ML20235G911
| ML20235G911 | |
| Person / Time | |
|---|---|
| Site: | Catawba |
| Issue date: | 07/01/1987 |
| From: | DUKE POWER CO. |
| To: | |
| Shared Package | |
| ML20235G890 | List: |
| References | |
| NUDOCS 8707140426 | |
| Download: ML20235G911 (19) | |
Text
_ _ - _ _, _ _ _ _ _ _ _ _ _ _ _ _ _ _ _.
e 8
DEFINITIONS SOURCE CHECK 1.33 A SOURCE CHECK shall be the qualitative assessment of channel response when the channel sensor is exposed to a source of increased radioactivity.
STAGGERED TEST BASIS, 1.34 A STAGGERED TEST BASIS shall consist of:
a.
A test schedule for n systems, subsystems., trains, or other designated components obtained by dividing the specified test interval into n equal subintervals, and b.
The testing of one system, subsystem, train, or other designated component at the beginning of each subinterval.
THERMAL POWER 1.35 THERMAL POWER shall be the total reactor core heat transfer rate to the reactor coolant.
TRIP ACTUATING DEVICE OPERATIONAL TEST 1.36 A TRIP ACTUATING DEVICE OPERATIONAL TEST shall consist of operating the Trip Actuating Device and verifying OPERABILITY of alarm, interlock and/or trip functions.
The TRIP ACTUATING DEVICE OPERATIONAL TEST shall include adjustment, as necessary, of the Trip Actuating Device such that it actuates at the required Setpoint within the required accuracy.
UNIDENTIFIED LEAKAGE 1.37 UNIDENTIFIED LEAKAGE shall be all leakage which is not IDENTIFIED LEAKAGE or CONTROLLED LEAKAGE.
UNRESTRICTED AREA 1.38 An UNRESTRICTED AREA shall be any area at or beyond the SITE BOUNDARY
)
access to which is not controlled by the licensee for purposes of protection of
)
individuals from exposure to radiation and radioactive materials, or any area
{
within the SITE BOUNDARY used for residential quarters or for industrial, commercial, institutional, and/or recreational purposes.
VENTILATION EXHAUST TREATMENT SYSTEM g4;e4c3cArb
]
JE 1.39 A VENTILATION EXHAUST TREATMENT SYSTEM shall be any system designed and R8' installeo to reduce gaseous radiciodine or radioactive material 'n particulate O@
form in - Uluents by passing ventilation or vent exhaust gases t ough :nr aait cao adscreers and/or HEPA filters for the purpose of removing iocines agti cu-Idtes from the gaseous exhaust stream prior to the release to the environment.
p Such a system is not considered to have any effect on noble gas effluents.
f J
Engineered Safety Features (ESF) Atmospheric Cleanup Systems are not considered oo f
to be VENTILATION EXHAUST TREATMENT SYSTEM components.
\\
ox sea CATAWBA - UNITS 1 & 2 1-6
TABLE 3.3-3 (Continued)
ACTION STATEMENTS (Centinued)
I ACTION 20 - With.less than the Minimum Channels OPERABLE, within 1. hour determine by observation of the associated permissive status light (s) that the interlock is in its required state for the existing plant condition, or apply Specification 3.0.3.
ACTION 21 - With the number of' OPERABLE channels one less than the Minimum Channels OPERABLE requirement, be in at least HOT STANDBY within 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> and in at least HOT SHUTDOWN within the following 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br />; however, one channel may be bypassed for up to 2 hours2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br /> for surveillance testing per Specification 4.3.2.1 provided the other channel is OPERABLE.
ACTION 22 - With the number of OPERABLE channels one less than the Total Number of Channels, restore the inoperable channel to OPERABLE status within 48 hours5.555556e-4 days <br />0.0133 hours <br />7.936508e-5 weeks <br />1.8264e-5 months <br /> or be in at least HOT STANDBY within 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> and in at least HOT SHUTDOWN within the following 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br />.
ACTION 23 - With the number of OPERABLE channels one less than the Total Number of Channels, restore the inoperable channel to OPERABLE status within 48 hours5.555556e-4 days <br />0.0133 hours <br />7.936508e-5 weeks <br />1.8264e-5 months <br /> or declare the associated valve inoperable and take the ACTION required by Specification 3.7.1.4.
s ACTION 24 - With the number of OPERABLE channels one less than the Minimum Channels OPERABLE, restore the inoperable channel to OPERABLE status within 48 hours5.555556e-4 days <br />0.0133 hours <br />7.936508e-5 weeks <br />1.8264e-5 months <br />, or initiate and maintain operation of the Control Ro e
ilation System with flow througn the rbers.
HEPA filters and g g a ACTION 25 - With the number o vr:NAw channels one less than the Minimum Channels OPERABLE requirement, be in at least HOT STANDBY within 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br />.
ACTION 26 - With the number of OPERABLE channels one less than the Minimum i
Channels OPERABLE requirement, be in at least HOT STANDBY within 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> and in at least HOT SHUTDOWN within the following 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br />.
ACTION 27 - With the number of OPERABLE channels one less than the Minimum Channels OPERABLE requirement, be in at least HOT STANDBY within 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br />; however, one channel may be bypassed for up to 2 hours2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br /> for surveillance testing per Specification 4.3.2.1 provided the other channel is OPERABLE.
