44 Unit 1 ICP 2.1*
MAJOR Date Revision 39 11-11-86 PERIODIC TEST REACTOR PROTECTION AND SAFEGUARDS ANALOG CHANNELS I THROUGH IV 1.0 PURPOSE To satisfy the monthly. testing requirements for the following:
1.1 Overtemperr*ure AT 1.2 Overpower AT 1.3 Containment pressure 1.4 Reactor coolant flow 1.5 Pressurizer level 1.6 Pressurizer pressure 1.7 Steam generator level 1.8 Steam generator flow mismatch 1.9 Steam generator pressure 1.10 Turbine first stage pressure 1.11 Power-operated relief valve operability.
2.0 REQUIREMENTS 2.1 Technical Specification Requirement:
2.1.1 Section 15.4 Table 15.4.1-1, Items 4,5,6,7,11,12,18,24, 25,26,33 2.1.2 Perform this procedure monthly (every four weeks) 2.2 Maintain machinery history
3.0 REFERENCES
Point Beach Nuclear Plant Setpoint Document 4.0 CONDITIONS The test may be run at any power level.
(See Precaution Step t 5)
- There is an identical procedure for Unit 2.
8705220437 870515 PDR ADOCK 05000266 L
P PDR
<;r *.
v, s
j'[
it p
ICP 2.I'U1 Page 2 Unit 1 5.01' PRECAUTIONS 5.1 The test may be performed on only one of the four protection
' channel'at a. time. The protection channels not under test must be capable-of performing the trip logic required.
.5.2' Ensure that no:NIS channels.are placed in' test while this~ test'is-being run.
5.3 If, during any part of the test, a reactor protection channel-alert is' actuated from another channel, the test must-be terminated and the channel in test returned to normal.
5.4 The~ test will require personnel'to be working in only one channel-at a time; therefore, two channel in test alarms should not'be.
actuated at the same time.
- 5.5 If the unit is shut down and depressurized and the reactor trip -
breakers ~are closed, a reactor trip will occur when first stage pressure bistables are placed in the trip mode.
6.0 DISCUSSION 6.1 If test-is interrupted for any reason other than quitting for.the day, the following sequence should be followed:
6.1.1 -
Stop test at a convenient point.
6.1.2 Ensure all channel test switches and shunts are returned to normal.
4 6.1.3 Ensure all bistable trip switches are returned to normal.
6.1.4 Close doors that bring in channel test alarm.
6.1.5 Check that all alarms and trips have cleared.
I 6.1.6 Inform operator of status of racks before leaving.
6.2 To continue. test performance after a short interruption, the following sequence should be followed:
6.2.1 Inform DSS and operator that testing is going to resume.
6.2.2 Ensure.that Tavg, AT, pressurizer press and pressurizer level defeat switches are in the proper position as required.
6.2.3 Continue with testing.
L
D '. _,
- n-
- s. - s
, ' f,, -
g n
c
.o.
r ICP 2.1 U1 Page 3 Unit 1 6i. 3 If test needs to be terminated, prior to completion, at the 'end of shift, Attachment "A" must be performed.-
1
' 6.4 To resume test at'the beginning of a shift, Attachment "B" must be performed.
7.0 PROCEDURE.
Initials-
- 7.1 Obtain permission of the' Duty Shift Superintendent and the Control Operator before-starting the test.
(DSS)-
Checkoff "7.2.
Observe the trip status light panel for any trips on the
. channels-to be tested.
7.3 Request the operator.to test all alarm panels.
7.4 Observe'the alarm panel for any trips on the channels
~to be tested.
7.5' Request the operator to suppress Channel I (red) alarms on the computer.
7.6
' Request the operator to select a channel other than the red on the AT and pressurizer pressure and level recorders.
- 7.7-Request the operator to place the pressurizer relief valve switches (430'and 431C) in-the close position.
7.8 Request ~the operator to place the rod control selector switch into the manual position.
- 7.9 Inform the operator that the pressurizer level and pressure controllers will be placed in manual.
7.10 Place the Tavg defeat switch (C107) to the defeat Channel I (red) position.
- These steps may be deleted if the pressurizer pressure defeat switch is already in the defeat Channel I (red) position.
- These steps may be deleted if the pressurizer level defeat switch is already in the defeat channel I (red) position.
L
,s-f.
q.
s o
ICP 2.1 U1 Page 4 Unit'l checkoff 7.11 Place the AT' defeat switch -(C108)' to the defeat
~
Channel I (red) position.
- 7.12 Place pressurizer level controller in manual.
- 7.13 Place the pressurizer level defeat switch to the defeat Channel I (red) position.
- 7.14 Place pressurizer level controller in auto.
- 7.15 Place the pressurizer pressure controller in manual.
- 7.16 Place the pressurizer pressure defeat switch (C110) to.
(
the defeat Channel I (red) position.
- 7.17 Return the pressurizer pressure controller to auto.
- 7.18' Request the operator to place the pressurizer relief valve switches (430 and 431C) in the automatic position.
- 7.19 Inform the operator that the pressurizer level and pressure controllers are back in automatic.
7.20 Inform the operator that he may return the rod control selector switch to automatic.
7.21 Place the following bistable switches to the trip pc.4 tion:
Channel I (Red)
Overpower Trip Rod Stop High Tavg Overtemp. Trip Rod Stop Low Tavg High Press Trip Low Press Trip SI Unblock SI 7.22 Verify the following alarms on 1C04 or C01:
RC Tavg High Auto Turbine Runback OT AT RC Tavg Low Auto Turbine Runback OP AT RC OT AT Channel Alert Analog Channel I Test RC OP.aT Channel Alert PRZR Low Pressure Ch Alert PRZR High Press Alert U1 PRZR Press SI Ch Alert
- These steps may be deleted if the pressurizer pressure defeat switch is already in the defeat Channel I (red) position.
- These steps may be deleted if the pressurizer level defeat switch is already in the defeat Channel I (red) position.
(L
e y,
't g
ICP 2.1.U1 Page 5 Unit 1 Checkoff 7.23 open the shunts on the Th and Tc test switches.
7.24-Read Ago:
Ideal As Found As Left 10.010.03 ma 7.25 Insert Th and Tc resistances for 540*F:
Th 416.41 Ohms Tc 416.03 ohms Ideal As Found As Lef t Th 2.00 1 0.01 V Tc 2.00 1 0.01 V Tavg V 2.00 V
Tavg ma 10.00 1 0.20 ma AT 0.00 1 0.02 V f(Tavg) 10.00+0.20
-0.00
- AT s.p.2 541.66 7.26 Change Th to 615*F:
Th 446.83 Ohms Th 10.00 1 0.01 V Tavg 6.00 V
Tavg ma 30.00 1 0.20 ma AT 8.00 1 0.02 V 7.27 Change Tc to 615*F:
Tc 446.35 Ohms Tc 10.00 1 0.01 V Tavg V 10.00 V
Tavg ma 50.00 i 0.20 ma AT 0.00 1 0.02 V 7.28 Adjust Th and Tc resistance to give a positive AT voltage of 4.00 V.
See Note 2 at end of test b
c-n-
ICP 2'1 U1 Page 6 Unit 1 Checkoff
- 7.29 Insert a current-calibrator into' Tavg ' test jack and verify Tavg high-low bistable settings:*
Ideal As Found As Left Low 211.60 dec.
-High 528.66 inc.
7.30 -Insert an analog simulator in the pressurizer pressure -
test jack and set to a.value between 50 and 75%.
7.31 Set Tavg current calibrator to 44.24 ma.
7.32 Read f(Tavg):
Ideal As Found As Left 211.09 7.33 Read AT s.p.2:
Ideal As Found As Left 540.57 7.34 Install 1000 precision resistors in the q and q 1
test jacks.
