CPS No.

2800.91 EMERGENCY RESERVE AUXILIARY TRANSFORMER TEST SCOPE OF REVISION:

i o New procedure.

This procedure will be used for initial testing of the LTC ERAT transformer installed under Plant Modification AP-40.

~

)

l CONHNUGUSUSE ORTGTNATOR:

Duffy Harmaker/ Gary Grizard CLASS CODE:

SNND APPROVAL DATE:

l CHANGE NO.

DATE PAGES O

O O

l O

9007200254 900717'-

DR ADOCK 05 4i Page No.

1 of 91 c-_----------

CPS No.

2800.91 TABLE OF CONTENTS j

i 1.0 Purpose 2.0 Discussion / Definitions 3.0 Responsibility 4.0 Precautions 5.0 Prerequisites i

i 6.0 Limitations 7.0 Materials and/or Test Equipment 8.0 Procedure 8.1 ERAT Transformer Component Testing 8.2 ERAT Annunciator Points 8.3 ERAT Transformer Cooling Fan Operation 8.4 ERAT Transformer Load Tap Changer 8.5 ERAT Circuit Switcher Operation 8.6 ERAT Protective Relay Scheme S 8.7 ERAT Protective Relay Scheme F

)

8.8 ERAT Transformer Initial Energization 9.0 Acceptance Criteria 10.0 Final Conditions 11.0 References 12.0 Appendices 13.0 Documents Rev. No.

O Page No.

2 of 91

CPS No.

2000.91 l

1.0' PURPOSE L

Provide for post-modification testing of the Emergency Reserve Auxiliary Transformer (ERAT), 0AP03E and 138KV Circuit Switcher (CS B018), OAP095E, for work performed y

i under plant modification AP-040.

This procedure does not include the Transformer Fire Protection deluge. nozzles discharge test, which will be performed as a separate procedure.

2.0-DISCUSSION / DEFINITIONS 2.1 Discussion 2.1.1 Modification Package AP-40 will install the new Emergency Reserve Auxiliary Transformer (ERAT) and Load Tap Changer (LTC).' Major components of this modification include the new ERAT transformer foundation, the new ERAT oil spill retention system, a new 138KV switcher. foundation, relocation of the existing circuit switcher (CS B018), 1AP095E, installation of new 4000 ampere overhead non-segregated bus duct, and associated foundations, a new-fire protection system, a.new grounding grid and additional area-lighting. The new transformer will be installed in the area southwest of the existing transformer. Installation of the new transformer-results from the degraded supply voltage occurrences experienced recently at Clinton Power Station. This-f Degraded Voltage problem has become a regulatory issue due to the frequency of entering the limited condition of operation LCO state. Another possible regulatory issue. concerns the operation of required equipment during-accident conditions. The reason for changing the existing ERAT is due to its MVA rating.

Once the static VAR (Volt Ampere Reactive) compensator is installed and placed in service there will be the possibility of' exceeding the MVA rating of the 1

transformer. The addition of the new ERAT, together with the added Static VAR Compensator will minimize degraded supply voltage problems and concerns.

j l

2.1.2 While performing this test, the initialing of a procedure step indicates that the step was completed satisfactorily p

and is acceptable.

2.1.3

'The Test Director (or certified test personnel designated by the Test Director) may sign for completion of

. prerequisites or test steps.

These items may be verified by personal observation, signature of responsible party, statement from certified personnel or operators completed documentation, or other means that the Test Director (or designee). deem suf ficient.

l

.Rev. No.

O Page No.

3 of 91

CPS No.

2800.91 2.1.4 Problems may be encountered which are not related to the Testing.

If this occurs, the Test Director shall evaluate the situation and note the resolution in the Test Log.

Sections of the Test may be re-performed as many times as necessary to ensure satisfactory operation.

2.1.5 Once in a section, that section shall be performed in sequence (except as noted in Section 8.2).

However, sections can be performed out of sequence to allow testing to continue.

(i.e. plant conditions or suppori from other departments.)

i 2.' 2 Definitions 2.2.1 Independent Verification - The act of Two qualified individuals independently or separately verifying that an action has been performed correctly.

Independent verification shall not be performed simultaneously with the action.

Independent is intended to require time and distance between the act and the verification.

This is denoted by a

/

in a procedure or document.

2.2.2 Double Verification - The act of two qualified individuals concurring that the action to be performed is correct.

This is denoted by a (DV)

/

in a procedure or locument.

2. 2. 3' Momentary Jumper - Application of a hand held jumper between designated' location points.

The jumper is applied o

and held only long enough to be sure that is applied to both points at the same time and is then removed.

3.0 RESPONSIBILITY 3.1 The Director of Plant Engineering is responsible for the proper implementation of the test procedure.

3.2 The Test Director is responsible for ensuring the test is i

performed in a safe and efficient manner, that required support is available and properly coordinated, all prerequisites are met, and dissemination of test status is p

made as appropriate.

The Test Director is responsible for informing the SM/WCS/CRS of changes in the test status and upon completion-of the test.

4.O PRECAUTIONS 4.- l Voltage measurements will be obtained on energized 120 Volt circuits. Ensure proper safety precautions are observed.

4.2 All work performed under this procedure shall comply with I

-Site Safety Procedures.

1 Rev.;No.

O Page No.

4 of 91

l CPS No.

2800.91' i

c4.3 ERAT transformer Fire Protection deluge valve 1FP101C will be blocked from initiating-a deluge during several sections of this test'by_ installation of a "C" clamp per Appendix B.

l 5.0

-PREREQUISITES-l

'5.1

.In conjunction with the SM/WCS/CRS,freview the following impact statements to determine required plant status to

-perform this test:

L ITS FUNCTIONS IMPACTED ITS 3.8.2 - AC Sources - Shutdown RPS TRIP - None CRVICS' ISOLATION - None

(

LOGIC TYPE - None MINIMUM OPERABLE CHANNELS - None PLANT / SYSTEM CONDITIONS REQUIRED TO CONDUCT THIS TEST Class 1E 4.16kV busses 1A1, 1B1, and'1Cl are powered from L

the-Reserve Auxiliary Transformer ( RAT) '.

i L-Emergency Reserve Auxiliary Transformer deenergized, ERAT i

transformer low side power terminations disconnected and I

tagged out. Disconnect switch IET4 tagged out in the OPEN position. The 138Kv line is disconnected from ERAT via L

circuit switcher B018 and a hold card in place from the Decatur Dispatcher.

OTHER SYSTEMS AFFECTED - ERAT Transformer Fire Protection Deluge Valve 1FP101C will be blocked from initiating a deluge of the ERAT during several sections of this test.

L OTHER. CHANNELS REQUIRED OPERABLE TO PREVENT INADVERTENT ACTUATION.

Reserve-Auxiliary-Transformer.available to supply the Class 1E-AC power distribution system.

/

SM/WCS/CRS TEST PERFORMER 5.2' Shift Manager Permission

'I Shift Manager's permission to perform test.

/

/

SM/WCS/CRS (Init. )

DATE TIME L

Rev. No.

O Page No.

5 of 91

CPS No.

2800.91 INITIALS 5.3 ERAT transformer low side power terminations disconnected and danger tagged.

5.4 Disconnect switch IET4 danger tagged in the OPEN position.

5.5 4KV Bus 1Al feed breaker 252-221A1, 4KV Bus 1B1 252-221B1, and 4kv Bus 1C1 feed breaker 252-221C1 are danger tagged open and racked out.

5.6 The ERAT Transformer is set on pad, fully assembled, and transformer control connections completed.

5.7 Establish communications between Main Control Room (MCR) and ERAT area.

5.~ 8 ABB site vendor testing has been reviewed and determined to be acceptable by the cognizant engineer. (MWR # D82231) 5.9 All inspections / testing by IP (Decatur) Doble Crew completed (TTR, Doble, Oil Sample, Excitation) and test results have been reviewed.

(If performed) (MWR # D82970) 5.10 Verify calibration of Measuring and Test Equipment to be useo.

5.11 Verify ERAT instrument calibration / loop checks for the following instruments / relays are-completed:

OEYAP066,27-1, Loss of Voltage Relay (MWR # D79983)

OEYAP067,27-2, Loss of Voltage Relay (MWR # D79984)

OEYAP068,27-3, Loss of Voltage Relay (MWR # D79985) l OEYAP066,27-4, Loss of Voltage Relay (MWR # D79986)

OTEAP070,49, Hot Spot Thermometer (MWR # D79987)

OXYAP071,59, Backup Relay LTC, (M-0329) (MWR # D79988)

OPYAP072,63, Sudden Pressure Relay (MWR # D79989)

OPYAP073,63FP, Fault Pressure Relay (MWR # D79990)

OPYAP074,63B, Pressure Relay (Tap changer)

(MWR # D79991)

OEYAP080,90, Voltage Regulating Relay (M-0067E)

(MWR # D79994)

I OTISAP063,2601, Hot Oil Thermometer (Transformer)

(MWR # D79981)-

l OTISAP063,26Q2, Hot Oil Thermometer (Tap Changer)

(MWR # D79982) l OPSAP059,Inertaire pressure switch, high pressure (MWR # D79979)

OPSAP060,Inertaire pressure switch, low pressure (MWR # D79980)

OPSAP061,Inertaire pressure switch, empty cylinder (MWR # D79978) i j

Rev. No.

O Page No.

6 of 91 j

i L_

___________________J

CPS No.

2800.91 INITIALS

.5.12 '

ERAT control wiring inspection complete.

(MWR # D82232).

5.13

, Ensure the following breakers are positioned as i

listed:

Breaker 8-l'(ERAT)

Off.

/

Breaker 8-2. (ERAT)

Off

/

l Breaker 8-3 (ERAT)

Off.

/

' Breaker.8-4 (ERAT)

Off

/-

Breaker 8-5-(ERAT)

Off

/

L Breaker,8-6 (ERAT)

ON

/

Breaker 8-7 (ERAT)

ON

/

Breaker 8M- (ERAT LTC)

ON(up or vr"tical)

/

g 480 VAC. ERAT RESERVE POWER (disconnect switch)

Of'f

/

'480 VAC ERAT' NORMAL POWER l

(disconnect switch)

Off

/

l-5.14' Ensure the following switches at the ERAT are positione'd as listed:

Main Cabinet 43-1, AUTO /OFF/ MAN OFF

/

43-2, AUTO /OFF/ MAN OFF

/-

43C, POS. 1/POS. 2

'POS.

1.

/

l 43S, LOCAL CONTROL /

LOCAL CONTROL

/-

REMOTE CONTROL TS, RELAY TEST /

RELAY TEST

/

RELAY OPERATE 43T, MANUAL CONTROL /

MANUAL CONTROL

/

AUTOMATIC CONTROL CS, MANUAL RAISE /

MID POSITION

/

MANUAL LOWER 90 VOLTAGE REGULATOR Direct

/

LTC Compartment 43TC, LOCAL /OFF/ REMOTE OFF

/

l 84CS, LOWER /OFF/ RAISE OFF

/

u L

5.15 Ensure Pre ERAT outage phase rotation check has L

been performed (MWR # D82234)

/

j i

L 5.16' (Record)

At the ERAT transformer, LIFT, identify-l' and tape ~theLPotential transformer field leads j

from the terminal locations listed below at ERAT Transformer Control Cabinet (Record on wire removal and installation form CPS No.

~

'8801.16F001.)

j

, Terminal Point B3 (DV)

/

Terminal Point B4 (DV)

/

L 15.17

'At the ERAT Transformer Area, OPEN, if necessary, 120'VAC ERAT TEMPORARY POWER' breaker.

(DV)

/

LRev. No..

O Page No.

7 of 91

CPS No.

2800.91 INITIALS 5.18 (Record)

At the ERAT Transformer, connect 120 VAC ERAT TEMPORARY POWER, by terminating the power source to the following locations (Record on wire ren. oval and installation form CPS No. 8801.16F001):

Terminal Point B3 (DV)

/

Terminal Point B4 (DV)

/

5.19 At the ERAT Transformer Area, OPEN, if necessary, 480 VAC ERAT NORMAL POWER disconnect switch. (DV)

/

5.20 (Record) ERAT Transformer, disconnect 480 VAC ERAT NORMAL POWER, by LIFTING the power source to the following locations at the ERAT Transformer (Record on wire removal and installation form CPS No. 8801.16F001):

l Terminal Point A37 (DV)

/

Terminal Point A38 (DV)

/

Terminal Point A39 (DV)

/

5.21 At the ERAT Transformer Area, OPEN, if necessary, 480 VAC ERAT. TEMPORARY POWER disconnect switch.

(DV)

'/

5.22 (Record)

At ERAT Transformer, connect 480 VAC l

ERAT TEMPORARY POWER, by LANDING the power source to the following locations at the ERAT Transformer (Record on wire removal and installation form CPS No. 8801.16F001):

Terminal Point A37 (DV)

/

Terminal Point A38 (DV)

/

]

Terminal Point A39 (DV)

/

NOTE Wire B31 is shown on drawing E02-AP99, Sht. 120 as being lifted from its normal terminal location until such. time that the NRC submittal for Automatic operation of the ERAT LTC is approved. It is landed in this procedure to enable testing of LTC Automatic Controls while the ERAT ir MOT connected to the plant electrical distribution system, and then lifted again prior to exiting the procedure.

5.23 (Record) At ERAT Transformer control cabinet, l

LAND, if necessary, wire 31 to Terminal Point l

B31. (Record on wire removal and installation form I

CPS No. 8801.16F001):

Terminal Point B31 (DV)

/

Rev. No.

O Page No.

8 of 91

CPS No.

2800.91 6.0 LIMITATIONS 6.1; HIf test ~results are unacceptable, the SM/WCS/CRS shall be notified immediately.to determine component / system operability.

6.2 Component / system operation shall be pcr approved plant procedures.

NOTE

,If a temporary. modification is used to support this test, install the temporary modification per CPS No. 1014.03, TEMPORARY MODIFICATIONS.

6.3 No test:or experiment.which involves a change in the ITS/ORM/ODCM cn: an unreviewed safety question shall be

, performed.

6.4 Should. unplanned bus transfers occur during the testing, testing shall be secured until the desired bus L

configuration can be reestablished, and questions / design i

reverified.

6.5 The transformer turns ratio shall be verified to be within tolerance, or: credit taken for IP Doble crew testing prior to electrical loads being transferred to the ERAT. This

-will ensure that an overvoltage condition is not created on the AC distribution system.

6.6 If at anytime during the performance.of this test procedure the SM/CRS deems it necessary to stop the performance of l

this test procedure, the testing shall be stopped,

l equipment placed in safe condition, and the jobsite

[

secured.

Interruption of this test. procedure at any point l

will not result in adverse impact on plant equipment.

l l

p.

i-Rev. No.

O Page No.

9 of 91

CPS No.

2800.91 6.8 Test steps shall be performed in the order written except as specified in section 8.2. Test Sections will be performed in the following sequence. Test Sections 8.1 through 8.7. may be performed in any order, but prior ic Test Section 8.8.

Test Section 8.8 must be performed after completion of Test Sections 8.1 through 8.7.

3.

START ll

!l mm a>vr ia l

I I

I I

I 8.1 8.2 8.3 8.4 8.5 8.6 8.7 I

I I

I I

I 8.8 END d

3

.. s 3

m

.o.

Rev. No.

O Page No.

10 of 91

CPS No.

2800.91 7.0 TEST EQUIPMENT 7.1 The following is a list of the test equipment required for the performance of this procedure. Equivalent tes.t equipment may be used.

TEST CALIB.

EQUIPMENT EIN ACCURACY RANGE DUE DATE 2 Voltmeters

+0.5% or 0-200 VAC Fluke 45 better (slow response)

TTR Tester N/A N/A 0-20 psig 15%

0-20 PSI Nitrogen Bottle with Pressure Gauge Chance Phasing Tool Hot Air Gun N/A N/A Recorder N/A 0-120 VAC 7.2 The following is a list of tools and material required for the performance of this procedure.

7.2:1 Wrenches as required to loosen the nitrogen fittings and connect an air bottle.

7.2.2 Wire Jumpers, 12 awg Rev. No.

O Page No.

11 of 91

r__.

CPS No.

2800.91 8.O PROCEDURE 8.1 ERAT TRANSFORMER COMPONENT TESTING NOTE Test Section 8.1 performs ERAT Transformer Component Testing. (TTR, DOBLE, Baseline Oil Sample)

NOTE The transformer turns ratio shall be. verified to-be'within tolerance, or credit taken for IP Doble' crew testing prior to electrical loads being transferred to the ERAT.

IF after review by the TEST Director, it has been determined that credit will be taken for Doble crew

itesting, THEN the applicable signoffs in.this section and

-Data Sheet.1 may be marked N/A'and Doble Crew Test results attached to this test package.

8.1.1 Verify ERAT Transformer is de-energized and obtain clearance.

/

8.1.2 Install safety grounds, as necessary.. Record on wire removal and installation form.

(DV)

/

8.1.3 Determinate High and Low side connections listed.

below, as necessary.(These_ leads will be reterminated in section 8.8 of:this test) Record on wire' removal and installation form 8801.16F001.

H0 (DV)

/

H1 (DV)

/

a H2 (DV)

/

H3 (DV)

/

X0 (DV)

/

X1 (DV)

/

l.

X2 (DV)

/

l X3 (DV)

/

8.1.4 At the ERAT Load Tap Changer Compartment, locate and_ engage the manual _ hand crank for the load tap changer.

8.1.5-(Record)'At the ERAT LTC Compartment locate the mechanical tap position indicator. Record the As Found Tap position Rev. No.

O.

Page No.

12 of 91

CPS No.

2800.91 8.1.6 (Record)

With the ERAT out of service, record on Data Sheet 1 the transformer turns ratio (As measured with the transformer turns ratio tester) for the mechanical tap position displayed on the tap position indicator in the LTC compartment.

8.1.7 VERIFY the reading obtained is within the tolerance as specified in Data Sheet 1.

8.1.8

.(Record)

Repeat steps 8.1. 6 and 8.1.'i for all ERAT tap positions.

8.1.9 Verify the readings obtained in step 8.1.6 are within the tolerance stated in Data Sheet 1 for all ERAT Load Tap Changer positions.

0A OB OC

\\

8.1.10 Return the LTC to the position recorded in step I

8.1.5 (As Found Position).

8.1.11 Disengage the LTC hand crank and return it to its storage location in the LTC compartment.

8.1.12 Perform Doble test of ERAT Transformer. Attach results to test package.

8.1.13 If not already performed, obtain Baseline Oil sample of ERAT Transformer per PEMAPM352.

l I

i I

i l

Rev. No.

O Page No.

13 of 91

L CPS No.

2800.91 8.2

' Annunciator Points NOTE Test Section 8.2 will functionally demonstrate proper operation of the ERAT local and Main Control Room Alarms.

NOTE This Section will cause_the following Main Control Room annunciator windows to alarm:

l

'5010-5F SUDDEN PRESS EMERG RES AUX TRANSFORMER 5010-6F TROUBLE EMERG RES AUX TRANSFORMER 5010-7F. HIGH TEMP EMERG RES AUX TRANSFORMER 8.2.1 Notify the Control Room. Operator that the following Main Control Room Annunciators will alarm during this test section:

5010-5E SUDDEN PRESS.EMERG RES AUX TRANSFORMER l

5010-6F TROUBLE EMERG RES AUX TRANSFORMER 5010-7F HIGH TEMP EMERG RES AUX TRANSFORMER

'8.2.2 CLOSE-the following breakers:

Breaker 8-1 (ERAT)

/

Breaker 8-3 (ERAT)

/

Breaker 8-4 (ERAT)

./

Breaker 8-5.(ERAT)'.

/

l 480VAC-ERAT-RESERVE POWER (disconnect switch)

/

480 VAC ERAT TEMPORARY POWER (disconnect switch)

/

120 VAC ERAT TEMPORARY POWER

/

'8.2.3 At'the ERAT,. perform the following:

a).

Ensure the following switches at the ERAT are

~

L positioned as listed:

l Main Cabinet

.43C, POS. 1/POS. 2

-POS. 1

/

435,, LOCAL' CONTROL /'

LOCAL CONTROL

/

i REMOTE CONTROL TS, RELAY' TEST /.

