RS-20-087, Request for a License Amendment to LaSalle County Station, Units 1 and 2, Technical Specification 3.7.3, Ultimate Heat Sink
| ML20204A775 | |
| Person / Time | |
|---|---|
| Site: | LaSalle |
| Issue date: | 07/17/2020 |
| From: | Demetrius Murray Exelon Generation Co |
| To: | Document Control Desk, Office of Nuclear Reactor Regulation |
| References | |
| RS-20-087 | |
| Download: ML20204A775 (29) | |
Text
4300 Winfield Road Warrenville, IL 60555 Exelon Generation RS-20-087 July 17, 2020 U.S. Nuclear Regulatory Commission Attn: Document Control Desk Washington, DC 20555-0001 LaSalle County Station, Units 1 and 2 630 657 2000 Office Renewed Facility Operating License Nos. NPF-11 and NPF-18 NRC Docket Nos. 50-373 and 50-37 4 10 CFR 50.90
Subject:
Request for a License Amendment to LaSalle County Station, Units 1 and 2, Technical Specification 3.7.3, "Ultimate Heat Sink" In accordance with 10 CFR 50.90, "Application for amendment of license or construction permit," Exelon Generation Company, LLC (EGC) is requesting a change to the Technical Specifications (TS) of Renewed Facility Operating License Nos. NPF-11 and NPF-18 for LaSalle County Station (LSCS), Units 1 and 2. Currently, TS Surveillance Requirement (SR) 3.7.3.1 verifies the cooling water temperature supplied to the plant from the Ultimate Heat Sink (UHS) is within the limits of the diurnal curve in LSCS TS Figure 3.7.3-1. SR 3.7.3.2 verifies sediment level less than or equal to 1.5 feet in the intake flume and the CSCS pond, and SR
- 3. 7.3.3 verifies CSCS pond bottom elevation is less than or equal to 686.5 feet.
Should the UHS indicated temperature exceed the limits of Figure 3.7.3-1, TS 3.7.3 Required Actions C.1 and C.2 would be entered concurrently, requiring both LSCS units to be placed in Mode 3 within 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> and Mode 4 within 36 hours4.166667e-4 days <br />0.01 hours <br />5.952381e-5 weeks <br />1.3698e-5 months <br />.
Recent summer meteorological conditions have resulted in the TS UHS temperature limit being challenged. These conditions include elevated air temperatures, high humidity, and low wind speed. Meteorological conditions in the future may continue challenging the current TS limit in TS Figure 3. 7.3-1. These changing metrological conditions prompted EGC to assess the current inputs for the current diurnal curve limits.
As described in Regulatory Guide 1.27, "Ultimate Heat Sink for Nuclear Power Plants,"
Revision 2, the predicted response of the UHS temperature to the design basis event is a function of the historical weather including the diurnal variations in air temperature. In its letter to EGG dated November 19, 2015, the NRG approved the diurnal temperature curve, LSGS TS Figure 3.7.3-1, for LSCS (ML15202A578).
This license amendment is being requested to expand the already-approved TS temperature limit of the cooling water supplied to the plant from the UHS to vary with the diurnal cycle by changing the average sediment level limit in the intake flume and UHS to 6 inches. SR 3.7.3.2 will be modified to account for averaging the sedimentation level measurement. In addition to the proposed modification to SR 3.7.3.2, SR 3.7.3.3 would be deleted because the requirement
July 17, 2020 U.S. Nuclear Regulatory Commission Page 2 to ensure adequate long term cooling can be maintained through verification of average sedimentation level as proposed in SR 3.7.3.2. Lastly, a correction is being made to TS 3.7.3 by deleting Condition B, and modifying SR 3.7.3.1 Frequency to incorporate the one-hour monitoring frequency.
The purpose of the UHS TS temperature limit is to restrict the initial UHS temperature such that the maximum UHS temperature experienced during the UHS design basis event (i.e., the temperature of the cooling water supplied to the plant safety systems from the UHS) would not exceed the design limit of 107°F. The proposed TS temperature limits will continue to vary with the diurnal cycle to limit the maximum temperature of the UHS supplied to plant safety systems to s 107°F, and the sedimentation level limit will be adjusted from 18 inches to an average of 6 inches.