7.35 Insert a current calibrator into g, test jack. Set q 2.26 V higher than.q1, and read f TAq):
Ideal As Found As Left 20.0010.03 ma 7.36 Remove current calibrator from q test jack and insert into u
the q, test jack. Set q1 3.55 V higher than q and read u
f (Aq):
Ideal As Found As Left 20.0010.03 ma l
See Note 1 at end of test
-. -., - -., -. -,,, - -.. -,,....,.,,.., ~,, _ _... - - - - - -,, - - - - -..., -,
,...n-.r.-
F t
.g ICP 2.1 U1 Page 7 Unit 1 Checkoff
~7.37_ Turn analog / calibrator' switch to analog and record the following:
f (aq)
AT s.p.1 AT s.p.2 7.38 _ Turn analog / calibrator switch to calibrator and change f (&Q) by increasing q controller output by several ma.
1 Record the following:
f (aq)
AT s.p.1 AT s.p.2 7.39 The change in each parameter should be the same f (aq)
AT s.p.1 AT s.p.2 7.40 Return both flux tilt test jacks to normal.
- 7.41 Insert the appropriate values and record the following:
AT s.p.1 Pzr.
Tavo Press Ideal As Found As Left 50 ma 15 ma
$19.73 ma 50 ma 30 ma 26.71 ma 50 ma 45 ma 33.70 ma 30 ma 45 ma 50.26 ma 22 ma 30 ma 49.89 ma 18 ma 15 ma 46.22 ma 7.42 Adjust the pressurizer pressure to some value greater than 75% and Tavg to a value greater than 90%.
7.43 Slowly decrease pressure and record the following values of AT s.p.1:
Ideal As Found As Left Rod Stop 231.60 dec.
Overtemp 230.00 dec.
- See Note 2
(
t
.y.'
~t-'
.c ICP 2.1 U1 Page 8.
-Unit 1 Checkoff 7.44 Insert a current calibrator in the f (Tavg) test jack.
'-7.45 Using a calibrator, decrease AT s.p.2 and record the following values at AT s.p.2:
Ideal As Found As Left Rod Stop 230.80 dec.
Overpower 230.30 dec.
7.46 Using the analog simulator, check the following P429 pressurizer pressure setpoints:
Ideal As Found As Left High press trip 543.25 inc.
- Low press trip 215.50 dec.
l.
Safety Injection 211.75 dec.
Unblock SI
$13.75 inc.
7.46.1 Test power-operated relief valve operability by performing the following:
a.
Have operator place PC-430 control switch in the close position.
b.
Check the setpoint of PC-429B. Use TP-429A and a test lamp connected across PC-429B output terminals.
Ideal As Found As Left PC-429B 41.75t NOTE: PC-429B output terminals are C110-T3 & T4.
c.
Remove test lamp when test is complete.
d.
Simultaneous to Step b, perform the following:
- 1) Preliminary - Attach an ohmmeter across Contacts 2 & 6 of relay PC-429BX in C150.
(Verify no voltage exists first.)
- Use comp, press testpoint L
gc e
g 9
. c
,..I a
ICP 2.1 U1-Page 9; Unit-l' checkoff
- 2) With PC-429BX'deenergized (PC-4298 input
'less than'setpoint), contacts-2 & 6
- indicate open.
- 3) With PC-429BX energized (PC-429B input greater than'setpoint), Contacts 2 & 6-indicate shut.
4)' Remove the chameter.
.e.
Verify PC-429BX is deenergized. Have operator place-PCV-430 control switch in the auto position.
L7.47 Return all test jacks to normal.
~
t 7.48 Remove all. test equipment.
Close the sh'nts on Th and Tc test switches.
7.49 u
7.50 Return all bistable trip switches to normal.
7.51 Place the'following L426 pressurizer level bistable
-test switches in the trip position and verify alarms.
High level trir
'PRZR High Level Ch Alert Low Le',el.
U1 PRZR Low Level-Ch Alert 7.52 U4ing an analog sbaulator, check the following L426
.ptessurizer level setpoints:
Ideal As Found As Left High level trip 546.00 inc.
Low Level 212.80 dec.
7.53 Return the test jack to normal and remove the simulator.
7.54 atturn the L426 trip switches to normal.
7.55 Place the following P483 steam generator pressure bistable test switches in the trip position and verify alarms.
Safeguards. actuation Steam Line Loop "B Press Low-Lo'w Ch Alert Low pressure Steam Line Loop "B" Press Low L
t 9
9~
ICP 2.1 U1 Page 10 Unit 1 Checkoff 7.56 Using an analog simulator, check the following P483 steam generator pressure setpoints (use comp. press testpoint).
~
Ideal As Found As Left Safeguard actuation 225.14 dec.
Low press alarm 227.14 dec.
7.57 Return the test jack to normal and remove the simulator.
7.58 Return the P483 trip switches to normal.
7.59 Place the following F414 reactor coolant flow bistable test switch in the trip position and verify alarm.
RC flow RC Low Flow Loop "B" Ch Alert 7.60 Using an analog simulator, check the following F414 reactor coolant flow setpoint:
-Ideal As Found As Left RC flow 238.60 dec.
7.61 Return the test jack to normal and remove the simulator.
7.62 Return the F414 trip switch to normal.
7.63 Place the following P945 containment pressure bistable test switches in the trip position and verify alarm.
Safeguards action U1 Cont. Press Ch Alert Containment spray logic 7.64 Using an analog simulator, check the following P945 containment pressure setpoints:
Ideal As Found As Left Safeguards action $17.33 inc.
Cont. spray logic $30.67 inc.
7.65 Return the test jack to normal and remove the simulator.
7.66 Return the P945 trip switches to normal.
L
9 :
5 ICP 2.1 U1 Page 11 Unit 1 Checkoff-7.67 Place the following F411 reactor coolant flow bistable test switch in the trip position and verify alarm.
RC flow RC Flow Loop "A" Ch Alert 6.68 Using an analog simulator, check the following F411 reactor coolant flow setpoint:
Ideal As Found As Left J
RC flow 238.60 dec.
7.69 Return the test jack to normal and remove the simulator.
7.70 Return the-F411 trip switch to normal.
7.71 Place the following L472 steam generator level bistable test switches in the trip position and verify alarms.
Low-low level SG "B" Low-low Level Ch Alert High level SG "B" High Level Ch Alert Low level SG "B" Low Level Ch Alert 7.72 Using an analog simulator, check the following L472 steam generator level setpoints:
Ideal As Found As Left Lo-lo level 216.00 dec.
High level 538.00 inc.
Low level 218.00 dec.
7.73 Return the test jack to normal and remove the simulator.
7.74 Return the L472 trip switches to normal.
7.75 Request the operator to do the following:
1.
Place pressure controller 468 in manual.
- 2.
Place steam generator level controller 480 in manual.
- 3.
Place steam generator level controller 466 in manual.
- 4.
Place the "A" loop steam flow selector switch in the white position.
L
l
~
ICP 2.1.Ulz
'i
.Page 12
. Unit 1 Checkoff
_ Place the "A" loop feedwater' flow selector switch in-the white position.
- 6.
^ Place steam generator-level controller 466 in automatic.
. *7.
Place steam generator level controller 480 in
. automatic.
These' steps may be deleted if both selector switches are already_in the white position.
7.76 Place.the following P468, F464 and F466 bistable test-switces in the trip position and verify alarms.
Safeguard actuation Steam Line Loop "A" Press Low-Low Ch Alert Low pressure alarm-Steam Line Loop "A" Press Low High Trip High-High Trip Steam Line Loop "A" Iso Ch Alert-SF<FWF SG "A" Feedwater Flow High
'SF>FWF SG "A" Feedwater. Flow Ch Alert-7.77. Using an analog simulator, check the following P468 steam generator' pressure setpoints:
(Use the comp. steam press testpoint)
Ideal As Found As Left Safeguard actuation 225.14 dec.
