary accident induced leakage rate for any design basis accident, other than a SG tube rupture, shall not exceed the leakage rate assumed in the accident analysis in terms of total leakage rate for all SGs and leakage rate for an individual SG. Leakage is not to exceed 0.27 gallons per minute total.
3.
The operational LEAKAGE performance criterion is specified in LCO 3.4.13, RCS Operational LEAKAGE.
c.
Provisions for SG tube plugging criteria. Tubes found by inservice inspection to contain flaws with a depth equal to or exceeding 40% of the nominal tube wall thickness shall be plugged.
d.
Provisions for SG tube inspections. Periodic SG tube inspections shall be performed.
The number and portions of the tubes inspected and methods of inspection shall be performed with the objective of detecting flaws of any type (e.g., volumetric flaws, axial and circumferential cracks) that may be present along the length of the tube, from the tube-to-tubesheet weld at the tube inlet to the tube-to-tubesheet weld at the tube outlet, and that may satisfy the applicable tube plugging criteria. The tube-to-tubesheet weld is not part of the tube. In addition to meeting the requirements of d.1, d.2, and d.3 below, the inspection scope, inspection methods, and inspection intervals shall be such as to ensure that SG tube integrity is maintained until the next SG inspection. A degradation assessment shall be performed to determine the type and location of flaws to which the tubes may be susceptible and, based on this assessment, to determine which inspection methods need to be employed and at what locations.
(continued)
McGuire Units 1 and 2 5.5-8 Amendment No.
5.5 Programs and Manuals (continued) 5.5.9 Steam Generator (SG) Program (continued) 1.
Inspect 100% of the tubes in each SG during the first refueling outage following SG installation.
2.
After the first refueling outage following SG installation, inspect 100% of the tubes in each SG at least every 96 effective full power months, which defines the inspection period.
3.
If crack indications are found in any SG tube, then the next inspection for each affected and potentially affected SG for the degradation mechanism that caused the crack indication shall be at the next refueling outage. If definitive information, such as from examination of a pulled tube, diagnostic non-destructive testing, or engineering evaluation indicates that a crack-like indication is not associated with a crack(s), then the indication need not be treated as a crack.
e.
Provisions for monitoring operational primary to secondary LEAKAGE.
Reporting Requirements 5.6 (continued)
McGuire Units 1 and 2 5.6-5 Amendment Nos.
5.6 Reporting Requirements 5.6.8 Steam Generator Tube Inspection Report A report shall be submitted within 180 days after the initial entry into MODE 4 following completion of an inspection performed in accordance with the Specification 5.5.9, Steam Generator (SG) Program. The report shall include:
a.
The scope of inspections performed on each SG; b.
The nondestructive examination techniques utilized for tubes with increased degradation susceptibility; c.
For each degradation mechanism found:
- 1. The nondestructive examination techniques utilized;
- 2. The location, orientation (if linear), measured size (if available),
and voltage response for each indication. For tube wear at support structures less than 20 percent through-wall, only the total number of indications needs to be reported;
- 3. A description of the condition monitoring assessment and results, including the margin to the tube integrity performance criteria and comparison with the margin predicted to exist at the inspection by the previous forward-looking tube integrity assessment; and
- 4. The number of tubes plugged during the inspection outage.
d.
An analysis summary of the tube integrity conditions predicted to exist at the next scheduled inspection (the forward-looking tube integrity assessment) relative to the applicable performance criteria, including the analysis methodology, inputs, and results; e.
The number and percentage of tubes plugged to date, and the effective plugging percentage in each SG; and f.
The results of any SG secondary side inspections.
DUKE ENERGY PROGRESS, LLC DOCKET NO. 50-400 SHEARON HARRIS NUCLEAR POWER PLANT, UNIT 1 AMENDMENT TO RENEWED FACILITY OPERATING LICENSE Amendment No. 191 Renewed License No. NPF-63
- 1.
The Nuclear Regulatory Commission (the Commission) has found that:
A.
The application for amendment by Duke Energy Progress, LLC (the licensee),
dated September 16, 2021, complies with the standards and requirements of the Atomic Energy Act of 1954, as amended (the Act), and the Commissions rules and regulations set forth in 10 CFR Chapter I; B.
The facility will operate in conformity with the application, the provisions of the Act, and the rules and regulations of the Commission; C.
There is reasonable assurance (i) that the activities authorized by this amendment can be conducted without endangering the health and safety of the public, and (ii) that such activities will be conducted in compliance with the Commissions regulations; D.
The issuance of this amendment will not be inimical to the common defense and security or to the health and safety of the public; and E.
The issuance of this amendment is in accordance with 10 CFR Part 51 of the Commissions regulations and all applicable requirements have been satisfied.
- 2.
Accordingly, the license is amended by changes to the Technical Specifications, as indicated in the attachment to this license amendment, and Paragraph 2.C.(2) of Renewed Facility Operating License No. NPF-63 is hereby amended to read as follows:
(2)
Technical Specifications and Environmental Protection Plan The Technical Specifications contained in Appendix A and the Environmental Protection Plan contained in Appendix B, both of which are attached hereto, as revised through Amendment No. 191, are hereby incorporated into this license. Duke Energy Progress, LLC shall operate the facility in accordance with the Technical Specifications and the Environmental Protection Plan.
- 3.
This license amendment is effective as of the date of its issuance and shall be implemented within 120 days of issuance.
FOR THE NUCLEAR REGULATORY COMMISSION David J. Wrona, Chief Plant Licensing Branch II-2 Division of Operating Reactor Licensing Office of Nuclear Reactor Regulation
Attachment:
Changes to Renewed Facility Operating License No. NPF-63 and the Technical Specifications Date of Issuance: March 4, 2022 David J.
Wrona Digitally signed by David J. Wrona Date: 2022.03.04 16:04:26 -05'00'
ATTACHMENT TO LICENSE AMENDMENT NO. 191 SHEARON HARRIS NUCLEAR POWER PLANT, UNIT 1 RENEWED FACILITY OPERATING LICENSE NO. NPF-63 DOCKET NO. 50-400 Replace the following pages of the Renewed Facility Operating Licenses and the Appendix A Technical Specifications with the attached revised pages. The revised pages are identified by amendment number and contain marginal lines indicating the areas of change.