I CATAWBA - UNITS 1 & 2 3/4 3-26
TABLE 3.3-6.(Continued' TABLE NOTATIONS l
With fuel in the fuel storage pool areas, q
With irradiated fuel in the fuel storage pool areas.
When venting or purging from containment to the atmosphere, the trip set-c
]
point shall not exceed the equivalent limits of Specification 3.11.2.1 in
(
l accordance with the methodology and parameters in the ODCM. When not vent- )
j ing or purging in Modes 5 or 6, the alarm setpoint concentration (pCi/ml)
(
1 shall be such that the actual submersion dose rate would not exceed SmR/hr
?
)
without alarm. When not venting or purging in Modes 1 through 4 the alarm P
l setpoint shall be no more than 3 times the containment atmosphere activity (
as indicated by the radiation monitor.
(
ACTION STATEMENTS I
ACTION 30 - With less than the Minimum Channels OPERABLE requirement, l
operation may continue provided the containment purge and exhaust valves are maintained closed.
)
1 ACTION 31 - With the number of operable channels one less than the Minimum l
Channels OPERABLE requirement, within 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> isolate the affected j
Control Room Ventilation System in from outside air with flow through the HEPA filters a cy g rbers.
ACTION 32 - With less than the Minimum Channels rERABi.c requirement, opera-tion may continue for up to 30 days provided an appropriate portable continuous monitor with the same Alarm Setpoint is provided in the fuel storage pool area.
Restore the inoperable monitors to OPERABLE status within 30 days or suspend all operations involving fuel movement in the fuel building.
ACTION 33 - Must satisfy the ACTION requirement for Specification 3.4.6.1.
ACTION 34 - With the number of OPERABLE channels less than the Minimum Channels OPERABLE requirement, operation may continue provided the Fuel Handling Ventilation Exhaust Systein is operating and discharging through the HEPA filters /and arb~
dsorbers.
Otherwise, suspend all operations in lying fuel mo ent in the fuel building.
a.ckwahd ACTION 35 - With the number of OPERABLE channels less than the Minimum Channels OPERABLE requirement, operation may continue provided the Auxiliary Building Filtered Exnaus <yster is operating and discharging orbers.
through the HEPA filter and c bop ACTION 36 - With the number of OPERABLE cnanneis less than the Minimum Channels OPERABLE requirement, operation may continue for up to 30 days provided that, at least once per 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br />, grab samples are collected and analyzed for radioactivity (gross gamma) at a lower limit of detection of no more than 10 7 pCi/ml.
CATAWBA - UNITS 1 & 2 3/4 3-53 Amendment No. M (Unit 1)
~
Amendment No. yf (Unit 2)
1 INSTRUMENTATION CHLORIh'E DETECTION SYSTEMS LIMITING CONDITION FOR OPERATION 1
I 3.3.3.7 Two independent Chlorire Detection Systems, with their Alarm / Trip Setpoints adjusted to actuate at a chlorine concentration of less than or equal to 5 ppe, shall be OPERABLE.
APPLICABILITY: All MGOES.
ACTION:
With one Chlorine Detection System inoperable, restore the inoperable a.
system to OPERABLE status within 7 days or within the next 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> initiate and maintain operation of the Control R -- Are; l
nd - P.:r; :t Ventilation System with flow through'the HEPA' filters achded cadon l
A adsorbers.
b.
'With both Chlorine Detection Systems inoperable, within 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> initiate and maintain operation of the Control Room Ar
=
Ventilation System with flow through the HEPA filter and '"---a=1-
,4gM carbon
^
adsorbers.
The provisions of Specification 3.0.4 are not cpplicable.
c.
SURVEILLANCE REQUIREMENTS Each Chlorine Detection System shall be demonstrated OPERABLE by 4.3.3.7 performance of a CHANNEL CHECK at least once per 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br />, an ANALOG CHANNEL OPERATIONAL TEST at least once per 31 days and a CHANNEL CALIBRATION at least once per 18 months.
CATAWBA - UNITS 1 & 2 3/4 3-70
I CONTAINMENT SYSTEMS ANNULUS VENTILATION SYSTEM LIMITING CONDITION FOR OPERATION
APPLICABILITY.Y:
MODES 1, 2, 3, and 4.
ACTION:
With one Annulus Ventilation System inoperable, restore the inoperable system to OPERABLE status within 7 days or be in at least HOT STANDBY within the next 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> and in COLD SHUTDOWN within the following 30 hours3.472222e-4 days <br />0.00833 hours <br />4.960317e-5 weeks <br />1.1415e-5 months <br />.
SURVEILLANCE REQUIREMENTS
)
- 4. 6.1. 8 Each Annulus Ventilation System shall be demonstrated OP IbEIT e%McA a.
At least once per 31 days on a STAGGERED TEST BASIS (nitiatin, from the control room, flow through the HEPA filters and]carb adsorbers and verifying that the system operates for st 10 continuous hours.
~
he
-heaters operating; aa$WO b.