Low pressure alarm 227.14 dec.
7.78 Return the test jack to normal and remove the simulator.
7.79 Return the P468 trip switchew to normal.
i 7.80 Request the operator to return pressure controller 468 i-to the automatic mode.
i l
7.81 Using a analog simulator, check the following F464 steam flow setpoints:
(Use the steam flow testpoint)
Ideal As Found As Left A
High trip 510.44 inc.
l Hi-hi trip 547.00 inc.
i 7.82 Set the steam flow to read 30.00 ma at the " linear comp SF" j_
testpoint.
i t.
i.
U
o.
ICP 2.1 U1 Page 13 p
Unit 1 Checkoff 7.83 Using an analog simulator, check the following F466 feedwater flow setpointsi' (Use the " linear FWF" testpoint)
Ideal ~
As Found As Left SF <LFWF
$38.00 inc.
SF > FWF 222.00 dec.
7.84 Return the F464 and the F466 test jacks to normal and remove the simulator.
7.85 Return the F-464 and F-466 trip switches to normal.
7.86 Request the operator to do the following:
1.
Place steam generator level controller 466 in manual.
2.
Place steam generator level controller 480 in manual.
7.87 Place the follow.ng L461 steam generator level bistable test switches in the trip position and verify alarms.
High level SG "A" High Level Ch Alert-Low-low level SG "A" Low-Low Level Ch Alert 7.88 Using an analog simulator, check the following L461 steam generator level setpoints:
Ideal As Found As Left i
l High level 538.00 inc.
Lo-lo level '216.00 dec.
7.89 Return the L461 test jack to normal and remove the simulator.
7.90 Return the L461 trip switches to normal.
7.91 Request the operator to do the following:
1.
Place the "A" loop steam flow selector switch in the red position.
2.
Place the "A" loop feedwater flow selector switch in the red position.
t
7-.
~s ICP 2.11U1 Page'14 Unit 1 Checkoff 3.
Place steam generator level controller 466 in automatic.
4.
Place steam generator level controller 480 in automatic.
7.92 Close all doors on Channel I (red).
7.93 Check that all Channel I (red) alarms and trips have cleared.
7.93.1 Request the operator to reinstate Channel I (red) alarms and to suppress channel II (white) alarms on the computer.
7.94 Request the operator to select the red channel on the AT and pressurizer pressure and level recorders.
I 7.95 Request the operator to place the pressurizer relief valve switches (430 and 431C) in the close position.
7.96 Request'the operator to place the rod control selector switch into the manual position.
7.97 Inform the operator that the pressurizer level and pressure controllers will be placed in manual.
7.98 Place the Tavg defeat switch (C107) to the defeat-Channel II (white) position.
7.99 Place the AT defeat switch (C108) to the defeat Channel II (white) position.
7.100 Place the pressurizer pressure controller in manual.
7.101 Place the pressurizer pressure defeat switch (C110) to the defeat Channel II (white) position.
4 7.102 Return the pressurizer pressure controller to auto.
7.103 Place pressurizer level controller in manual.
7.104 Place the pressurizer level defeat switch to the defeat channel II (white) position.
7.105 Place pressurizer level controller in auto.
k
ICP 2.1 U1 Page 15 Unit 1-Checkoff.
7.106 Request the operator to place the pressurizer relief valve switches (430 and 431C) in the automatic position.
7.107 Inform the operator that the pressurizer level and
. pressure controllers are back in automatic.
7.108 Inform the operator that he may return the rod control selector switch to the automatic position.
7.109 Place the following bistable switches to the trip position:
Channel II (White)
Overpower Trip Rod Stop High Tavg Overtemp. Trip Rod Stop Low Tavg High Press Trip Low Press Trip SI Unblock SI 7.110 Verify the following alarms on 1C04 or C01:
RC Tavg High Auto Turbine Runback OT AT RC Tavg Low Auto Turbine Runback OP AT RC OT AT Channel Alert Analog Channel II Test RC OP AT Channel Alert PRZR Low Press Ch Alert PRZR High Press Ch Alert U1 PRZR Press SI Ch Alert 7.111 Open the shunts on the Th and Tc test switches.
7.112 Read ago:
Ideal As Found As Left 10.0i0.03 ma 7.113 Insert Th and Tc resistances for 540*F:
Th 416.05 Ohms Tc 416.26 ches Ideal As Found As Left Th 2.00 1 0.01 V Tc 2.00 1 0.01 V Tavg V 2.00 V
Tavg ma 10.00 1 0.20 ma AT 0.00 1 0.02 V f(Tavg) 10.00{0.20
- aT s.p.2 541.66 ma
- See Note 2 L
re
'?
- s ICP 2.1 U1 Page 16~
Unit 1-checkoff
~
7.114' Change Th to 615'F:
.Th 446.40 ohns Th 10.00 1 0.01.V Tavg.
6.00 V
Tavg na H30.00 1 0.20 ma AT 6.00 1 0.02 V 7.115 Change Tc to 615'F:
Tc 446.68 Ohms'
' Ideal' As Found As Left Tc 10.00 1 0.0117 Tavg V 10.00 V
Tavg na 50.00 i 0.20 ma AT 0.00 1 0.02 V 7.116' Adjust Th and Tc resistance to give a positive AT voltage of 4.00 V.
o~
7.117 Insert a current calibrator into Tavg test jack and verify Tavg high-low bistable settings:
~Idkal As Found As Left Low 211.60 dec.
u
'High
$28.66 inc.
i 7.118 Insert an analog simulator in the pressurizer pressure test jack and set to a value between 50 and 75%.
7.119 Set Tavg current calibrator to 44.24 ma.
7.120 Read f(Tavg):
Ideal As Found As Left l-211.09 7.121 Read AT s.p.2:
Ideal As Found As Left
{
$40.57 I
i V
ICP 2.1 U1 Page 17 Unit 1 Checkoff 7.122 Install 1000 precision resistors in the q and q l
test jacks.
7.123 Insert a current calibrator into g,Aq):
test jack. Set q 2.06 V higher than q, and read f [
1 Ideal As Found As Left 20.0010.03 ma 7.124 Remove current calibrator from g test jack and insert i
into the q test jack. Set q1 3.23 V higher than q 1
and read f (Aq):
Ideal As Found As Left l
20.0010.03 ma 7.125 Turn analog / calibrator switch to analog and record the following:
f (Aq)
AT s.p.1 AT s.p.2 7.126 Turn analog / calibrator switch to calibrator and change f (AQ) by increasing q controller output by several ma.
Record '
g the following:
f (Aq)
AT s.p.1 AT s 3 2 7.127 The change in each parameter should be the same:
f (aq)
AT s.p.1 AT s.p.2 7.128 Remove calibrator and precision resistors from q and q 3
test jacks and return test jack switches to normal
,~
- .n ICP 2.1 U1-Page 18 Unit I checkoff
- 7.129 Insert the appropriate values and record the following:
AT s.p.1-Pzr.
Tavg Press Ideal As-Found As-Left
-50 ma 15 ma 519.73 ma 50 ma 30 ma 26.71 ma 50 ma 45 ma 33.70 ma 30 ma 45 ma 50.26 ma 22 ma 30 ma 49.89 ma
.18 ma
-15 ma 46.22 ma
-7.130 Adjust the pressurizer pressure to some value greater than 75% and Tavg to a value greater than 90%.
7.131 Slowly decrease pressure and record the following values of AT s.p.1:
Ideal As Found As Left Rod Stop 231.60 dec.
Overtemp~
230.00 dec.
7.132 Insert a current calibrator in the f (Tavg) test jack.
7.133 Using a calibrator, decrease AT s.p.2 and record the following values at AT s.p.2:
Ideal As Found As Left g
i f
Rod Stop 230.80 dec.
y Overpower 230.30Ldec.