Remove Insert License License NPF-63, Page 4 NPF-63, Page 4 Technical Specifications Technical Specifications Remove Insert 6-19d 6-19d 6-19e 6-19e 6-19f 6-24a 6-24a 6-24b 6-24b
5HQHZHG/LFHQVH1R13)
$PHQGPHQW1R
&
7KLVOLFHQVHVKDOOEHGHHPHGWRFRQWDLQDQGLVVXEMHFWWRWKHFRQGLWLRQVVSHFLILHG LQWKH&RPPLVVLRQ VUHJXODWLRQVVHWIRUWKLQ&)5&KDSWHU,DQGLVVXEMHFWWRDOO DSSOLFDEOHSURYLVLRQVRIWKH$FWDQGWRWKHUXOHVUHJXODWLRQVDQGRUGHUVRIWKH
&RPPLVVLRQQRZRUKHUHDIWHULQHIIHFWDQGLVVXEMHFWWRWKHDGGLWLRQDOFRQGLWLRQV VSHFLILHGRULQFRUSRUDWHGEHORZ
0D[LPXP3RZHU/HYHO
'XNH(QHUJ\\3URJUHVV//&LVDXWKRUL]HGWRRSHUDWHWKHIDFLOLW\\DWUHDFWRU
&RUHSRZHUOHYHOVQRWLQH[FHVVRIPHJDZDWWVWKHUPDOSHUFHQW UDWHGFRUHSRZHULQDFFRUGDQFHZLWKWKHFRQGLWLRQVVSHFLILHGKHUHLQ
7HFKQLFDO6SHFLILFDWLRQVDQG(QYLURQPHQWDO3URWHFWLRQ3ODQ 7KH7HFKQLFDO6SHFLILFDWLRQVFRQWDLQHGLQ$SSHQGL[$DQGWKH (QYLURQPHQWDO3URWHFWLRQ3ODQFRQWDLQHGLQ$SSHQGL[%ERWKRIZKLFKDUH DWWDFKHGKHUHWRDVUHYLVHGWKURXJK$PHQGPHQW1RDUHKHUHE\\
LQFRUSRUDWHGLQWRWKLVOLFHQVH'XNH(QHUJ\\3URJUHVV//&VKDOORSHUDWH WKHIDFLOLW\\LQDFFRUGDQFHZLWKWKH7HFKQLFDO6SHFLILFDWLRQVDQGWKH (QYLURQPHQWDO3URWHFWLRQ3ODQ
$QWLWUXVW&RQGLWLRQV
'XNH(QHUJ\\3URJUHVV//&VKDOOFRPSO\\ZLWKWKHDQWLWUXVWFRQGLWLRQV GHOLQHDWHGLQ$SSHQGL[&WRWKLVOLFHQVH
,QLWLDO6WDUWXS7HVW3URJUDP6HFWLRQ
$Q\\FKDQJHVWRWKH,QLWLDO7HVW3URJUDPGHVFULEHGLQ6HFWLRQRIWKH
)6$5PDGHLQDFFRUGDQFHZLWKWKHSURYLVLRQVRI&)5VKDOOEH UHSRUWHGLQDFFRUGDQFHZLWKEZLWKLQRQHPRQWKRIVXFKFKDQJH
6WHDP*HQHUDWRU7XEH5XSWXUH6HFWLRQ
3ULRU
VWDUWXS
IROORZLQJ
WKH
ILUVW
UHIXHOLQJ
RXWDJH
&DUROLQD3RZHU /LJKW
&RPSDQ\\ VKDOOVXEPLWIRU15&UHYLHZDQGUHFHLYHDSSURYDOLIDVWHDP JHQHUDWRUWXEHUXSWXUHDQDO\\VLVLQFOXGLQJWKHDVVXPHGRSHUDWRUDFWLRQV
ZKLFKGHPRQVWUDWHVWKDWWKHFRQVHTXHQFHVRIWKHGHVLJQEDVLVVWHDP JHQHUDWRUWXEHUXSWXUHHYHQWIRUWKH6KHDURQ+DUULV1XFOHDU3RZHU3ODQW DUHOHVVWKDQWKHDFFHSWDQFHFULWHULDVSHFLILHGLQWKH6WDQGDUG5HYLHZ 3ODQ185(*DW6XESDUWV,,DQGIRUFDOFXODWHGGRVHV IURPUDGLRORJLFDOUHOHDVHV,QSUHSDULQJWKHLUDQDO\\VLV&DUROLQD3RZHU
/LJKW&RPSDQ\\ ZLOOQRWDVVXPHWKDWRSHUDWRUVZLOOFRPSOHWHFRUUHFWLYH DFWLRQVZLWKLQWKHILUVWWKLUW\\PLQXWHVDIWHUDVWHDPJHQHUDWRUWXEHUXSWXUH
7KHSDUHQWKHWLFDOQRWDWLRQIROORZLQJWKHWLWOHRIPDQ\\OLFHQVHFRQGLWLRQVGHQRWHVWKHVHFWLRQRIWKH6DIHW\\(YDOXDWLRQ
5HSRUWDQGRULWVVXSSOHPHQWVZKHUHLQWKHOLFHQVHFRQGLWLRQLVGLVFXVVHG
2Q$SULOWKHQDPHRI³&DUROLQD3RZHU /LJKW&RPSDQ\\'&3 /ZDVFKDQJHGWR³'XNH(QHUJ\\3URJUHVV
,QF'2Q$XJXVWWKHQDPH³'XNH(QHUJ\\3URJUHVV,QF'ZDVFKDQJHGWR³'XNH(QHUJ\\3URJUHVV//&'
SHEARON HARRIS - UNIT 1 6-19d Amendment No.
ADMINISTRATIVE CONTROLS PROCEDURES AND PROGRAMS (Continued) l.
Steam Generator (SG) Program An SG Program shall be established and implemented to ensure that SG tube integrity is maintained. In addition, the SG Program shall include the following:
1.
Provisions for condition monitoring assessments. Condition monitoring assessment means an evaluation of the "as found" condition of the tubing with respect to the performance criteria for structural integrity and accident induced leakage. The "as found" condition refers to the condition of the tubing during a SG inspection outage, as determined from the inservice inspection results or by other means, prior to the plugging of tubes. Condition monitoring assessments shall be conducted during each outage during which the SG tubes are inspected or plugged to confirm that the performance criteria are being met.
2.
Performance criteria for SG tube integrity. Steam generator tube integrity shall be maintained by meeting the performance criteria for tube structural integrity, accident induced leakage, and operational leakage.
a)
Structural integrity performance criterion. All inservice SG tubes shall retain structural integrity over the full range of normal operating conditions (including startup, operation in the power range, HOT STANDBY, and cooldown), all anticipated transients included in the design specification, and design basis accidents. This includes retaining a safety factor of 3.0 (3deltaP) against burst under normal steady-state full power operation primary-to-secondary pressure differential and a safety factor of 1.4 against burst applied to the design basis accident primary-to-secondary pressure differentials. Apart from the above requirements, additional loading conditions associated with the design basis accidents, or combination of accidents in accordance with the design and licensing basis, shall also be evaluated to determine if the associated loads contribute significantly to burst or collapse. In the assessment of tube integrity, those loads that do significantly affect burst or collapse shall be determined and assessed in combination with the loads due to pressure with a safety factor of 1.2 on the combined primary loads and 1.0 on axial secondary loads.
b)
Accident induced leakage performance criterion. The primary-to-secondary accident induced leakage rate for any design basis accident, other than a SG tube rupture, shall not exceed the leakage rate assumed in the accident analysis in terms of total leakage rate for all SGs and leakage rate for an individual SG. Accident induced leakage is not to exceed 1 gpm total for all three SGs.
c)
The operation leakage performance criterion is specified in LCO 3.4.6.2, "Reactor Coolant System Operational Leakage."