RELAY TEST

/

RELAY OPERATE

,43T, MANUAL CONTROL /

MANUAL CONTROL

/

-AUTOMATIC. CONTROL CS, MANUAL RAISE /

MID-POSITION

/

MANUAL LOWER LTC. Compartment 43TC, LOCAL /OFF/ REMOTE OFF

/

.84CS, LOWER /OFF/ RAISE OFF

/

Re'v.fNo.

0-Page No.

14 of 91

CPS No.

2800.91 b)

PLACE the following switches to the AUTO position:

43-1

/

43-2

/

NOTE Removal of relay K8 in the next step faciltates removal of a closed contact in parallel with 5 normally open contacts. The removed relay allows each normally open contact to be monitored during L

testing.The relay will be reinstalled later in this section and tested.

8.2.4 (Record)At ERAT transformer control panel, REMOVE auxiliary relay K8 from its' socket. Record on wire removal and installation form 8801.16F001.

(DV)

/

8.2.5 At ERAT Transformer control cabinet, INSTALL Digital Multimeter at Terminal Points W95 and W96 to monitor EMERG. RES. AUX. TRANSF. AVAILABLE INIDCATION signal to ERAT SVC.

8.2.6 At ERAT Transformer, perform the following:

a)

At local ERAT annunciator panel ENSURE there are no alarms present at points 1 through 11.

b)

Verify DMM reads an OPEN Circuit.

8.2.7 If necessary, at 1H13-P850, RESET the following annunciators:

5010-5F, SUDDEN PRESS RES AUX TRANSFORMER.

5010-6F, TROUBLE EMERG RES AUX TRANSFORMER I

5010-7F, HIGH TEMP EMERG RES AUX TRANSFORMER.

NOTE Steps 8.2.8 through 8.2.18 may be performed in any l

order to support testing.

NOTE The following steps will demonstrate the ERAT LOSS l

OF VOLTAGE ALARM 8.2.8 Perform ERAT LOSS OF VOLTAGE ALARM testing as follows.

Rev. No.

O Page No.

15 of 91 i.

CPS No.

2800.91 J

8.2.8.1 At ERAT local annunciator panel, PLACE the TEST-RESET /OFF-ON switch for point 6, LOSS OF VOLTAGE ALARM, to.the. TEST position.

[

8.2.8.2.At. ERAT Transformer, perform the following.:

a)

At local ERAT. annunciator panel, VERIFY ERAT local annunciator point 6, LOSS OF VOLTAGE ALARM, is in alarm, b)' Verify DMM reads a Closed Circuit.

8.2.8.3 Verify annunciator window 5010-6F,. TROUBLE l

EMERG RES' AUX TRANSFORMER, is in alarm.

8.2.8.4 At ERAT local annunciator panel, PLACE the TEST-l RESET /OFF-ON switch 'for point 6, LOSS OF VOLTAGE ALARM, to the OFF position.

8.2.8.5 At ERAT Transformer, perform the following:

l

-a)

At local ERAT annunciator panel, VERIFY ERAT l

local'annunci'ator point 6,= LOSS OF VOLTAGE i-ALARM, will c1 ear L

b)

Verify DMM reads an OPEN Circuit.

l' l-8.2.8.6 Verify annunciator. window 5010-6F, TROUBLE EMERG i

RES AUX TRANSFORMER, will clear.

('

8.2.8.7 At ERAT l'ocal annunciator panel, PLACE the TEST-RESET /OFF-ON switch for point 6, LOSS OF VOLTAGE ALARM, to'the ON position.

8.2.8.8 At' ERAT Transformer, perform the fol-lowing:

a)

At local ERAT annunciator panel, VERIFY ERAT local annunciator-point 6, LOSS OF VOLTAGE l-ALARM, is clear b)

Verify DMM reads an OPEN Circuit.

8.2.8.9 Verify annunciator' window 5010-6F, TROUBLE EMERG RES AUX. TRANSFORMER, is clear.

+

NOTE ERAT Local Annunciator Point 11, BACKUP RELAY, will l-alarm if ERAT transformer breaker 8-1 is open for l

. great'er than 3 minutes. This is an expected-response.

8.2.8.10 OPEN breaker 8-1.

(DV)

-/

l

' Rev.L No'.

O Page No.

16 of 91 t.

l

CPS No.

2800.91 8.2.8.11 At' ERAT T.ransformer, perform the ' following:

a)- VERIFY ERAT local annunciator point 6, - LOSS i

OF VOLTAGE ALARM, is in alarm.

.b)

Ver;fy DMM. reads a Closed Circuit.

8.2.8.11 Verify annunciator window 5010-6F, TROUBLE EMERG RES AUN TRANSFORMER, is in alarm.

l 8.2.8.13 After approximately 3 minutes after opening breaker 8-1. (step. 8.2. 8.10) verify ERAT local annunciator point 11, BACKUP RELAY, is in alarm.

/

8.2.8.14 AT ERAT Transformer, Breaker S.1._

(DV)

/

1' l

8.2.8.15 Verify the following:

a)

VERIFY ERAT local annunciator point 6, LOSS OF VOLTAGE ALARM, is'still in alarm.

I b). Verify DMM' reads a Closed Circuit.

c)

. Verify annunciator. window 5010-6F, TROUBLE EMERG RES AUX TRANSFORMER, is still in alarm.

d)

VERIFY ERAT local' annunciator point ll, l

BACKUP RELAY, is still in alarm.

8.2.8.16 At ERAT local annunciator panel perform the following:

a)~

PLACE the TEST-RESET /OFF-ON switch ~for point L

6, LOSS OF VOLTAGE' ALARM, to the OFF

. position.

b)

PLACE the-TEST-RESET /OFF-ON switch for point 11-BACKUP RELAY, to the OFF position.

8.2.8.17 At ERAT Transformer, perform the following:

a) ~

At local ERAT-annunciator panel, VERIFY ERAT local annunciator point 6, LOSS OF VOLTAGE ALARM, will clear b)

At local ERAT annunciator panel, VERIFY ERAT local annunciator point 11, BACKUP RELAY, o

will clear c)

Verify DMM reads an OPEN Circuit.

8.2.8.18. Verify' annunciator window 5010-6F, TROUBLE EMERG RES AUX TRANSFORMER, will clear.

I

\\

8.2.8.19 At ERAT local annunciator panel, PLACE the TEST-l RESET /OFF-ON switch for point 6 to the ON

~

position.

j L

'RevfNo.

0-Page No.

17 of 91 e

CPS No.

2000.91 0.2.8.20 At ERAT Transformer, perform the following:

a)

At local ERAT annunciator panel, VERIFY ERAT local annunciator point 6, LOSS OF VOLTAGE ALARM, is clear b)- Verify DMM reads an OPEN Circuit.

)

8.2.8.21 Verify annunciator window 5010-6F, TROUBLE EMERG RES AUX TRANSFORMER, is clear.

8.2.8.22 OPEN breaker 8-6.

(DV)

/

8.2.8.23 At ERAT Transformer, perform the following:

I a)

VERIFY ERAT local annunciator point 6, LOSS OF VOLTAGE ALARM, is in alarm.

b)

Verify DMM reads a Closed Circuit.

8.2.8.24 Verify annunciator window 5010-6F, TROUBLE EMERG RES AUX TRANSFORMER, is in alarm.

8.2.8.25 CLOSE breaker 8-6.

/

8.2.8.26 At ERAT Transformer, perform the following:

a)

VERIFY ERAT local annunciator point 6, LOSS OF VOLTAGE ALARM, is still in alarm.

l b)

Verify DMM reads a closed Circuit.

l 8.2.8.27 Verify annunciator window 5010-6F, TROUBLE EMERG RES AUX TRANSFORMER, is still in alarm.

8.2.8.28 At ERAT local annunciator panel, PLACE the TEST-RESET /OFF-ON switch for point 6, LOSS OF VOLTAGE ALARM, to the OFF-position.

8.2.8.29 At ERAT Transformer, perform the following:

a)

At local ERAT annunciator panel, VERIFY ERAT local annunciator point 6, LOSS OF VOLTAGE ALARM, will clear l

b)

Verify DMM reads an OPEN Circuit.

8.2.8.30 Verify annunciator window 5010-6F, TROUBLE EMERG RES AUX TRANSFORMER,-will clear.

8.2.8.31 At ERAT local annunciator panel, PLACE the TEST-RESET /OFF-ON switch for point 6 to the ON position.

l L

f

-Rev. No.

O Page No.

18 of 91 l

L

CPS No.

.2800.91 8.2.8.32 At ERAT Transformer, perform the following:

a)

At' local ERAT annunciator panel, VERIFY ERAT local annunciator point 6, LOSS OF VOLTAGE ALARM,'will clear b).

Verify DMM reads an OPEN Circuit..

. 8.2.8.33. Verify annunciator window 5010-6F, TROUBLE EMERG RES AUX TRANSFORMER is clear.

8.2.8.34 OPEN breaker 8-7.

(DV)

/

8.2.8.35-At ERAT Transformer, perform the following:

a). VERIFY ERAT local annunciator point;6, LOSS

'OF VOLTAGE ALARM, is in alarm.

b)

Verify DMM reads a Closed Circuit.

'8.2.8.36 Verify annunciator window.5010-6F, TROUBLE EMERG RES AUX TRANSFORMER, is in alarm.

8.2.8.37 CLOSE breaker 8-7.

/

8.2.8.38 At ERAT Transformer, perform the following:

a)

VERIFY. ERAT local annunciator point 6, LOSS OF VOLTAGE ALARM, is still.in alarm.

b). Verify DMM reads a Closed Circuit.

8.2.8.39 Verify-annunciator window'5010-6F, TROUBLE EMERG RES AUX TRANSFORMER, is still in alarm.

8.2.8.40 At ERAT local annunciator panel, PLACE the TEST-RESET /OFF-ON switch for point 6, LOSS OF VOLTAGE j

ALARM, to the OFF position.

8.2.8.41 At ERAT Transformer, perform the follcwing:

a)

At local ERAT annunciator panel, VERIFY ERAT local annunciator point 6, LOSS OF VOLTAGE ALARM, will clear b)

Verify DMM reads an OPEN Circuit.

1 8.2.8.42 Verify annunciator window 5010-6F, TROUBLE EMERG RES AUX TRANSFORMER, will clear.

i 8.2.8'.43 At ERAT local annunciator panel, PLACE the TEST-L RESET /OFF-ON switch for point 6 to the ON position.

l l

1;

Rev; No.

O Page No.

19 of 91

CPS No.

2800.91 8.2.8.44 At ERAT Transformer, perform the following:

a)

At local ERAT annunciator panel, VERIFY ERAT local annunciator point 6, LOSS OF VOLTAGE ALARM, will clear b)

Verify DMM reads an OPEN Circuit.

8.2.8.45 Verify annunciator window 5010-6F, TROUBLE EMERG RES AUX TRANSFORMER will clear.

8.2.8.46 OPEN breaker 8-4.

(DV)

/

l-l 8.2.8.47 At ERAT Transformer, perform the following:

1 a)

VERIFY ERAT local annunciator point 6, LOSS OF VOLTAGE ALARM, is in alarm.

b)

Verify DMM reads a Closed Circuit.

8.2.8.48 Verify annunciator window 5010-6F, TROUBLE EMERG RES AUX TRANSFORMER, is in alarm.

8.2.8.49 CLOSE breaker 8-4.

/

8.2.8.50 At ERAT Transformer, perform the following:

a)

VERIFY ERAT local annunciator point 6, LOSS OF VOLTAGE ALARM, is still in alarm.

b)

Verify DMM reads a closed Circuit.

'8.2.8.51 Verify annunciator window 5010-6F, TROUBLE EMERG RES AUX TRANSFORMER, is still in alarm.

8.2.8.52 At ERAT local annunciator panel, PLACE the TEST-RESET /OFF-ON switch for point 6, LOSS OF VOLTAGE ALARM, to the OFF position.

8.2.8.53 At ERAT Transformer, perform the following:

a)

At local ERAT annunciator panel, VERIFY ERAT local annunciator point 6, LOSS OF VOLTAGE ALARM, will clear b)

Verify DMM reads an OPEN Circuit.

8.2.8.54 Verify annunciator window 5010-6F, TROUBLE EMERG RES AUX TRANSFORMER, will clear.

8.2.8.55 At ERAT. local annunciator panel, PLACE the TEST-RESET /OFF-ON switch for point 6 to the ON position.

Rev.'No.

O Page No.

20 of 91

-____x___.__

CPS No.

2800.91 8.2.8.56 At ERAT Transformer, perform the following:

i a)

At local ERAT annunciator panel, VERIFY ERAT local annunciator point 6, LOSS OF VOLTAGE ALARM, will clear, b)

Verify DMM reads an OPEN Circuit.

8.2.8.57 Verify annunciator window 5010-6F, TROUBLE EMERG RES AUX TRANSFORMER will clear.

l 8.2.8.58 AT ERAT Transformer control panel, PLACE 43-1, l

AUTO /OFF/ MAN switch to the OFF position.

(DV)

/

8.2.8.59 At ERAT Transformer, perform the following:

a)

VERIFY ERAT local annunciator point 6, LOSS OF VOLTAGE ALARM, is in alarm.

b)

Verify DMM reads a Closed Circuit.

i 8.2.8.60 Verify annunciator window 5010-6F, TROUBLE EMERG I

RES AUX TRANSFORMER, is in alarm.

' 8.2.8.61 AT ERAT Transformer control panel, PLACE 43-1, AUTO /OFF/ MAN switch to the AUTO position.

/

8.2.8.62 At ERAT Transformer, perform the following:

l a)

VERIFY ERAT local annunciator point 6, LOSS I

OF VOLTAGE ALARM, is still in alarm.

b)

Verify DMM reads a Closed Circuit.

8.2.8.63 Verify annunciator window 5010-6F, TROUBLE EMERG RES AUX TRANSFORMER, is still in alarm.

8.2.8.64 At ERAT local annunciator panel, PLACE the TEST-RESET /OFF-ON switch for point 6, LOSS OF VOLTAGE ALARM, to the OFF position.

8.2.8.65 At ERAT Transformer, perform the following:

a)

At local ERAT annunciator panel, VERIFY ERAT l

local annunciator point 6, LOSS OF VOLTAGE

)

ALARM, will clear

(

b)

Verify DMM reads an OPEN Circuit.

i i

8.2.8.66 Verify annunciator window 5010-6F, TROUBLE EMERG RES AUX TRANSFORMER, will clear.

8.2.8.67 At ERAT local annunciator panel, PLACE the TEST-RESET /OFF-ON switch for point 6 to the ON position.

Rev. No.

O Page No.

21 of 91 L_

CPS No.

2800.91 0.2.8.68 At ERAT Transformer, perform the following:

a)

At local ERAT annunciator panel, VERIFY ERAT local annunciator point 6, LOSS OF VOLTAGE ALARM, will clear b)

Verify DMM reads an OPEN Circuit.

8.2.8.69 Verify annunciator window 5010-6F, TROUBLE EMERG RES AUX TRANSFORMER will clear.

8.2.8.70 AT ERAT Transformer control panel, PLACE 43-2, AUTO /OFF/ MAN switch to the OFF position.

(DV)

/

8.2.8.71 At ERAT Transformer, perform the following:

a)

VERIFY ERAT local annunciator point 6, LOSS OF VOLTAGE ALARM, is in alarm.

b)

Verify DMM reads a Closed Circuit.

8.2.8.72 Verify annunciator window 5010-6F, TROUBLE EMERG RES' AUX TRANSFORMER, is in alarm.

8.2.8.73 AT ERAT Transformer control panel, PLACE 43-2, AUTO /OFF/ MAN switch to the AUTO position.

/

8.2.8.74 At ERAT Transformer, perform the following:

.a)

VERIFY ERAT local annunciator point 6, LOSS OF VOLTAGE ALARM, is still in alarm.

b)

Verify DMM reads a closed Circuit.

8.2.8.75 Verify annunciator window 5010-6F, TROUBLE EMERG RES AUX TRANSFORMER, is still in alarm.

8.2.8.76 At ERAT local annunciator panel, PLACE the TEST-RESET /OFF-ON switch for point 6, LOSS OF VOLTAGE ALARM, to the OFF position.

8.2.8.77 At ERAT Transformer, perform the following:

a)

At local ERAT annunciator panel,. VEh1FY ERAT local annunciator point 6, LOSS OF VGLTAGE ALARM, will clear b)

Verify DMM reads an OPEN Circuit.

8.2.8.78 Verify annunciator window 5010-6F, TROUBLE EMERG i

RES AUX TRANSFORMER, will clear.

8.2.8.79 At ERAT local annunciator panel, PLACE the TEST-RESET /OFF-ON switch for point 6 to the ON position.

Rev.-No.

O Page No.

22 of 91_

l I

CPS No.

2800.91 8.2.8.80 At ERAT Transformer, perform the following:

a)

At local ERAT annunciator panel, VERIFY ERAT local annunciator point 6, LOSS OF VOLTAGE ALARM, will clear b)

Verify DMM reads an OPEN Circuit.

8.2.8.81 Verify annunciator window 5010-6F, TROUBLE EMERG RES AUX TRANSFORMER will clear.

NOTE The following steps will demonstrate the ERAT BACK UP RELAY ALARM 8.2.9 Perform ERAT BACK UP RELAY ALARM testing as follows:

8.2.9.1 At ERAT local annunciator panel, PLACE the TEST-RESET /OFF-ON switch for point 11, BACK-UP RELAY to the TEST position.

8.2.9.2 At ERAT Transformer, perform the following:

a)

VERIFY ERAT local annunciator point 11, BACK-UP RELAY, is in alarm.

b)

Verify DMM reads a Closed Circuit.

8.2.9.3 Verify annunciator window 5010-6F, TROUBLE EMERG RES AUX TRANSFORMER, is in alarm.

8.2.9.4 At ERAT local annunciator panel, PLACE the TEST-RESET /OFF-ON switch for point 11, BACK-UP RELAY to the OFF position.

8.2.9.5 At ERAT Transformer, perform the following:

a)

At local ERAT annunciator panel, VERIFY ERAT local annunciator point 11, BACK-UP RELAY will clear, b)

Verify DMM reacs an OPEN Circuit.

8.2.9.6 Verify annunciator window 5010-6F, TROUBLE EMERG RES AUX TRANSFORMER, will clear.

8.2.9.7 At ERAT local annunciator panel, PLACE the TEST-RESET /OFF-ON switch for point 11, BACK-UP RELAY to the ON position.

8.2.9.8 At ERAT Transformer, perform the following:

a)

At local ERAT annunciator panel, VERIFY ERAT local annunciator point 11, BACK-UP RELAY will clear.

b)

Verify DMM reads an OPEN Circuit.

Rev. No.

O Page No.

23 of 91

CPS No.

2800.91 8.2.9.9 Verify annunciator window 5010-6F, TROUBLE EMERG RES AUX TRANSFORMER, is clear.

8.2.9.10 At ERAT control panel, Locate LTC BACKUP RELAY M-0329A (Device 59 as shown on Dwg.

E02-1AP99-120) i 8,2.9.11 RECORD setting for BANDCENTER and BANDWIDTH below (AS Found Setting):

I I

BANDCENTER Volts BANDWIDTH Volts 8.2.9.12 Set the BANDCENTER dial to 100V (minimum setting).

8.2.9.13 After approximately 3 minutes, perform the following:

a)

VERIFY ERAT local annunciator point 11, BACK-UP RELAY, is in alarm.

I b)

Verify DMH reads a Closed Circuit.

8.2.9.14 Verify annunciator window 5010-6F, TROUBLE EMERG RES AUX TRANSFORMER, is in alarm.

8.2.9.15 Return BANDCENTER dial setting to the AS FOUND SETTING.

Record the AS LEFT setting below:

Volts 8.2.9.16 At ERAT Transformer, perform the following:

a)

VERIFY ERAT local annunciator point 11, BACK-UP RELAY, is still in alarm.

]

b)

Verify DMM reads a Closed Circuit.

8.2.9.17 Verify annunciator window 5010-6F, TROUBLE EMERG RES AUX TRANSFORMER, is still in alarm.

l 8.2.9.18 At ERAT local annunciator panel, PLACE the TEST-RESET /OFF-ON switch for point 11, BACK-UP RELAY to the OFF position.