7$134 Using the. analog simulator, check the following P430 '
pressurizer pressure setpoints:
Ideal As Found As Left High press trip
$43.25 inc.
- Low press trip 215.50 dec.
l Safety Injection 211.75 dec.
Unblock SI
$13.75 inc.
- See Note 2.
- Use comp. press testpoint i
t
r
.O IL 2.1 U1 Page 19 Unit 1 Checkoff 7.134.1 Test power-operated relief valve operability
.by perfo'rming the following:
a.
Have. operator place PCV-430 and PCV-431C control switches in the close. position.
b.
Place the pressurizer pressure controller in manual.
c.
Place the pressurizer pressure defeat switch (C110) to operate position.
d.
Place pressurizer pressure controller in auto.
e.
Have operator place PCV-431C in auto position.
f.
Check the setpoint of PC-430B. Use TP-430A and test lamp connected across PC-430B output terminals.
Ideal As Found As Le'ft PC-430B 41.75t NOTE: PC-430B OUTPUT TERMINALS ARE C110-W1 & W2.
g.
Remove test lamp when test is complete.
h.
Simultaneots to Step f, perform the following:
- 1) Preliminary - attach an ohmmeter across contacts 1 & 5 of relay PC-430BX in C158.
(Verify ro voltage exists first.)
- 2) With PC-430BX deenergized (PC-430B input less than setpoint), contacts 1 & 5 indicate open.
t
r ICP 2.1 U1 Page 20 Unit 1 Checkoff
- 3) With PC-430BX energized (PC-430B input greater than setpoint), Contacts 1 & 5 indicate shut.
- 4) Remove the ohmmeter.
i.
Verify PC-430BX is deenergized. Have the operator place PCV-430 control switch in the auto position.
7.135 Return all test jacks to normal.
7.136 Remove all test equipment and close the shunts on Th and Tc test switches.
7.137 Return all bistable trip switches to normal.
7.138 Place the following L427 pressurizer level bistable test switches in the trip position and verify alarms.
High level trip PRZR High Level Ch Alert Low Level U1 PRZR Low Level Ch Alert 7.139 Using an analog simulator, check the following L427 pressurizer level setpoints:
Ideal As Found As Left High level trip 546.00 inc.
Low Level 212.80 dec.
7.140 Return the test jack to normal and remove the simulator.
7.141 Return 1he L427 trip switches to normal.
7.142 Request the operator to place the rod control selector switch into the manual position.
l-7.143 Place the steam dump controller TC-401I (located in rack C107) in manual.
l 7.144 Place the steam generator level programmer LM-463F j
(located in rack C127) in manual.
I l
l l
r
< v
.l 1*
v ICP.2.1 U1-Page 21-Unit 1 I
checkoff
.a
- 7.145 Place khe following P485 first stage steam pressure-bistable test switches in the trip position:
-Turbine Power >X%
Load Limit Reduction Lo:
~
7.146 Using an analog simulator, check the following P485 first stage steam pressure setpoints:
Ideal As'Found As Left' Turbine Power >X%
$13.27 inc.
Load Limit Reduction Lo 537.57 dec.
. 7.147 Return' the test jack' to normal and remove the simulator.
7.148 Return the P485 trip switches to normal.
7.149 Place the steam generator level programmer LM-463F in automatic.
7.150 Place the steam. dump controller TC-401I'in automatic.
7.151 Request the operator to place the rod control selector switch into the auto position after Tref has returned
'to normal. (s2 min.)
7.152 Place the following P949 containment pressure bistable test switches in the trip position and verify alarm.
Safeguards action U1 Cont. Press Ch Alert Containment spray logic 7.153' Using an analog simulator, check the following P949 containment pressure setpoints:
Ideal As Found As Left Safeguards action $17.33 inc.
Cont. spray logic $30.67 inc.
7.154 Return the test jack to normal and remove the simulator.
}
7.155 Return the P949 trip switches to normal.
'* See Step 4.1 under Conditions before proceeding.
I
1 ICP 2.1 U1 Page 22 Unit 1 Checkoff 7.156 Place the following P946 containment pressure bistable test' switches in the trip position and verify alarm.
Steam line isolation U1 Cont. Press Ch Alert
' Cont. spray logic 7.157 Using an analog simulator, check the following P946 containment pressure setpoints:
Ideal As Found As Left Steam line isolation $16.67 inc.
Cont. spray logic
$21.11 inc.
7.158 Return the test jack to normal and remove the simulator.
7.159 Return the P946 trip switches to normal.
7.160 Place the following F412 reactor coolant flow bistable test switch in the trip position and verify alarm.
Low flow RC Flow Loop "A" Ch Alert 7.161 Using an analog simulator, check the following F412 reactor coolant' flow setpoint:
Ideal As Found As Left Low flow B38.60 dec.
7.162 Return the test jack to normal and remove the simulator.
7.163 Return the F412 trip switch to normal.
7.164 Place the following L473 steam generator level bistable test switches in the trip position and verify alarms.
Low-low level SG "B" Low-Low Level Ch Alert l
High level SG "B" High Level Ch Alert Low level SG "B" Low Level Ch Alert i
l l
l
e; ICP 2.1 U1 Pagel23 Unit 1 Checkoff 7.'165;Using an~ analog simulator, check.the following L473 steam generator: level setpoints:
Ideal As Found
As Left Lo-lo level-216.00 dec.
High level,
$38.00 inc.
-l Low level 218.00 dec.
j
.l 7.166 Return the test jack to normal and remove the simulator.
7.167 Return _the L473 trip switches to' normal.
(Ensure the SF-FWF switches are in red) 7.168 Place'the following P469, F465 and F467 bistable test switches in the trip position and verify alarms.
Safeguard actuation Steam Line Loop "A" Press Low-Low Ch Alert Low press alarm Steam Line Loop "A"-Press Low
~
High trip
- High-High Trip Steam Line Loop "A" Iso. Ch Alert SF'< FWF SG "A" Feedwater Flow High-SF > FWF SG "A" Feedwater Flow Ch Alert-
- 7.169 Using an analog simulator,. check the following P469 steam generator pressure setpoints:
(Use the comp. steam press testpoint)
Ideal As Found As Left Safeguard actuation 225.14 dec.
Low pressure alarm 227.14 dec.
l 7.170 Return the test jack to normal and remove the simulator.
7.171 Return.the P469 trip switches to normal.
7.172 Using a analog simulator, check the.following F465 steam flow setpoints:
(Use the steam flow testpoint) 4 Ideal As Found As Left High trip 510.44 inc.
Hi-hi trip 547.00 inc.
7.173 Set the steam flow to read 30.00 ma at the " linear comp SF" testpoint.
4 h
---..e-
,+~.,-r-.-
-,--n-n-,,
- -,.w.
,,n.,,
--,-----n..
-..,.,v.-
n u.
e,
T
- e e
ICP 2.1.U1 Page 24 Unit 1 Checkoff 7.174 Using an analog simulator, check the following F467 feedwater flow setpoints:
(Use the " linear, flow" testpoint)'
. Ideal As Found As Left SF <.FWF 538.00 inc.
SF >.FWF 222.00 dec.-
7.175 Return the F465 and the F467 test jacks to normal and remove the simulator.-
.7.176 Return the F465 and F467 trip switches to normal.
7.177 Close all doors on Channel-II (white).
7.178 Check that all Channel II (white) alarms and trips have cleared.
7.178.1l Request the operator to reinstate Channel II (white) alarms and'to suppress Channel III (blue) alarms on the computer.
7.179 Request the operat'or to place the pressurizer relief valve switches (430 and 431C) to the close position.
7.180 Request the operator to place the rod control selector switch into.the manual position.
7.181 Inform the operator that the pressurizer level and-
~
pressure controllers will be placed in manual.
L i
7.182' Place the Tavg defeat switch (C107) to the defeat Channel i
III.(blue) position.