(PAGE 6-19f DELETED By Amendment No. 191)
SHEARON HARRIS - UNIT 1 6-19e Amendment No.
ADMINISTRATIVE CONTROLS PROCEDURES AND PROGRAMS (Continued) 3.
Provisions for SG tube plugging criteria. Tubes found by inservice inspection to contain flaws with depth equal to or exceeding 40% of the nominal tube wall thickness shall be plugged.
4.
Provisions for SG tube inspections. Periodic SG tube inspections shall be performed. The number and portions of the tubes inspected and methods of inspection shall be performed with the objective of detecting flaws of any type (e.g., volumetric flaws, axial and circumferential cracks) that may be present along the length of the tube, from tube-to-tubesheet weld at the tube inlet to the tube-to-tubesheet weld at the tube outlet, and that may satisfy the applicable tube plugging criteria. The tube-to-tubesheet weld is not part of the tube. In addition to meeting the requirements of 4a, 4b, and 4c below, the inspection scope, inspection methods and inspection intervals shall be such as to ensure that SG tube integrity is maintained until the next SG inspection. A degradation assessment shall be performed to determine the type and location of flaws to which the tubes may be susceptible and, based on this assessment, to determine which inspection methods need to be employed and at what locations.
a)
Inspect 100% of the tubes in each SG during the first refueling outage following SG installation.
b)
After the first refueling outage following SG installation, inspect 100% of the tubes in each SG at least every 96 effective full power months, which defines the inspection period.
c)
If crack indications are found in any SG tube, then the next inspection for each affected and potentially affected SG for the degradation mechanism that caused the crack indication shall be at the next refueling outage. If definitive information, such as from examination of a pulled tube, diagnostic non-destructive testing, or engineering evaluation indicates that a crack-like indication is not associated with a crack(s), then the indication need not be treated as a crack.
5.
Provisions for monitoring operational primary-to-secondary leakage.
SHEARON HARRIS - UNIT 1 6-24a Amendment No.
ADMINISTRATIVE CONTROLS 6.9.1.6 CORE OPERATING LIMITS REPORT (Continued) h.
DPC-NE-1008-P-A, Nuclear Design Methodology Using CASMO-5/SIMULATE-3 for Westinghouse Reactors, as approved by NRC Safety Evaluation dated May 18, 2017.
i.
DPC-NF-2010-A, Nuclear Physics Methodology for Reload Design, as approved by NRC Safety Evaluation dated May 18, 2017.
j.
DPC-NE-2011-P-A, Nuclear Design Methodology Report for Core Operating Limits of Westinghouse Reactors as approved by NRC Safety Evaluation dated May 18, 2017.
k.
DPC-NE-3008-P-A, Thermal-Hydraulic Models for Transient Analysis, as approved by NRC Safety Evaluation dated April 10, 2018.
l.
DPC-NE-3009-P-A, FSAR / UFSAR Chapter 15 Transient Analysis Methodology, as approved by NRC Safety Evaluation dated April 10, 2018.
m.
ANP-10341P-A, The ORFEO-GAIA and ORFEO-NMGRID Critical Heat Flux Correlations, approved version as specified in the COLR.
6.9.1.6.3 The core operating limits shall be determined so that all applicable limits (e.g., fuel thermal-mechanical limits, core thermal-hydraulic limits, nuclear limits such as shutdown margin, and transient and accident analysis limits) of the safety analysis are met.
6.9.1.6.4 The CORE OPERATING LIMITS REPORT, including any mid-cycle revisions or supplements, shall be provided, upon issuance for each reload cycle, to the NRC Document Control Desk, with copies to the Regional Administrator and Resident Inspector.
6.9.1.7 STEAM GENERATOR TUBE INSPECTION REPORT A report shall be submitted within 180 days after the initial entry into HOT SHUTDOWN following completion of an inspection performed in accordance with Specification 6.8.4.l. The report shall include:
a.
The scope of inspections performed on each SG; b.
The nondestructive examination techniques utilized for tubes with increased degradation susceptibility; c.
For each degradation mechanism found:
1.
The nondestructive examination techniques utilized; 2.
The location, orientation (if linear), measured size (if available), and voltage response for each indication. For tube wear at support structures less than 20 percent through-wall, only the total number of indications needs to be reported; 3.
A description of the condition monitoring assessment and results, including the margin to the tube integrity performance criteria and comparison with the margin predicted to exist at the inspection by the previous forward-looking tube integrity assessment; and 4.
The number of tubes plugged during the inspection outage.
(PAGES 6-24c THROUGH 6-24d DELETED By Amendment No. 185)
(PAGE 6-25 DELETED By Amendment No.92)
SHEARON HARRIS - UNIT 1 6-24b Amendment No.
ADMINISTRATIVE CONTROLS 6.9.1.7 STEAM GENERATOR TUBE INSPECTION REPORT (Continued) d.
An analysis summary of the tube integrity conditions predicted to exist at the next scheduled inspection (the forward-looking tube integrity assessment) relative to the applicable performance criteria, including the analysis methodology, inputs, and results; e.
The number and percentage of tubes plugged to date, and the effective plugging percentage in each SG; and f.
The results of any SG secondary side inspections.
SPECIAL REPORTS 6.9.2 Special reports shall be submitted to the NRC in accordance with 10 CFR 50.4 within the time period specified for each report.
6.10 DELETED
SAFETY EVALUATION BY THE OFFICE OF NUCLEAR REACTOR REGULATION RELATED TO AMENDMENT NO. 311 TO RENEWED FACILITY OPERATING LICENSE NO. NPF-35 AND AMENDMENT NO. 307 TO RENEWED FACILITY OPERATING LICENSE NO. NPF-52 DUKE ENERGY CATAWBA NUCLEAR STATION, UNITS 1 AND 2 DOCKET NOS. 50-413 AND 50-414 Application (i.e., initial and supplements)
Safety Evaluation Date September 16, 2021, ADAMS Accession No. ML21259A093 March 4, 2022 Principal Contributors to Safety Evaluation Clinton Ashley
1.0 PROPOSED CHANGE
S Duke Energy (the licensee) requested changes to the technical specifications (TSs) for Catawba Nuclear Station (CNS), Units 1 and 2, by license amendment request (application). In its application, the licensee requested that the U.S. Nuclear Regulatory Commission (NRC, the Commission) process the proposed amendment under the Consolidated Line Item Improvement Process (CLIIP). The proposed changes would revise the Steam Generator (SG) Program and the Steam Generator (SG) Tube Inspection Report TSs based on Technical Specifications Task Force (TSTF) Traveler TSTF-577, Revision 1, Revised Frequencies for Steam Generator Tube Inspections (TSTF-577) (Agencywide Documents Access and Management System (ADAMS) Accession No. ML21060B434), and the associated NRC staff safety evaluation (SE) of TSTF-577 (ADAMS Accession No. ML21098A188).
The tubes within an SG function as an integral part of the reactor coolant pressure boundary and, in addition, isolate fission products in the primary coolant from the secondary coolant and the environment. SG tube integrity means that the tubes are capable of performing this safety function in accordance with the plant design and licensing basis.