8.2.9.19 At ERAT Transformer, perform the following:

a)

At local ERAT annunciator panel, VERIFY ERAT local annunciator point 11, BACK-UP RELAY will clear.

b)

Verify DMM reads an OPEN Circuit.

l 8.2.9.20 Verify annunciator window 5010-6F, TROUBLE EMERG RES AUX TRANSFORMER, will clear.

j 8.2.9.21 At ERAT local annunciator panel, PLACE the TEST-RESET /OFF-ON switch for point 11, BACK-UP RELAY to the ON position.

Rev. No.

O Page No.

24 of 91

CPS No.

2800.91 8.2.9.22 At ERAT Transformer, perform the following:

a)

At local ERAT annunciator panel, VERIFY ERAT local annunciator point 11, BACK-UP RELAY will clear.

b)

Verify DMM reads an OPEN Circuit.

8.2.9.23 Verify annunciator window 5010-6F, TROUBLE EMERG RES AUX TRANSFORMER is clear.

NOTE The following steps will demonstrate the ERAT INERTAIRE ALARM 8.2.10 Perform INERTAIRE ALARM testing as follows:

8.2.10.1 At ERAT local annunciator panel, PLACE the TEST-RESET /OFF-ON switch for point 10, INERTAIRE, to the TEST position.

8.2.10.2 At ERAT Transformer, perform the following:

a)

VERIFY ERAT local annunciator point 10, INERTAIRE,is in alarm.

b)

Verify DMM reads a Closed Circuit.

8.2.10.3 Verify annunciator window 5010-6F, TROUBLE EMERG RES AUX TRANSFORMER, is in alarm.

.8.2.10.4 At ERAT local annunciator panel, PLACE the TEST-RESET /OFF-ON switch for point 10, INERTAIRE, to the OFF position.

8.2.10.5 At ERAT Transformer, perform the following:

a)

VERIFY ERAT local annunciator point 10, INERTAIRE,will clear.

b)

Verify DMM reads an OPEN Circuit.

j l

8.2.10. 6. Verify annunciator window 5010-6F, TROUBLE EMERG RES AUX TRANSFORMER, will clear.

8.2.10.7 At ERAT local annunciator panel, PLACE the TEST-RESET /OFF-ON switch for point 10, INERTAIRE, to the ON position.

l 1

8.2.10.8 At ERAT Transformer, perform the following:

a)

VERIFY ERAT local annunciator point 10, INERTAIRE,will clear.

b)

Verify DMM reads an OPEN Circuit.

Rev. No.

O.

Page No.

25 of 91 E_______________

CPS No.

2800.91 8.2.10. 9 Verify ' annunciator window 5010-6F, TROUBLE EMERG RES AUX TRANSFORMER, is clear.

8.2.10.10 CLOSE 0AP012, CONDENSATE SUMP OUTLET VALVE, to isolate the transformer gas space from the regulator system.

(DV)

/

8.2.10.11 OPEN 0AP014, HIGH PRESSURE REGULATOR BYPASS VALVE.

(DV)

/

8.2.10.12 Loosen the 1/2 inch jam nut on the high pressure regulator's T-handle.

NOTE The INERTAIRE pressure relief unit will begin relieving at approximately 6.5 psi, venting pressure through two ports in the rear of the unit.

This is an expected response.

8.2.10.13 While watching the pressure / vacuum gauge, turn the T-handle clockwise slowly to increase the pressure.

Continue to increase the pressure until local annunciator point 10, INERTAIRE, is in alarm (Appre..mately 8.5 psi), and DMM reads a Closed Circuit (Test Engineer may restrict flow through the ports i

of the INERTAIRE pressure relief unit with his finger, as needed).

l 8.2.10.14 Verify annunciator window 5010-6F, TROUBLE EMERG RES AUX TRANSFORMER, is in alarm.

8.2.10.15 (Record) Turn the regulator T-handle counter-clockwise to reduce the pressure to approximately 5 psi as read on the pressure / vacuum gauge. Excess pressure may be bled by briefly opening the manifold's drain cock and watching the pressure / vacuum gauge stabilize. When' pressure has stabilized at approximately 5 psi, retighten the jam nut.

Record the as left pressure below:

psi (As Left) 8.2.10.16 At ERAT Transformer, perform the following:

a) VERIFY ERAT local annunciator point 10, INERTAIRE, is still in alarm.

b) Verify DMM reads a Closed Circuit.

8.2.10.17 Verify annunciator window 5010-6F, TROUBLE EMERG RES AUX TRANSFORMER, is still in alarm.

Rev. No.

-0 Page No.

26 of 91 L______-_-_-___________-_-____-__

CPS No.

2800.91 8.2.10.18 At ERAT local annunciator panel, PLACE the TEST-RESET /OFF-ON switch for point 10, INERTAIRE, to the OFF position.

8.2.10.19 At ERAT Transformer, perform the following:

a) VERIFY ERAT local annunciator point 10, INERTAIRE,will clear, b) Verify DMM reads an OPEN Circuit.

8.2.10.20 Verify annunciator window 5010-6F, TROUBLE EMERG RES AUX TRANSFORMER, will clear.

8.2.10.21 At ERAT local annunciator panel, PLACE the TEST-RESET /OFF-ON switch for point 10, INERTAIRE, to the ON position.

8.2.10.22 At ERAT Transformer, perform the following:

a) VERIFY ERAT local annunciator point 10, INERTAIRE, is clear.

b) Verify DMM reads an OPEN Circuit.

8.2.10.23 Verify annunciator window 5010-6F, TROUBLE EMERG RES AUX TRANSFORMER is clear.

8.2.10.24 Slowly CLOSE 0AP014, HIGH PRESSURE REGULATOR BYPASS VALVE,until the manifold pressure, as read on the pressure / vacuum gauge, is approximately 0.5 psi. Continue closing the bypass valve until it is completely closed.

(DV)

/

8.2.10.25 OPEN 0AP015, CONDENSATE SUMP DRAINCOCK, as necessary, until the local annunciator point 10, INERTAIRE, is in alarm, (Approximately 0.25 psi manifold pressure as read on the pressure / vacuum gauge), and VERIFY DMM reads a closed circuit.

(DV)

/

8.2.10.26 Verify annunciator window 5010-6F, TROUBLE EMERG RES AUX TRANSFORMER, is in alarm.

8.2.10.27 CLOSE 0AP015, CONDENSATE SUMP DRAINCOCK.

/

l 8.2.10.28 At ERAT Transformer, perform the following:

a) VERIFY ERAT local annunciator point 10, INERTAIRE, is still in alarm.

b) Verify DKM reads a Closed Circuit.

8.2.10.29 Verify annunciator window 5010-6F, TROUBLE EMERG RES AUX TRANSFORMER, is still in alarm.

Rev. No.

O Page No.

27 of 91 l;

CPS No.

2800.91 8.2.10.30 At ERAT local annunciator panel, PLACE the TEST-RESET /OFF-ON switch for point 10, INERTAIRE, to the OFF position.

8.2.10.31 At ERAT Transformer, perform the following:

a) VERIFY ERAT local annunciator point 10, INERTAIRE, will clear.

b) Verify DMM reads an OPEN Circuit.

8'.2.10.32 Verify annunciator window 5010-6F, TROUBLE EMERG RES AUX TRANSFORMER, will clear.

8.2.10.33 At ERAT local annunciator panel, PLACE the TEST-RESET /OFF-ON switch for point 10, INERTAIRE, to the ON position.

1 8.2.10.34 At ERAT Transformer, perform the following:

a) VERIFY ERAT local annunciator point 10, INERTAIRE,will clear, b) Verify DMM reads an OPEN Circuit.

8.2.10.35 Verify annunciator window 5010-6F, TROUBLE EMERG RES AUX TRANSFORMER will clear.

8.2.10.36 CLOSE 0AP001, NITROGEN CYLINDER ISOLATION

]

valve, located on top of the installed nitrogen cylinder.

8.2.10.37 Slowly loosen the connection between the nitrogen cylinder and the INERTAIRE system's high pressure hose by turning the union nut counterclockwise until local ERAT annunciator point 10, INERTAIRE, alarms, and VERIFY DMM reads Closed Circuit.

8.2.10.38 Verify annunciator window 5010-6F, TROUBLE i

EMERG RES AUX TRANSFORMER, is in alarm.

L8.2.10.39 Tighten the connection between the nitrogen cylinder and the Inertaire's high pressure hose.

8.2.10.40 OPEN OAP001, NITROGEN CYLINDER ISOLATION valve, located on top of the installed nitrogen cylinder.

8.2.10.41 At ERAT Transformer, perform the following:

a) VERIFY ERAT local annunciator point 10, INERTAIRE, is still in alarm.

b) Verify DMM reads a Closed Circuit.

Rev. No.

O Page No.

28 of 91 L

CPS No.

2800.91 8.2.10.42

. Verify annunciator window 5010-6F, TROUBLE EMEBG RES AUX TRANSFORMER,.is still in alarm.

8.2.10.43 At ERAT local annunciator panel, PLACE the TEST-RESET /OFF-ON switch for point 10, INERTAIRE, to the OFF position.

8.2.10.44 At ERAT Transformer, perform the following:

a) VERIET ERAT local annunciator point 10, INERTAIRE,will clear.

b) Verify DMM reads an OPEN Circuit.

8.2.10.45 Verify annunciator window 5010-6F, TROUBLE EMERG RES AUX TRANSFORMER, will clear.

8.2.10.46 At ERAT local annunciator panel, PLACE the TEST-RESET /OFF-ON switch for point 10, INERTAIRE, to the ON position.

8.2.10.47 At ERAT Transformer, perform the following:

a)

VERIFY ERAT local' annunciator point 10, INERTAIRE,will clear.

b)

Verify DMM reads an OPEN Circuit.

8.2.10.48 Verify annunciator window 5010-6F,. TROUBLE EMERG RES AUX TRANSFORMER, will clear.

8. 2.10. t3 OPEN 0AP012, CONDENSATE SUMP OUTLET VALVE.

(DV)

/

NOTE The following steps will demonstrate the ERAT LOSS OF NORMAL SUPPLY ALARM 8.2.11 Perform NORMAL SUPPLY ALARM testing as follows:

8.2.11.1 At ERAT local annunciator panel, PLACE the TEST-RESET /OFF-ON switch for point 9, LOSS OF NORMAL SUPPLY, to the TEST position.

8.2.11.2 At ERAT Transformer, perform the following:

a)

VERIFY ERAT local annunciator point 9, LOSS l'

OF NORMAL SUPPLY, is in alarm.

b)

Verify DMM reads a Closed Circuit.

8.2.11.3 Verify annunciator window 5010-6F, TROUBLE EMERG RES AUX TRANSFORMER, is in alarm.

j Rev. No.

O Page No.

29 of 91 I

L--__-._ _ _ __ _

CPS No.

2800.91 8.2.11.4 At ERAT local annunciator panel, PLACE the TEST-RESET /OFF-ON switch for point 9, LOSS OF NORMAL SUPPLY, to the OFF position.

j

(

8.2.11.5 At ERAT Transformer, perform the following:

l a)

VERIFY ERAT local annunciator point 9, LOSS OF NORMAL SUPPLY, will clear.

b)

Verify DMM reads an OPEN Circuit.

8.2.11. 6 Verify annunciator window 5010-6F, TROUBLE EMERG RES AUX TRANSFORMER, will clear.

8.2.11.7 At ERAT local annunciator panel, PLACE the TEST-RESET /OFF-ON switch for 9, LOSS 07 NORMAL SUPPLY, to the ON position.

8.2.11. 8 At ERAT Transformer, perform the fol] owing:

a)

VERIFY ERAT local annunciator point 9, LOSS OF NORMAL SUPPLY, still clear.

b)

Verify DMM reads an OPEN Circuit.

8.2.11.9 Verify annunciator window 5010-6F, TROUBLE EMERG RES AUX TRANSFORMER is clear.

l 8.2.11.10 OPEN 480 VAC ERAT TEMPORARY POWER disconnect switch.

8.2.11.11 At ERAT Transformer, perform the following:

a) VERIFY ERAT local annunciator point 9, LOSS OF NORMAL SUPPLY, is in alarm.

)

b) Verify DMM reads a closed Circuit.

8.2.11.12 Verify annunciator window 5010-6F, TROUBLE EMERG RES AUX TRANSFORMER, is in alarm.

8.2.11.13 CLOSE 480 VAC ERAT TEMPORARY POWER disconnect switch.

8.2.11.14 At ERAT Transformer, perform the following:

a) VERIFY ERAT local annunciator point 9, LOSS OF NORMAL SUPPLY, is still in alarm.

j b)

Verify DMM reads a Closed Circuit.

8.2.11.15 Verify annunciator window 5010-6F, TROUBLE EMERG RES AUX TRANSFORMER, is still in alarm.

Rev.1No.

O Page No.

30 of 91 E--___________________________-..__

r CPS No.

2800.91 8.2.11.16 At ERAT local annunciator panel, PLACE the j

TEST / RESET /OFF-ON switch for point 9, LOSS l

OF NORMAL SUPPLY, to the OFF position.

i 8.2.11.17 At ERAT Transformer, perform the following:

a) VERIFY ERAT local annunciator point 9, LOSS OF NORMAL SUPPLY, will clear, b) Verify DMM reads an OPEN Circuit.

8.2.11.18 Verify annunciator window 5010-6F, TROUBLE EMERG RES AUX TRANSFORMER, will cleur.

8.2.11.19 At ERAT local annunciator panel, PLACE the TEST-RESET /OFF-ON switch for 9, LOSS OF

)

NORMAL SUPPLY, to the ON position.

8.2.11.20 At ERAT Transformer, perform the following:

a) VERIFY ERAT local annunciator point 9, LOSS OF NORMAL SUPPLY, will clear.

b) Verify DMM reads an OPEN Circuit.

8.2.11.21 Verify annunciator window 5010-6F, TROUBLE EMERG RES AUX TRANSFORMER is clear.

NOTE The following steps will demonstrate the ERAT LOW OIL LEVEL ALARM 8.2.12 Perform ERAT LOW OIL LEVEL ALARM testing as follows:

8.2.12.1 At ERAT local annunciator panel, PLACE.the TEST-RESET /OFF-ON switch for point 4, LOW OIL LEVEL, j

to the TEST position.

8.2.12.2 At ERAT Transformer, perform the following:

a)

VERIFY ERAT local annunciator point 4, LOW OIL LEVEL, is in alarm.

b)

Verify DMM reads a Closed Circuit.

8.2.12.3 Verify annunciator window 5010-6F, TROUBLE EMERG RES AUX TRANSFORMER, is in alarm.

~

l 8.2.12.4 At ERAT local annunciator panel, PLACE the TEST-RESET /OFF-ON switch for point 4, LOW OIL LEVEL, g

to the OFF position.

i Rev. No.

O Page No.

31 of 91

CPS No.

2800.9i_

8.2.12.5 At ERAT Transformer, perform the following:

a)

VERIFY ERAT local annunciator point 4, LOW OIL LEVEL will clear.

b)

Verify DMM reads an OPEN Circuit.

8.2.12. 6 Verify annunciator window 5010-6F, TROUBLE EMERG RES AUX TRANSFORMER, will clear.

\\

l 8.2.12.7 At ERAT local annunciator panel, PLACE the TEST-RESET /OFF-ON switch for point 4, LOW OIL LEVEL, to the ON position.

8.2.12.8 At ERAT Transformer, perform the followingi a)

VERIFY ERAT local annunciator point 4, LOW h

OIL LEVEL will clear.

)

b)

Verify DMM reads an OPEN Circuit.

8.2.12.9 Verify annunciator window 5010-6F, TROUBLE EMERG RES AUX TRANSFORMER, is clear.

8.2.12.10 LOCATE 710-1, LIQUID LOW LEVEL GAUGE on the ERAT Transformer.

CAUTION The following step is carried out on an energized 325 VDC circuit. Proper safety precautions should be used.

8.2.12.11 At tr.e Level Gauge, disconnect the threaded connection for the alarm switch wiring.

8.2.12.12 Momentarily jumper the 710-1, LIQUID LOW LEVEL GAUGE level switch white to green wires.

(Reference Appendix D for connector wiring development.)

8.2.12.13 At ERAT Transformer, perform the following:

a)

VERIFY ERAT local annunciator point 4, LOW OIL LEVEL, is in alarm.

b)

Verify DMM reads a Closed Circuit.

8.2.12.14 Verify annunciator window 5010-6F, TROUBLE EMERG RES AUX TRANSFORMER, is in alarm.

8.2.12.15 At ERAT local annunciator panel, PLACE the TEJT-RESET /OFF-ON switch for point 4, LOW OIL LEVEL, to the OFF position.

Rev. No.

O Page No.

32 of 91

CPS No.

2800.91 8.2.12.16 At ERAT Transformer, perform the following:

a) VERIFY ERAT local annunciator point 4, LOW OIL LEVEL will clear, b) Verify DMM reads an OPEN Circuit.

8.2.12.17 Verify annunciator window 5010-6F, TROUBLE EMERG RES AUX TRANSFORMER, will clear.

8.2.12.18 Rect'nnect the 710-1 alarm switch wiring 3

threaded connection.

8.2.12.19 At ERAT local annunciator panel, PLACE the TEST-RESET /OFF-ON switch for. point 4, LOW OIL LEVEL, to the ON position.

8.2.12.20 If necessary, At ERAT Transformer, perform the following:

a) VERIFY ERAT local annunciator point 4, LOW OIL LEVEL will clear.

b) Verify DMM reads an OPEN Circuit.

8.2.12.21 If necessary Verify annunciator window 5010-6F, TROUBLE EMERG RES AUX TRANSFORMER will clear.

t 8.2.12.22 LOCATE 710-2, LIQUID LEVEL GAUGE (TAP CHANGER) on Ne ERAT Transformer.

CAUTION The following step is carried out on an energized 125 VDC circuit. Proper safety precautions should be used.

8.2.12.23 At the level gauge, disconnect the threaded connection for the alarm switch wiring.

8.2.12.24 Momentarily jumper the 710-2, LIQUID LOW LEVEL GAUGE level switch white to green wires.

(Reference Appendix D for connector wiring diagram.)

8.2.12.25 At ERAT Transformer, perform the following:

a) VERIFY ERAT local annunciator point 4, LOW OIL LEVEL, is in alarm.

b) Verify DMM reads a Closed Circuit.

8.2.12.26 Verify annunciator window 5010-6F, TROUBLE EMERG RES AUX TRANSFORMER, is in alarm.

r l

i Rev. No.

'O Page No.

33 of 91

CPS No.

2800.91 8.2.12.27 At ERAT local annunciator panel, PLACE the TEST-RESET /OFF-ON switch for point 4, LOW OIL LEVEL, to the OFF position.

8.2.12.28 At ERAT Transformer, perform the following:

a) VERIFY ERAT local annunciator point 4, LOW OIL LEVEL will clear.

b) Verify DMM reads an OPEN Circuit.

8.2.12.29 Verify annunciator window 5010-6F, TROUBLE EMERG RES AUX TRANSFORMER, will clear.

8.2.12.30 Reconnect the 710-2 alarm switch wiring threaded connection.

/

8.2.12.31 At ERAT local annunciator panel, PLACE the TEST-RESET /OFF-ON switch for point 4, LOW OIL LEVEL, to the ON position.

8.2.12.32 At ERAT Transformer, perform the following:

a) VERIFY. ERAT local annunciator point 4, LOW OIL LEVEL will clear.

b) Verify DMM reads an OPEN Circuit.

8.2.12.33 Verify annunciator window 5010-6F, TROUBLE EMERG RES AUX TRANSFORMER will clear.

NOTE The following steps will demonstrate the ERAT MECHANICAL RELIEF DEVICE ALARM.

8.2.13 Perform MECHANICAL RELIEF DEVICE ALARM testing as follows:

8.2.13.1 At ERAT local annunciator panel, PLACE the TEST-RESET /OFF-ON~ switch for point 3, MECHANICAL RELIEF DEVICE, to the TEST position.

l 8 ~ 2.13.2 At ERAT Transformer, perform the following:

a)

VERIFY ERAT local annunciator point 3, l

MECHANICAL RELIEF DEVICE, is in alarm, b)

Verify DMM reads a Closed Circuit.