At least once per 8 months or (11 after any structural maintenance on the HEPA filt or carbon a rber housings, or (2) following painting, fire, c h
elease in any ventilation zone communi-cating with the system by:
1)
Verifying that the cleanup system satisfies the in place pene-tration and bypass leakage testing acceptance criteria of less than 1% (Unit 1), 0.05% (Unit 2) and uses the test procedure guidance in Regulatory Positions C.5.a, C.S.c, and C.5.d" of Regulatory Guide 1.52, Revision 2, March 1978, and the system flow rate is 9000 cfm 10%;
g 2)
Verifying, within 31 days ter removal hat a laboratory analysis of a representat e carbo pie obtained in accord-ance with Regulatory Posi
..b of Regulatory Guide 1.52, Revision 2, March 1978, meets the laboratory testing criteria of Regulatory Position C.6.a of Regulatory Guide 1.52, Revision 2, March 1978, for a methyl iodide penetration of less than 1%; and 3)
Verifying a system flow rate of 9000 cfm 10% during system operation when tested in accordance with ANSI N510-1980.
- The requirement for reducing refrigerant concentration to 0.01 ppm may be satisfied by operating the system for 10 hours1.157407e-4 days <br />0.00278 hours <br />1.653439e-5 weeks <br />3.805e-6 months <br /> with heaters on and operating.
CATAWBA - UNITS 1 & 2 3/4 6-14
CONTAINMENT SYSTEMS SURVEILLANCE REQUIREMENTS (Continued]
f ackwde.A Afterevery720hoursof[ carbon orber operation, by verifying, c.
within s after
, that a laboratory analysis.~of a repre-
"sentativelca bon sample obtained in accordance with Regulatory Cg PMit.
..b of Regulato g Guide 1.52 Revision 2, March 1978, meets the laboratory testing criteria of Regulatory Position C.6.a of Regulatory Guide 1.52, Revision 2, March 1978, for a methyl iodide penetration of less than 1%-
d.
At least once p months y:
/ actN4td 1)
Verify' that the assure drop across the combined HEPA filt s,.carb sorber banks, and moisture separators is le an 8 inches Water Gauge while operating the system at a flow rate of 9000 cfm t 10%;
2)
Verifying that the system starts automatically on any Phase "t,"
Isolation test signal,"*
3)
Verifying that the filter cooling electric motor-operated bypass valves can be manually opened, 4)
Verifying that each system produces a negative pressure of greater than or equal to 0.5 inch Water Gauge in the annulus within 1 minute after a start signal, and 5)
Verifying that the pre-heaters dissipate 45 2 6.7 kW.
After each complete or partial replacement of a HEPA filter bank, by e.
verifying that the cleanup system satisfies the in place penetra-tion and bypass leakage testing acceptance criteria of less than 1%
(Unit 1), 0.05% (Unit 2) in accordance with ANSI H510-1980 for a DOP test aerosol while operating the system at a flow rate o 000 cfm 10%; and g
f.
After each complete or partial replacement f as arbon rber the in-place j
bank, by verifying that the cleanup system e
penetration and bypass Irakage testing acceptance criteria of less than 1% (Unit 1), 0.05% (Unit 2) in accordance with ANSI N510-1980 for a halogenated hydrocarbon refrigerant test gas while operating the i
system at a flow rate of 9000 cfm i 10%.
"*This surveillance need not be performed until prior to entering HOT SHUTDCWN following the Unit 1 first refueling.
CATAWBA - UNITS 1 & 2 3/4 6-15
PLANT SYSTEMS 3/4.7.6 CONTROL ROOM AREA VENTILATION SYSTEM LIMITING CONDITION FOR OPERATION 3.7.6.Two independent Control Room Area Ventilation Systems shall be OPERABLE.
APPLICABILITY:
ALL MODES i
ACTION:
(Units 1 and 2)
MODES 1, 2, 3 and 4:
l With one Control Room Area Ventilation System inoperable, restore the
. inoperable system to OPERABLE status within 7 days or be in at least HOT STANDBY within the next 6 nours and in COLD SHUTDOWN within the following 30 hours3.472222e-4 days <br />0.00833 hours <br />4.960317e-5 weeks <br />1.1415e-5 months <br />.
MODES 5 and 6:
a.
With one Control Room Area Ventilation System inoperable, restore the inoperable system to OPERABLE status within 7 days or initiate-and maintain operation of the remaining OPERABLE Contr a
l Ventilation System with flow through the HEPA filter and carbop 4
adsorbers.
achdM b.
With both Control Roon Area Ventilation Systems inoperable, or with the OPERABLE Control Room Area Ventilation System, required to be operating by ACTION a., not capable of being powered by an OPERABLE emergency oower source, suspend all operations involving CORE ALTERATIONS or positive reactivity changes.
c.
The provisions of Specification 3.0.4 are not applicable.
SURVEILLANCE REQUIREMENTS 4.7.6 Each Control Room Area Ventilation System shall be demonstrated OPERABLE:
l a.
At least once per 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> by verifying that the control air temperature is less than or equal to 90 F;
,,4ed b.