CNS has two Units. The Unit 1 SGs have Alloy 690 thermally treated (Alloy 690TT) tubes. The Unit 2 SGs have Alloy 600 thermally treated (Alloy 600TT) tubes.
1.1 Proposed TS Changes to Adopt TSTF-577 In accordance with NRC staff-approved TSTF-577, the licensee proposed changes that would revise CNS TS 5.5.9, Steam Generator (SG) Program, and TS 5.6.8, Steam Generator (SG)
Tube Inspection Report. Specifically, the licensee proposed the following changes to adopt TSTF-577:
TS 5.5.9, Steam Generator (SG) Program:
TS 5.5.9 introductory paragraph would be revised by replacing steam generator with SG in a few instances.
TS 5.5.9.d would be revised by adding a phrase regarding portions of the tube that are exempt from inspection by alternate repair criteria that replaces Unit 2 information specifying distances from top of the tubesheet.
TS 5.5.9.d.2 and TS 5.5.9.d.3 would be revised by deleting the requirement to base inspection frequency on the more restrictive metric between either the effective full power months (EFPM) or refueling outage and to use just the EFPM metric.
TS 5.5.9.d.2 and TS 5.5.9.d.3 would be revised by deleting the allowance to extend the inspection period by 3 months and by deleting the discussion of prorating inspections.
TS 5.5.9.d.2 would be revised by deleting the requirement to inspect 100 percent of the tubes during each period in paragraphs d.2.a, d.2.b, d.2.c, and d.2.d (144, 120, 96, and 72 EFPM, respectively) and by adding the requirement to inspect 100 percent of the tubes every 96 EFPM.
TS 5.5.9.d.3 would be revised by changing the requirement to inspect 100 percent of the tubes at periods of 120, 96, and 72 EFPM to 54 EFPM. A 72 EFPM inspection period would be permitted if SG tubing has never experienced cracking (not including regions exempt from inspection by alternate repair criteria) and the SG inspection was performed with enhanced probes. A description of the enhanced probe inspection would be added.
TS 5.5.9.d.4 would be revised by changing the next inspection after crack indications are found from shall not exceed 24 effective full power months or one refueling outage (whichever results in more frequent inspections) to shall be at the next refueling outage.
TS 5.5.9.d.4 would be revised by adding a phrase regarding portions of the tube that are exempt from inspection by alternate repair criteria that replaces Unit 2 information specifying distances from top of the tubesheet. An additional phrase would be added that permits deferring SG inspections after cracking indications are found if the 100 percent inspection was performed with enhanced probes.
TS 5.6.8, Steam Generator (SG) Tube Inspection Report:
Existing reporting requirement b. would be renumbered as c. and be revised by editorial and punctuation changes.
New reporting requirement b. would be added to require the nondestructive examination (NDE) techniques utilized for tubes with increased degradation susceptibility be reported.
Existing reporting requirement c. would be renumbered as c.1. and be revised by editorial and punctuation changes.
Existing reporting requirement d. would be renumbered as c.2. and be revised to note that the location, orientation (if linear), measured size (if available), and voltage response do not need to be reported for tube wear indications at support structures that are less than 20 percent through-wall. However, the total number of tube wear indications at support structures that are less than 20 percent through-wall would be reported.
New reporting requirement d. would be added to require an analysis summary of the tube integrity conditions predicted to exist at the next scheduled inspection relative to the applicable performance criteria, including the analysis, methodology, inputs, and results.
Existing reporting requirement e. would be renumbered as c.4. and be revised by editorial and punctuation changes.
Existing reporting requirement f. would be renumbered as e. and be revised by editorial and punctuation changes.
New reporting requirement f. would be added to require the results of any SG secondary side inspections be reported.
Existing reporting requirement g. would be renumbered as c.3. and be revised to add the requirements to report a description of the condition monitoring assessment, the margin to the tube integrity performance criteria, and a comparison with the margin predicted to exist at the inspection by the previous forward-looking tube integrity assessment. In addition, the requirement to report the results of tube pulls and in-situ testing would be deleted.
Existing reporting requirements h., i., and j. would be renumbered as reporting requirements g., h., and i. and be revised by punctuation changes.
1.2 Additional Proposed TS Changes In addition to the changes proposed consistent with the traveler discussed in Section 1.1, the licensee proposed the following variations.
1.2.1 Editorial Variations The licensee noted that CNS uses different numbering than the Standard Technical Specification on which TSTS-577 was based. Specifically, CNS uses TS 5.6.8 for Steam Generator (SG) Tube Inspection Report and the TSTF-577 uses TS 5.6.7.
The licensee noted that CNS Unit 1 has a different SG design than CNS Unit 2. Therefore, the current CNS TS 5.5.9 includes requirements specific to Unit 1 and requirements specific to Unit 2. The proposed TS markups for CNS incorporate the intent of the TSTF-577 changes, while retaining the unit-specific formatting of the existing CNS TSs.
1.2.2 Other Variation The licensee noted that the CNS SG Program TSs currently contain a provision for an alternate tube plugging criteria. The description of the alternate tube plugging criteria in the proposed change is equivalent to the descriptions in the current CNS TSs.
2.0 REGULATORY EVALUATION
The regulations in Title 10 of the Code of Federal Regulations (10 CFR) paragraph 50.36(c)(5),
Administrative controls, state that [a]dministrative controls are the provisions relating to organization and management, procedures, recordkeeping, review and audit, and reporting necessary to assure operation of the facility in a safe manner. Each licensee shall submit any reports to the Commission pursuant to approved technical specifications as specified in
[10 CFR] 50.4. Technical Specification Section 5.0, Administrative Controls, requires that an SG Program be established and implemented to ensure that SG tube integrity is maintained.
Programs established by the licensee, including the SG Program, are listed in the administrative controls section of the TS to operate the facility in a safe manner.
The NRC staffs guidance for the review of TSs is in NUREG-0800, Standard Review Plan for the Review of Safety Analysis Reports for Nuclear Power Plants: LWR [Light-Water Reactor]
Edition (SRP), Chapter 16.0, Technical Specifications, Revision 3, dated March 2010 (ADAMS Accession No. ML100351425). As described therein, as part of the regulatory standardization effort, the NRC staff has prepared STSs for each of the LWR nuclear designs.
Accordingly, the NRC staffs review includes consideration of whether the proposed changes are consistent with NUREG-14311, as modified by NRC-approved travelers.
TSTF-577 revised the STSs related to SG tube inspections and SG tube inspection reporting requirements. The NRC approved TSTF-577, under the CLIIP on April 14, 2021 (ADAMS Package Accession No. ML21099A086). It addressed the applicable 10 CFR Part 50, Appendix A, General Design Criteria for Nuclear Power Plants requirements with respect to the integrity of the SG tubing.