8.2.13.3 Verify annunciator window 5010-6F, TROUBLE EMERG RES AUX TRANSFORMER, i t, in alarm.

l 8,2 13.4 At. ERAT local annunciator panel, PLACE the TEST-J RESET /OFF-ON switch for point 3, MECHANICAL l

RELIEF DEVICE, ' to the OFF position.

Rev..No.

O Page No.

34 of 91

1 i

?

CPS No.

2800.91

, 8.2.13.5 At ERAT Transformer, perform the following:

a)

VERIFY ERAT local annunciator point'3, j

MECHANICAL RELIEF DEVICE, will clear.

i b) _ Verify DMM-reads an OPEN Circuit.

8.2.13. 6' Verify annunciator window 5010-6F, TROUBLE EMERG RES AUX TRANSFORMER, will clear.

8.2._1.7 At ERAT local annunciator panel, PLACE the TEST-RESET /OFF-ON switch for point 3, MECHANICAL

. RELIEF DEVICE,-to the.ON position.

8.2.13.8 At ERAT. Transformer, perform the.following:

n a)

VERIFY ERAT local annunciator point 3, MECHANICAL RELIEF DEVICE, will clear.

b)

Verify DMM reads an OPEN Circuit.

8.2.13.9 Verify annunciator window 5010-6F, TROUBLE EMERG RES AUX TRANSFORMER,- is clear.

8.2.13.10 LOCATE 63P-1, Mechanical Relief Device (Transformer) on the ERAT Transformer.

8.2.13.11 At 63P-1, Mechanical Relief Device (Transformer), LIFT the se_maphore on top of 63P-1 until the microswitch rocker arm is engaged.

E 8.2.13.12 At ERAT Transformer, perform the.following:

a) VERIFY ERAT local annunciator point 3, MECHANICAL RELIEF DEVICE, is in alarm.

b) Verify DMM reads a Closed Circuit.

i'

~8.2.13.13 Verify annunciator window 5010-6F, TROUBLE EMERG RES AUX TRANSFORMER, is in alarm.

8.2.13.14 At 63P-1, Mechanical Relief Device (Transformer), DEPRESS the semaphore on top of 63P-1 until the microswitch rocker arm is i

disengaged.

8.2.13.15-At ERAT Transformer, perform the following:

a) VERIFT ERAT local annunciator point 3, MECHANICAL RELIEF DEVICE, is still in

alarm.-

b)-Verify DMM reads a Closed Circuit.

8.2.13.16 Verify annunciator window 5010-6F, TROUBLE EMERG~RES AUX TRANSFORMER, is still in alarm.

Rev.'No.

O Page No.

35 of 91

CPS No.

2800.91

~8.2.13.17 At ERAT' local annunciator panel, PLACE the TEST-RESET /OFF-ON switch for point 3, MECHANICAL RELIEF DEVICE, to the OFF position.

8.2.13.18 At ERAT Transformer, perform the following:

a) VERIFY ERAT local annunciator point 3, MECHANICAL RELIEF DEVICE, will clear.

b) Verify DMM reads an OPEN Circuit.

8.2.13.19 Verify annunciator window 5010-6F, TROUBLE EMERG RES AUX TRANSFORMER, will clear.

8.2.13.20 At ERAT local annunciator panel, PLACE the TEST-RESET /OFF-ON switch for point 3, MECHANICAL RELIEF DEVICE, to the ON position.

8.2.13.21 At ERAT Transformer, perform the following:

a) VERIFY ERAT local annunciator point 3, MECHANICAL RELIEF DEVICE, will clear.

b) Verify DMM reads an OPEN Circuit.

8.2.13.22 Verify annunciator window 5010-6F, TROUBLE EMERG RES AUX TRANSFORMER will clear.

8.2.13.23 LOCATE 63P-2, Mechanical Relief Device (Tap Changer)on the ERAT Transformer.

L HB.2.13.24 At 63P-2, Mechanical Relief Device (Tap Changer), LIFT the semaphore on top of 63P-2 i

until the microswitch rocker arm is engaged.

)

(

l 8.2.13.25 At ERAT Transformer, perform the following:

]

l a) VERIFY ERAT local annunciator point 3, MECHANICAL RELIEF DEVICE, is in alarm.

i b) Verify DMM reads a Closed Circuit.

l 8.2.13.26 Verify annunciator window 5010-6F, TROUBLE EMERG RES AUX TRANSFORMER, is in alarm.

8.2.13.27 At 63P-2, Mechanical Relief Device (Tap Changer), DEPRESS the semaphore on top of 63P-2 until the microswitch rocker arm is disengaged.

i

-Rev.1No.

O Page No.

36 of 91 L_-_-__--------.--

CPS No.

2800.91

.8.2.13.28 At ERAT Transformer, perform the following:

a) VERIFY ERAT local annunciator point 3, MECHANICAL RELIEF DEVICE, is still in alarm.

b) Verify DMM reads a Closed Circuit.

8.2.13.29 Verify annunciator window 5010-6F, TROUBLE EMERG RES AUX TRANSFORMER, is still in alarm.

8.2.13.30 At-ERAT local annunciator panel, PLACE the TEST-RESET /OFF-ON switch for point 3, MECHANICAL RELIEF DEVICE, to the OFF position.

8.2.13.31 At ERAT Transformer, perform the following:

a) VERIFY ERAT local annunciator point 3, MECHANICAL RELIEF DEVICE, will clear.

b) Verify DMM reads an OPEN Circuit.

i 8.2.13.32 Verify annunciator window 5010-6F, TROUBLE EMERG RES AUX TRANSFORMER, will clear.

8.2.13.33 At ERAT local annunciator panel, PLACE the TEST-RESET /OFF-ON switch for point 3, I

MECHANICAL RELIEF DEVICE, to the ON

position, 8.2.13.34 At ERAT Transformer, perform the following:

a) VERIFY ERAT local annunciator point 3, 1

MECHANICAL RELIEF DEVICE, will clear.

b) Verify DMM reads an OPEN Circuit.

8.2.13.35 Verify annunciator window 5010-6F, TROUBLE I

EMERG RES AUX TRANSFORMER will clear.

8.2.14 Perform ERAT HOT SPOT THERMOMETER ALARM testing l

as follows:

i NOTE The following steps will demonstrate the ERAT HOT

. SPOT THERMOMETER ALARM

.8.2.14.1 At ERAT local annunciator panel, PLACE the TEST-RESET /OFF-ON switch for point 2, HOT SPOT THERMOMETER, to the TEST position, l

Rev. No.

O Page No.

37 of 91

CPS Wo.

2000.91 8.2.14.2 At ERAT Transformer, perform the following:

s a)

VERIFY ERAT local annunciator point 2, HOT SPOT THERMOMETER, is in alarm, b)

Verify DMM reads a Closed Circuit.

8.2.14.3 Verify annunciator window 5010-7F, HIGH TEMP EMERG RES AUX TRANSFORMER, is in alarm.

8.2.14 '.4 At ERAT local annunciator panel, PLACE the TEST-RESET /OFF-ON switch for point 2, HOT SPOT THERMOMETER to the OFF position.

8.2.14.5 At ERAT Transformer, perform the following:

1 a)

VERIFY ERAT local annunciator point 2, HOT f

SPOT THERMOMETER, will clear.

b)

Verify DMM reads an OPEN Circuit.

l 8.2.14.6 Verify annunciator window 5010-7F, HIGH TEMP EMERG=RES AUX TRANSFORMER, will clear.

8.2.14.7 At ERAT local annunciator panel, PLACE the TEST-RESET /OFF-ON switch for point 2, HOT SPOT THERMOMETER, to the ON position.

8.2.14.8 At ERAT Transformer, perform the following:

a)

VERIFY ERAT local annunciator point 2, HOT SPOT THERMOMETER, will clear.

b)

Verify DMM reads an OPEN Circuit.

8.2.14.9 ENSURE that Main Control Room Alarm 5010-7F, HIGH TEMP EMERG RES AUX TRANSFORMER, is clear.

8.2.14.10 LOCATE the ERAT Transformer Hotspot THERMOMETER 49.

Remove the cover and the thermometer from the thermowell.

8.2.14.11 Apply an increasing amount of heat to the thermometer, until local annunciator point 2, HOT SPOT THERMOMETER, comes into alarm condition APPROXIMATELY 117 oC), and verify the following:

NOTE Cooling groups 1 and 2 will start running at approximately 75 degrees C.

a) ERAT Transformer Cooling Group 1 RUNNING b) ERAT Transformer Cooling Group 2 RUNNING c) DMM reads a Closed Circuit.

Rev.-No.

O.

Page No.

38 of 91

I CPS No.

2800.91

)

8.2014.12 Verify Main Control Room Alarm 5010-7F, HIGH TEMP EMERG RES AUX TRANSFORMER, is in alarm.

8.2.14.13 Remove the heat source from ERAT Transformer Hotspot THERMOMETER 49, and allow the Thermometer to cool.

8.2.14.14 After allowing the THERMOMETER to cool, Verify.the following:

a) local annunciator point 2, HOT SPOT THERMOMETER, is still in alarm.

b) ERAT Transformer Cooling Group 1 STOPPED l

c) ERAT Transformer Cooling Group 2 STOPPED l

d) DMM reads a CLOSED Circuit.

l l

8.2.14.15 Verify Main Control Room Alarm 5010-7F, HIGH TEMP EMERG RES AUX TRANSFORMER, is still in alarm.

3 l

8.2.14.16 At ERAT local annunciator' panel, PLACE the i

TEST-RESET /OFF-ON switch for point 2, HOT SPOT THERMOMETER to the OFF position.

8.2.14.17 At ERAT Transformer, perform the following:

a) VERIFY ERAT local annunciator point 2, HOT SPOT THERMOMETER, will' clear.

b)-Verify DMM reads an OPEN Circuit.

l 8.2.14.18 Verify annunciator window 5010- 7F, HIGH TCMP EMERG RES AUX TRANSFORMER, will clear.

8.2.14.19 At ERAT local annunciator panel, PLACE the TEST-RESET /OFF-ON switch for point 2, HOT SPOT THERMOMETER, to the ON position.

8.2.14.20 At ERAT Transformer, perform the following:

l a) VERIFY ERAT local annunciator point 2, l

HOT SPOT THERMOMETER, will clear, b) Verify DMM reads an OPEN Circuit.

8.2.14.21 ENSURE that Main Control Room Alarm 5010-7F, HIGH TEMP EMERG RES AUX TRANSFORMER, is clear.

8.2.14.22 REINSTALL the ERAT Transformer Hotspot THERMOMETER into the associated Thermowell, and reinstall the cover.

8.2.15-Perform ERAT HOT OIL THERMOMETER testing as follows:

l l

Rev. No.

O Page No.

39 of 91

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ - _ _ _ _ _ _ - _ _ ~

CPS No.

2800.91 NOTE The following steps will demonstrate the ERAT HOT OIL THERMOMETER ALARM 8.2.15.1 At ERAT local annunciator panel, PLACE the TEST-RESET /OFF-ON switch for point 1, HOT OIL THERMOMETER, to the TEST position.

8.2.15.2 At ERAT Transformer, perform the following:

a)

At local ERAT annunciator panel, VERIFY ERAT local annunciator point 1, HOT OIL THERMOMETER, is in alarm.

b)

Verify DMM reads a Closed Circuit.

8.2.15.3 Verify annunciator window 5010-7F, HIGH TEMP EMERG RES AUX TRANSFORMER, is in alarm.

8.2.15.4 At ERAT local annunciator pancl, PLACE the TEST-RESET /OFF-ON svitch for point 1, HOT OIL THERMOMETER, to the OFF position.

8.2.15.5 At ERAT Transformer, perform the following:

I a)

VERIFY ERAT local annunciator point 1, HOT OIL THERMOMETER, will clear.

b)

Verify DMM reads an OPEN Circuit.

8.2.15. 6 Verify annunciator window 5010-7F, HIGH TEMP EMERG RES AUX TRANSFORMER, will clear.

8.2.15.7 At ERAT local annunciator panel, PLACE the TEST-RESET /OFF-ON switch for point 1, HOT OIL THERMOMETER, to the ON position.

8.2.15.8 At ERAT Transformer, perform the following:

a)

VERIFY ERAT local annunciator point 1, HOT OIL THERMOMETER, still clear.

b)

Verify DMM reads an OPEN Circuit.

8.2.15.9 Verify annunciator window 5010-7F, HIGH TEMP EMERG RES AUX TRANSFORMER, is clear.

l E

8.2.15.10 LOCATE the ERAT Transformer HOT OIL l

THERMOMETER 260-1, remove the thermometer cover and remove the thermometer from the thermowell.

l

- Rev.-No.

O Page No.

40 cf 91 l

u_

CPS No.

2800.91 8.2.15.11 Apply an' increasing amount of heat to the THERMOMETER, and Verify the following:

a) At local ERAT annunciator panel, VERIFY ERAT local annunciator point 1, HOT OIL THERMOMETER, is in alarm.

b) Verify DMM reads a Closed Circuit.

8.2.15.12 Verify Main Control Room Alarm 5010-7F, HIGH TEMP EMERG RES AUX TRANSFORMER, is in alarm.

B.2.15.13 Remove the heat source from ERAT Transformer HOT OIL THERMOMETER 260-1.

8.2.15.14 After allowing the THERMOMETER to cool, Verify the following:

a) At local ERAT annunciator panel, VERIFY ERAT local annunciator point 1, HOT OIL THERMOMETER, is still in alarm.

b) Verify DMM reads a

.u sed Circuit.

8.2.15.15 At ERAT local annunciator pant 1.,

PLACE the TEST-RESET /OFF-ON switch for point 1, HOT OIL THERMOMETER, to the OFF position.

8.2.15.16 At ERAT Transformer, perform the following:

a) VERIFY ERAT local annunciator point 1, HOT OIL THERMOMETER, will clear.

b) Verify DMM reads an OPEN Circuit.

8.2.15.17 Verify annunciator window 5010-7F, HIGH TEMP EMERG RES AUX TRANSFORMER, will clear.

8.2.15.18 At ERAT local annunciator panel, PLACE the TEST-RESET /OFF-ON switch for point ' 1, HOT OIL THERMOMETER, to the ON position.

8.2.15.19 At ERAT Transformer, perform the following:

a) VERIFY ERAT local annunciator point 1, HOT OIL THERMOMETER, will clear.

b) Verify DMM reads an OPEN Circuit.

8.2.15.20 Verify Main Control Room Alarm 5010-7F, HIGH l

TEMP EMERG RES AUX TRANSFORMER, will clear.

8.2.15.21 REINSTALL the ERAT Transformer Hot Oil THERMOMETER 260-1 into the associated Thermowell, and reinstall the cover.

i l,

i l

'Rev. No.

O Page No.

41 of 91 j

q R-.___

CPS No.

2800.91 8.2.15.22 LOCATE the' ERAT Transformer HOT OIL THERMOMETER 260-2 (Tap Changer), remove the

~

cover and remove the thermometer from the thermowell.

8.2.15.23 Apply an increasing amount of heat to the THERMOMETER,-and Verify the following:

a)

At local ERAT annunciator panel, VERIFY ERAT local annunciator point 1, HOT OIL THERMOMETER, is in alarm.

b)

Verify DMM' reads a Closed Circuit.

8.2.15.24 Verify Main Control' Room Alarm.5010-7F, HIGH TEMP EMERG RES AUX TRANSFORMER, is in alarm.

8.2.15.25 Remove the heat source from ERAT Transformer HOT-OIL ~ THERMOMETER 260-2 (Tap Changer).

8.2.15.26 After. allowing the THERMOMETER to cool, Verify the following:

a).At local ERAT annunciator panel, VERIFY ERAT local annunciator point 1, HOT OIL THERMOMETER, is still in~ alarm.

.b)

Verify DMM reads'a Closed Circuit.

l c)

Main Control Room Alarm 5010-7F, HIGH TEMP EMERG RES AUX TRANSFORMER, is'still in alarm.

8.2.15.27

.At ERAT local annunciator panel, PLACE the TEST-RESET /OFF-ON switch for point 1, HOT

-OIL THERMOMETER, to the OFF' position.

8.2.15.28 At ERAT Transformer, perform the following:

-a) VERIFY ERAT local annunciator. point 1, HOT OIL THERMOMETER, will clear.

H b) Verify DMM reads an OPEN Circuit.

p 8.2.15.29 Verify annunciator window 5010-7F, HIGH TEMP EMERG RES AUX TRANSFORMER, will clear.

8.2.15.30 At ERAT local. annunciator panel, PLACE the TEST-RESET /OFF-ON switch for point 1,-HOT OILLTHERMOMETER,.to the ON position.

8.2.15.31-At ERAT Transformer, perform the following:

a) VERIFY ERAT local' annunciator point 1, HOT OIL THERMOMETER, still clear.

b) Verify DMM reads an OPEN Circuit.

8.2.15.32 Verify Main Control Room Alarm 5010-7F, HIGH TEMP EMERG RES AUX-TRANSFORMER, will clear.

Rev. No.

0-Page No.

42 of 91 1

CPS No.

2000.91 8.2.15.33-REINSTALL the ERAT Transformer Hot Oil THERMOMETER.260-1 into the associated Thermowell, and reinstall the cover.

NOTE The following steps will demonstrate the ERAT l'

SUDDEN PRESSURE RELAY ALARM 8.2.16-Perform ERAT-SUDDEN PRESSURE RELAY ALARM testing as follows:

l 8.2.16.1~At ERAT local annunciator panel, PLACE the: TEST-RESET /OFF-ON' switch for point 7, SUDDEN PRESSURE RELAY, to the TEST position.

8.2.16.2 Verify the following:

a).

AL local ERAT annunciator panel, VERIFY ERAT local: annunciator point 7, SUDDEN PRESSURE RELAY, is in alarm.

b)

Verify DMM reads a Closed Circuit.

l-8.2.16.3 Verify annunciator window 5010-5F, SUDDEN PRESS-EMERG~RES AUX' TRANSFORMER, is in alarm.

8.2.16.4 At ERAT local annunciator panel, PLACE the TEST-l

' RESET /OFF-ON switch for point 7, SUDDEN PRESSURE:

L RELAY, to the-off' position.

- 8.2.16.5 At ERAT Transformer, perform the following:

a)

VERIFY ERAT local annunciator point 7, p

SUDDEN PRESSURE RELAY, will clear.

)

b)

Verify DMM reads an OPEN Circuit.

/

8.2.16.6 Verify annunciator window 5010-5F, SUDDEN PRESS EMERG RES AUX TRANSFORMER,-will clear.

l

_8.2.16.7 At-ERAT local annunciator panel, PLACE the TEST-RESET /OFF-ON switch for point 7, SUDDEN PRESSURE D

RELAY,' to the ON position.

8' 2.16.8 At ERAT Transformer, perform the following:

a)

VERIFY' ERAT local annunciator point 7,-

SUCDEN PRESSURE RELAY, will clear.

b)-. Verify DMM reads an.OPEN Circuit.

8.2.16.9 VERIFY at annunciator window 5010-5F, SUDDEN PRESS EMERG-RES AUX TRANSFORMER is clear.

L Rev. No.

O' Page No.

43 of 91'

CPS No.

2800.91 NOTE The Sudden Pressure relay alarm contact will be functionally tested in section 8.6, ERAT PROTECTIVE RELAY SCHEME S 8.2.17 Perform ERAT TAP CHANGER PRESSUBE RELAY ALARM testing as follows:

8.2.17.1 Locate the ERAT Transformer Sudden Pressure Relay 63 Relay Panel.

NOTE The following steps will demonstrate the ERAT TAPCHANGER PRESSURE RELAY ALARM

'j 8.2.17.2 At ERAT local annunciator panel, PLACE the TEST-RESET /OFF-ON switch for point 5, TAPCHANGER PRESSURE RELAY, to the TEST position.

8.2.17.3 Verify the following:

a)

At local ERAT annunciator panel, VERIFY ERAT local annunciator point 5, TAPCHANGER PRESSURE RELAY,is in alarm.

b)

Verify DMM reads a Closed Circuit.

8.2.17.4 Verify annunciator window 5010-5F, SUDDEN PRESS EMERG RES AUX TRANSFORMER, is in alarm.

8.2.17.5 At ERAT local annunciator panel, PLACE the TEST-RESET /OFF-ON switch for point 5, TAPCHANGER PRESSURE RELAY, to the OFF position.

