ML20247D861

From kanterella
Jump to navigation Jump to search

Application for Amends to Licenses NPF-35 & NPF-52,changing Tech Spec 4.7.6.D Re Control Room Area Ventilation Sys Surveillance Requirements by Extending Carbon Absorber Sampling Frequency from 720 H to 1,440 H
ML20247D861
Person / Time
Site: Catawba  
Issue date: 07/14/1989
From: Tucker H
DUKE POWER CO.
To:
NRC OFFICE OF INFORMATION RESOURCES MANAGEMENT (IRM)
Shared Package
ML20247D867 List:
References
TAC-69503, TAC-69504, NUDOCS 8907250318
Download: ML20247D861 (3)


Text

i Dmus Powirn GoMrm P.O. Itax 33180 CHARLOTTE, N.C. 28242 HALB. TUCKER TELEPHONE 1

vue eummuerst (704) 373-4531 wtwera rmormmon l

July 14, 1989 1

Document Control Desk U.-S. Nuclear Regulatory Commission Washington, DC 20555

Subject:

Catawba Nuclear Station, Units 1 and 2 Docket Nos. 50-413 and 50-414 l

Proposed Technical Specification Amendment Technical Specification 4.7.6 Gentlemen:

My December 21, 1987 letter to the NRC transmitted a proposed Technical Specification amendment to Facility Operating License Nos. NPF-35 and l

NPF-52 far Catawba Units 1 and 2, respectively. The proposed change to Technical Specification, 4.7.6.D Control Room Area Ventilation System Surveillance Requirements, extended the carbon adsorber sampling frequency from 720 hours0.00833 days <br />0.2 hours <br />0.00119 weeks <br />2.7396e-4 months <br /> to 1440 hours0.0167 days <br />0.4 hours <br />0.00238 weeks <br />5.4792e-4 months <br />. The following information is provided to update my December 21, 1987 submittal.

Additional changes to Technical Specifications 3.7.6.A, 4.7.6.C, 4.7.6.D, 4.7.6.F, and 4.7.6.G seeking administrative clarifications and more conservative bypass leakage and methyl iodide penetration acceptance criteria are also being proposed.

Attachment I contains marked up pages of the current Technical

]

Specifications reflecting the requested change s.

Attachment II contains an updated No Significant Hazards Analysis and Environmental Impact Statement.

~

l l

It should be noted that my December 21, 1987 submittal indicated that j

sample canisters were used to obtain carbon adsorber samples. However, I

this practice was discontinued prior to submittal of the Technical j

Specification amendment request. Currently, sample.; are obtained by the j

grain thief method which involves insertion of a sampling rod into the

)

bed. The grain thief method provides samples more representative of the i

carbon adsorber bed condition than the sample canister method.

l Additional laboratory carbon sample analysis results have also become available since my December 21, 1987 submittal. A total of 67 tests have j

been performed over a period of six years covering typical atmospheric and j

seasonal conditions. These carbon sample analysis.results are discussed in the attached No Significant Hazards Analysis and Environmental Impact Statement.

f0 8907250318 890714 0i PDR ADOCK 05000413 P

FOC i ii

l 1

1 l

Document Control Desk i

Page 2 July 14, 1989 l

The conclusions of my December 21, 1987 submittal to the NF.C remain valid.

The proposed changes do not involve significant hazards considerations.

I i

Very truly yours, I

,4/h$ cot l

H. B. Tucker JGT/100/td Attachments I

cc:

Mr. E. D. Ebneter Regioaal Administrator, Region II U. S. Nuclear Regulatory Commission 101 Marietta St., NW, Suite 2900 Atlanta, Georgia 30323 Mr. W. T. Orders NRC Resident Inspector Catawba Nuclear Station Mr. Heyward Shealy, Chief l

Bureau of Radiological Health

(

l South Carolina Pepartment of Health &

Environmental Control 2600 Bull Street Columbia, SC 28201 American Nuclear Insurers c/o Dottie Sherman,.ANI Library The Exchange, Suite 245 270 Farmington Avenue Farcington, CT 06032 M&M Nuclear Consultants 1221 Avenue of the Americas New York, New York 10020 INPO Records Center Suite 1500 1100 Circle 75 Parkway Atlanta, GA 30339 l

1

'4' O

ATTACIMENT I MARKED-UP PAGES OF CURRENT TECHNICAL SPECIFICATIONS RFFLECTING REQUESTED CHANGES 1

1

_