7.183 Place the AT defeat switch (C108) to the defeat Channel III (blue) position.
7.184 Place the pressurizer pressure controller in manual.
7.185 Place the pressurizer pressure defeat switch (C110) to the defeat Channel III (blue) position.
L 7.186 Return the pressurizer pressure controller to auto.
l-7.187 Place pressurizer level controller in manual.
l!-
l I-L
. ~
~
ICP 2.1 U1.
Page 25 Unit 1 Checkoff 7.188 Place the pressurizer level defeat switch in the defeat Channel III (blue) position.
-7.189 Place pressurizer level controller in auto.
7.190 Request the operator to place the pressurizer relief valve switches (430 and 431C) in the automatic position.
7.191 Inform the operator that the pressurizer level and pressure controllers are back in automatic.
7.192 Inform the operator that he may return the rod control selector switch to automatic.
7.193 Place the following bistable switches to the trip position:
Channel III (Blue)
Overpower Trip Rod Stop High Tavg overtemp. Trip Rod Stop Low Tavg High Press Trip Low Press Trip SI Unblock SI 7.194 Verify the following alarms on IC04 or C01:
RC Tavg High Auto Turbine Runback OT AT RC Tavg Low Auto Turbine. Runback OP AT RC OT AT Channel Alert Analog Channel III Test RC OP AT Channel Alert PRZR Low Press Ch Alert PRZR High Press Ch Alert U1 PRZR Press SI Ch Alert 7.195 Open the shunts on the Th and Tc test switches.
7.196 Read Ago:
Ideal As Found As Left 10.010.03 ma 7.197 Insert Th and Tc resistances for 540*F:
Th 416.01 Ohms Tc 416.03 Ohms Ideal As Found As Left Th 2.00 i 0.01 V Tc 2.00 1 0.01 V Tavg V 2.00 V
Tavg ma 10.00 1 0.20 ma 6T 0.00 1 0.02 V f(Tavg) 10.00[0.20
- AT s.p.2 541.25 ma
- See Note 2
~
.o.
ICP 2.1 U1 Page 26 Unit 1 Checkoff 7.198 Change Th to 615'F:
Th 446.38 chms Th-10.00 1 0.01 V Tavg 6.00 V
Tavg ma 30.00 1 0.20 ma AT 8.00 1 0.02 V
'7.199 Change Tc to 615*F:
Tc 446.35 Ohms Ideal As Found As Left Tc 10.00 i 0.01 V Tavg V 10.00 V
Tavg ma 50.00 t 0.20 ma AT 0.00 i 0.02 V 7.200 Adjust Th'and Tc resistance to give a positive aT voltage of 4.00 V.
7.201 Insert a current calibrator into Tavg test jack and verify Tavg high-low bistable settings *:
Ideal As Found As Left Low 211.60 dec.
High 528.66 inc.
7.202 Insert an analog simulator in the pressurizer pressure test jack and set to a value between 50 and 75%.
7.203 Set Tavg current calibrator to 44.24 ma.
7.204 Read f(Tavg):
L Ideal As Found As Left i-211.07 7.205 Read AT s.p.2:
Ideal As Found As Left l
640.18 7.206 Install 1000 precision resistors in the q and q 1 test jacks.
l
'e ICP'2.1 U1 Page 27 Unit 1 Checkoff 7.207 Insert a current calibrator into g test jack. Set q 2.29 V higher-than q, and read f [Aq):
1 Ideal As Found As Left 20.0010.03 ma 7.208 Remove. current calibrator from g test jack and insert into.the q test jack. Set q 3.58 V higher than q g
1 and read f (AQ):
Ideal As Found As Left 20.0010.03 ma 7.209 Tdrn analog / calibrator switch to analog and record the following:
f (Aq)
AT s.p.1 AT s.p2 7.210 Turn analog calibrator switch to calibrator and change f (Aq) by increasing q controller output by several ma.
1 Record the following:
f (Aq)
AT s.p.1 AT s.p.2 7.211 The change in each parameter should be the same:
f (Aq)
AT s.p.1 AT s.p.2 7.212 Remove calibrator and precision resistors from q and q y test jacks and return test jack switches to normal h
,,,,__n m
,,.y.,-..,
r
~~
a-ICP 2.1 U1 Page 28 Unit 1 Checkoff
- 7.213 Insert the appropriate values and record the following:
AT s.p.1 Pzr.
Tavq Press Ideal As-Found As left 50 ma.
15 ma
$19.60 ma 50 ma 30 ma 26.49 ma 50 ma 45 ma 33.39 ma 30 ma 45 ma
'49.74 ma 22 ma 30 ma 49.38 ma 18 ma 15 ma 45.76 ma 7.214 Adjust the pressurizer pressure to some value greater than 75% and Tavg to a value greater than~ 90%.
7.215 Slowly decrease pressure and record the following values of AT s.p.1:
Ideal As Found As Left Rod Stop 231.60 dec.
Overtemp 230.00 dec.
7.216 Insert a current calibrator in the f (Tavg) test jack.
7.217 Using a calibrator, decrease AT s.p.2 and record the following values at ATs.p.2:
Ideal As Found As Left i
I Rod Stop 230.80 dec.
Overpower 230.30 dec.
7.218 Using the analog simulator, check the following P431 pressurizer pressure setpoints:
i Ideal As Found As Left I
l High press trip 543.25 inc.
- Low press trip 215.50 dec.
l Safety Injection 211.75 dec.
l-Unblock SI
$13.75 inc.
- See Note 2
- Use comp. pressure testpoint.
t i
ICP 2.1 U1 Page 29 Unit 1 Checkoff 7.218.1' Test power-operated relief valve operability by performing the following:
a.
Have operator assume manual control of-pressurizer pressure by placing spray valve control stations HC-431C and HC-431H and-proportional heater controller PC-431L in manual.
b.
Have operator place PCV-431C control switch
)
in the shut position.
NOTE: THE OPERATOR MUST BE AWARE THAT DURING THE PERFORMANCE OF THE NEXT STEPS HE WILL HAVE TO CONTROL PRESSURIZER PRESSURE USING MANUAL CONTROL OF THE SPRAY VALVES AND BACKUP HEATERS. THE PROPORTIONAL HEATERS WILL NOT RESPOND TO ACTUAL PRESSURIZER PRESSURE REQUIREMENTS.
c.
Take manual control of PC-431K and vary its output to check the setpoint of PC-431B. Use TP-431K and a test lamp attached across PC-431B output terminals.
Ideal As Found As Left PC-431B 50.00t NOTE: PC-431B OUTPUT TERMINAL ARE C110-S5 & S6.
d.-
Remove the test lamp when test is complete.
e.
Simultaneous to Step c, perform the following:
- 1) Preliminary - attach an ohmmeter across Contacts 1 & 5 of relay PC-431BX in C158.
(Verify no voltage exists first.)
- 2) With PC-431BX deenergized (PC-431B input less than setpoint), Contacts 1 & 5 indicate open.
=
1 ICP 2.1 U1-Page 30
. Unit 1.
Checkoff
'3) With PC-431BX energized (PC-431B input greater than setpoint), contacts 1 & 5 indicate shut.
- 4) Remove the ohmmeter.
f.
Verify PC-431BX is deenergized.
g.
Return PC-431K to automatic _
h.
Return PC-431L to automatic i.
When the output of PC-431K is stable and no deviation exists on HC-431C and HC-431H, place the spray valve control stations in automatic.
j.
Have operator place PCV-431C control switch in the auto position.
7.219 Return all test jacks to normal.
7.220 Remove all test equipment.
7.221 Close the shunts on Th and Tc test switches.
7.222 Return all bistable trip switches to normal.
7.223 Place the following L428 pressurizer level bistable test switches in the trip. position and verify alarms.
High level trip PRZR High Level Ch Alert Low Level U1 PRZR Low Level Ch Alert 7.224 Using an analog simulator, check the following L428 pressurizer level setpoints:
Ideal As Found As Left High level trip 146.00 inc.