3.0 TECHNICAL EVALUATION
3.1 Proposed TS Changes to Adopt TSTF-577 In the SE of TSTF-577, the NRC staff concluded that the TSTF-577 changes to STS 5.5.9, Steam Generator (SG) Program, and STS 5.6.7, Steam Generator Tube Inspection Report, were acceptable because, as discussed in Section 3.0 of that SE, they continued to ensure SG tube integrity and, therefore, protected the public health and safety. In particular, the structural integrity performance criterion and accident-induced leakage performance criterion (explained in STS 5.5.9.b, items 1 and 2, respectively) will continue to be met with the proposed revised SG 1 U.S. Nuclear Regulatory Commission, Standard Technical Specifications, Westinghouse Plants, NUREG-1431, Volume 1, Specifications, and Volume 2, Bases, Revision 5, September 2021 (ADAMS Accession Nos. ML21259A155 and ML21259A159, respectively).
inspection intervals (maximum allowable time between SG inspections) and inspection periods (maximum allowable time between 100 percent of SG tubes inspections). Additionally, the proposed changes to the reporting requirements will provide more detailed and consistent information to the NRC. Therefore, the NRC staff found that the proposed changes to the SG program and inspection reporting requirements were acceptable because they continued to meet the requirements of 10 CFR 50.36(c)(5) by providing administrative controls necessary to assure operation of the facility in a safe manner.
The NRC staff compared the licensees proposed TS changes in Section 1.1 of this SE against the changes approved in TSTF-577. In accordance with SRP Chapter 16.0, the NRC staff determined that the STS changes approved in TSTF-577 are applicable because CNS Units 1 and 2 are pressurized water reactors (PWRs) and the NRC staff had generically approved the TSTF-577 changes for all operating PWRs. The NRC staff finds that the licensees proposed changes to the CNS Units 1 and 2 TSs in Section 1.1 of this SE are consistent with those found acceptable in TSTF-577. Thus, the NRC staff concludes that the corresponding proposed changes to the CNS Units 1 and 2 TSs in Section 1.1 of this SE continue to meet the requirements of 10 CFR 50.36(c)(5).
3.2 Additional Proposed TS Changes 3.2.1 Editorial Variations The licensee noted that CNS uses different numbering than the Standard Technical Specification on which TSTS-577 was based. Specifically, CNS uses TS 5.6.8 for Steam Generator (SG) Tube Inspection Report and the TSTF-577 uses TS 5.6.7. The NRC staff finds the different TS numbering is acceptable because it does not substantively alter TS requirements.
The licensee noted that CNS Unit 1 has a different SG design than CNS Unit 2. Therefore, the current CNS TS 5.5.9 includes requirements specific to Unit 1 and requirements specific to Unit 2. The licensee also noted that the proposed TS markups for CNS incorporate the intent of the TSTF-577 changes, while retaining the unit-specific formatting of the existing CNS TSs.
The NRC staff finds the proposed changes to CNS TS 5.5.9 are consistent with the staff-approved TSTF-577 requirements, appropriately identifying Unit applicability due to differences in SG tube alloy, and therefore, are acceptable.
3.2.2 Other Variation The licensee noted that the CNS SG Program TS currently contains a provision for an alternate tube plugging criteria and the descriptions of the alternate tube plugging criteria in the proposed change are equivalent to the descriptions in the current CNS TS.
The current CNS TS that addresses alternate tube plugging criteria (i.e., TS 5.5.9.c.1) reflects NRC approved changes contained in Amendment No. 267 and Amendment No. 263 for CNS, Units 1 and 2, respectively (ADAMS Accession No. ML12054A692). As part of the request to adopt TSTF-577, the licensee did not propose any changes to these criteria. Therefore, the staff considers this variation as information for awareness purposes, rather than a variation from the traveler or a change to the plant-specific TS.
3.3 TS Change Consistency The NRC staff reviewed the proposed TS changes for technical clarity and consistency with the existing requirements for customary terminology and formatting. The NRC staff finds that the proposed changes are consistent with Chapter 16.0 of the SRP and are therefore acceptable.
4.0 CONCLUSION
The Commission has concluded, based on the considerations discussed above, that: (1) there is reasonable assurance that the health and safety of the public will not be endangered by operation in the proposed manner, (2) there is reasonable assurance that such activities will be conducted in compliance with the Commissions regulations, and (3) the issuance of the amendment will not be inimical to the common defense and security or to the health and safety of the public.
SAFETY EVALUATION BY THE OFFICE OF NUCLEAR REACTOR REGULATION RELATED TO AMENDMENT NO. 321 TO RENEWED FACILITY OPERATING LICENSE NO. NPF-9 AND AMENDMENT NO. 300 TO RENEWED FACILITY OPERATING LICENSE NO. NPF-17 DUKE ENERGY MCGUIRE NUCLEAR STATION, UNITS 1 AND 2 DOCKET NOS. 50-369 AND 50-370 Application (i.e., initial and supplements)
Safety Evaluation Date September 16, 2021, ADAMS Accession No. ML21259A093 March 4, 2022 Principal Contributors to Safety Evaluation Clinton Ashley
1.0 PROPOSED CHANGE
S Duke Energy (the licensee) requested changes to the technical specifications (TSs) for McGuire Nuclear Station (MNS), Units 1 and 2, by license amendment request (application). In its application, the licensee requested that the U.S. Nuclear Regulatory Commission (NRC, the Commission) process the proposed amendment under the Consolidated Line Item Improvement Process (CLIIP). The proposed changes would revise the Steam Generator (SG) Program and the Steam Generator (SG) Tube Inspection Report TSs based on Technical Specifications Task Force (TSTF) Traveler TSTF-577, Revision 1, Revised Frequencies for Steam Generator Tube Inspections (TSTF-577) (Agencywide Documents Access and Management System (ADAMS) Accession No. ML21060B434), and the associated NRC staff safety evaluation (SE) of TSTF-577 (ADAMS Accession No. ML21098A188).
The tubes within an SG function as an integral part of the reactor coolant pressure boundary and, in addition, isolate fission products in the primary coolant from the secondary coolant and the environment. SG tube integrity means that the tubes are capable of performing this safety function in accordance with the plant design and licensing basis.
MNS has two units. The Unit 1 SGs have Alloy 690 thermally treated (Alloy 690TT) tubes. The Unit 2 SGs have Alloy 690 thermally treated (Alloy 690TT) tubes.
1.1 Proposed TS Changes to Adopt TSTF-577 In accordance with NRC staff-approved TSTF-577, the licensee proposed changes that would revise MNS TS 5.5.9, Steam Generator (SG) Program, and TS 5.6.8, Steam Generator Tube Inspection Report. Specifically, the licensee proposed the following changes to adopt TSTF-577:
TS 5.5.9, Steam Generator (SG) Program:
The introductory paragraph to TS 5.5.9 would be revised by replacing steam generator with SG in a couple of instances.
TS 5.5.9.b.1 would be revised by replacing steam generator with SG in one instance.
TS 5.5.9.d.2 would be revised by deleting the requirement to base inspection frequency on the more restrictive metric between either the effective full power months (EFPM) or refueling outage and to use just the EFPM metric.
