a.-

g I-ENCLOSURE 2 BRUNSWICK STEAM ELECTRIC PIANT, UNITS 1 AND 2 NRC DOCKETS 50-325 & 50-324 OPERATING LICENSES DPR-71 & DPR-62 REMOTE SHUTDOWN MONITORING INSTRUMENTATION i

UPDATED TECHNICAL SPECIFICATION PAGES (NRC. TAC NOS. 68982 AND 68983)-

TECHNICAL SPECIFICATION PAGES - UNIT 1 i:

I 8907190297 890713 PDR ADOCK 05000324 P

PDC

- _ _ = - _ - _ _ _ _

s.

TABLE 3.3.5.2-1 REMOTE SHUTDOWN MONITORING INSTRUMENTATION MINIMUM READOUT CHANNELS FUNCTIONAL UNIT LOCATION OPERABLE

1. Reactor Vessel Pressure RSP(a) 1
2. Reactor Vessel Water Level RSP(a) y
3. Suppression Chamber Water Level RSP(a) 1
4. Suppression Chamber' Water Temperature RSP(a) 1 5.'Drywell Pressure RSP(a) 1
6. Drywell Temperature RSP(a) 1
7. Residual Heat Removal Head Spray Flow RSP(a) 1
8. Residual Heat Removal System Flow RSP(a) 1 (a) Remote Shutdown Panel, Reactor Building 20' Elevation BRUNSWICK - UNIT 1 3/4 3-57 Amendment No.

d l:

4 1

i >

TABLE 4.3.5.2-1 REMOTE SHUTDOWN MONITORING INSTRUMENTATION SURVEILLANCE REQUIREMENTS CHANNEL CHANNEL FUNCTIONAL UNIT CHECK CALIBRATION

1. Reactor Vessel Pressure M

Q

2. Reactor Vessel. Water Level N017 Instrument Loop:

NA Q

Remaining Instruments:

M Q

3. Suppression Chamber Water Level M

R

4. Suppression Chamber Water Temperature M

R

5. Drywell Pressure M

Q

6. Drywell Temperature' M

R 7.. Residual Heat Removal Head Spray Flow M

Q

8. Residual Heat Removal System Flow M

Q BRUNSWICK - UNIT 1 3/4 3-58 Amendment No.

1

.l 4

  • i ENCLOSURE 3 BRUNSWICK STEAM ELECTRIC PLANT, UNITS 1 AND 2 NRC DOCKETS 50-325 & 50-324 OPERATING LICENSES DPR-71 & DPR-62 REMOTE SHUTDOWN MONITORING INSTRUMENTATION UPDATED TECHNICAL SPECIFICATION PACES (NRC TAC NOS 68982 AND 68983)

TECHNICAL SPECIFICATION PAGES - UNIT _2

. +.

TABLE 3.,3.5.2-1 REMOTE SHUTDOWN MONITORING INSTRUMENTATION MINIMUM READOUT CHANNELS FUNCTIONAL UNIT LOCATION OPERABLE

1. Reactor Vessel Pressure RSP(a) 1
2. Reactor Vesse', Water Level RSP(a) 1
3. Suppression Chamber Water Level RSP(a) 1
4. Suppression Chamber Water Temperature RSP(a) 1
5. Drywell Pressure RSP(a) 1
6. Drywell Temperature RSP(a) 1-
7. Residual Heat Removal Head Spray Flow RSP(a) 1
8. Residual Heat Removal System. Flow RSP(a) 1 l.

(a) Remote Shutdown Panel, Reactor Building 20' Elevation BRUNSWICK - UNIT 2' 3/4 3-57 Amendment No.

lt--___----._--__-_

p:

.c TABLE 4.3.5.2-1 l?

REMOTE SHUTDOWN MONITORING INSTRUMENTATION SURVEILLANCE REQUIREMENTS CHANNEL CHANNEL.

FUNCTIONAL UNIT CHECK.

CALIBRATION'

1. Reactor Vessel Pressure M

Q

2. Reactor Vessel Water Level l

N017 Instrument Loop:

NA Q

Remaining Instruments:

M Q

3. Suppression Chamber Water Level M

R

4. Suppression Chamber Water Temperature M

R

5. Drytiell Pressure M

Q

6. Drywell Temperature M

R

7. Residual Heat Removal Head Spray Flow M

Q 8, Residual Heat Removal System Flow M

Q i

1 1

BRUNSWICK - UNIT 2 3/4 3-58 Amendment No.