8.2.17.6 At ERAT Transformer, perform the following:

a)

VERIFY ERAT local annunciator point 5, TAPCHANGER PRESSURE RELAY, will clear.

b)

Verify DMM reads an OPEN Circuit.

8.2.17.7 Verify annunciator window 5010-5F, SUDDEN PRESS EMERG RES AUX TRANSFORMER, will clear.

8.2.17.8 At ERAT local annunciator panel, PLACE-the TEST-RESET /OFF-ON switch for point 5, TAPCHANGER PRESSURE RELAY, to the ON position.

8.2.17.9 At ERAT Transformer, perform the following:

j a)

VERIFY ERAT local annunciator point 5, j

TAPCHANGER PRESSURE RELAY, will clear.

l b)

Verify DMM reads an OPEN Circuit.

Rev. No.

O Page No.

44 of 91 i

L_________

t CPS No.

2800.91 l

8.2.17.10-Verify annunciator window 5010-5F, SUDDEN PRESS EMERG RES AUX TRANSFORMER is clear.

NOTE The tap changer pressure relay alarm contact will L

be tested in section 8.6, ERAT PROTECTIVE RELAY SCHEME S NOTE The following steps will demonstrate the ERAT EAULT PRESSURE RELAY ALARM 8.2.18.1 At ERAT local annunciator panel, PLACE the TEST-RESET /OFF-ON switch for point 8, EAULT PRESSURE RELAY, to the TEST position.

8.2.18.2 Verify the following:

a)

At local ERAT annunciator panel, VERIFY ERAT local annunciator point 8, EAULT PRESSURE RELAY, is in alarm, b)

Verify DMM reads a Closed Circuit.

8.2.18.3 Verify annunciator window 5010-5F, SUDDEN PRESS EMERG RES AUX TRANSFORMER, is in alarm.

8.2.18.4 At ERAT local annunciator panel, PLACE the TEST-RESET /OFF-ON switch for point 8, EAULT PRESSURE RELAY, to the OFF position.

B.2.18.5 At ERAT Transformer, perform the following:

a)

VERIFY ERAT local annunciator point 8, EAULT PRESSURE RELAY, will clear.

b)

Verify DMM reads an OPEN Circuit.

8.2.18.6 Verify annunciator window 5010-5F, SUDDEN PRESS EMERG RES AUX TRANSFORMER, will clear.

8.2.18.7 At ERAT local annunciator panel, PLACE the TEST-RESET /OFF-ON switch for point 8, EAULT PRESSURE RELAY, to the ON position.

8.2.18.8 At ERAT Transformer, perform the following:

a)

VERIFY ERAT local annunciator point 8, EAULT PRESSURE RELAY, will clear.

1 b)

Verify DMM reads an OPEN Circuit.

l l

l l

Rev. No.

O Page No.

45 of 91

_m

CPS No.

2800.91 NOTE

'The' fault-pressure relay. alarm contact will be tested in sec~ tion 8.6, ERAT PROTECTIVE RELAY SCHEME S

8.2.19 Relay K8 test.

E 8.2.19.1 At the ERAT Transformer, Close Circuit breaker 8-3.

/

8.2.19.2 (Record)At ERAT' transformer control panel, INSTALL auxiliary relay K8 into its socket.

Record on wire removal and installation form 8801.16F001.

(DV)

/

8.2.19. 3 At the ' ERAT ' transformer, place the following control switches to'the positions indicated:

43TC, 3 EMOTE

/

43S, LOCAL' CONTROL

/

8.2.19.4 At.the ERAT transformer, verify DMM reads an CLOSED Circuit.

8.2.19.5 At the ERAT-transformer, place' control switch 43T, MANUAL ~ CONTROL / AUTOMATIC CONTROL to the AUTOMATIC CONTROL. position.

8.2.1'9.6 At'the ERAT-transformer, verify DMM reads an OPEN Circuit.

8.2.19.7 At the ERAT transformer, place control switch,

MANUAL CONTROL / AUTOMATIC CONTROL in the MANUAL CONTROL position.

NOTE The next:2 steps.will cause the following' annunciator to alarm:.

5010-6F TROUBLE EMERG RES AUX TRANSFORMER 8.2".20 OPEN the following breakers:

Breaker 8-1 (DV)

/

Breaker-8-3 (DV)

/

Breaker 8-4 (DV)

/

-BreakerL8-5 (DV)

/

480 VAC ERAT RESERVE POWER (disconnect switch)

(DV)

/

400 VAC ERAT TEMPORARY POWER (disconnect switch) (DV)

/

'120 VAC ERAT-TEMPORARY POWER (DV)

/

. Rev. No Page No.

46 of 91

CPS No.

2800.91 8.2.21 PLACE the following switches to the position indicated:

43-1, AUTO /OFF/ MAN switch OFF (DV)

/

43-2, AUTO /OFF/ MAN switch OFF (DV)

/

43TC, LOCAL /OFF/ REMOTE OFF (DV)

/

43S, LOCAL CONTROL /

REMOTE CONTROL (DV)

/

REMOTE CONTROL 8.2.22 At the ERAT Transformer Control Cabinet, REMOVE the Digital multimeter from Terminal points W95 and W96.

/

l l

l t

l l

I l

'Rev. No.

O Page No.

47 of 91

I CPS No.

2800.91 8.3-ERAT Trr.ncformer Cooling Fr.n Operntion NOTE TestSection-8.3 performs ERAT Transformer Cooling L

Fan Controls testing.

NOTE Test Section 8.3 will cause the followingLalarm:

5010-6F TROUBLE EMERG RES AUX TRANSFORMER l

8.3.1 Notify ~the Control Room Operator that Main Control Room annunciator 5010-6F, TROUBLE EMERG RES' AUX TRANSFORMER,. will alarm during this section of the test.

8.3.2 CLOSE 480VAC ERAT RESERVE POWER disconnect switch (DV)

/

8.3.3 CLOSE breaker 8-4 (ERAT).

(DV)

/

8. 3. 4 -

CLOSE breaker 8-5(ERAT).

(DV)

/

8.3.5-At ERAT, ENSURE 43C,.POS. 1/POS. 2 switch is placed in the #1' position.

/

8.3.6 At ERAT, PLACE, if necessary, 43-2, AUTO /OFF/ MAN switch in the OFF~ position.

/'

8.3.7 At ERAT, PLACE 43-1,-AUTO /OFF/ MAN swit'ch,.if p

necessary in the MAN position ~

(DV)

/

8.3.8 VERIFY ERAT Transformer Cooling Group #1 is i

running, and that Cooling Group #2 is not running.

8.3.9 PLACE 43C, POS. 1/POS. 2 switch to the #2 position.

(DV)

/

l-8.3.10 VERIFY ERAT Transformer Cooling Group #1 has stopped and that Group #2 is running.

l' 8.3.11 PLACE 43-1, AUTO /OFF/ MAN switch to the OFF position.

/

8.3.12 VERIFY ERAT' Transformer Cooling Group #1 and Group #2 are not' running.

8.3.13 PLACE'43-2, AUTO /OFF/ MAN switch to the MAN position..

(DV)

/

8.3.14 VERIFY ERAT Transformer Cooling Group #1 is running, and Cooling Group # 2 is not running.

n Rev..No.

O Page No.

48"of 91

CPS No.

2800.91 8.3.15 PLACE 43C, POS. 1/POS. 2 switch to the #1 position.

(DV)

/

8.3.16 VERIFY ERAT Transformer Cooling Group #1 has stopped and that Group #2 is running.

8.3.17 PLACE 43-1, AUTO /OFF/ MAN switch to the MAN position.

(DV)

/

8.3.18 VERIFY ERAT Transformer Cooling Group #1 and Group #2 are running.

8.3.19 PLACE 43C, POS. 1/POS. 2 switch to the #2 position.

(DV)

/

8.3.20 VERIFY ERAT Transformer Cooling Group #1 and Group #2 are running.

8.3.21 PLACE 43-1, AUTO /OFF/ MAN switch to the AUTO position.

(DV)

/

8.3.22 VERIFY ERAT Transformer Cooling Group #2 has stopped and that Group #1 is running.

8.3.23 Locate ERAT.HOTSPOT THERMOMETER 49, remove the cover and remove the sensing bulb from the thermowell.

8.3.24 Apply a continuous heat source to ERAT hotspot Thermometer 49 approximately as indicated on the ERAT HOTSPOT THERMOMETER and VERIFY ERAT Transformer Cooling Group #1 and Group #2 are running.

8.3.25 PLACE 43-2, AUTO /OFF/ MAN switch to the OFF position.

(DV)

/

8.3.26 VERIFY ERAT Transformer Cooling Group #1 has l

stopped and that Group #2 is running.

8.3.27 PLACE 43-2, AUTO /OFF/ MAN switch to the AUTO position.

(DV)

/

8.3.28 VERIFY ERAT Transformer Cooling Group #1 and Group #2 are running.

8.3.29 Allow the thermometer to cool until both Transformer Cooling Fan Groups have stopped.

l l

8.3.30 PLACE 43C, POS. 1/POS. 2 switch to the #1 position.

(DV)

/

j 8.3.31 Apply a source of heat to hotspot thermometer 49, and VERIFY ERAT Transformer Cooling Group #1 and Group #2 are running.

Rev. No ' O Page No.

49 of 91

CPS No.

2800.91 8.3.32 Allow the Hotspot thermometer to cool, reinstall it into the hotspot thermowell, and reinstall the cover.

8.3.33 VERIFY ERAT Transformer Cooling Group #1 and Group #2 have stopped.

8.3.34 PLACE 43-2, AUTO /OFF/ MAN switch to the MAN position.

(DV)

/

8.3.35 VERIFY ERAT Transformer Cc; ling Group #1 is stopped and Group #2 is running.

8.3.36 PLACE 43-2, AUTO /OFF/ MAN switch to the AUTO position.

(DV)

/

8.3.37 PLACE 43-1, AUTO /OFF/ MAN switch to the MAN position.

(DV)

/

8.3.38 VERIFY ERAT Transformer Cooling Group #1 is running and Group #2 has stopped.

8.3.39 PLACE 43-1, AUTO /OFF/ MAN switch to the OFF position.

(DV)

/

8.3.40 VERIFY ERAT Transformer Cooling Group #1 and Group #2 have stopped.

8.3.41 PLACE 43-2, AUTO /OFF/ MAN switch to the OFF position.

(DV)

/

8.3.42 VERIFY ERAT Transformer Cooling Group #1 and Group #2 are not running.

8.3.43 OPEN breaker 8-4.

(DV)

/

8.3,44 OPEN breaker 8-5.

(DV)

/

8.3.45 OPEN 480VAC ERAT RESERVE POWER disconnect switch.

(DV)

/

l l

r l

Rev. No.

O Page No.

50 of 91 m-_________-.

CPS No.

2800.91

'8~.4' ERAT Trnncfermer Lord Tap Changer NOTE

. Test Section 8.4 demonstrates hand crank operation of the load tap changer, as well as local manual, remoteJmanual, and automatic control of.the load tap changer via the LTC motor.

8.4.1 Notify the Control Room Operator that this test sectionLwill cause Main Control Room Annunciator i

5010-6F, TROUBLE EMERG RES AUX TRANSFORMER, to

. alarm.

8.4.2 Ensure the following switches at the ERAT are positioned as listed:

Main Cabinet 43-1, AUTO /OFF/; MAN switch Off

/

43-2, AUTO /OFF/ MAN switch Off

/

43C, POS. 1/POS. 2 switch

  1. 1

/

43S, LOCAL CONTROL /

LOCAL CONTROL

/

REMOTE CONTROL TS, RELAY TEST /

RELAY TEST

/

RELAY OPERATE-

.43T, MANUAL CONTROL /

MANUAL CONTROL

/

AUTOMATIC CONTROL

.CS, MANUAL RAISE /

MID-POSITION

/

MANUAL LOWER LTC Compartment 43TC, LOCAL /OFF/ REMOTE OFF

/

84CS, LOWER /OFF/ RAISE OFF

/

8.4.3 Verify Transformer Load Tap Changet (LTC),

including cam and limit switches, has been set per vendor recommendations. (MWR # D82231) 8.4.4 LOCATE the motor drive mechanism of the ERAT Load Tap Changer, and engage the hand crank mechanism.

L 8.4.5 (Record)

Note the As Found position of the ERAT L

Tap Charger as displayed on the LTC Mechanical Indication.

Record the As Found position below:

As Found 8.4.6 OPERATE the driving mechanism by manual operation to the full raise position.

l l

1

~

Rev. No.

Oi Page No.

51 of 91 C____-______-

j

CPS No.

2800.91 8.4.7 CHECK the mechanical end stop by attempting to hand crank it beyond the end raise position.

After'several turns on the hand crank, verify

.that it is mechanically stopped.

~

8.4.8-

_ OPERATE.the driving mechanism by manual operation to the full lower position.

8.4.9 LCHECK the' mechanical end stop by attempting to hand crank it beyond the end lower position.

After several turns on the hand crank, verify that it is mechanically stopped.

8.4.10 (Record)

Operate the driving mechanism by manual (hand crank) operation to the approximate position found in step 8.4.5 as displayed on the LTC mechanical position indicator. Record the position the-LTC was left in (e.g. 4R, IL,

- etc. )'

8.4.11 CLOSE the following breakers:

8-2

/

8-3

/

480 VAC ERAT RESERVE POWER (disconnect switch)

/

120 VAC ERAT TEMPORARY POWER

/

L~

8.4.12 At-ERAT. transformer Load Tap Changer - (LTC) -

compartment, PLACE transfer switch 43TC, LOCAL /OFF/ REMOTE to the LOCAL position.

8.4.13 At ERAT LTC compartment, PLACE 84CS, LOWER /OFF/ RAISE switch to the RAISE position and release. -Verify tap. charger did not move.

8.4.14 At ERAT LTC compartment, PLACE 84CS, LOWER /OFF/ RAISE switch to the LOWER position and release. Verify tap changer did not move.

8.4.15 (Record) REMOVE the. hand _ crank from the driving mechanism and record the following:

LTC position (e.g. 7L, 2R, etc.)

LTC Operation Counter Reading 8.4.lf'

.(Record)

At ERAT LTC compartment, PLACE 84CS, LOWER /OFF/ RAISE switch to the RAISE position ar.d release. VERIFYfthat the tap changer moved in the raise direction. Record new position and LTC operation counter reading below:

1 LTC position (e.g. 7L, 2R, etc.)

LTC Operation Counter Reading

Rev.' ' No.

0 Page No.

52 of 91

.O

CPS No.

2800.91 8.4.17 (Record)

PLACE :84CS, LOWER /OFF/ RAISE switch in the LOWER position'and release. VERIFY that the tap changer moved in1the lower direction. Record new position below:

(e.g. 7L, 2R, etc.)

LTC operation-counter reading 8.4.18 Place and' hold 84CS, LOWER /OFF/ RAISE switch -in the: LOWER position'until it has reached the end lower position, then release.

t 8.4.19 (Record) Check the LOWER electrical stop by momentarily placing 84CS, LOWER /OFF/ RAISE switch in the. LOWER-position. VERIFY that the tap change motor.does not1 energize and the Electrical Lower Stop Position-is 8L. Record this Tap Position below:

(Electrical Lower Stop Position) (8L) 8.4.20 Place and hold 84CS, LOWER /OFF/ RAISE switch in the RAISE position until it has reached the end raise' position.

8.4.21-(Record) Check the RAISE electrical stop by momentarily placing 84CS, LOWER /OFF/ RAISE-switch in the RAISE position. VERIFY that the tap change-motor does.not energize and the Electrical Raise Stop Position is BR. Record this Tap Position below:

(Electrical Raise Stop Position) (8R) 8.4.22 Place and. hold.84CS, LOWER /OFF/ RAISE switch in the LOWER position until it has reached approximately mid-position.

Record the Tap Position below:

(e.g. 1R, 2L, etc.)

8.4.23 At ERAT transformer Load Tap Changer (LTC) compartment, PLACE transfer switch 43TC, LOCAL /OFF/ REMOTE to the REMOTE position.

8.4.24 Momentarily place 84CS, LOWER /OFF/ RAISE switch in f

'the RAISE position. VERIFY that the tap change motor does not energize.

8.4.25 Momentarily place 84CS, LOWER /OFF/ RAISE switch in the' LOWER position. VERIFY that the tap changer motor.does not energize.

8.4.26-At ERAT transformer main cabinet, PLACE selector switch TS, RELAY TEST / RELAY OPERATE in the RELAY j

OPERATE position.

t Rev. No.

O Page No.

53 of 91

CPS No.

2800.91 i

8.4.27 At ERAT transformer main

cabinet, PLACE control switch CS, MANUAL RAISE / MANUAL LOWER in the LOWER position and release. VERIFY that the tap changer moved in the lower direction.

Record this tap position below:

(e.g. 21, etc.)

8.4.28 At ERAT tranofutmer main cabinet, PLACE control switch CS, MANUAL RAISE / MANUAL LOWER, in the raise position and release. VERIFY that the tap changer moved in the raise direction.

8.4.29 At ERAT transformer main cabinet, PLACE 43S, LOCAL CONTROL / REMOTE CONTROL Switch in the REMOTE CONTROL position.

l l8.4.30 At ERAT transformer main cabinet, PLACE control switch CS, MANUAL RAISE / MANUAL LOWER, in the LOWER position and release.

VERIFY that the tap j

changer does not move.

j 8.4.31 At ERAT transformer main cabinet, PLACE control switch CS, MANUAL RAISE / MANUAL LOWER, in the RAISE position and release. VERIFY that the tap changer does not move.

8.4.32 At ERAT transformer. main cabinet, PLACE 43S, LOCAL CONTROL / REMOTE CONTROL switch in the LOCAL CONTROL position.

8.4.33 At ERAT transformer main cabinet, PLACE selector switch TS, RELAY TEST / RELAY OPERATE in the RELAY TEST position.

8.4.34 HOLD control switch CS, MANUAL RAISE / MANUAL

-LOWER, in the MANUAL RAISE position.

VERIFY at the ERAT main cabinet that the white test light comes.ON, and the tap changer does not move, then release CS.

8.4.35 HOLD control switch CS, MANUAL RAISE / MANUAL LOWER, in the LOWER position. VERIFT at the ERAT main cabinet that the white test light comes ON, and the tap changer does not move, then release CS.

8.4.36 At ERAT transformer main cabinet, PLACE selector switch TS, RELAY TEST / RELAY OPERATE in the RELAY OPERATE position.

8.4.37 At ERAT transformer main cabinet, PLACE selector switch 43T, MANUAL CONTROL / AUTOMATIC CONTROL, in the AUTOMATIC CONTROL position.

Rev. No.

O Page No.

54 of 91

CPS No.

2800.91 8.4.38 Momentarily place CS, MANUAL RAISE / MANUAL LOWER, l

in the RAISE position. VERIFY that the tap change motor does not energize.

NOTE The following step temporarily prevents input into the VOLTAGE REGULATING RELAY 90 from current

{

transformer ACT by shorting the LDC CT output wires together.

8.4.39 At ERAT VOLTAGE REGULATING RELAY 90,CLOSE, as necessary, shorting link 17 Shorting link 17 Closed (DV)

/

NOTE At the time of installation of the ERAT transformer, the Static VAR Compensator interface control contacts are not installed. Demonstration of proper operation of the LTC from SVC control will be accomplished upon completion of the ERAT SVC installation.

i 8.4.40 CLOSE breaker 8-1.

/

8.4.41 Place TEST / Operate switch on VOLTAGE REGULATING

' RELAY 90 to the TEST position.

8.4.42 Slowly adjust the TEST knob until the point where the RAISE LED is illuminated.

8.4.43 After an approximate 7 second time delay, VERIFY that the load tap changer moves in the RAISE l-direction.

8.4.44 Adjust the TEST knob to the point where the RAISE LED goes out. VERIFY the LTC stops after the LED j

goes out.

8.4.45 Slowly adjust the TEST knob until the point where the LOWER LED is illuminated.

8.4.46 Af ter an approximate 7 second time delay, VERIFY that the load tap changer moves in the LOWER i

direction.

L 8.4.47 Adjust the TEST knob to the point where the LOWER LED goes out. VERIFY the LTC stops af ter the LED goes out.

Rev. No.

O Page No.

55 of 91

CPS No.