Low Level 212.80 dec.
7.225 Return the test jack to normal and remove the simulator.
7.226 Rcturn the L428 trip switches to normal.
7.227 Request the operator to hold the steam dump selector switch in the reset positon.
=
.9 4
ICP 2.1 U1 Page 31 Unit 1.
Checkoff-7.228 Using a current calibrator, apply 30 ma into test jack P486B (C107). Read at-testpoint P486B.
7.229 When' test light P486B has gone out,' request the operator to return the steam dump selector switch to the auto position.
- 7.230 Place the following P486 first stage steam pressure bistable test switches in the trip position:
Turbine Power >K%
Load Limit Reduction Lo 7.231 Using an analog simulator, check the following P486 first stage steam pressure setpoints:
Ideal As Found As Left Turbine Power >X%
$13.27 inc.
Load Limit Reduction Lo $37.57 dec.
7.232 Return the test jack to normal and remove the simulator.
7.233 Return the P486 trip switches to normal.
7.234 Request the operator to hold the steam dump selector switch in the reset position.
7.235 Return test jack P486B (C107) to normal and remove the current calibrator.
7.236 When test light P486B has gone out, request the operator to return the steam dump selector switch to the auto position.
7.237 Place the following P948 containment pressure bistable test switches in the trip position and verify alarms.
Steam line isolation U1 Cont. Press Ch Alert Cont. spray logic
- See Step 4.1 under Conditions before proceeding.
ICP 2.1 U1 Page 32 Unit 1 Checkoff 7.238 Using an analog. simulator, check the following P948 containment pressure setpoints:
Ideal As Found As Left Steam line isolation $16.67 inc.
Cont. spray logic 521.11 inc.
7.239 Return the test jack to normal and remove the simulator.
7.240 Return'the P948 trip switches to normal.
7.241 Place the following F415 reactor coolant flow bistable test switch in the trip position and verify alarms.
Low flow RC Flow Loop "B" Ch Alert 7.242 Using an analog simulator, check the following F415 reactor coolant flow setpoint:
Ideal' As Found As Left Low flow 238.60 dec.
7.243 Return the test jack to normal and remove-the simulator.
7.244 Return the F415 trip switch to normal.
7.245 Place the following P947 containment pressure bistable test switches in the trip position and verify alarm.
Safeguards action U1-Cont. Press Ch Alert containment' spray logic 7.246 Using an analog simulator, check the following P947 containment pressure setpoints:
Ideal As Found As Left Safeguards action 517.33 inc.
Cont. spray logic 530.67 inc.
7.247 Return the test. jack to normal and remove the simulator.
7.248 Return the P947 trip switches to normal.
-m-a
,,,, ~, - - - - -
,ne
-,a
o ICP 2.1 U1 Page 33 Unit 1 Checkoff
~
7.249 Place the following F413 reactor coolant flow bistable test switch in the trip position and verify alarm.
. Low flow RC Flow Loop "A" Ch Alert 7.250 Using an analog simulator, check the following F413 reactor coolant flow setpoint:
Ideal As Found As Left Low flow 238.60 dec.
7.251 Return the test jack to normal and remove the simulator.
7.252 Return the F413 trip switch to normal.
7.253 Place-the following L462 steam generator level bistable-test switches in the trip position and verify alarms.
Low-low level SG "A" Low-Low Level Ch Alert High level SG "A" High Level Ch Alert Low level SG "A" Low Level Ch Alert 7.254 Using an analog simulator, check the following L462 steam generator level setpoints:
Ideal As Found As Left Lo-lo level 216.00 dec.
High level 538.00 inc.
Low level 218.00 dec.
7.255 Return the test jack to normal and remove the simulator.
7.256 Return the L462 trip switches to normal.
7.257 Place the following P482 steam generator pressure bistable test switches in the trip position and verify alarms.
Safeguard actuation Steam Line Loop "A" Press Low-Low Ch Alert Low pressure,
Steam Line Loop "A" Press Low
. o ICP 2.1 U1 Page 34 Unit 1 Checkoff 7.258 Using'an analog simulator, check _the following P482 steam generator pressure setpoints:
(Use comp. press
-testpoint)
Ideal As Found As Lef t Safeguard actuation _ 225.14 dec.
Low pressure 127.14 dec.
7.259 Return the test. jack to normal and remove the simulator.
7.260 Return the P482 trip' switches to normal.
7.261 Request the operator to do the following:
1.
Place pressure controller 478 in manual.
- 2.
Place steam generator level controller 481 in manual.
- 3.
Place steam generator level controller 476 in manual.
- 4.
Place the "B" loop steam flow selector switch in the yellow position.
- 5.
Place the "B" loop feedwater flow selector switch in the yellow position.
- 6.
Place steam generator. level controller 476 in automatic.
- 7.
Place steam generator' level controller-481 in automatic.
These steps may be deleted if both selector switches are already in the yellow position 7.262 Place the following P478, F474 and F476 bistable test-switces in the trip position and verify alarms.
Safeguard actuation Steam Line Loop "B" Press Low-Low Ch Alert Liow pressure alarm Steam Line Loop "B" Press Low High trip High-High Trip Steam Line Loop "B" Iso. Ch Alert
-SF < FWF SG "B" Feedwater Flow High SF > FWF SG "B" Feedwater Flow Ch Alert
m.
^*
-6 ICP 2.1 U1 Page 35 Unit 1 Checkoff-7.263 Using an analog simulator, check the 'following P478 steam generator pressure setpoints:
(Use the comp. steam press testpoint)
Ideal As Found As Left Safeguard actuation 125.14 dec.
Low pressure alarm 227.14 dec.
7.264 Return the test jack to normal and remove the simulator.
7.265 Return the P478 trip switches to normal.
7.266 Request the operator to return pressure controller 478 to the automatic mode.
7.267 Using a analog simulator, check the following F474 steam cflow setpoints:
(Use the " steam flow" testpoint)
Ideal As Found As Left High trip 510.44 inc.
Hi-hi trip 547,00 inc.
7.268 Set the steam flow to read 30.00 ma at the " linear comp SF" testpoint.
7.269 Using~an analog simulator, check the following F476 feedwater flow setpoints:
(Use the " linear FWF" testpoint)
Ideal As Found As Left SF < FWF 538.00 inc.
SF > FWF 222.00 dec.
l 7.270 Return the F474 and the F476 test jacks to normal and remove the simulator.
7.271 Return the F474 and F476 trip switches to normal.
7.272 Close all doors on Channel III (blue).
7.273 Check that all channel III (blue) alarms and trips have cleared.
7.273.1 Request the operator to reinstate Channel III (blue)
. alarms and to suppress Channel IV (yellow) alarms on the computer.
l l
,. _ _ _ _ ~.
-~
w.
ICP 2.1 U1 Page 36 Unit'l checkoff 7.274 Request the operator to place the pressurizer relief valve switches (430 and 431C) to tLe close positfon.
7.275_ Request the operator to place the rot control selector switch into the manual position.
4 7.276 Inform the operator that the pressurizer level and
. pressure controllers will be placed in manual.
7.277 Place-the, Tavg defeat ~ switch (C107) to the defeat channel IV (yellow) position.
7.278 Place the AT defeat switch (C108) to the defeat Channel IV (yellow) position.
7.279 Place _the pressurizer pressure controller in manual.
7.280 Place the pressurizer pressure defeat switch (C110) to the defeat Channel IV (yellow) position.
7.281 Return the pressurizer pressure controller to' auto.
7.282 Place pressurizer level controller in manual.
7.283 Place the~ pressurizer level defeat switch in the I
operate position.