TS 5.5.9.d.2 would be revised by deleting the requirement to inspect 100 percent of the tubes during each period in paragraphs d.2.a, d.2.b, d.2.c, and d.2.d (144, 120, 96, and 72 EFPM, respectively) and by adding the requirement to inspect 100 percent of the tubes every 96 EFPM.
TS 5.5.9.d.2 would be revised by deleting the allowance to extend the inspection period by 3 effective full power months and by deleting the discussion of prorating inspections.
TS 5.5.9.d.3 would be revised by replacing shall not exceed 24 effective full power months or one refueling outage (whichever results in more frequent inspections) with shall be at the next refueling outage.
TS 5.6.8, Steam Generator Tube Inspection Report:
Existing reporting requirement b. would be renumbered as c. and be revised by editorial and punctuation changes.
New reporting requirement b. would be added to require the nondestructive examination (NDE) techniques utilized for tubes with increased degradation susceptibility be reported.
Existing reporting requirement c. would be renumbered as c.1. and be revised by editorial and punctuation changes.
Existing reporting requirement d. would be renumbered as c.2. and be revised to note that the location, orientation (if linear), measured size (if available), and voltage response do not need to be reported for tube wear indications at support structures that are less than 20 percent through-wall. However, the total number of tube wear indications at support structures that are less than 20 percent through-wall would be reported.
New reporting requirement d. would be added to require an analysis summary of the tube integrity conditions predicted to exist at the next scheduled inspection relative to the applicable performance criteria, including the analysis, methodology, inputs, and results.
Existing reporting requirement e. would be renumbered as c.4. and be revised by editorial and punctuation changes.
Existing reporting requirement f. would be renumbered as e. and be revised by editorial and punctuation changes.
New reporting requirement f. would be added to require the results of any SG secondary side inspections be reported.
Existing reporting requirement g. would be renumbered as c.3. and be revised to add the requirements to report a description of the condition monitoring assessment, the margin to the tube integrity performance criteria, and a comparison with the margin predicted to exist at the inspection by the previous forward-looking tube integrity assessment. In addition, the requirement to report the results of tube pulls and in-situ testing would be deleted.
1.2 Additional Proposed TS Changes In addition to the changes proposed consistent with the traveler discussed in Section 1.1, the licensee proposed the following variations.
1.2.3 Editorial Variations The licensee identified one variation. The licensee noted that MNS TSs have different numbering than standard technical specifications (STSs) on which TSTF-577 was based.
Specifically, the Steam Generator Tube Inspection Report is numbered 5.6.8 in MNS Units 1 and 2 TSs rather than 5.6.7 as stated in the TSTF.
2.0 REGULATORY EVALUATION
The regulations in Title 10 of the Code of Federal Regulations (10 CFR) paragraph 50.36(c)(5),
Administrative controls, state that [a]dministrative controls are the provisions relating to organization and management, procedures, recordkeeping, review and audit, and reporting necessary to assure operation of the facility in a safe manner. Each licensee shall submit any reports to the Commission pursuant to approved technical specifications as specified in
[10 CFR] 50.4. Technical Specification Section 5.0, Administrative Controls, requires that an SG Program be established and implemented to ensure that SG tube integrity is maintained.
Programs established by the licensee, including the SG Program, are listed in the administrative controls section of the TS to operate the facility in a safe manner.
The NRC staffs guidance for the review of TSs is in NUREG-0800, Standard Review Plan for the Review of Safety Analysis Reports for Nuclear Power Plants: LWR [Light-Water Reactor]
Edition (SRP), Chapter 16.0, Technical Specifications, Revision 3, dated March 2010 (ADAMS Accession No. ML100351425). As described therein, as part of the regulatory standardization effort, the NRC staff has prepared STSs for each of the LWR nuclear designs.
Accordingly, the NRC staffs review includes consideration of whether the proposed changes are consistent with NUREG-14312, as modified by NRC-approved travelers.
TSTF-577 revised the STSs related to SG tube inspections and SG tube inspection reporting requirements. The NRC approved TSTF-577, under the CLIIP on April 14, 2021 (ADAMS Package Accession No. ML21099A086). It addressed the applicable 10 CFR Part 50, Appendix A, General Design Criteria for Nuclear Power Plants requirements with respect to the integrity of the SG tubing.
3.0 TECHNICAL EVALUATION
3.1 Proposed TS Changes to Adopt TSTF-577 In the SE of TSTF-577, the NRC staff concluded that the TSTF-577 changes to STS 5.5.9, Steam Generator (SG) Program, and STS 5.6.7, Steam Generator Tube Inspection Report, were acceptable because, as discussed in Section 3.0 of that SE, they continued to ensure SG tube integrity and, therefore, protected the public health and safety. In particular, the structural integrity performance criterion and accident-induced leakage performance criterion (explained in STS 5.5.9.b, items 1 and 2, respectively) will continue to be met with the proposed revised SG inspection intervals (maximum allowable time between SG inspections) and inspection periods (maximum allowable time between 100 percent of SG tubes inspections). Additionally, the proposed changes to the reporting requirements will provide more detailed and consistent information to the NRC. Therefore, the NRC staff found that the proposed changes to the SG program and inspection reporting requirements were acceptable because they continued to meet the requirements of 10 CFR 50.36(c)(5) by providing administrative controls necessary to assure operation of the facility in a safe manner.
The NRC staff compared the licensees proposed TS changes in Section 1.1 of this SE against the changes approved in TSTF-577. In accordance with SRP Chapter 16.0, the NRC staff determined that the STS changes approved in TSTF-577 are applicable because MNS is a PWR design plant and the NRC staff approved the TSTF-577 changes for PWR designs. The NRC staff finds that the licensees proposed changes to the MNS TSs in Section 1.1 of this SE are consistent with those found acceptable in TSTF-577. Thus,the NRC staff concludes that the corresponding proposed changes to the MNS TSs in Section 1.1 of this SE continue to meet the requirements of 10 CFR 50.36(c)(5).
3.2 Additional Proposed TS Changes 3.2.1 Editorial Variations The licensee noted that MNS TSs have different numbering than STSs on which TSTF-577 was based. Specifically, MNS uses TS 5.6.8 for Steam Generator Tube Inspection Report and the 2 U.S. Nuclear Regulatory Commission, Standard Technical Specifications, Westinghouse Plants, NUREG-1431, Volume 1, Specifications, and Volume 2, Bases, Revision 5, September 2021 (ADAMS Accession Nos. ML21259A155 and ML21259A159, respectively).
TSTF-577 uses TS 5.6.7. The NRC staff finds that the different TS numbering is acceptable because it does not substantively alter TS requirements.
3.3 TS Change Consistency The NRC staff reviewed the proposed TS changes for technical clarity and consistency with the existing requirements for customary terminology and formatting. The NRC staff finds that the proposed changes are consistent with Chapter 16.0 of the SRP and are therefore acceptable.
4.0 CONCLUSION
The Commission has concluded, based on the considerations discussed above, that: (1) there is reasonable assurance that the health and safety of the public will not be endangered by operation in the proposed manner, (2) there is reasonable assurance that such activities will be conducted in compliance with the Commissions regulations, and (3) the issuance of the amendment will not be inimical to the common defense and security or to the health and safety of the public.