The attached amendment request is subdivided as follows: provides an evaluation of the proposed changes. provides the current TS pages with the proposed changes indicated with markups. provides the current TS Bases pages with the proposed changes indicated with markups. The TS Bases pages are provided for information only and do not require NRC approval.
EGC requests approval of the proposed changes by July 17, 2021, with the amendment being implemented within 30 days of issuance.
The proposed amendment has been reviewed by the LSCS Plant Operations Review Committee in accordance with the requirements of the EGC Quality Assurance Program.
EGC is notifying the State of Illinois of this application for a change to the TS by sending a copy of this letter and its attachments to the designated State Official in accordance with 10 CFR 50.91, "Notice for public comment; State consultation," paragraph (b).
There are no regulatory commitments contained in this letter. Should you have any questions concerning this letter, please contact Jason Taken at (630) 806-9804.
I declare under penalty of perjury that the foregoing is true and correct. Executed on the 17th day of July 2020.
Respectfully, Dwi Murray Senior Manager, Licensing Exelon Generation Company, LLC
July 17, 2020 U.S. Nuclear Regulatory Commission Page 3 : Evaluation of Proposed Changes : Mark-up of Proposed Technical Specifications Page Changes : Markup of Proposed Technical Specifications Bases Page Changes - For Information Only cc:
Illinois Emergency Management Agency - Division of Nuclear Safety NRC Regional Administrator-Region Ill NRC Senior Resident Inspector - LaSalle County Station
ATTACHMENT 1 Evaluation of Proposed Changes
Subject:
Request for a License Amendment to Technical Specification 3.7.3, "Ultimate Heat Sink"
1.0 DESCRIPTION
2.0 PROPOSED CHANGE
S
3.0 BACKGROUND
4.0 TECHNICAL ANALYSIS
5.0 REGULATORY ANALYSIS
5.1 Applicable Regulatory Requirements/Criteria 5.2 No Significant Hazards Consideration 5.3 Conclusions 6.0 ENVIRONMENTAL EVALUATION
7.0 REFERENCES
Page 1 of 16
1.0 DESCRIPTION
ATTACHMENT 1 Evaluation of Proposed Changes In accordance with 10 CFR 50.90, "Application for amendment of license or construction permit," Exelon Generation Company, LLC (EGC) is requesting a change to the Technical Specifications (TS) of Renewed Facility Operating License Nos. NPF-11 and NPF-18 for LaSalle County Station (LSCS), Units 1 and 2. Currently, TS Surveillance Requirement (SR) 3.7.3.1 verifies the cooling water temperature supplied to the plant from the Ultimate Heat Sink (UHS) is within the limits of the diurnal curve in LSCS TS Figure 3.7.3-1. SR 3.7.3.2 verifies sediment level less than or equal to 1.5 feet in the intake flume and the CSCS pond, and SR 3.7.3.3 verifies CSCS pond bottom elevation is less than or equal to 686.5 feet.
Should the UHS indicated temperature exceed the limits of Figure 3.7.3-1, TS 3.7.3 Required Actions C.1 and C.2 would be entered concurrently, requiring both LSCS units to be placed in Mode 3 within 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> and Mode 4 within 36 hours4.166667e-4 days <br />0.01 hours <br />5.952381e-5 weeks <br />1.3698e-5 months <br />.
Recent summer meteorological conditions have resulted in the TS UHS temperature limit being challenged. These conditions include elevated air temperatures, high humidity, and low wind speed. Meteorological conditions in the future may continue challenging the current TS limit in TS Figure 3.7.3-1. These changing metrological conditions prompted EGC to assess the current inputs for the current diurnal curve limits.