At least once per 31 days on a STAGGERED TEST BASI by(initiating, from the control room, flow through the HEPA filte s andAcarbon adsorbers and verifying that the syster, operates r at 1 e
10 continuous hours with the heaters operating; l
CATAWBA - UNITS 1 & 2 3/4 7-14
l l
PLANT SYSTEMS SURVEILLANCE RE0UIREMENTS (Continue h
/ activded.
c.
At least once per 4(monthsor(1)afteranystructuralmaintenance on the HEPA filte orAcarbo adsorber housings, or (2) following painting, fire, o chemi release in any ventilation zone communicating with e system by:
1)
Verifying that the cleanup system satisfies the in-place penetration and bypass leakage testing acceptance criteria of less than 1% (Unit 1), 0.05% (Unit 2) and uses the test proce-dure guidance in Regulatory Position C.5.a, C.S.c, and C.5,d* of Regulatory Guide 1.52, Revisions 2 1978, and the sytem flow rate is 6000 cfm 10%;
gym 2)
Verifying, within 31 days y er remova, that a laboratory analysis of a representative carbo ample obtained in accor-dance with Regulatory Pos'
..b of Regulatory Guide 1.52, Revision 2, March 1978, meets the laboratory testing criteria of Regulatory Position C.6.a of Regulatory Guide 1.52, Revi-sion 2, March 1978, for a methyl iodide penetration of less than 1%; and 3)
Verif 'ng a system flow rat of 6000 cfm 2 10% during system era when teste agco[ nce with ANSI N510-1980.
acftW ac h N d.
A-ter ever 720 hour0.00833 days <br />0.2 hours <br />0.00119 weeks <br />2.7396e-4 months <br />sof[ carbo dsorber operation, by verifying, w' thin 31 days fter that a laboratory analysis of a repre-se tative,carb n sample obtained in accordance with Regulatory Pos' ion C.6 of Regulatory Guide 1.52, Revision 2, March 1978, meets aboratory testing criteria of Regulatory Position C.6.a of Regulatory Guide 1.52, Revision 2, March 1978, for a methyl iodide penetration of less than 1%;
e.
At least once per 18 months by:
ing that the pressure drop across the combined HEPA filters, g,4el yaroon dsorber banks, and moisture separators is less than 8 nen Water Gauge while operating the system at a flow rate of 6000 cfm 2 10%;
2)
Verifying that on a High Radition-Air Intake, or Smoke Density-High test signal, the system automatically isolates the affected M*Q intake W-utside air with recirculating flow through the HEPA filters andicJrbon adsorber banks; 3)
Verifying that the system maintains the control room at a positive p' essure of greater than or equal to 1/8 inch Water Gauge relative to adjarent areas at less than or equal to pressurization flow of 4000 cfm to the control room during system operation; 4)
Verifying that the heaters dissipate 25 2 2.5 kW, and "The requirement for reducing refrigerant concentration to 0.01 ppm may be satisfied by operating the system for
'.0 hours0 days <br />0 hours <br />0 weeks <br />0 months <br /> with heaters on and operating.
CATAW8A - UNITS 1 & 2 3/4 7-15
PLANT SYSTEMS l
SURVEILLANCE REQUIREMENTS (Continued) ac46 vaded 5)
' Verifying that on a High Chlorine / Toxic Gas test s' nal, the i
system automatically isolates the affected intake rom outsid air with recirculating flow through the HEPA filt rs and arbon l
adsorbers banks within 10 seconds (plus air trave time bet i
the detectors and the isolation dampers).
l f.
After each complete or partial replacement of a HEPA filter bank, by l
verifying that the cleanup system satisfies the in place penetration i
and bypass leakage testing acceptance criteria of less than 1%
(Unit 1), 0.05% (Unit 2) in accordance with ANSI N510-1980 for a DOP test aerosol while operating the system at a flo.
e of 0 cfm 10%; and g
g.
After each complete or partial replacemen of(_d7arbona rber bank, by verifying that the cleanup syste satisfi e in place penetration and cypass leakage. testing acce e criteria of less than 1% (Unit 1), 0.05% (Unit 2) in accordance with ANSI N510-1980 for a halogenated hydrocarbon refrigerant test gas while operating i
the system at a flow rate of 6000 cfm i 10%.
i CATAWBA - UNITS 1 & 2 3/4 7-16
PLANT SYSTEMS
.3/4.7.7 AUXILIARY sVILDING FILTERED EXHAUST SYSTEM
. LIMITING CONDITION FOR OPERATION
.l 3.7.7 Two independent trains of the Auxiliary Building Filtered Exhaust System p
shall be OPERABLE.
APPLICABILITY: MODES 1, 2, 3, and 4.
l ACTION:
With one train of the Auxiliary Building Filtered Exhaust System inoperable, 5-restore the inoperable train to OPERABLE status within 7 days or be in at least /'
HOT STANDBY within the next 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> and in COLD SHUTOOWN within the following 30 hours3.472222e-4 days <br />0.00833 hours <br />4.960317e-5 weeks <br />1.1415e-5 months <br />.
SURVEILLANCE REQUIREMENTS
's 4.7.7 Each train of.the Auxiliary Building Filtered Exhaust System shall be
[hM Ng" demonstrated OPERABLE:
g a.
