b.
With primary-to-secondary leakage. IDENTIFIED LEAKAGE, or CONTROLLED LEAKAGE greater than the appropriate limit, reduce the leakage rate to within limits within 4 hours4.62963e-5 days <br />0.00111 hours <br />6.613757e-6 weeks <br />1.522e-6 months <br /> or be in at least HOT STANDBY in the next 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> and at least COLD SHUTDOWN within the following 30 hours3.472222e-4 days <br />0.00833 hours <br />4.960317e-5 weeks <br />1.1415e-5 months <br />.
d.1 With UNIDENTIFIED LEAKAGE greater than 1 gnm*, but less than or equal to 3 gpm, identify leakage or reduce to less than or equal to 1 gpm within 4 hours4.62963e-5 days <br />0.00111 hours <br />6.613757e-6 weeks <br />1.522e-6 months <br /> or be in at least HOT STANDBY within the next 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> and in COLD SHUTDOWN in the following 102 hours0.00118 days <br />0.0283 hours <br />1.686508e-4 weeks <br />3.8811e-5 months <br />.
In addition, verify that the total of UNIDENTIFIED LEAKAGE, IDENTIFIED LEAKAGE, and Reactor Coolant Pump Seal Leakage is not greater than 26 gpm, or declare the Standby Makeup Pump INOPERABLE.
d.2 With UNIDENTIFIED LEAKAGE greater than 3 gpm*, identify or reduce leakage to less than or equal to 3 gpm within 4 hours4.62963e-5 days <br />0.00111 hours <br />6.613757e-6 weeks <br />1.522e-6 months <br /> and take ACTION di above, or be in at least HOT STANDBY within the following 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> and COLD SHUTDOWN within the following 30 hours3.472222e-4 days <br />0.00833 hours <br />4.960317e-5 weeks <br />1.1415e-5 months <br />.
- Entrance into either ACTION di or d2 shall be considered the initiation of the event regardless of a change from one ACTION to the other; i.e.,
the time at which the various mode changes must occur is not reset upon entrance to a new ACTION.