As described in Regulatory Guide 1.27, "Ultimate Heat Sink for Nuclear Power Plants,"
Revision 2, the predicted response of the UHS temperature to the design basis event is a function of the historical weather including the diurnal variations in air temperature. In its letter to EGC dated November 19, 2015, the NRC approved the diurnal temperature curve, LSCS TS Figure 3.7.3-1, for LSCS (Reference 2).
This license amendment is being requested to expand the already-approved TS temperature limit of the cooling water supplied to the plant from the UHS to vary with the diurnal cycle by changing the average sediment level limit in the intake flume and UHS to 6 inches. SR 3.7.3.2 will be modified to account for averaging the sedimentation level measurement. In addition to the proposed modification to SR 3.7.3.2, SR 3.7.3.3 would be deleted because the requirement to ensure adequate long term cooling can be maintained through verification of average sedimentation level as proposed in SR 3.7.3.2. SR 3.7.3.3 is redundant to SR 3.7.3.2. Since the UHS is not at a constant elevation, at its most shallow point, it is 685 ft in elevation and at its deepest point, it is 674 ft in elevation to allow for a gravity feed of the intake structure. Due to its shape, the verification of an absolute value for bottom elevation applies only to the portion of the UHS at its shallowest point or approximately a portion of the UHS surface area. The use of average sedimentation depth of no greater than 6 inches ensures that a sufficient UHS volume remains for use during a design basis accident.
TS 3.7.3 is being modified to address a discrepancy with the TS rules of usage. Specifically, Condition B of TS 3.7.3 is being deleted and the SR 3.7.3.1 Frequency is being revised to encapsulate performance of SR 3.7.3.1 (i.e., once per hour) that is directed by Condition B of TS 3.7.3. This is an administrative change that maintains the intent of conditions that require performance of the SR. With the proposed change, SR 3.7.3.1 will continue to be performed when CSCS pond supply temperature is~ 101°F in addition to the existing Frequency outlined in the Surveillance Frequency Control Program.
Page 2 of 16
ATTACHMENT 1 Evaluation of Proposed Changes This change is needed because, as required by LCO 3.0.2, Required Actions of the associated Conditions are only required to be met upon discovery of a failure to meet an LCO. LCO 3.7.3 requires the CSCS pond to be operable. The CSCS pond can be within the limits of Figure 3.7.3-1 at certain times with temperature.:::_ 101°F and remain operable. However, in this scenario LCO 3.0.2 would not require entry into Condition B because the CSCS pond remains operable. The proposed change ensures performance of SR 3.7.3.1 once per hour with CSCS pond temperature.:::_ 101°F.
The purpose of the UHS TS temperature limit is to restrict the initial UHS temperature such that the maximum UHS temperature experienced during the UHS design basis event (i.e., the temperature of the cooling water supplied to the plant safety systems from the UHS) would not exceed the design limit of 107°F. The proposed TS temperature limits will continue to vary with the diurnal cycle to limit the maximum temperature of the UHS supplied to plant safety systems to s; 107°F, and the sedimentation level limit will be adjusted from 18 inches to an average of 6 inches.
The proposed license amendment will continue to ensure the maximum temperature of the cooling water supplied to the plant during the UHS design basis event remains s; 107°F, which is LSCS current safety-related cooling water design temperature. Therefore, there is no impact of this change on LSCS safety analyses including the long term suppression pool temperature.
2.0 PROPOSED CHANGE
S The proposed changes to TS 3.7.3 are shown in Attachment 2 and are as follows:
TS SR 3.7.3.2 would be modified to include the new average sediment level of 6 inches.
s Ve *i -'" y av era ge s.e
- e t ev e 1 - s :S 1 _ a ft.Q.
Iii e a nd t e C.S S TS Figure 3.7.3-1 diurnal curve would be modified with new temperature limits.
Page 3 of 16 In ace rdan ce l-l i h t e S r v eill= ce r eque c.Y Co r 1 Pro g a
10650 106..00 10550 105..00
- J 104.50
- Qi.