At least once per 31 days y initiating, from e control room, f1'ov through the HEPA filters nd
=;;. ad ers.and verifying that the system operates for at lea
~
ous hours with the heaters operating; 4g wWn b.
At least once per 18 s or (1) after ructural maintenance on the HEPA filter of-chcr:::1 r housings, or (2) fnllowing painting, fire, or c' release in any ventilation zone communicating with the same by:
1)
Verifying that the clear.up system satisfies the in-place penetration and bypass leakage testing acceptance criteria of less than 1% (Unit 1), 0.05% (Unit 2) and uses the test proce-dure guidance in Regulatory Positions C.5.a. C.5.c, and C.5.d*
of Regulatory Guide 1.52, Revision
": ret 978, and the system flow rate is 30,000 cfm i 10%-
p % 4el 2)
Verifying, within 31 days e
- emoval, t a laboratory analysis of a representat' e carbon e obtained in accor-dance with Regulatory Pos' of Regulatory Guide 1.52, Revision 2, March 1978, meets the laboratory testing criteria of Regulatory Position C.6.a of Regulatory Guide 1.52, Revi-sion 2, March 1978, for a methyl iodide penetration of less than 1%; and
- The requirement for reducing refrigerant concentration to 0.01 ppm may be satisfied by operating the system for 10 hours1.157407e-4 days <br />0.00278 hours <br />1.653439e-5 weeks <br />3.805e-6 months <br /> with heaters on and operating.
CATAWBA - UNITS 1 & 2 3/4 7-17 Amendment No.
(Unit 1)
Amendment No.
(Unit 2)
PLANT SYSTEMS
/
5, SURVEILLANCE REQUIREMENTS (Continued) 3)
Verifying a system flow rate of 30,000 cfm i 10% during system ordance with ANSI N510-1980.
operation when testade c.
After every 720 b urs f carbon sorber operation, by verifying, 3
within fter r at a laboratory analysis of a bon sample obtained in accordance with Regulatory
[A re tv Position C A Regulatory Guide 1.52, Revision 2, March 1978, Mhe laboratory testing criteria of Regulatory Position C.6.a of Regulatory Guide 1.52, Revision 2, March 1978, for a methyl iodide penetration of less than 1%;
d.
At least once per 18 months ale) caAm 1)
Verifyi at the pressure drop a s the combined HEPA s, and moisture separators of filters -chr:c e ad a
less than B incnes ater Gauge while operating the system at a flow rate of 30,000 cfm t 10%,
2)
Verifying that the system starts on a Safety Injection test signal, and directs its exhaust flow through the HEPA filters and-chrecc1 adsorbers,**
g 3adiva+ed carbon 3)
Verifying that the system mair,tains the ECCS pump room at a
)
negativepressurerelativetoadjacentareas, 4)
Verifying that the filter cooling bypass valves can be manually opened, and 5)
Verifying that the heaters dissipate 40 1 4 kW.
After each complete or partial replacement of a HEPA filter bank, e.
by verifying that the cleanup system satisfies the in-place pene-tration and bypass leakage testing acceptance criteria of less than 1% (Unit 1), 0.05% (Unit 2) in accordance with ANSI N510-1980 for a 00P test aerosol while opera. ting the system at a flow rate of 30,000 cfm i 10%; and ygn After each complete or partial replacemen ofg d r:: '
er f.
bank, by verifying that the cleanup system nunies the in place penetration and bypass leakage testing acceptance criteria of less than 1% (Unit 1), 0.05% (Unit 2) in accordance with ANSI N510-1980 for a halogenated hydrocarbon refrigerant test gas while operating 1
the system at a flow rate of 30,000 cfm i 10%.
l
- This surveillance need not be performed until prior to entering HOT SHUTDOWN following the Unit 1 first refueling.
CATAWBA - UNITS 1 & 2 3/4 7-18 1
m REFUELING OPERATIONS
- 3/4; 9'. 4 CONTAINME'NT BUILDING' PENETRATIONS
' LIMITING CONDITION FOR OPERATION 3.9.4'. The containment building penetrations shall be in the following status:
a.
The equipment hatch closed and held in place by a minimum of four
- bolts, b.
A minimum' of one door in each airlock is closed, and c.
Each. penetration providing direct access from'the containment atmosphere to the outside -atmosphere shall be either:
l 1)
Closed by an isolation valve, blind flange, or ' manual valve, or 2).
Exhausting through an~0PERA8 sE0uil" Containment
- j Purge System HEPA filters 1 adsorbers.
nd cherc^;d ceben
%Wah APPLICABILITY:
During CORE ALTERATIONS or movement or irraalated fuel within the containment.
ACTION:
g
'With the requirements of the above specification not satisfied, immediately suspend all operations involving CORE ALTERATIONS or movement of irradiated fuel-in the containment building.
SURVEILLANCE RE0VIREMENTS 4.9.4.1 Each of the above required containment building penetrations shall be determined to be either in its closed / isolated condition or exhausting through an OPERABLE Reactor Building Containment Purge Syst'em with the capability of being automatically isolated upon heater failure within 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> prior to the start of and at least once per 7 days during CORE ALTERATIONS or movement of-irradiated fuel in the containment building by:
a.
Verifying the penetrations are in their closed / isolated condition, or I
b.