2800.91 8.4.48 (Record)At 59 VOLTAGE BACKUP RELAY, record the as found position of the BANDCENTER dial:

(Volts) 8.4.49 At VOLTAGE REGULATING RELAY 90, slowly adjust the TEST knob until the point where the LOWER LED is illuminated.

\\

8.4.50 After an approximate 7 second time delay VERIFY that the load tap changer moves in the LOWER direction.

8.4.51 At 59 VOLTAGE BACKUP RELAY, adjust the BANDCENTER dial until the BLOCK RAISE / LOWER LED comes on.

8.4.52 VERIFY that at VOLTAGE REGULATING RELAY 90, the lower LED is still on and that the tap changer has stopped movement.

8.4.53 At 59 VOLTAGE BACKUP RELAY, adjust the BANDCENTER dial until the BLOCK RAISE / LOWER LED goes out.

8.4.54 VERIFY that the load tap changer resurues movement in the LOWER direction.

8.4.55 At VOLTAGE REGULATING RELAY 90, adjust the TEST knob until the point where the lower LED is out, and VERIFY that the tap changer has stopped movement.

8.4.56 At VOLTAGE REGULATING RELAY 90, adjust the TEST knob until the point where the RAISE LED is on.

8.4.57 After approximate 7 second time delay VERIFY that the load tap changer moves in the RAISE direction.

8.4.58 At 59 VOLTAGE BACKUP RELAY adjust the BANDCENTER dial until the BLOCK RAISE / LOWER LED comes on.

8.4.59 VERIFY that at VOLTAGE REGULATING RELAY 90, the raise LED is still on and that the tap changer has stopped movement.

8.4.60 At 59 VOLTAGE BACKUP RELAY, adjust the BANDCENTER dial until the BLOCK RAISE / LOWER LED goes out.

8.4.61 VERIFY that the load tap changer resumes movement in the RAISE direction.

Rev. No.

O Page No.

56 of 91

L CPS No.

2800.91 NOTE The next sequence of steps will cause the following annunciator to clarm (if not already in alarm):

5010-6F TROUBLE EMERG RES AUX TRANSFORMER 8.4.62 At 59 VOLTAGE BACKUP RELAY, adjust the BANDCENTER dial until the LOWER LED comes on.

8.4.63 After an approximate 5 second time delay VERIFY that the load tap changer moves in_the LOWER 1

direction, and that at VOLTAGE REGULATING RELAY 90, the raise LED is still on.

8.4.64 At 59 VOLTAGE BACKUP RELAY, adjust the BANDCENTER dial until the LOWER LED goes out, but the BLOCK

(

j RAISE / LOWER LED remains on, and VERIFY that the tap changer has stopped movement.

8 4.65 After an approximate 3 minute time delay, verify l

that local annunciator point 11, BACK-UP RELAY, comes into alarm.

8.4.66 At 59 VOLTAGE BACKUP RELAY, adjust the BANDCENTER dial until the BLOCK RAISE / LOWER LED goes out.

L8.4.67 (Record)At 59 VOLTAGE BACKUP RELAY, return the BANDCENTER dial to the as found position.(Step 8.4.48) Record the AS Left reading:

volts 8.4.68 At ERAT local annunciator panel, reset alarm point 11, BACK-UP RELAY.

8.4.69 OPEN breaker 8-1.

(DV)

/

j 8.4.70 Place TEST / OPERATE' switch on VOLTAGE REGULATING RELAY 90 to the OPERATE position.

8.4.71 At the ERAT transformer main cabinet, PLACE selector switch 43T, MANUAL CONTROL / AUTOMATIC CONTROL in the MANUAL CONTROL position.

8.4.72 Using.the CS, MANUAL RAISE / MANUAL LOWER, switch position the LTC to the 4L position.

Record this as left position:

(4L) i 8.4.73 RESTORE Current Transformer ACT by OPENING shorting link 17.

' Shorting link 17 OPEN

/

Rev..No.

O Page No.

57 of 91

CPS No.

2800.91 8.4.74 Place the following switches in the positions

-indicated:

43T, MANUAL CONTROL /

MANUAL CONTROL

/

AUTOMATIC CONTROL TS, RELAY-TEST /

-RELAY TEST

/

RELAY OPERATE 43TC, LOCAL /OFF/ REMOTE OFF

/

NOTE The following step will bring Main Control Room Annunciator 5010-6F, TROUBLE EMERG RES AUX TRANSFORMER into alarm.

8.4.75 OPEN che following breakers:

8.2 (DV)

/

8.3 (DV)

/

480 VAC ERAT RESERVE POWER (disconnect switch)

(DV)

/

120 VAC ERAT TEMPORARY POWER (DV)

/

i

)

l-i l

Rev.'No.

O Page No.

50 of 91

CPS No.

2800.91 8.5 ERAT Circuit Switcher Operation NOTE Test Section:8.5 demonstrates proper operation of Circuit Switcher B018.

8.5.1 Notify the Control Room Operator that.this test

-section will bring in.the following Main Control Room alarms:

5010-1A, AUTO TRIP SWITCHER 5010-4E, LOCK-OUT TRIP EMERG RES AUX TRANSF PROT SYS S 5010-4F, LOCK-OUT TRIP EMERG RES AUX TRANSF PROT SYS F 8.5.2 Ensure Circuit Switcher. control wiring,

including Auto Trip Alarm and Computer Point 1SY-BC610 have been functionally checked. (MWR #

D82234) 8.5.3 At ERAT Protective Relay panel OPL91J, remove the

-back of relay panel 0PL91J, and OPEN Test Switch for contacts 7-8 of TS-86F-ET.

8.5.4 At OPL91J, ENSURE 86S-ET, LOCKOUT RELAY ERAT SLOW SYSTEM, is Reset.

8.5.5 At 0PL91J, ENSURE 86F-ET, LOCKOUT RELAY ERAT FAST SYSTEM, is Reset.

8.5.6-At OPL91J, ENSURE Blue light for 86S-ET is ON.

(1DC17E, Ckt. #23) 8.5.7 At OPL91J, ENSURE Blue light for 86F-ET is ON.

(1DC17E, Ckt. #23)~

8.5.8 At 1H13-P870-51C, ENSURE green open light for ERAT Circuit Switcher B018 is ON.(1DC17E, Ckt.

  1. 17) 8.5.9 CLOSE ERAT Circuit Switcher B018, using the local l

control switch, and verify that the red light at 1H13-P870-51C associated with ERAT Circuit l

Switcher B018 is ON.

8.5.10 OPEN circuit switcher B018, using local control switch, and verify that the ' green light at 1H13-P870-51C associated with ERAT Circuit Switcher B018 is~ON.

l f8.5.11 At panel.1H13-P870-51C, CLOSE ERAT Circuit Switcher.B018 at and verify red light is on.

1 Rev.I No.

CF Page No.

59 of 91 L

m

CPS No.

2800.91 8.5.12 At computer readout display, verify closed contact signal to computer point 15Y-BC610, ERAT-138KV CKT SWCH B018

'B.5.13

At panel 1H13-P870-51C,'OPEN ERAT Circuit Switcher B018 and verify green light is on.

8.5.14 At computer readout display, verify open contact signal to computer point 1SY-BC610, ERAT-138KV CKT.SWCH B018 8.5.'15 VERIFY alarm " AUTO TRIP SWITCHER" is off at

. annunciator window 5010-1A on panel 1H13-P850.

8.5.16 At panel 1H13-P870-51C, CLOSE ERAT Circuit Switcher B018 and verify red light is on.

8.5.17 At 0PL91J, Momentarily jumper from terminals 1 to 10 of 351B-ET 138KV O.C. OB ERAT.

8.5.18

. VERIFY circuit switcher B018 opens.

8.5.19 At panel 1H13-P870-51C, place ERAT Circuit Switcher B018 handswitch to the CLOSE position and release.

Verify. circuit switcher B018 does

.not close.

I L

8.5.20 At panel 1H13-P870-51C, PLACE ERAT Circuit

-Switcher B018 handswitch to the OPEN positjon and l

release to match target.

8.5.21 VERIFY alarm " AUTO TRIP SWITCHER" is on at.

annunciator window 5010-1A on panel 1H13-P850.

-8.5.22' VERIFY alarm " LOCK-OUT TRIP EMERG RES AUX TRANSF PROT'SYS S" is on at annunciator window 5010-4E L

on panel 1H13-P850.

8.5.23 At computer readout display, verify closed contact signal to computer. point 1AP-BC907, ERAT PROT SYS S LOCKOUT.

8.5.24 VERIFY white light for Lock Out' relay-865-ET at OPL91J is on.

'8.5.25-RESET 86S-ET, LOCKOUT RELAY ERAT SLOW SYSTEM, by I

placing the-handle of'865-ET to the RESET position'and releasing.

L 8.5.26

' VERIFY. alarm " AUTO TRIP SWITCHER" at annunciator window 5010-1A on panel 1H13-P850 clears.

?8.5.27 VERIFY' alarm'" LOCK-OUT TRIP EMERG RSS AUX TRANSF PROT SYS S" at annunciator window 5010-4E on panel 1H13-P850 clears.

Rev. No; 0:

Page No.

60 of 91 L

CPS No.

2800.

l_

l 8.5.28 At computer readout display, verify open contact l

signal to computer point 1AP-BC907, ERAT PROT SYS S LOCKOUT.

I L

8.5.29 VERIFY white light for Lock Out relay 86S-ET at OPL91J is off.

{

l.

8.5.30 At panel 1H13-P870-51C, CLOSE ERAT Circuit

)

Switcher E018 and verify red light is on.

l 8.5.31 At OPL91J, Momentarily jumper from terminals 1 l

to 10 of 87C-ET DIFF. RELAY O'C ERAT.

8.5.32 VERIFY circuit switcher opens.

8.5.33 VERIFY alarm " AUTO TRIP SWITCHER" is on at annunciator window 5010-1A on panel 1H13-P850.

)

8.5.34 At panel 1H13-P870-51C, place ERAT Circuit Switcher B018 handswitch to the CLOSE position and release.

Verify circuit switcher B018 does j

not close.

8.5.35 At panel 1H13-P870-51C, place ERAT Circuit l

Switcher B018 handswitch to the OPEN position and release to match target.

8.5.36 VERIFY alarm " LOCK-OUT TRIP EMERG RES AUX TRANSF PROT SYS F" is on at annunciator window 5010-4F l

on panel 1H13-P850.

l 8.5.37 At computer readout display, verify closed contact signal to computer point 1AP-BC908, ERAT PROT SYS F LOCKOUT 10 9.

i l

8.5.38 VERIFY white-light for Lock Out relay 86F-ET at OPL91J ic on.

8,5.39 RESET 86F-ET, LOCKOUT RELAY ERAT FAST SYSTEM, by placing the handle for 86F-ET to the RESET position and releasing.

8.5.40 VERIFY alarm " AUTO TRIP SWITCHER" at annunciator window 5010-1A on panel 1H13-P850 clears.

l.

8.5.41-VERIFY alarm " LOCK-OUT TRIP EMERG RES AUX TRANSF l

PROT SYS F" at annunciator window 5010-4F on panel 1H13-P850 clears.

8.5.42 At computer readout display, verify open contact signal to computer point 1AP-BC908, ERAT PROT SYS F LOCKOUT 10 9.

Rev. No.

O Page No.

61 of 91 l

CPS No.

?.800.91 8.5.43 VERIFY white light for Lock Out relay 86F-ET at OPL91J is off.

8.5.44 At ERAT Protective Relay panel OPL91J, CLOSE Test Switch for contacts 7-8 of TS-86FET, and reinstall back cover to panel OPL91J.

I i

j L

Rev. No.

O Page No.

62 of 91

CPS No.

2800.91 8.6 ERAT Protretiva Relry Scheme S l

NOTE Test Section 8.6 demonstrates proper operation of ERAT Protective Relay Scheme S.

8.6.1 Notify the Control Room Operator that the following Main Control Room annunciators will come into alarm during this test section:

5010-5F SUDDEN PRESS EMERG RES AUX TRANSFORMER 5010-4E LOCK-OUT TRIP EMERG RES AUX TRANSFORMER 8.6.2 VERIFY computer input 1AP-BC2C4 has been functionally checked. (MWR # D82234)

CAUTION ERAT Deluge Valve 1FP101C will be disabled by placing a "C" clamp so as to prevent the weight from striking the valve trigger.

8.6.3 AT ERAT Deluge Valve 1FP101C, BLOCK valve by applying a "C" clamp per Appendix B so as to prevent the weight from striking the valve trigger 8.6.4 At ERAT Transformer, perform the following:

a)

LOCATE ERAT Transformer FAULT PRESSURE RELAY 63FP, relay subpanel.

b)

At ERAT transformer control panel, VERIFY that the Fault Pressure Relay 63FP relay subpanel is reset by depressing the reset switch and verifying that the LED at the relay not illuminated.

8.6.5 At ERAT Transformer, perform the following:

a)

LOCATE ERAT Transformer SUDDEN PRESSURE RELAY 63, relay subpanel.

b)

At ERAT transformer control panel, VERIFY that the Sudden Pressure Relay 63 relay

.subpanel is reset by depressing the reset switch and verifying that the LED at the relay not illuminated.

Rev. No.

O Page No.

63 of 91

CPS No.

2800.91 8.6.6 VERIFY the following computer input contacts are open:

1AP-BC907, ERAT PROT SYS S LOCKOUT 1AP-BC567, ERAT 138 KV 1AP-BC582, ERAT SEC WNDG NEUTRAL OC 1AP-BC583, ERAT PRI WNDG NEUTRAL OC 8.6.7 At OPL91J, ERAT PROTECTIVE RELAY PANEL perform the following:

a) remove the back cover of the panel.

b)

OPEN TS3-4 of TS-86S-ET, OPL91J.

8.6.8

. At OPL91J, verify the following:

a)

Blue light for Lockout Relay 286S-BE is OFF.

b)

Blue light for lockout relay 86S-ET is ON.

8.6.9 VERIFY alarm " LOCK-OUT TRIP EMERG RES AUX TRANSF PROT SYS" at annunciator window 5010-4E is OFF.

8.6.10 VERIFY alarm " SUDDEN PRESS EMERG RES AUX TRANSFORMER"'at annunciator window 5010-5F is OFF.

CAUTION The folzowing step is carried out on an energized 125 VDC circuit.

Proper safety precautions should be used.

8.6.11 Simulate a fault pressure on 63FP, Fault Pressure Relay by momentarily jumpering terminals 1 to 12.

8.6.12 VERIFY 63FP, Fault Pressure Relay, LED is ON.

8.6.13 At EPAT Transformer, perform the following:

a). VERIFY ERAT local annunciator point 8, FAULT PRFSSURE RELAY, is in alarm.

b)

Verify DMM reads a CLOSED Circuit.

0.6.14 VERIFY alarm " SUDDEN PRESS EMERG RES AUX TRANSFORMER" at annunciator window 5010-5F is ON.

i 8.6.15 VERIFY' relay 86S-ET LOCKOUT RELAY ERAT SLOW l

SYSTEM is tripped.

8.6.16 VERIFY alarm " LOCK-OUT TRIP EMERG RES AUX TRANSF PROT SYS" at annunciator window 5010-4E is ON.

8.6.17 VERIFY computer input 1A?-BC907, ERAT PROT SYS S LOCKOUT, indicates trip.

l Rev. No.

O Page No.

64 of 91 l

l

CPS No.

2800.91 8.6.18

. VERIFY computer input 1AP-BC204, ERAT SUDDEN PRESS indicates trip.

8.6.19 VERIFY ERAT Deluge valve 1FP101C trips.

8.6.20 RESET 63FP, Fault Pressure Relay, by depressing the reset switch and verifying that the LED at the relay is out.

8.6.21 At ERAT Transformer, perform the following:

a)

VERIFY ERAT local annunciator point 8, FAULT PRESSURE RELAY, is still in alarm.

b)

Verify DMM reads a CLOSED Circuit.

8.6.22 VERIFY annunciator window 5010-5F, SUDDEN PRESS EMERG RES AUX TRANSFORMER, is still in alarm.

8.6.23 At ERAT local annunciator panel, PLACE the TEST-RESET /OFF-ON switch for point 8, FAULT PRESSURE RELAY, to the OFF position.

8.6.24.

At ERAT Transformer, perform the following:

a)

VERIFY ERAT local annunciator point 8, FAULT PRESSURE RELAY, will clear.

b)

Verify DMM reads an OPEN Circuit.

8.6.25 VERIFY that annunciator window 5010-5F, SUDDEN PRESS EMERG RES AUX TRANSFORMER, is still in alarm.

8.6.26 At ERAT local annunciator panel, PLACE the TEST-AESET/OFF-ON switch for point 8, FAULT PRESSURE RELAY, to the ON position.

l 8.6.27 At ERAT Transformer, perform the following:

a)

VERIFY ERAT local annunciator point 8, FAULT PRESSURE RELAY, will clear.

b)

Verify DMM reads an OPEN Circuit.

8.6.28 RESET lock-out relay 86S-ET, LOCKOUT RELAY ERAT SLOW SYSTEM.

8.6.29 VERIFY alarm " SUDDEN PRESS EMERG RES AUX l

TRANSFORMER" at annunciator window 5010-5F will clear.

1 8.6.30 VERIFY alarm " LOCK-OUT TRIP EMERG RES AUX TRANSF PROT SYS" at annunciator window 5010-4E will clear.

Rev. No.

O Page No.

65 of 91 L__________ _

CPS'No.

2800'.91 8.6.31 VERIFY computer input 1AP-BC907, ERAT PROT SYS S LOCKOUT, indicates reset.

8.6.32 VERIFY computer input 1AP-BC204,. ERAT SUDDEN PRESS, indicates reset.

8.6.33 RESET ERAT Deluge Valve 1FP101C per step B of Appendix B(Do not remove clamp at this time) 8'6.34 Locate the ERAT Transformer Sudden Pressure Relay 63' Relay Panel.

CAUTION The following step is carried out on an energized 125 VDC circuit.

Proper safety precautions should

-be used.

8.6.35~

At the ERAT Sudden Pressure' relay panel, momentarily jumper the 63, Sudden Pressure Relay switch A29 - (White) and A17 (Green) wires.

l 8.6.36-VERIFY Sudden Pressure Relay panel alarm light (LED) comes on.

8.6.37 At ERAT Transformer, perform the following:

a). VERIFY ERAT local annunciator point 7, i

SUDDEN PRESSURE RELAY, is in alarm.

b)

Verify DMM reads a CLOSED Circuit.

8.6.38 VERIFY annunciator window' 5010-5F, SUDDEN PRESS EMERG RES AUX TRANSFORMER IS IN ALARM.

i 8.6.39 VERIFY relay'86S-ET, LOCKOUT RELAY ERAT SLOW SYSTEM trips.

18. 6. 4 0 '

. VERIFY' annunciator window 5010-4E, LOCK-OUT TRIP 1

EMERG RES AUX TRANSFORMER,- is in alarm.

8.6.41 VERIFY computer. input 1AP-BC907, ERAT PROT SYS S LOCKOUT, indicates trip.

8.6.42 VERIFY computer input 1AP-BC204, ERAT SUDDEN PRESS,' indicates trip.

18.6.43L VERIFY ERAT deluge valve 1FP101C trips.

8.6.44 At the Sudden Pressure Relay Panel,-RESET the Sudden Pressure Relay by depressing ~the reset button, and. VERIFY Sudden Pressure Relay alarm light. (LED). goes out.

Rev.fNo.

O' Page No.

66 of 91

CPS No.

2800.91 8.6.45 At ERAT Transformer, perform the following:

a)

VERIFY ERAT local annunciator point 7, SUDDEN PRESSURE RELAY, is still in alarm.

b)

Verify DMM reads a CLOSED Circuit.

8.6.45 At ERAT local annunciator panel, PLACE the TEST-RESET /OFF-ON switch for point 7, SUDDEN PRESSURE RELAY, to the off position.

8.6.46 At ERAT Transformer, perform the following:

a)

VERIFY ERAT local annunciator point 7, SUDDEN PRESSURE RELAY, will clear.

b)

Verify DMM reads a OPEN Circuit.

8.6.47 VERIFY that annunciator window 5010-5F, SUDDEN PRESS EMERG RES AUX TRANSFORMER, is still in alarm.

8.6.48 At ERAT local annunciator panel, PLACE the TEST-RESET /OFF-ON switch for point 7, SUDDEN PRESSURE RELAY, to the ON position.