E 104.00 10350 103..00 I
'1\\05.32)1
\\
\\
ATTACHMENT 1 Evaluation of Proposed Changes I
(106.00) (106.00)
Un accept:a b le v---
Operation I (l.05_76,}
I (104.79) v
/
(104.77)
Acceptable
/
(104.18)
Operation (106.00)
~
'\\ (105.32) 0:00 3:00 6:00 9:00 12:00 15:00 18:00 21.:00 24:00 Time of Day f igure 3.7.3-1(page1of1)
Temperature of Cooling Water Supplied to the Plant from the CSCS Pond Versus Time of Day Requirements TS SR 3.7.3.3 would be deleted because the requirement to ensure adequate long term cooling can be maintained through verification of average sedimentation level as proposed in TS SR 3.7.3.2.
TS 3.7.3 Condition A would be modified to remove reference to UHS bottom elevation limit.
e r*ab l e t
b:;it*tgi;:
il !il'C.ilt:i C!l:I
~Qt l!l it~i ~
.est e
SCS ar.d *. a DP :.... B E.stat s _
Lastly, Condition Bis being deleted from TS 3.7.3, and SR 3.7.3.1 is being modified to correct a discrepancy in the TS and allow proper application of TS 3.7.3.
Page 4 of 16
ATTACHMENT 1 Evaluation of Proposed Changes s
3_7_3 _
Ver-fy coo g wa*er - e era* re s e
3.0 BACKGROUND
a - f ro
- e CSCS o d s of F-g re 3_7 _3 __
Once oer hour when suool y fro m cscs oond
> 101° F AND ce e
an e Freq ency Co
- ro Progra m!
The UHS provides a heat sink for process and operating heat from safety related components during the UHS design basis event. The Residual Heat Removal Service Water (RHRSW) system and Diesel Generator Cooling Water (DGCW) system are the principal systems at LSCS that utilize the UHS to reject heat from safety related plant loads.
The UHS consists of an excavated pond integral with the cooling lake. The volume of the pond is sized to permit the safe shutdown and cooldown of both LSCS units for a 30-day period design basis event with no additional makeup water source. The UHS design basis event includes a failure of the LSCS cooling lake dike resulting in the UHS as the remaining source of cooling water to plant safety systems. The design basis event for the LSCS UHS is a loss of offsite power (LOOP) on both units resulting in all emergency diesel generators running, while one unit experiences an accident (i.e., a design basis accident (OBA) loss of coolant accident (LOCA)) while the other unit is shutdown normally. The function of the UHS is to provide cooling of the RHR heat exchangers, diesel generator coolers, Emergency Core Cooling System (ECCS) cubicle area cooling coils, RHR pump seal coolers, and Low Pressure Core Spray (LPCS) pump motor cooling coils. The UHS provides indirect heat rejection for the containment through the RHR heat exchangers. The current maximum safety-related cooling water design temperature at LSCS has been evaluated to be 107°F.
The UHS also provides a source of emergency makeup water for the spent fuel pools and can provide water for fire protection equipment. Loss of UHS inventory due to spent fuel pool makeup and fire protection usage is considered in the UHS analyses for both the temperature response and the inventory response.
Recent summer meteorological conditions have challenged TS UHS temperature limit in LSCS TS Figure 3.7.3-1 These conditions include elevated air temperatures, high humidity, and low wind speed. Weather conditions in the future may continue challenging this limit.
This license amendment is being requested to raise the TS temperature limit of the cooling water supplied to the plant from the UHS to continue varying with the diurnal cycle while accounting for an average sediment limit of 6 inches, instead of an 18-inch sedimentation level limit.
Page 5 of 16
ATTACHMENT 1 Evaluation of Proposed Changes
4.0 TECHNICAL ANALYSIS
The UHS follows a diurnal cycle where it warms up during the day and cools off at night.
Because of this diurnal cycle, its thermal response following an accident is dependent upon the temperature of the lake and the time of day when the postulated failure of the dike occurs. The results of the analysis for the worst-case historical weather effect on the temperature of cooling water supplied to the plant from lake/UHS indicate the peak temperature of cooling water from the lake occurs late in the afternoon (approximately 6 pm).