Verifying the upper and lower containment purge supply and exnaust valves close upon a High Relative Humidity test signal.
i
- CATAWBA - UNITS 1 & 2 3/4 9-4
_ )
1 REFUELING OPERATIONS SURVEILLANCE RE0VIREMENTS (Continued) l 4.9.4.2 _The React ilding Containment Purge System shall be demonstrated OPERABLE:
j.,g a.
least on" per 31 days by initiating flow through the HEPA filters nd carb adsorbers and verifying that the system operates for at continuous he w
the heaters operating; w'tWAeb b.
At least once per 8(months or
- 1) after any structural maintenance on the HEPA filte orXcarbo dsorber housings, nr (2) following painting, fire, er 1 cal. release in any ventilation :ene communi-cating with the system by:
1)
Verifying that the cleanup system satisfies the in place penetration and bypass leakage testing acceptance criteria of less than 1% and uses the test procedures guidance in Regula-tory Positions C.S.a C.S.c, and C.S.d* of Regulatory Guide 1.52.
Revision 2, March 1978, and the system flow rate is 25,000 cfm
! 10% (both exhaust fans o ating'
- etWdeA, 2)
Verifying within 31 d s fter remov 1, that a laboratory analysis of a present ive carbo ample obtainea in accordance with Regulatory Position' t.o.o of Regulatory Guide 1.52, Revi-sion 2,. March 1978, meets the laboratory testing criteria of Regulatory Position C.6.a of Regulatory Guide 1.52, Revision 2, March 1978, for a methyl iodide penetration of less than 6%;
and 1
3)
Verifying e system flow rate of 25l000 cfm 10% (both exhaust fans operating) during s em operation when testeo in accoraance with ANSI N510-1980.Qvbb
'y Af g every 720 hours0.00833 days <br />0.2 hours <br />0.00119 weeks <br />2.7396e-4 months <br /> of carb adsorber operation, by verifying, 3
within s after r
, that a laboratory analvsis of a repre-ywd*dO ntati M car on sample obtained in accordance with ' Regulatory Pncitinn F. 6.
of Regulatory Guide 1.52, Revision 2, March 1978, f
meets the laboratory testing criteria of Regulatory Position C.6.a of Regulatory Guide 1.52, Revision 2, March 1978, for a methyl iodide penetration of less than 6%;
d.
At least once per 18 months by:
Verifying the pressure drop across the combined HEPA fil-carbon a orber banks, and prefilters is less than 8 inch auge while operating the system at a flow rate ga o 25,000 cfm ! 10% (both exhaust fans operating); and
- The requirement for reducing refrigerant concentration to 0.01 ppm may be satisfied by operating the system for 10 hours1.157407e-4 days <br />0.00278 hours <br />1.653439e-5 weeks <br />3.805e-6 months <br /> with heaters on and operating.
CATAWBA - UNITS 1 & 2 3/4 9-5
l l
REFUELING OPERATIONS I
SURVEILLANCE REQUIREMENTS (Continued)
)
2')
Verifying that the filter train duct heater dissipates i
120 12 kW.
j e,
- After each complete or partial replacement of a HEPA filter bank,. by verifying that the cleanup system satisfies the in place penetration and bypass leakage testing acceptance criteria of less then 1% in accorcance with ANSI N510-1980 for a DOP test aerosol while operating l
the system at a flow rate of 25,000 cfm 10% (bot ans j
operating); and gg I
f.
After each complete or partial replacemen of rbon ads r
f bank, by verifying that the cleanup system m;rk ;t;a les the in place penetration and bypass leakage testing acceptance criteria of less than 1% in accordance witn ANSI N510-1980 for a halogenated hydrocarbon refrigerant test gas while operating the system at a
)
flow rate of 25,000 cfm 10% (both exhaust fans operating).
1 I
i 1
CATAWBA - UNITS 1 & 2 3/4 9-6
-REFUELING OPERATION'S 3/4.9.11 FUEL HANDLING V'ENTILATION EXHAUST SYSTEM LIMITING CONDITION FOR OPERATION
~
Atleastonetrain-oftheFuelHandlingVenti[ationExhaustSystem 3.9.11 shall be'0PERABLE.
APPLICABILITY:
Whenever irradiated fuel is in the storage pool.
ACTION:
a.
With both trains of the Fuel Handling
- ilation Exhaust System inoperable, suspend all operations i; ag movement of fuel within the' storage pool or crane operation wit...oads over the storage pool until the Fuel Handling Ventilation Exhaust System is restored to OPERABLE status.
b.
The provisions of Specifications 3.0,3 and 3.0.4 are not applicable.
SURVEILLANCE.RE0UIREMENTS adiabt:R 4.9.11.1 One train of the Fuel Handling Ventilation Exhaust Sys m shall be
.determined to be operating and discharging through the HEPA fil r anc carb adsorbers at least once per 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> whenever irradiated fuel i bein ed in the storage pool and;during crane operation with loads over the s rage pool.
4.9.11.2 Both trains of the Fuel Handling Ventilation Exhaust System shall be
~
demonstrated OPERABLE:
ar.4 M a.