7.284 Place pressurizer level controller in' auto, i..
7.285 Request the operator to place the pressurizer relief valve switches-(430'and 431C) in the automatic position.
7.286 Inform the operator that the pressurizer level and pressure controllers are back in automatic.
7.287' Inform the operator-that he may return the rod control selector switch to automatic.
E
~
7.288 Place the following bistable trip switches to the trip position:
Channel IV (Yellow)
Overpower Trip Rod Stop High Tavg Overtemp. Trip Rod Stop Low Tavg Low Press trip 4
i ICP 2.1 U1 Page 37
-Unit 1-
-Checkoff
~
-7.289 Verifyfthe'fol1owing alarms on-1C04:
RC-Tavg High Auto Turbine Runback'OT AT RC Tavg Low
' Auto Turbine Runback OP AT RC Cf AT Channel Alert Analog Channel IV-Test
~
'RC OP AT Channel Alert PRZR Low Press Ch-Alert 7.290 Open the. shunts on the.Th and Tc test switches.
7.291 Read ago:
Ideal As Found As Left 10.010.03 ma 7.292 Insert-Th and Tc resistances for 540*F:
Th 416.41 Ohms:
Tc 416.00 Ohms Ideal
-As Found As Left Th' 2.00 i 0.01 V 4
Tc 2.00 i 0.01 V
^
Tavg V 2.00-V Tavg ma 10.00.1 0.20 ma
}
AT 0.00 i 0.02 V
.f(Tavg) 10.00[0.20
.*aT s.p.2 541.25 ma 7.293 Change Th to 615'F:
Th 446.86 Ohms Th 10.00 1 0.01 V Tavg 6.00 V
Tavg ma 30.00 i 0.20 ma AT 8.00 1 0.02 V
- See Note 2.
A 1
,, ~ - - - - -,,. -.. - - -, - -,, - - -...,,,. - - -.-.
---,,---,..-,,.,,-,,~
ICP 2.1 U1 Page 38 Unit 1 Checkoff I
l
.7.294 Change Tc to 615'F:
.Tc 446.35 Ohms Ideal As Found As Left Tc 10.00 1 0.01 V Tavg V 10.00 V
.Tavg ma 50.00 1 0.20 ma AT 0.00 1 0.02 V 7.295 Adjust Th and Tc resistance to give a positive AT voltage of 4.00 V.
7.296 Insert a current calibrator into Tavg test jack and verify Tavg high-low bistable settings:
Ideal As Found As Left Low 211.60 dec.
High
.528.66 inc.
7.297 Insert an analog simulator in the pressurizer pressure test jack and set to a value between 50 and 75%.
7.298 Set Tavg current calibrator to 44.24 ma.
7.299 Read f(Tavg):
Ideal As Found As Left 211.07 7.300 Read AT s.p.2:
Ideal As Found As Left 540.18 7.301 Install 1000 precision resistors in the q and q u
1 test jacks.
7.302 Insert a current calibrator into g test jack. Set q.
2.08 V higher than q, and read f (Aq):
g Ideal As Found As Left 20.0010.03 ma
--..i - '.
ICP 2.1 U1 Page 39 Unit 1 Checkoff 7.303 Remove current calibrator from g test jack and insert into the q test jack. Set q 3.25 V higher than q 1
1 u
and read f (6Qq):
' Ideal As Found As Left 20.0010.03 ma 7.304 Turn analog / calibrator switch to analog and record the following:
f (aq)
AT s.p.1 AT s.p.2 7.305 Turn analog calibrator switch to calibrator and change f (AQ) by increasing q controller output by several ma.
Record 1
the following:
f (aq)
AT s.p.1 AT s.p.2 7.306 The change in each parameter should be the same:
f (aq)
AT s.p.1 AT s.p.2 7.307 Remove calibrator and precision resisters from qu "" 91 test jacks and retuin test jack switches to normal
- 7.308 Insert the appropriate values and record the following:
AT s.p.1 Pzr.
Tavq Press Ideal As Found As Left 50 ma 15 ma
$19.60 ma 50 ma 30 ma 26.49 na 50 ma 45 ma 33.39 ma 30 ma 45 ma 49.74 ma 22 ma 30 ma 49.38 ma 18 ma 15 ma 45.76 ma
- See Note 2
e-ICP 2.1 U1 Page 40 Unit.1 Checkoff 7.309 Adjust the pressurizer pressure to some value greater-than 75% and Tavg to a value greater than 90%.
7.310 Slowly decrease pressure and record the following values of AT s.p.1:
Ideal As Found As Left Ro'd Stop 231.60 dec.
Overtemp 230.00 dec.
7.311 Insert a current calibrator in the f (Tavg) test jack.
7.312 Using a calibrator, decrease AT s.p.2 and record the following values at AT s.p.2:
Ideal As Found As Left Rod Stop 230.80 dec.
Overpower 230.30 dec.
7.313 Using the analog simulator, check the following P449 pressurizer pressure setpoint:
Ideal As Found As Left
- Low Pressure trip 215.50 dec.
6.313.1 Test power-operated relief valve operability by performing the following:
a.
Have operator place PCV-431C control switch in the close position.
l b.
Check the setpoint of PC-449B. Use TP-449A and a test lamp connected across PC-449B output terminals.
Ideal As Found As Left PC-449B 41.75t NOTE: PC-449B OUTPUT TERMINALS ARE C110-T5 & T6.
c.
Remove test lamp when test is complete.
i
- Use comp. press testpoint l
l
.1 e
s (n,
ICP 2.1 U1 Page 41 Unit 1 Checkoff d.
Simultaneous to Step b, perform the following:
- 1) Preliminary - attach an ohmmeter across Contacts 2 & 6 of relay PC-449BX in C158.
(Verify no voltage exists first.)
- 2) With PC-449BX deenergized (PC-449B input less than setpoint), Contacts 2 & 6 indicate open.
- 3) With PC-449BX energized (PC-449B input greater than setpoint), Contacts 2 & 6 indicate shut.
- 4) Remove the ohmmeter.
e.
Verify PC-449BX is deenergized. Have operator place PCV-431C control switch in the auto position.'
7.314 Return all test-jacks to normal.
7.315 Remove all test equipment.
7.316 Close the shunts on Th and Tc test switches 7.317 Return all bistable trip switches to normal.
7.318 Place the following P950 containment pressure bistable test switches in the trip position and verify alarm.
Steam line isolation U1 Cont. Press Ch Alert Cont. spray logic 7.319 Using an analog simulator, check the following P950 containment pressure setpoints:
Ideal As Found As Left Steam line isolation $16.67 inc.
Cont. spray logic 521.11 inc.
7.320 Return the test jack to normal and remove the simulator.
7.321 Return the P950 trip switches to normal.
P ICP 2.1 U1 Page 42 Unit 1 Checkoff 7.322 Place the following F416 reactor coolant flow bistable test switch in the trip position and. verify alarm.
Low flow RC Flow Loop "B" Ch Alert 7.323 Using an analog simulator, check the following F416 reactor coolant flow setpoint:
Ideal As Found As Left Low flow 238.60 dec.
7.324 Return'the test jack to normal and remove the simulator.
7.325 Return the F416 trip switch to normal.
.7.326 Place the following L463 steam generator level bistable test switches in the trip position and verify alarms.
Low-low-level SG "A" Low-Low Level Ch Alert High level SG "A" High Level Ch Alert Low level SG "A" Low Level-Ch Alert 7.327 Using an analog simulator, check the following L463 steam generator level setpoints:
Ideal As Found As Left Lo-lo level 216.00 dec.
~~
High level 538.00 inc.
- ~
Low level 218.00 dec.
[
7.328 Return the test jack to normal and remove the simulator.
.7.329 Return the L463 trip switches to normal.
I I
7.330 Request the operator to do the following:
f 1.
Place the steam generator level controller 481 l:
in manual.