9.6.49 At ERAT Transformer, perform the following:

a)

VERIFY ERAT local annunciator point 7, SUDDEN PRESSURE RELAY, will clear.

b)

Verify DMM reads a OPEN Circuit.

8.6.50 Reset lock-out relay 86S-ET, LOCKOUT RELAY ERAT SLOW SYSTEM.

8.6.51 VERIFY annunciator window 5010-5F, SUDDEN PRESS EMERG RES AUX TRANSFORMER, will clear.

8.6.52 VERIFY annunciator window 5010-4E, LOCK-OUT TRIP EMERG RES AUX TRANSFORMER, will clear.

8.6.53 VERIFY computer input 1AP-BC907, ERAT PROT SYS S LOCKOUT, indicates reset.

8.6.54 VERIFY computer input 1AP-BC204, ERAT SUDDEN PRESS, indicates reset.

8.6.55 RESET ERAT Deluge Valve 1FP101C per step B of Appendix B (Do not remove clamp at this time) 8.6.56 LOCATE the ERAT Transformer Pressure Relay (Tapchanger) 63B.

8.6.57 Set the handle of 0AP016, LTC OIL TANK PRESS RELAY ISOL VLV, to the Test position as shown on the information plate.

Rev. No.

O Page No.

67 of 91

CPS No.

2800.91 8.6.58 CONNECT a 0-20 psi nitrogen source and pressure test gauge to the test tap on the pressure relay (ihread R 1/8").

8.6.59 INCREASE the nitrogen pressure and Verify the following:

a)

At local ERAT annt'nciator panel, VERIFY ERAT i

local annunciator point 5, TAPCHANGER PRESSURE RELAY,is in alarm. (approximately 7 psi) b)

Verify DMM reads a Closed Circuit.

8.6.60 VERIFY annunciator window 5010-5F, SUDDEN PRESS EMERG RES AUX TRANSFORMER IS IN ALARM.

8.6.61 VERIFY relay 86S-ET, LOCKOUT RELAY ERAT SLOW SYSTEM trips.

8.6.62 VERIFY annunciator window 5010-4E, LOCK-OUT TRIP EMERG RES AUX TRANSFORMER, is in alarm.

8.6.63 VERIFY computer input 1AP-BC907, ERAT PROT SYS S LOCKOUT, indicates trip.

8.6.64 VERIFY computer input 1AP-BC204, ERAT SUDDEN PRESS, indicates trip.

8.6.65 VERIFY ERAT deluge valve 1FP101C trips.

8.6.66 DECREASE the nitrogen pressure to approximately zero psig and Verify the following:

a)

Local annunciator point 5, TAPCHANGER PRESSURE RELAY, is still in alarm.

b)

DMM reads CLOSED circuit.

8.6.67 At ERAT local annunciator panel, PLACE the TEST-RESET /OFF-ON switch for point 5, TAPCHANGER PRESSURE RELAY, to the OFF position.

8.6.68 At ERAT Transformer, perform the following:

a)

VERIFY ERAT local annunciator point 5, TAPCHANGER PRESSURE RELAY, will clear.

b)

Verify DMM reads an OPEN Circuit.

8.6.69 Verify the following:

a) 5010-4E, LOCK-OUT TRIP EMERG RES AUX TRANSFORMER,is still in alarm.

b) 5010-5F, SUDDEN PRESS EMERG RES AUX TRANSFORMER, is still in alarm.

Rev. No.

O Page No.

68 of 91

CPS No. _2800.91 8.6.70 At ERAT local annunciator panel, PLRCE the TEST-RESET /OFF-ON switch for point 5, TAPCHANGER PRESSURE RELAY, to the ON position.

l 8.6.71 At ERAT Transformer, perform the following:

I a)

VERIFY ERAT local annunciator point 5, TAPCHANGER PRESSURE RELAY, will clear.

l b)

Verify DMM reads an OPEN Circuit.

l 8.6.72 Reset lock-out relay 86S-ET, LOCKOUT RELAY ERAT j

SLOW SYSTEM.

i 8.6.73 VERIFY annunciator window 5010-5F, SUDDEN PRESS EMERG RES AUX TRANSFORMER, will clear.

8.6.74 VERIFY annunciator window 5010-4E, LOCK-OUT TRIP j

EMERG RES AUX TRANSFORMER, will clear.

8.6.75 VERIFY computer input 1AP-BC907, ERAT PROT SYS S LOCKOUT, indicates reset.

8.6.76 VERIFY computer input 1AP-BC204, ERAT SUDDEN PRESS, indicates reset.

8.6.77 RESET ERAT Deluge Valve 1FP101C per step B of Appendix B (Do not remove clamp at this time) l 8.6.78 Return the handle of 0AP016, LTC OIL TANK PRESS RELAY ISOL VLV, to the SERVICE (vertical) position.

8.6.79 DISCONNECT the nitrogen source and pressure gauge

{

from Tapchanger Pressure Relay 63B.

8.6.80 At OPL91J, Momentarily jumper from terminals 1 to 10 of overcurrent Relay 351A-ET 138KV O.C.

OA ERAT.

8.6.81

' VERIFY Lockout Relay 86S-ET, LOCKOUT RELAY ERAT SLOW SYSTEM, trips.

8.6.82 VERIFY alarm " LOCK-OUT TRIP EMERG RES AUX TRANSF I

PROT SYS" at annunciator window 5010-4E is ON.

8.6.83 VERIFY computer input 1AP-BC907, ERAT PROT SYS S l

LOCKOUT, indicates trip.

l-8.6.84 VERIFY computer input 1AP-BC567, ERAT 138 KV L

indicates trip.

l 8.6.85 RESET Lock-Out Relay 86S-ET_

Rev. No.

O Page No.

69 of 91 m

r l

CPS No.

2800.91 8.6.86

' VERIFY alarm " LOCK-OUT TRIP EMERG RES AUX TRANSF PROT SYS" at annunciator window 5010-4E will clear.

(

)

8.6.87 VERIFY computer input 1AP-BC907, ERAT PROT SYS S LOCKOUT, indicates reset.

l l

8.6.88 VERIFY computer input 1AP-BC567, ERAT 138 KV i

indicates reset.

r 8.6.89 At OPL91J momentarily jumper from terminals 1 to 10 of overcurrent Relay 350/351-ET OB.

8.6.90 VERIFY Lockout Relay 86S-ET trips.

8.6.91 VERIFY alarm " LOCK-OUT TRIP EMERG RES AUX TRANSF PROT SYS" at annunciator window 5010-4E is ON.

l 8.6.92 VERIFY computer input 1AP-BC907, ERAT PROT SYS S LOCKOUT, indicates trip.

8.6.93 VERIFY computer input 1AP-BC567, ERAT 138 KV j

indicates trip.

8.6.94 RESET Lockout Relay 86S-ET.

8.6.95 VERIFY alarm " LOCK-OUT TRIP EMERG RES AUX TRANSF PROT SYS" at annunciator window 5010-4E will clear.

8.6.96 VERIFY computer input 1AP-BC907, ERAT PROT SYS S LOCKOUT, indicates reset.

8.6.97 VERIFY computer input 1AP-BC567, ERAT 138 KV indicates reset.

8.6.98 At OPL91J, momentarily jumper from terminals 1 to 10 of overcurrent relay 350/351-ET OC.

.8.6.99 VERIFY Lockout Relay 86S-ET trips.

1 i

8.6.100 VERIFY alarm " LOCK-OUT TRIP EMERG RES AUX TRANSF PROT SYS" at annunciator window 5010-4E is ON.

8.6.101 VERIFY computer input 1AP-BC907, ERAT PROT SYS S LOCKOUT, indicates trip.

8.6.102 RESET Lock-Out Relay 86S-ET.

8.6.103 VERIFY alarm " LOCK-OUT TRIP EMERG RES AUX TRANSF PROT SYS" at annunciator window 5010-4E will clear.

8.6.104 VERIFY computer input 1AP-BC907, ERAT PROT SYS S i

LOCKOUT, indicates reset.

I l

Rev. No.-

0 Page No.

70 of 91

l CPS No.

2800.91 8.6.105 VERIFY computer input 1AP-BC567, ERAT 138 KV indicates reset.

8.6.106 At OPL91J, momentarily jumper from terminals 1 to 10 of 351N -ET, 138KV NEUT. O.C. ERAT.

8.6.107 VERIFY Lockout Relay 86S-ET trips.

I 8.6.108 VERIFY alarm " LOCK-OUT TRIP EMERG RES AUX TRANSF PROT SYS" at annunciator window 5010-4E is ON.

8.6.109 VERIFY computer input 1AP-BC907, ERAT PROT SYS S LOCKOUT, indicates trip.

8.6.110 VERIFY computer input 1AP-BC567, ERAT 138 KV' indicates trip.

8.6.111 VERIFY computer input 1AP-BC583 indicates trip.

8.6.112 RESET Lock-Out Relay 86S-ET.

8.6.113 VERIFY alarm " LOCK-OUT TRIP EMERG RES AUX TRANSF PROT SYS" at annunciator window 5010-4E will clear.

8.6.114 VERIFY computer input 1AP-BC907, ERAT PROT SYS S LOCKOUT, indicates reset.

8.6.115 VERIFY computer input 1AP-BC583, ERAT PRI WNDG NEUTRAL OC indicates reset.

8.6.116 At OPL91J, momentarily jumper from terminals 1 to 10 of 251N-ET, 4KV NEUT. O.C. ERAT.

8.6.117 VERIFY Lockout Relay 86S-ET trips.

l 8.6.118 VERIFY alarm " LOCK-OUT TRIP EMERG RES AUX TRANSF 4

PROT SYS" at annunciator window 5010-4E is ON.

8.6.119 VERIFY computer input 1AP-BC907, ERAT PROT SYS S LOCKOUT, indicates trip.

j l

8.6.120 VERIFY computer input 1AP-BC582, ERAT SEC WNDG NEUTRAL OC indicates trip.

l 8.6.121 RESET Lock-Out Relay 86S-ET.

I 8.6.122 VERIFY alarm " LOCK-OUT TRIP EMERG RES AUX TRANSF 1

PROT SYS" at annunciator window 5010-4E will clear.

8.6.123 VERIFY computer input 1AP-BC907, ERAT PROT SYS S LOCKOUT, indicates reset.

Rev. No.

O Page No.

71 of 91

CPS No.

2800.91 8.6.124 VERIFY computer input 1AP-EC582, ERAT SEC WNDG NEUTRAL OC indicates reset.

8.6.125 CLOSE TS3-4 of TS-86 SET at ERAT PROTECTIVE RELAY PANEL, OPL91J, and reinstall the back cover for OPL91J.

8.6.126 AT ERAT Deluge Valve 1FP101C, RESTORE valve by removing the "C" clamp per Appendix B

)

i I.

Rev. No.

O Page No.

72 of 91

CPS No.

2800.91 8.7 ERAT Protective Relay Scheme F NOTE Test Section 8.7 demonstrates proper operation of ERAT Protective Relay Scheme F 8.7.1 Notify the Control Room Operator that the following annunciators will alarm in this section:

5010-4F LOCK-OUT TRIP EMERG RES AUX TRANSF PROT SYS F 5010-1A AUTO TRIP SWITCHER 8.7.2 Ensure Circuit Switcher control wiring, including Auto Trip Alarm and Computer Point 1SY-BC610 have been functionally checked. (MWR # D82234) 8.7.3 AT ERAT Deluge Valve 1FP101C, BLOCK valve by applying a "C" clamp per Appendix B so as to prevent the weight from striking the valve trigger 8.7.4 VERIFY computer input 1AP-BC908, ERAT PROT SYS F LOCKOUT 10 9, contacts are open.

8.7.5 At OPL91J, verify Blue light for Lockout Relay 286F-BE is OFF and that the blue light for lockout relay 86F-ET is ON ( l 'iC17E, ckt. #23).

8.7.6 VERIFY alarm " LOCK-OUT TRIP EMERG RES AUX TRANSF PROT SYS F" at annunciator window 5010-4F is OFF.

8.7.7 At OPL91J, VERIFY lock out relay 86F-ET, LOCKOUT RELAY ERAT FAST SYSTEM is reset.

8.7.8 At OPL91J, VERIFY lock out relay 86S-ET, LOCKOUT RELAY ERAT SLOW SYSTEM is reset.

8.7.9 At panel 1H13-P870-51C, CLOSE circuit switcher B018A and verify red light is on.

8.7.10 VERIFY alarm " AUTO TRIP SWITCHER" at annunciator window 5010-1A is OFF.

Rev. No.

O Page No.

73 of 91

CPS No.

2800.91 CAUTION L

The following step is carried out on an energized 125 VDC circuit. Proper safety precautions should l

be used.

l l

8.7.11 At OPL91J, OPEN the back panel and momentarily jumper from terminals 1 to 10 of Differential Relay 87-ET OA.

8.7.12 At OPL91J, VERIFY lock out relay 86F-ET is tripped.

8.7.13 VERIFY computer input 1AP-BC908, ERAT PROT SYS F LOCKOUT 10 9, contacts are closed.

I 8.7.14 VERIFY alarm " LOCK-OUT TRIP EMERG RES AUX TRANSF PROT SYS F" at annunciator window 5010-4F is ON.

8.7.15 VERIFY alarm " AUTO TRIP SWITCHER" at annunciator window 5010-1A is ON.

8.7.16 VERIFY ERAT Deluge valve 1FP101C trips.

8.7.17 Reset' lockout relay 86F-ET.

8.7.18 VERIFY computer input 1AP-BC908, ERAT PROT SYS F LOCKOUT 10 9, contacts are open.

8.7.19 VERIFY alarm " LOCK-OUT TRIP EMERG RES AUX TRANSF PROT SYS F" at annunciator window 5010-4F will clear.

8.7.20 VERIFY alarm " AUTO TRIP SWITCHER" at annunciator window 5010-1A will clear.

8.7.21 RESET ERAT Deluge valve 1FP101C per step B of Appendix B(Do not remove clamp at this time).

8.7.22 At panel 1H13-P870-51C, CLOSE circuit switcher B018A and verify red light is on.

CAUTION The following step is carried out on an energized 125 VDC circuit. Proper safety precautions should be used.

8.7.23 At OPL91J, momentarily jumper from terminals 1 to 10 of Differential Relay 87-ET OB.

.Rev. No.

0-Page No.

74 of 91 j

CPS No.

2800.91 8.7.24 At OPL91J, VERIFY lock out relay 86F-ET is tripped.

8.7.25 VERIFY computer input 1AP-BC908, ERAT PROT SYS F LOCKOUT 10 9, contacts are closed.

8.7.26 VERIFY alarm " LOCK-OUT TRIP EMERG RES AUX TRANSF PROT SYS F" at annunciator window 5010-4F is ON.

8.7.27 VERIFY alarm " AUTO TRIP SWITCHER" at annunciator window 5010-1A is ON.

3.7.28 VERIFY ERAT Deluge valve 1FP101C trips.

8.7.29 Reset lockout relay 86F-ET.

8.7.30 VERIFY computer input 1AP-BC908, ERAT PROT SYS F LOCKOUT 10 9, contacts are open.

8.7.31 VERIFY alarm " LOCK-OUT TRIP EMERG RES AUX TRANSF PROT SYS F" at annunciator window 5010-4F will clear.

8.7.32 VERIFY alarm " AUTO TRIP SWITCHER" at annunciator window 5010-1A will clear.

8.7.33 RESET ERAT Deluge valve 1FP101C per step B of Appendix B(Do not remove clamp at this time).

8.7.34 At panel 1H13-P870-51C, CLOSE circuit switcher B018A and verify red light is on.

CAUTION The following step is carried out on an energized 125 VDC circuit. Proper safety precautions should be used.

8.7.35 At OPL91J, momentarily jumper from terminals 1 to 10 of Differential Relay 87-ET OC.

8.7.36 At OPL91J, VERIFY lock out relay 86F-ET is tripped.

8.7.37 VERIFY computer input 1AP-BC908, ERAT PROT SYS F LOCKOUT 10 9, contacts are closed.

8.7.38 VERIFY alarm " LOCK-OUT TRIP EMERG RES AUX TRANSF PROT SYS F" at annunciator window 5010-4F is ON.

I 8.7.39 VERIFY alarm " AUTO TRIP SWITCHER" at annunciator window 5010-1A is ON.

I 8.7.40 VERIFY ERAT Deluge valve 1FP101C trips.

Rev. No.

O Page No.

75 of 91

CPS No.

2800.91 8.7.41 Reset lockout relay 86F-ET, and restore the back panel for OPL91J.

8.7.42 VERIFY computer input 1AP-BC908, ERAT PROT SYS F LOCKOUT 10 9, contacts are open.

8.7.43 VERIFY alarm " LOCK-OUT TRIP EMERG RES AUX TRANSF PROT SYS F" at annunciator window 5010-4F will clear.

8.7.44 VERIFY alarm " AUTO TRIP SWITCHER" at annunciator window 5010-1A will clear.

8.7.45 RESTORE ERAT Deluge valve 1FP101C by removing the C clamp installed at the beginning of the section per Appendix B Rev. No.

O Page No.

76 of 91

CPS No.

2800.91 l-8.8 ERAT Transformer Initial Enargization NOTE Test Section 8.8 performs the initial energization of the ERAT,. including coordination of a pre-energization walkdown, Voltage Phase Measurements prior to energization,~ Primary and Secondary.

j Voltage measurements at all load tap positions, and demonstration of LTC control.

8.8.1 Perform the following:

'a)

Inform the Control Room Operator that the following main' Control-Room Annunciators will come into. alarm during this test section:

i 5010-6F, TROUBLE EMERG RES AUX TRANSFORMER b)

Request Operations to obtain a switching order from.the Load Dispatcher to open and

-close ERAT Circuit Switcher B018.

8.8.2 Ensure the following switches at the ERAT are positioned ~as listed:

Main Cabinet 43-1, AUTO /OFF/ MAN Off

/

l 43-2, AUTO /OFF/ MAN Off

/

43C, POS.-1/POS. 2 POS.1

/

43S, LOCAL CONTROL /

LOCAL CONTROL

/

REMOTE CONTROL TS, _

RELAY-TEST /

RELAY TEST

/

RELAY OPERATE

43T, MANUAL CONTROL /

MANUAL CONTROL

/

AUTOMATIC CONTROL CS,

. MANUAL RAISE /

OFF

/

MANUAL LOWER Device 90 LDC Direct

/

LTC_ Compartment L

43TC, LOCAL /OFF/ REMOTE OFF

/

L 84CS, LOWER /OFF/ RAISE OFF

/

p 8:. 8. 3 Perform the following:

a)

At the-ERAT Transformer Area, OPEN, if necessary 120 VAC ERAT TEMPORARY POWER breaker.

(DV)

/

b)

(Record)

At the ERAT Transformer, disconnect 120 VAC ERAT TEMPORARY POWER, by LIFTING the power source to'the following locations (Record on wireremoval and installation form I

CPS No.8801.16F001):

Terminal Point B3 (DV)

/

3".'

Terminal. Point B4 (DV)

/

P,ev. No.

OL Page No.

77 of 91 t.

_ _ _ _ _ _ _ _ - _ _ _ - - _ _ _ _ ~

CPS No.

2800.91 l

8.8.4 (Record)

At the ERAT transformer, LAND the Potential transformer leads to the terminal locations listed below at ERAT Transformer Control Cabinet (Record on wire removal and installation form CPS No. 8801.16F001):

Terminal Point B3 (DV)

/

Terminal Point B4 (DV)

/

8.8.5 At the ERAT Transformer area, perform the following:

a)

At the ERAT Transformer Area, OPEN, if necessary, 480VAC ERAT TEMPORARY POWER disconnect switch.

(DV)

/

b)

(Record)

At ERAT Transformer, disconnect 480

.VAC ERAT TEMPORARY POWER, by LIFTING the power source to the following locations at the ERAT Transformer (Record on wire removal and installation form CPS No. 8801.16F001):

Terminal Point A37 (D 7)

/

Terminal Point A38 (DV)

/

Terminal Point A39 (DV)

/

8.8.6 Perform the following:

a)

OPEN, if necessary, 480 VAC ERAT NORMAL POWER disconnect switch.