At least once per 31 days b nitiating, irem the control room, flow through the HEPA filt s an c adsorbers and verifying that the system operates for east 10 continuous hours with the heaters operating; activch b.
At least once per months (1) after any structural maintenance on the HEPA~filte or car adsorber housings, or (2) following painting, fire, o cal release in any ventilation zone communicating with the system by:
1 ll 1)
Verifying that the cleanup system satisfies the in place
~
l penetration and bypass ~ leakage testing acceptance criteria of less than 1% (Unit 1), 0.05% (Unit 2) and uses tne test procedure guidance in Regulatory Positions C.S.a, C.5.c, and C.S.d* of Regulatory Guide 1.52, Revision 2, March 1978, and tne system flow rate is 16,565 cfm : 10%;
"Tne requirement for reducing refrigerant concentration to 0.01 ppm may be satisfied by operating the system for 10 hours1.157407e-4 days <br />0.00278 hours <br />1.653439e-5 weeks <br />3.805e-6 months <br /> with heaters on and operating.
I CATAWBA - UNITS 1 & 2 3/4 9-14
1 l
REFUELING OPERATIONS l
SURVEILLANCE REQUIREMENTS (Continued) 1 l
fa.divMed 2)
Verifying, within 31 days -
er remova hat a laboratory analysis of a representat' e carbo ample obtained in accor-l dance with Regulatory Pos ti
.6.b of Regulatory Guide 1.52 Revision 2, March 1978, meets the laboratory testing criteria of Regulatory Position C.6.a of Regulatory Guide 1.52, Revision 2, 1
March 1978, for a methyl iodide penetration of less than 1%;
and 3)
Verifying a system flow rate of 16,565 cfm ! 10% during system operation when teste acc dance with ANSI N510-1980.
I acihmkel c.
After every 720 hours0.00833 days <br />0.2 hours <br />0.00119 weeks <br />2.7396e-4 months <br /> of car adsorber operation in any train by a
verifying, with K after removal, that a laboratory analysis 8gydtd'of a representatTvtqcatpon sample obtained in accordance witn Regula-l tc y MiUun t..o.b of Regulatory Guide 1.52, Revision 2, March 1978, meets the laboratory testing criteria of Regulatory Position C.6.a of Regulatory Guide 1.52, Revision 2, March 1978, for a methyl iodice penetration of less than 1%.
d.
At least once r 18 mon s for each train by:
l ufivaN l
1)
Verifyi g that t pressure drop across the comcined HEPA 1
filter, car adsorber banks, and moisture separators is less inches Water Gauge while operating the system at a flow rate of 16,565 cfm : 10%.
2)
Verifying that the system maintains the spent fuel storage pool area at a negative pressure of greater than or equal to k inch l
Water Gauge relative to the outside amosphere during systen operation, 3)
Verifying that the filter cooling bypass valves can be manually opened, and I
4)
Verifying that the heaters dissipate 80 8 kW.
e.
After each complete or partial replacement of a HEPA filter bank in any train, by verifying that the cleanup system satisfies the in-place penetration and bypass leakage testing acceptance criteria of less than 1% (Unit 1), 0.05% (Unit 2) in accordance with ANSI N510-1980 for a 00P test aerosol while operating the eF =
- a flow rate of 16,565 cfm : 10%; and g
f.
After each complete or partial replacement f@
rbon
. rDer bank in any train, by verifying that the el an -
tem satisfies tne in place penetration ana bypass leakage testing acceptance criteria of less than 1% (Unit 1), 0.05% (Unit 2) in accordance with AN5I N510-1980 for a halogenated hydrocarbon refrigerant test gas anile operating the system at a flow rate of 16.565 cfm : 10%.
CATAWBA - UNITS 1 & 2 3/a 9-15
CONTAINMENT' SYSTEMS BASES 3/4.6.1.8 ANNULUS VENTILATJo M V5 TEM f ae W 4 4
.The OPERASILI f he Ann us Ventilation System ensures that during LOCA conditions, contai n vess leakage into the annulus will be filtered through the. HEPA: filters a d.carb adsorber trains prior to discharge to the atmosphere.
Operation of the yst with the heaters operating to maintain low humidity
'using automatR c rol for at least 10Tcontin~uous hours in a 31-day' period is sufficient to reduce the buildup of moisture on the adsorbers and.HEPA filters.
This requirement is necessary to meet the assumptions used in the safety analyses and limit the SITE BOUNDARY radiation doses to within the dose guide-line values of 10 CFR Part 100 during LOCA conditions.
ANSI N510-1980 will be used as a procedural guide for surveillance. testing.
3/4.6.1.9 CONTAINMENT PURGE SYSTEMS The containment purge supply mad exhaust isolation valves for the lower compartment and the upper compartrant (24-inch), and instrument room (12-inch),
and the Hydrogen Purge System (4-inch) are required to be sealed closed during plant operation since these valves have not been demonstrated capable of closing during a LOCA.
Maintaining these valves sealed closed during plant operations ensures that excessive quantities of radioactive materials will not be released via the Containment Purge System.
To provide assurance that these containment valves cannet be inadvertently opened, the valves are sealed closed in accord-ance with Standard Review Plan 6.2.4 which includes mechanical devices.to seal or lock the valve' closed, or prevents power from,being supplied to the valve operator.