2.
Place the steam generator level controller 476 in manual.
l l
=
-e e_ ~ '.. _.
ICP 2.1 U1 c
Page 43 Unit 1 Checkoff.
'7~ 331 Place the. following L471 steam generator level bistable test switches in the trip position and verify alarms.
High level-SG "B" High Level Ch Alert Low-low level-
-SG "B" Low-Low Level Ch Alert 7.332 Using an analog simulator, ' check the following L471 steam generator level setpoints:
Ideal As Found As Left High level 538.00 inc.
Lo-lo level-216.00 dec.
7.333 Return the L471 test jack to normal and remove the simulator.
7.334 Return the L471 trip switches to normal.
7.335 Request the operator-to do the following:
1.
Place the "B" loop steam flow selector switch in.
the. blue position.
2.
Place the "B" loop feedwater flow selector switch in the blue position.
3.
Place steam generator level controller 476 in automatic.
4.
Place steam' generator level controller 481 in automatic.
7.336 Place the following P479, F475 and F477 bistable test switches in the trip position and verify alarms.
Safeauard actuation Steam Line Loop "B" Pre:3 Low-Low Ch Alert
-Low press alarm Steam Line Loop "B" Press Low High trip-High-High trip Steam Line Loop."B" Iso. Ch Alert SF < FWF SG "B" Feedwater Flow High SF > FWF SG "B" Feedwater Flow Ch Alert
~_._.._.__,.,._---._-__----_-_..-J
ICP 2.1 U1 Page 44 Unit 1 Checkoff 7.337 Using an analog simulator, check the following P479 steam generator pressure setpoints:
(Use the comp. steam press testpoint)
Ideal As Found As Left Safeguard actuation 225.14 dec.
Low pressure alarm 227.14 dec.
7.338 Return the test jack to normal and remove the simulator.
7.339 Return the P479 trip switches to normal.
7.340 Using an analog simulator, check the following F475 steam flow setpoints:
(Use the " steam flow" testpoint)
Ideal As Found As Left High trip 510.44 inc.
Hi-hi trip 547.00 inc.
7.341 Set the steam flow to read 30.00 ma at the " linear comp SF" testpoint.
7.342 Using an analog simulator, check the'following F477 feedwater flow setpoints:
(Use the " linear FWF" testpoint)
Ideal As Found As Left SF < FWF
$38.00 inc.
SF > FWF 222.00 dec.
7.343 Return the F475 and the F477 test jacks to normal and remove the simulator.
L 7.344 Return the F475 and F477 trip switches to normal.
7.345 Close all doors on Channel IV (yellow)
(
7.346 Check that all Channel IV (yellow) alarms and trips have cleared.
L t
7.347 Request the operator to place the rod control selector i
switch into the manual position.
7.348 Place the Tavg defeat swtich (C107) to the normal position.
I i
i
't ICP 2.1 U1 Page 45 Unit 1
'{
- Checkoff
}'
'i 7.349 Place the AT defeat switch (C108) to the normal-position.
-7.350 Inform the operator that he may return the rod control selector switch to automatic.
7.351 Request the operator reinstate Channel IV (yellow)~
alarms on the computer.
Initials 7.352 Notify the Duty Shift Superintendent and the' Control-Operator that the test is complete.
(DSS) t 4
I 1
(
I 9
. i t
,,, -. - - -,, - ~.,,,
-s,-
,,w-,m-.
y
c- --
?
yy,
.3
..\\,;, - 4 7 s
l.
' N; l...
..; 3.
e s'
g,
=..,,
r.4 N.i+
ICP 2.1 U1
[
Page 46
!?
- Unit 1
./
i(
i s
- :8.0 PROBLEMS t
k r
s 5.
1.
~
Problem:
^5 h
y>'
c.
'N 5
i t
uc
,e =
1 M,
. Action Taken:
?-
g b
4
)
\\
9 i t' llow Action Required Yes No is.
i Completed BY Reviewed q3 J.
Technician I&C supervisor Date Date S
Approved s
.i Superintendent-I&C'
.c:
Date t
n
[>
. NOTE 1: Notify the Superintendent - I&C if the as-found reading is less
(
c.onservative than the ideal. Reset the bistable setting if the as-found reading is more than 0.15 ma different than, the ideal in the conservative direction. -This note applies to all bistable settings.
. r, z
= NOTE 2: Ensure. f (aq) value is at 10 ma 1.0.b3.
If not, open the q fand gy_ test jacks.
w
/f"9
.[
1-
. Equipment Used:
3 o'
.i
(
h a
)
l u
J{)p,
l f
'F l
/
l..
e l
I I
p,_. _
r.--.
-~m.
,w_,
y-
-,m. -,,.,
r.
-.'..f,.
o.
Attachment "A" 1.0 CONDITIONS This attachment is to be performed prior to leaving at-the end of a shift.
2.0 PROCEDURE checkoff Day 1 Day 2 2.1' Stop test at a convenient point.
2.2 Perform Steps 6.1.2 through 6.1.5 in the discussion section.
2.3 Request operator to place pressurizer relief valve switches (430 and 431C)
~
in the close pasition.
2.4 Request operator to place rod control selector switch in manual.
l 2.5 Inform operator that in the following sequence of steps that the pressurizer pressure and pressurizer level controllers will be placed in manual for a short period of time.
2.6-Place Tavg and AT defeat switches (C107 and C108) to the normal position.
2.7 Place pressurizer pressure controller in manual.
2.8 Place p.assurizer pressure defeat switch to normal.
2.9 Return pressurizer pressure controller to auto.
2.10 Place pressurizer level controller in manual.
2.11 Place pressurizer level defeat switch to normal.
1 2.12 Return pressurizer level controller to auto.
2.13 Request the operator to place pressurizer relief valve switches (430 and 431C) in the auto position.
E~
1
., e ; * ; s '
ICP 2.1 Attachment "A" Page 2 Unit ~1' checkoff.
Day 1
, Day-2 2.14 LRequest operator to place rod control-selector to switch in the auto position.
.2.15' Inform operator-that pressurizer pressure
~
and pressurizer level controllers are back in auto.
2.16'_ Request operator to return the computer to normal.
2.17 Inform DSS and operator that tests have been terminated for. the day and protection racks Land control switches-are returned to normal.
T r
s.>.
p.
.. ~,
l Attachment "B"-
.l 1.0 CONDITIONS This attachment is to be performed prior to continuing testing at the
~
start of a shift.
2.0 PROCEDURE Checkoff Day 1 Day 2 2.1 Inform DSS that testing is going to resume.
2.2
. Request operator to suppress alarms on the computer for the channel to be tested.
2.3 Request operator'to place pressurizer relief valve switches (430 and 431C) in the close position.
2.4 Request operator to place rod control selector switch in manual.
2.5 Inform operator that in the following sequence of steps that the pressurizer pressure and pressurizer level controllers will be placed.in manual for a.short period of time.
2.6
. Place Tavg and AT defeat switches (C107 and C108) to the proper defeat channel position.
2.7 Place pressurizer pressure controller in manual.
2.8 Place pressurizer pressure defeat switch to the proper defeat channel position.
2.9 Return pressurizer pressure controller to auto.
2.10 Place pressurizer level controller in manual.
r-~
~ ee e o... a-ICP 2.1 Attachment "B" Page-2 Unit'l Checkoff Day 1 Day 2 2.11 Place. pressurizer level. defeat switch to the proper defeat channel position.
2.12 Return pressurizer level. controller to auto.
2.13 ' Request operator to place pressurizer relief valve switches (430 and 431c) in the auto position.
.2.14: Request operator to place rod control selector switch in the auto position.
2.15 Inform operator that pressurizer pressure and level controllers are back in auto.
2.16 Inform operator that test will now be
-continued.
Inform operator of the rack and at what point the test will be resumed.