SAFETY EVALUATION BY THE OFFICE OF NUCLEAR REACTOR REGULATION RELATED TO AMENDMENT NO. 191 TO RENEWED FACILITY OPERATING LICENSE NO. NPF-63 DUKE ENERGY SHEARON HARRIS NUCLEAR POWER PLANT, UNIT 1 DOCKET NO. 50-400 Application (i.e., initial and supplements)
Safety Evaluation Date September 16, 2021, ADAMS Accession No. ML21259A093 March 4, 2022 Principal Contributors to Safety Evaluation Clinton Ashley
1.0 PROPOSED CHANGE
S Duke Energy (the licensee) requested changes to the technical specifications (TSs) for Shearon Harris Nuclear Power Plant (HNP), Unit 1, by license amendment request (application). In its application, the licensee requested that the U.S. Nuclear Regulatory Commission (NRC, the Commission) process the proposed amendment under the Consolidated Line Item Improvement Process (CLIIP). The proposed changes would revise the Steam Generator (SG) Program and the Steam Generator (SG) Tube Inspection Report TSs based on Technical Specifications Task Force (TSTF) Traveler TSTF-577, Revision 1, Revised Frequencies for Steam Generator Tube Inspections (TSTF-577) (Agencywide Documents Access and Management System (ADAMS) Accession No. ML21060B434), and the associated NRC staff safety evaluation (SE) of TSTF-577 (ADAMS Accession No. ML21098A188).
The tubes within an SG function as an integral part of the reactor coolant pressure boundary and, in addition, isolate fission products in the primary coolant from the secondary coolant and the environment. SG tube integrity means that the tubes are capable of performing this safety function in accordance with the plant design and licensing basis.
HNP has one unit. The Unit 1 SGs have Alloy 690 thermally treated (Alloy 690TT) tubes.
1.1 Proposed TS Changes to Adopt TSTF-577 In accordance with NRC staff-approved TSTF-577, the licensee proposed changes that would revise HNP TS 6.8.4.l, Steam Generator (SG) Program, and TS 6.9.1.7, Steam Generator Tube Inspection Report. Specifically, the licensee proposed the following changes to adopt TSTF-577:
TS 6.8.4.l, Steam Generator (SG) Program:
The introductory paragraph to TS 6.8.4.I would be revised by replacing steam generator with SG in a couple instances.
TS 6.8.4.l.4.b would be revised by deleting the requirement to base inspection frequency on the more restrictive metric between either the effective full power months (EFPM) or refueling outage and to use just the EFPM metric.
TS 6.8.4.l.4.b would be revised by deleting the requirement to inspect 100 percent of the tubes during each period in paragraphs 4.b.1, 4.b.2, 4.b.3, and 4.b.4 (144, 120, 96, and 72 EFPM, respectively) and by adding the requirement to inspect 100 percent of the tubes every 96 EFPM.
TS 6.8.4.l.4.b would be revised by deleting the allowance to extend the inspection period by 3 effective full power months and by deleting the discussion of prorating inspections.
TS 6.8.4.l.4.c would be revised by replacing shall not exceed 24 effective full power months or one refueling outage (whichever results in more frequent inspections) with shall be at the next refueling outage.
TS 6.9.1.7, Steam Generator Tube Inspection Report:
Existing reporting requirement b. would be renumbered as c. and be revised by editorial and punctuation changes.
New reporting requirement b. would be added to require the nondestructive examination (NDE) techniques utilized for tubes with increased degradation susceptibility be reported.
Existing reporting requirement c. would be renumbered as c.1. and be revised by editorial and punctuation changes.
Existing reporting requirement d. would be renumbered as c.2. and be revised to note that the location, orientation (if linear), measured size (if available), and voltage response do not need to be reported for tube wear indications at support structures that are less than 20 percent through-wall. However, the total number of tube wear indications at support structures that are less than 20 percent through-wall would be reported.
New reporting requirement d. would be added to require an analysis summary of the tube integrity conditions predicted to exist at the next scheduled inspection relative to the applicable performance criteria, including the analysis, methodology, inputs, and results.
Existing reporting requirement e. would be renumbered as c.4. and be revised by editorial and punctuation changes.
Existing reporting requirement f. would be renumbered as e. and be revised by editorial and punctuation changes.
New reporting requirement f. would be added to require the results of any SG secondary side inspections be reported.
Existing reporting requirement g. would be renumbered as c.3. and be revised to add the requirements to report a description of the condition monitoring assessment, the margin to the tube integrity performance criteria, and a comparison with the margin predicted to exist at the inspection by the previous forward-looking tube integrity assessment. In addition, the requirement to report the results of tube pulls and in-situ testing would be deleted.
1.2 Additional Proposed TS Changes In addition to the changes proposed consistent with the traveler discussed in Section 1.1, the licensee proposed the following variations.
1.2.4 Editorial Variations The licensee identified one variation. The licensee noted that HNP TS have different numbering than standard technical specifications (STSs) on which TSTF-577 was based. Specifically, the Steam Generator (SG) Program is numbered 6.8.4.l in HNP Unit 1 TSs rather than 5.5.9 as stated in the TSTF. In addition, the Steam Generator Tube Inspection Report is numbered TS 6.9.1.7 in HNP Unit 1 TSs rather than 5.6.7 as stated in the TSTF.
2.0 REGULATORY EVALUATION
The regulations in Title 10 of the Code of Federal Regulations (10 CFR) paragraph 50.36(c)(5),
Administrative controls, state that [a]dministrative controls are the provisions relating to organization and management, procedures, recordkeeping, review and audit, and reporting necessary to assure operation of the facility in a safe manner. Each licensee shall submit any reports to the Commission pursuant to approved technical specifications as specified in
[10 CFR] 50.4. Technical Specification Section 5.0, Administrative Controls, requires that an SG Program be established and implemented to ensure that SG tube integrity is maintained.
Programs established by the licensee, including the SG Program, are listed in the administrative controls section of the TS to operate the facility in a safe manner.
The NRC staffs guidance for the review of TSs is in NUREG-0800, Standard Review Plan for the Review of Safety Analysis Reports for Nuclear Power Plants: LWR [Light-Water Reactor]
Edition (SRP), Chapter 16.0, Technical Specifications, Revision 3, dated March 2010 (ADAMS Accession No. ML100351425). As described therein, as part of the regulatory standardization effort, the NRC staff has prepared STSs for each of the LWR nuclear designs.
Accordingly, the NRC staffs review includes consideration of whether the proposed changes are consistent with NUREG-14313, as modified by NRC-approved travelers.
TSTF-577 revised the STSs related to SG tube inspections and SG tube inspection reporting requirements. The NRC approved TSTF-577, under the CLIIP on April 14, 2021 (ADAMS Package Accession No. ML21099A086). It addressed the applicable 10 CFR Part 50, Appendix A, General Design Criteria for Nuclear Power Plants requirements with respect to the integrity of the SG tubing.