(DV)

/

b)

(Record) At ERAT Transformer, connect 480 VAC ERAT NORMAL POWER, by LANDING the power source to the following locations at the ERAT Transformer (Record on wire removal and installation form CPS No. 8801.16F001):

Terminal Point A37 (DV)

/

Terminal Point A38 (DV)

/

Terminal Point A39 (DV)

/

8.8.7 (Record) LAND High and Low side connections listed below,.as necessary.(Record on wire removal and I

installation form CPS No. 8801.16F001)

H0

/

H1

/

H2

/

H3

/

L X0

/

(

X1

/

x2

/

X3

/

8.8.8 (Record)

Verify safety grounds are removed, as necessary (Record on wire removal and l

installation form CPS No. 8801.16F001.

/

Rev. No.

O Page No.

78 of 91

CPS No.

2800.91 8.8.9 Release Danger Tags for ERAT, circuit Switcher B018. (Do not release danger tags for Disconnect-Switch 1ET4, 4KV Bus 1Al feed breaker 252-221A1, 4KV Bus 1B1 252-221B1, and 4kV Bus 1C1 feed breaker 252-221C1.

at this time.)-

8.8.10 Perform pre-energization walkdown of ERAT transformer. Walkdown members should consist of representatives from Substation Maintenance, Operations, Electrical Maintenance, and the Test Director. See Appendix C for minimum criteria.

8.8.11 CLOSE/ VERIFY CLOSED the follwing breakers:

480 VAC ERAT RESERVE POWER (disconnect switch)

(DV)

/

480 VAC ERAT NORMAL POWER (disconnect switch)

(DV)

/

Breaker 8-1 (ERAT)

(DV)

/

Breaker 8-2 (ERAT)

(DV)

/

Breaker 8-3 (ERAT)

(DV)

/

Breaker 8-4 (ERAT)

(DV)

/

Breaker 8-5 (ERAT)

(DV)

/

Breaker 8-6 (ERAT)

(DV)

/

Breaker 8-7 (ERAT)

(DV)

/

Breaker 8m (ERAT LTC)

(DV)

/

8.8.12 PLACE the following switches in AUTO:

43-1, AUTO /OFF/ MAN switch (DV)

/

l 43-2, AUTO /OFF/ MAN switch (DV)

/

l 8.8.13 Request operations to energize the ERAT in an unloaded condition per CPS No. 3505.01, 345 &

138KV SWITCHYARD (SY). Record Time and date.

Time Date CAUTION During the initial energization of the ERAT, watch closely for any sudden. change in the patameters lmonitoredinDataSheet3.

8.8.14 Perform transformer readings per Data Sheet 3, Initial Energization ERAT Transformer Checks.

Take readings hourly for the first 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br /> that the ERAT is energized.

Rev. No.. _0_

Page No.

79 of 91

1 CPS No.

2800.91 0.8.15 Perform the following:

l a)

Note tap position on Local tap position Indicator. Record position below:

b)

At the ERAT transformer control cabinet, connect a recorder across terminals B3 and l

B4.

(Set recorder to record 120 VAC)

(DV)

/

l (As Found Tap Position) l 8.8.16 At the ERAT Load Tap Changer, place transfer switch 43TC, LOCAL /OFF/ REMOTE in the LOCAL position, and turn on the recorder.

8.8.17 (Record)With the ERAT energized and unloaded, contact the load dispatcher and obtain the 138 KV line voltage. Record this as the ERAT primary voltage on Data Sheet 2 (Circle whether Primary or Alternate location) 8.8.18 (Record) At ERAT transformer, measure the voltage between terminals B3 and B4. (200 VAC range) (Record on Data Sheet 2)

'8.8.19 (Record)

Using the potential transformer winding ratio of 35:1, multiply the value obtained in step 8.8.18 by 35 and record the result in Data Sheet 2.

8.8.20 Using 84CS, LOWER /OFF/ RAISE switch, move tap changer to the next tap position Repeat steps 8.8.18, and 8.8.19 for all tap positions.

8.8.21 (Record)Using 84CS, LOWER /OFF/ RAISE switch, return tap changer to the AS Found Position. Note position and record below:

(Tap Position) 8.8.22 At the ERAT Load Tap Changer, place it necessary, transfer switch 43TC, LOCAL /OFF/ REMOTE in the REMOTE position, and turn off the recorder.

i 8.8.23 At ERAT transformer main cabinet, PLACE, if necessary, TS, RELAY TEST / RELAY OPERATE switch in i

the RELAY OPERATE position.

8.8.24 (Record)

PLACE and HOLD Control Switch CS, MANUAL RAISE / MANUAL LOWER, in the MANUAL RAISE position until at device 90, VOLTAGE REGULATING RELAY, the Lower LED is illuminated.

Record tap position below:

Tap position l

Rev. No.

O Page No.

80 of 91 L_________.

CPS No.

2800.91 8.8.25 (Record)

At ERAT transformer main cabinet, PLACE selector switch 43T, MANUAL CONTROL / AUTOMATIC CONTROL in the AUTOMATIC CONTROL position, and VERIFY that the tap changer moves in response to the VOLTAGE REGULATING RELAY 90.

When movement has completed, record the tap position below:

Tap position I

i 18.8.26 At ERAT transformer main cabinet, PLACE selector switch 43T, MANUAL CONTROL / AUTOMATIC CONTROL in the MANUAL CONTROL position.

8.8.27 (Record)

PLACE and HOLD Control Switch CS, MANUAL RAISE / MANUAL LOWER, in the LOWER position until at 90, VOLTAGE REGULATING RELAY, the Raise LED is illuminated. Record tap position below:

Tap position 8.8.28 (Record)

At ERAT transformer main cabinet, PLACE selector switch 43T, MANUAL CONTROL / AUTOMATIC CONTROL in the AUTOMATIC CONTROL position, and VERIFY that the tap changer moves in response to the VOLTAGE REGULATING RELAY 90.

When movement has completed, record the tap position below:

Tap position 8.8.29 At ERAT transformer control panel OPEN breaker 8-1.

(DV)

/

8.8.30 (Record)

At ERAT transformer, observe any load tap changer movement.

Record final tap setting below:

tap setting 8.8.31 At ERAT transformer main cabinet, PLACE selector switch 43T, MANUAL CONTROL / AUTOMATIC CONTROL in the MANUAL CONTROL position.

8.8.31 At ERAT transformer main cabinet, CLOSE breaker 8-1.

/

8.8.32 At ERAT transformer main cabinet, PLACE selector switch TS, RELAY TEST / RELAY OPERATE in the RELAY l

TEST position.

8.8.33 (Record)

At ERAT Transformer control cabinet, l

i LIFT and tape back wire 31 from Terminal Point B31.(Record on wire removal and installation form 8801.16F001):

Terminal Point B31 (DV)

/

Rev. No.

O Page No.

81 of 91

CPS No.

2800.91 8.8.34 Request operations to CLOSE disconnect switch ET14.

CAUTION The following step requires measurements across energized 4kv bus. Applicable safety requirements for personnel protection per Site Safety Standard 17 should be taken.

8.8.35.

(Record)

At disconnect switch ET4, using the Chance Phasing Tool, or equivalent, perform a phase check comparison across the open disconnect for'all three phases. RECORD results below.

ERAT side 0A Volts RAT. side OA Volts ERAT side OB Volts RAT side OB Volts ERAT side OC Volts RAT side OC Volts 8.8.36 Request operations to OPEN disconnect switch ET14.

j

-8.8.47 Remove the Ohmeter installed across terminals 1 and 2 of Load Tap Changer TAP Position transmitter EPI.

/

'8.8.48 At the ERAT transformer Cotrol Cabinet,-remove the recorder from terminals B3 and B4.

/

1

-9.0 ACCEPTANCE CRITERIA

~

9.1 operability

-9.1.1 Verify transformer turns ratio for all tap settings to be within +/- 0.85%(0.0085) of the ratio specified on the transformer nameplate.

i (Step 8.1. 9) (MWR D82232)

'9.1.2 ERAT. transformer can be energized via' station procedures and operate per vendor recommendations (8.8.14).

t i

9.2 other-i

.9.2.1 ERAT Transformer Cooling Fans shall function as designed.

(8.3.20,-8.3.28, 8.3.31) i Rev. No.

O Page No.

82 of 91 L_

CPS No.

2800.91 9.2.2 Verify Load Tap Changer Electrical stops will prevent tap changer movement beyond the 8 Raise (8R) and 8 Lower (8L) positions (Steps 8.4.19, 8.4.21) 9.2.3 Verify ERAT Transformer Voltage Regulating Relay 90, will produce RAISE and LOWER tap change signals upon a simulted error signal.

l (8.4.43,8.4.46) 9.2.4 Verify ERAT Transformer Voltage Backup Relay 59 will block tap changer movement upon a simulated error signal.

(8.4.52, 8.4.56) 9.2.5 Verify ERAT Transformer Voltage Backup Relay 59 will produce a LOWER tap changer signal upon a simulated error signal that is greater in magnitude than the BLOCK RAISE signal. (8.4.63) 9.2.6 ERAT Circuit Switcher controls, indications, and j

Alarms shall function as designed (8.5) 9.2.7 ERAT Transformer Protective Relay Scheme S Lockout Relay Actuates from simulated trip signals.

(8.6.15, 8.6.39, 8.6.61, 8.6.81, 8.6.90, 8.6.99, 8.6.107, 8.6.117) 9.2.8 ERAT Transformer Protective Relay Scheme F Lockout Relay Actuates from simulated trip signals. (8.7.12, 8.7.24, 8.7.36) j 10.0 FINAL CONDITIONS 10.1 Restorations 10.1.1 Plant AC electrical distribution system returned to desired configuration per procedure CPS No.

3501.01.

10.2 The SM/WCS/CRS notified of-test completion.

TIME DATE I

f Rev. No.

O Page No.

83 of 91

CPS Wo.

2800.91

11.0 REFERENCES

11.1 Site Safety Standards 11.2 ITS 3.8.2 11.3 CPS No. 1302.02, CONDUCT OF CLINTON POWER STATION TESTING 11.4 CPS No. 1014.03, TEMPORARY MODIFICATIONS

{

11.5 CPS No. 3505.01, 345 & 138 KV SWITCHYARD (SY) 11.6 Drawings E02-0AP54, Rev. K E02-1AP01-Sh.

1, Rev. L E02-1AP03, Rev. J E02-1AP04, Sht.

1, Rev. E E02-1AP04, Sht. 20, Rev. A E02-1AP12, Sht. 08, Rev. N E02-1AP12, Sht. 12, Rev. T E02-1AP99, Sht. 10, Rev. P E02-1AP99, Sht. 12, Rev. T E02-1AP99, Sht. 15, Rev. J E02-1AP99, Sht. 16, Rev. N E02-1AP99, Sht. 17, Rev. H E02-1AP99, Sht. 18, Rev. H E02-1AP99, Sht. 94, Rev. G E02-1DC05, Rev. P E02-1FP99, Sht. 58, Rev. C E02-1HP99, Sht. 108, Rev. K E02-9AP99, Sht.

1, Rev. 0 E03-0AP03E, Sht. 1 Rev. F E03-0AP03E, Sht. 2 Rev. J E03-0AP03E, Sht. 1 Rev. F E03-0AP95E, Rev. G E03-0PL91J, Sht.

1, Rev. F E03-0PL91J, Sht. 2, Rev. D E03-0PL91J, Sht.

3, Rev. P E03-0PL91J, Sht.

4, Rev. H E03-1AP55E, Sht.

3, Rev. L E03-1AP91E, Sht 2, Rev. E E03-1C91-P011, Sht.

1, Rev. R E03-1DC17E-004, Rev. S E03-1FP00, Sht. 33, Rev. E E03-1FP00. Sht. 42, Rev. B E03-1LV00, Sht.

1, Rev. C E03-1P732E, Sht. 2, Rev. M E03-1P744E, Sht. 2, Rev. P E03-09L91J, Sht.

3, Rev. P E03-09L91J, Sht.

4, Rev. H E04-0PL91J, Rev. A M01-1109, Sht 3, Rev. D T05-0022, Rev. H Rev. No.

O Page No.

84 of 91

CPS No. _2800.91 11.7 ABB Vendor Information SLL9407-1 SLL9407-2 SLL9407-3 SLL9407-04, Sht. 1-2 SLL9407-05. Sht. 1-3 SLL9407-6 SLL9407-7 SLL9407-8 SLL9407-9 SLL9407-10 SLL9407-11 Tapchanger Control M-0067E LTC Backup Control M-0329A 12.0 APPENDICES A.

TEST LOG B.

Model C Deluge Valve C.

Pre-Energization Walkdown D.

Connector Development, 710-1, Liquid Low Level Switch (Transformer) and 710-2, Liquid Low Level Switch (Tap Changer)

E.

Attachments 13.0 DOCUMENTS CPS No. 2800.91D001, ERAT TRANSFORMER TURNS RATIO VERIFICATION CPS No. 2800.91D002, ERAT TRANSFORMER TURNS RATIO VOLTAGE MEASUREMENT CPS No. 2800.91D003, INITIAL ENERGIZATION ERAT TRANSFORMER CHECKS Test Results Evaluation / Review Acceptable Not acceptable MWR #

(N/A if not applicable)

CR #

(N/A if not applicable)

Rev. No.

O Page No.

85 of 91

CPS No.

2800.91 COMMENTS / DEFICIENCIES l

l

)

\\

NOTE: Test performers may sign on CPS 1302.02F001.

1 Performed by:

(Print)

(Initials)

(Date) i (Print)

(Initials)

(Date)

(Print)

(Initials)

(Date)

(Print)

(Initials)

(Date)

(Print)

(Initials)

(Date)

(Print)

(Initials)

(Date) i 4

i-Rev. No.

O Page No.

86 of 91

~ _ _ _ _ _ _ _ _ _ _ -_

7 CPS No.

2800.91 l

APPENDIX A TEST LOG i

l PROCEDURE #

I 1

Page of PERFORMED BY:

(print name)

(signature)

(date) i i

Rev. No.

O Page No.

87 of 91

1 9

)

e d5 0

n4 0

a(

8 2

e

)

0l 2d r( n m

o a

a N

edh

=

m r

r s

m u

.u l o o== =,. _ o S

o

- =*

crt

_ _ M

=

=

P c

e

,e C

=g'%

eesp t

=m rdem

,o

,,s

,u

=o A

,v ua air a n

u l

r c

. ;:, u o

i s gt C an A o

m.oC u-

/7'

- gt r

r n

at e

f.a s

lWge a

nv fi o g-

{~

yol m f

l e ipur

}g y9 E

eet t) rop b

V cv ye9 B

i obs3

,[. =.

"b L

vdt e(

"_1,

^

X

=

. =- =

rn dr

- 'L

=

A ea)i r

I

~

_ - m.== = u

/NJ=.

D V

S 2ose

(

h" &,1 '=' b

==,-

G

~'

l2 niv

^

3 E

oe( e o

E P

..c tn.l.c

~'

o P

E c

a ot c.

A n pt s h e

, ~ Q.

E asl stp a.

U o

W c

i t tra L

tedeel

=

s e.@,-['b.~.i::

n E

reoef e D

oRHrAR hI t

1

\\"

4 N[ W W,

_ ~

s C

e RAB CD L

Wf E

A D

p 1

f

.m.-

k,"

O ota) i

.=

g%!

_. L ""

M e

c1 e

.4' Wl1d ev dg m.

(

.~Q'"*.

m ine sihmi) h==.[ O A"!-

ptr 2

11 n

w

.np as2

.==

./

oon i(

o

)

H 9

roh

  • L
. s 3 pd ct

,., E 8[

e m

ttnt

(

v t

atsaeW 3'

tvt fco a

mrl ael m v

\\.

eechr ew n_s soc l oal yc hl l e S

l cid pb el uwa u:-

==p~ = _/;.

J evas-el y rot t al

)

=

  • o umsx2see ceno2ndt "0

eRIb( iI a c.

e.

S j >

T.

o.

TAB

CPS No.

2800.91 APPENDIX C Pre-Energization Walkdown 1.

Walkdown all protective relays to ensure covers have been reinstalled and relays are reset.

2.

Ensure all Red Tags have been removed.

3.

Ensure all safety grounds have been removed.

4.

Perform general walkdown of area.

(Loose connections, construction materials, etc.)

i i

i i

Rev. No.

O Page No.

89 of 91

CPS No. d2800.91 APPENDIX D Connector Development 710-1, Liquid Low Level Switch (Trans former) and 710-2, Liquid Low Level Switch (Tap Changer)

Green Q

White 0"X O

O O

I l

l l

l I

Rev. No.

O Page No.

90 of 91

7-L CPS No.

2800.91 l

APPENDIX E Attachments l

i

)

i l

i t

Rev. No.

O Page No.

91 of 91

l CPS No.

2800.91D001 ERAT TRANSFORMER TURNS RATIO VERIFICATION SCOPE OF REVYSION:

o New datasheet.

l

)

I 1

CDNTINUGUSUSE

\\

l ORIGINATOR:

Duffy Harmaker/ Gary Grizard CLASS CODE:

SNNDI APPROVAL DATE:

CHANGC NO.

DATE PAGES O

O O.

O O

Rev. No.

O Page No. _1 of 1

[

CPS No.

2800.91D001 ERAT Transformer Turns Ratio Verifice. tion i

Tap Measured Tap Change Ratio j

Change TTR (Step Tolerance Range Position 8.1.6)

(i 0.0085) 2-8R 28.042 27.750 2-7R 28.563 28.081 l

2-6R 28.084 28.594 2-5R 29.605 29.105 2-4R 30.125 29.617 2-3R 30.645 30.129 2-2R 31.166 30.640 2-1R 31.686 31.152 2-N 32.207 31.665 2-1L 32.728 32.176 2-2L 33.248 32.688 2-3L 33.769 33.199 2-4L 34.289 33.711 2-5L 34.809 34.223 2-6L 35.330 34.734 j

2.7L 35.850 35.246 2-8L 35.371 35.757 Performed by:

Verified By:

\\

i Rev. No.

O Page No.

2 of 2

i CPS No.

2800.91D002 ERAT TRANSFORMER TURNS RATIO VOLTAGE MEASUREMENT SCOPE OF REVISION:

  • New datasheet.

l l

l l

l l

CONTINUGUSUSE ORIGINATOR:

Duffy Harmaker/ Gary Grizard CLASS CODE:

SNNDJ.

APPROVAL DATE:

CHANGE NO.

DATE PAGES O

8 9

0 8

Rev. No.

O Page No, 1 of 3

CPS No.

2800.91D002 I

8.8.17 ERAT Primary Voltage (Primary / Secondary location)

(from Load Dispatcher)

KV l

TAP Secondary Voltage Step,8.8.19.

I Position Step 8.8.18 (8.8.18) X 35 -

ERAT Secondary Volts 1R.

x 35 =

di 2R x'35 =

H.

3R x 35 =

Ui 4R x 35 =

SR x 35 =

i 1

6R x 35 =

l 7R x 35 =

BR x 35 =

N.

x 35 =

IL x 35 =

2L x 35 =

3L x 35 =

4L x 35 =

SL x.35 =

6L x 35 =

7L x 35 =

8L x 35 =

Where 35 is the. ratio of primary to secondary windings for the Potential Transformer.

Performed by 1

i Reviewed by i

l:.

i t

Rev.- No, O

Page No.

3 of 3

__m

CPS No.

2800.91D003 INITIAL ENERGIZATION ERAT TRANSFORMER CHECKS SCOPE OF REVISION:

New datasheet.

l

)

l I

i CONYINUGUSUSE ORIGINATOR:

Duffy Harmaker/ Gary Grizard CLASS CODE:

SNNDI APPROVAL DATE:

CHANGC NO.

DATE PAGES O

O O

O Rev. No.

O Page No.

1 of 2

CPS No.

2800.91D003 Initial Energizatic n ERAT Transformer Checks Time Hot Spot Hot Oil Hot Oil Inertaire Ambient Thermometer 49 Thermometer Thermometer Vacuum / Pressure Temperature (Transformer)

(Tap Changer)

Gauge 260-1 260-2 i

i l

l l

l 1

I l

l I

l l

l l

l l

i

(

Rev. No.

O Page No.

2 of 2 i

1

-... _ _ -. - - _. - - - - - - - - -. - - - - - - - - - - - - - - - - - - - - - - - - -