The use of the containment purge lines is restricted to the 4-inch Con-tainment Air Release and Addition System valves since, unlike the lower compart-ment and the upper compartment, instrument room, and the Hydrogen Purge System valves, these 4-inch valves are capable of closing during a LOCA.
Therefore, the SITE BOUNDARY dose guideline values of 10 CFR Part 100 would not be exceeced in the event of an accident during containment purging operation.
Operation with the line open will be limited to 2000 hours0.0231 days <br />0.556 hours <br />0.00331 weeks <br />7.61e-4 months <br /> during a calendar year for the 4-inch valves.
The total time the containment purge (vent) system isolation valves may be open during MODES 1, 2, 3, and 4 in a calendar year is a function of anticipated need and operating expericnce.
Only safety-related reasons; e.g.,
containment pressure control or the reduction of cirborne radioactivity i
to facilitate personnel access for surveillance and. maintenance activities, may be used to support the additional time requests.
Leakage integrity tests with a maximuni al'owable leakage rate for contain-ment purge supply and exhaust valves will provide early indication of resilient material seal degradation and will allow opportunity for repair before gross leakage failures could develop.
The 0.60 L, leakage limit of Specification 3.6.1.2b. shall not be exceeded when the leakage rates determined by the leakage integrity tests of these valves are added to the previously determined total for all valves and penetrations subject to Type B and C tests.
CATAWBA - UNITS 1 & 2 8 3/4 6-3 I
__ _D
i 3/4.9 REFUELING OPERATIONS BASES 3/4.9.1 BORON CONCENTRATION The limitations on reactivity conditions.during REFUELING ensure that:
(1) the reactor will remain subcritical during CORE ALTERATIONS, and (2) a j
uniform boron concentration is maintained for reactivity control in the water volume having direct access to the reactor vessel.
These limitations are consistent with the initial conditions assumed for the boron dilution incident in the safety analyses.
The value of 0.95 or less for K includes a-eff 1% Ak/k conservative allowance for uncertainties.
Similarly, the boron concentration value of 2000 ppm or greater includes a conservative uncertainty allowance of 50 ppm boron.
The locking closed of the required valves during refueling operation precludes the possibility of uncontrolled boron dilution of the filled pcrtion of the Reactor Coolant System.
This action prevents flow to the Reactor Coolant System of unborated water by closing flow paths from sources of unborated water.
3/4.9.2 INSTRUMENTATION The OPERABILITY of the Source Range Neutron Flux Monitors and/or the Baron 7 Dilution Mitigation System ensures that redundant monitoring capability is g
available to detect changes in the reactivity condition of the core.
3/4.9.3 DECAY TIi4E The minimum requirement for reactor subcriticality prior to movement of irradiated fuel assemblies in the reactor vessel ensures that sufficient time has elapsed to allow the radioactive decay of the short-lived fission products.
This decay time is consistent with the assumptions used in the safety analyses.
3/4.9.4 CONTAINMENT BUILDING PENETRATIONS Mt The requirements on containment building penetr ion losure and OP BILITY of the Reactor Building Containment Purge System en re tha a relea of radioactive material within containment will be re tricted from age to the environment or filtered through the HEPA filters and ch:m:F sorbers prior to release to the atmosphere.
The OPERABILITY anc closu restrictions are sufficient to restrict radioactive material release rom a fuel element rupture based upon the lack of containment pressurization potential while in the l
REFUELING MODE.
Operation of the Reactor Building Containment Purge System and the resulting iodine removal capacity are consistent with the assumption of the safety analysis.
Operation of the system with the heaters operating to maintain low humidity using automatic control for at least 10 continuous hours in a 31-day period is sufficient to reduce the buildup of moisture on the adsorbers and HEPA filters.
ANSI N510-1980 will be used as a procedural guide for surveillance testing.
l CATAWBA - UNITS 1 & 2 B 3/4 9-1 AmendmentNo[ Unit 1) l Amendment No.# (Unit 2)
REFUELING OPERATIONS JASES 3/4.9.9 and 3/4.9.10 WATER LEVEL - REACTOR VESSEL and STORAGE POOL The restrictions on minimum water level ensure that sufficient water depth is available to remove 99% of the assumed 10% iodine gap activity released from the rupture of an irradiated fuel assembly.
The minimum water depth is consistent with the assumptions of the safety analysis.
3/4.9.11 FUEL HANDLING VENTILATION EXHAUS STEM ac+ia4ed The limitations on the Fuel Handi'n Ventilatic Exhaust System ensure that all radioactive material releas rom an irr lated fuel assemoly will be filtered through the HEPA filters an carbon dsorber prior to discharge to the atmosphere.
Operation of th syste th the heaters operating to_ main-tain low humidity using automatic contro for at least 10 continuous hours in a 31-day period is sufficient to reduce the buildup of moisture on the adsorcers and HEPA filters.
The OPERABILITY of this system and the resulting iodine removal capacity are consistent with the assumptions of the safety analyses.
ANSI N510-1980 will be used as a procedural guide for surveillance testing.
l l
. CATAWBA - UNITS 1 & 2 8 3/4 9-3
-_- __ _ ______