3.0 TECHNICAL EVALUATION
3.1 Proposed TS Changes to Adopt TSTF-577 In the SE of TSTF-577, the NRC staff concluded that the TSTF-577 changes to STS 5.5.9, Steam Generator (SG) Program, and STS 5.6.7, Steam Generator Tube Inspection Report, were acceptable because, as discussed in Section 3.0 of that SE, they continued to ensure SG tube integrity and, therefore, protected the public health and safety. In particular, the structural integrity performance criterion and accident-induced leakage performance criterion (explained in STS 5.5.9.b, items 1 and 2, respectively) will continue to be met with the proposed revised SG inspection intervals (maximum allowable time between SG inspections) and inspection periods (maximum allowable time between 100 percent of SG tubes inspections). Additionally, the proposed changes to the reporting requirements will provide more detailed and consistent information to the NRC. Therefore, the NRC staff found that the proposed changes to the SG program and inspection reporting requirements were acceptable because they continued to meet the requirements of 10 CFR 50.36(c)(5) by providing administrative controls necessary to assure operation of the facility in a safe manner.
The NRC staff compared the licensees proposed TS changes in Section 1.1 of this SE against the changes approved in TSTF-577. In accordance with SRP Chapter 16.0, the NRC staff determined that the STS changes approved in TSTF-577 are applicable because HNP is a PWR design plant and the NRC staff approved the TSTF-577 changes for PWR designs. The NRC staff finds that the licensees proposed changes to the HNP TSs in Section 1.1 of this SE are consistent with those found acceptable in TSTF-577. Thus, the NRC staff concludes that the corresponding proposed changes to the HNP TSs in Section 1.1 of this SE continue to meet the requirements of 10 CFR 50.36(c)(5).
3.2 Additional Proposed TS Changes 3.2.1 Editorial Variations The licensee identified one variation. The licensee noted that HNP TSs have different numbering than STSs on which TSTF-577 was based. Specifically, the Steam Generator (SG)
Program is numbered 6.8.4.l in HNP Unit 1 TSs rather than 5.5.9 as stated in the TSTF. In addition, the Steam Generator Tube Inspection Report is numbered TS 6.9.1.7 in HNP Unit 1 3 U.S. Nuclear Regulatory Commission, Standard Technical Specifications, Westinghouse Plants, NUREG-1431, Volume 1, Specifications, and Volume 2, Bases, Revision 5, September 2021 (ADAMS Accession Nos. ML21259A155 and ML21259A159, respectively).
TSs rather than 5.6.7 as stated in the TSTF. The NRC staff finds that the different TS numbering is acceptable because it does not substantively alter TS requirements.
3.3 TS Change Consistency The NRC staff reviewed the proposed TS changes for technical clarity and consistency with the existing requirements for customary terminology and formatting. The NRC staff finds that the proposed changes are consistent with Chapter 16.0 of the SRP and are therefore acceptable.
4.0 CONCLUSION
The Commission has concluded, based on the considerations discussed above, that: (1) there is reasonable assurance that the health and safety of the public will not be endangered by operation in the proposed manner, (2) there is reasonable assurance that such activities will be conducted in compliance with the Commissions regulations, and (3) the issuance of the amendment will not be inimical to the common defense and security or to the health and safety of the public.
NOTICES AND ENVIRONMENTAL FINDINGS RELATED TO AMENDMENT NO. 311 TO RENEWED FACILITY OPERATING LICENSE NO. NPF-35 AND AMENDMENT NO. 307 TO RENEWED FACILITY OPERATING LICENSE NO. NPF-52 DUKE ENERGY CATAWBA NUCLEAR STATION, UNITS 1 AND 2 DOCKET NOS. 50-413 AND 50-414 AMENDMENT NO. 321 TO RENEWED FACILITY OPERATING LICENSE NO. NPF-9 AND AMENDMENT NO. 300 TO RENEWED FACILITY OPERATING LICENSE NO. NPF-17 DUKE ENERGY MCGUIRE NUCLEAR STATION, UNITS 1 AND 2 DOCKET NOS. 50-369 AND 50-370 AMENDMENT NO. 191 TO RENEWED FACILITY OPERATING LICENSE NO. NPF-63 DUKE ENERGY SHEARON HARRIS NUCLEAR STATION, UNITS 1 DOCKET NO. 50-400 Application (i.e., initial and supplements)
Safety Evaluation Date September 16, 2021, ADAMS Accession No. ML21259A093 March 4, 2022
1.0 INTRODUCTION
Duke Energy (the licensee) requested changes to the technical specifications (TSs) for Catawba Nuclear Station, Units 1 and 2, McGuire Nuclear Station, Units 1 and 2, and Shearon Harris Nuclear Power Plant, Unit 1 by license amendment request (application). In its application, the licensee requested that the U.S. Nuclear Regulatory Commission (NRC, the Commission) process the proposed amendment under the Consolidated Line Item Improvement Process (CLIIP). The proposed changes would revise the Steam Generator (SG) Program and the Steam Generator (SG) Tube Inspection Report TSs based on Technical Specifications Task Force (TSTF) Traveler TSTF-577, Revision 1, Revised Frequencies for Steam Generator Tube Inspections (TSTF-577) (Agencywide Documents Access and Management System (ADAMS)
Accession No. ML21060B434), and the associated NRC staff safety evaluation (SE) of TSTF-577 (ADAMS Accession No. ML21098A188).
2.0 STATE CONSULTATION
In accordance with the Commissions regulations, the North Carolina and South Carolina State officials were notified of the proposed issuance of the amendment on January 24,2022. The State officials had no comments.
3.0 ENVIRONMENTAL CONSIDERATION
The amendment relates, in part, to changes in recordkeeping, reporting, or administrative procedures or requirements. The amendment also relates, in part, to changing requirements with respect to the installation or use of facility components located within the restricted area as defined in Title 10 of the Code of Federal Regulations (10 CFR) Part 20. The NRC staff has determined that the amendment involves no significant increase in the amounts, and no significant change in the types, of any effluents that may be released offsite, and that there is no significant increase in individual or cumulative occupational radiation exposure. The Commission has previously issued a proposed finding that the amendment involves no significant hazards consideration, and there has been no public comment on such finding published in the Federal Register on December 28, 2021 (86 FR 73815). Accordingly, the amendment meets the eligibility criteria for categorical exclusion set forth in 10 CFR 51.22(c)(9) and 51.22(c)(10). Pursuant to 10 CFR 51.22(b), no environmental impact statement or environmental assessment need be prepared in connection with the issuance of the amendment.
- ML21342A272 OFFICE NRR/DORL/LPL2-2/PM NRR/DORL/LPL2-2/LA NRR/DSS/STSB/BC NAME AHon RButler VCusumano DATE 1/7/2022 1/20/2022 12/06/2021 OFFICE OGC/NLO NRR/DORL/LPL2-2/BC NRR/DORL/LPL2-2/PM NAME N/A*
DWrona AHon DATE 12/16/2021 3/4/2022 3/4/2022