After approximately 6 pm in the evening, the lake follows the diurnal cycle and cools off until the next morning where it begins to heat up again. A parametric study evaluating key parameters that affect UHS performance was completed. The key parameters that affect UHS performance are the UHS sediment level, the time of day when the postulated failure of dike occurs, and the initial UHS temperature (i.e., temperature of the lake when the postulated failure of dike occurs). The results show that the most severe time for the dike to fail is early in the morning around approximately 6 am. This is the start time which results in the highest peak UHS temperature. The referenced analysis shows that the temperature of cooling water supplied to the plant from the UHS during accident conditions will not exceed 107°F, if the maximum initial temperature of the UHS is between 102°F and 104.75°F, depending on the time of day. These temperatures do not include instrument uncertainty. The limiting case is 18 inches of sedimentation.
UHS Volume The volume of the UHS used as part of design bases analyses was determined utilizing the 1997 Contours Hydrographic Survey, 97ES083.1, performed by Ocean Surveys, Inc.
The volume of the UHS was determined by using AUTOCAD and the calculated volume and surface area did not correct to account for accumulated sediment. The analysis determined that the surface area and volume of the UHS was 83.8 acres and 465.4 acre-feet, respectively.
In the UHS transient analysis, 1.35 acre-ft is subtracted from the UHS volume to account for fire-fighting measures. Additionally, due to the Y-shape of the UHS, a portion of the UHS is stagnant during accident conditions due to the flow patterns from where the water enters the UHS and travels back to the intake.
This results in an effective surface area and volume of 48.52 acres and 293.89 acre-feet, respectively, or 57.9% of total free surface area and 63.4% of total volume.
UHS Siltation Approved design analyses were completed to show that reduced siltation levels in the UHS support a higher UHS starting temperature. The limitations for siltation of the UHS are based on the average height of the silt and are correlated to the overall reduction of the effective UHS water volume. The table below shows the results of these evaluations Page 6 of 16
ATTACHMENT 1 Evaluation of Proposed Changes for the most severe time that results in the highest peak UHS temperature of approximately 6 am in the morning for the limiting case of 18 inches of sedimentation.
Siltation Depth Starting UHS Peak UHS Inlet Total Transient Heat Temperature at 6am Temperature Up O"
102.0°F 103.12°F 1.12°F 6
102.0°F 103.21 °F 1.21 °F 12" 102.0°F 105.33°F 3.33°F
- 18" 102.0°F 106.15°F 4.15°F
- Current TS 3.7.3.2 limit The three (3) most recent siltation surveillances were reviewed. These surveillances were completed in 2014, 2016, and 2018. They indicate that the average siltation depth is less than 6 inches and that changes since the baseline survey in 1997 have been insignificant.
While there are localized peaks and valleys within the UHS in excess of 6 inches, the average siltation depth remains unaffected. The top water elevation of 690 feet based on contour depths at the perimeter of the UHS has been verified to ensure adequate volume remains within the UHS following dike breach.
Safety Related Component Cooling Capabilitv For safety related systems, the applicable components are part of the CSCS cooling system and are as follows:
RHR heat exchangers Diesel generator jacket water coolers ECCS cubicle coolers LPCS motor coolers RHR pump seal coolers The above components have all been analyzed for a cooling water temperature of 107°F. The cooling capability of these components was determined with a maximum cooling water temperature of 107°F, maximum process fluid temperature, minimum cooling water flow rate, minimum process fluid flow rate, maximum tube plugging, and maximum design basis fouling factors.
Predicted Post Accident UHS Transient Heat Up Approved design analyses have determined that the current diurnal curve utilizing 18 inches of siltation is conservative because the actual average siltation levels of the UHS are less than 6 inches over the UHS area. This results in an increase in UHS effective volume of 24% which decreases temperature response due to the increased volume. The table below provides the total transient heat-up values associated with the 6-inch siltation levels at each given time of day. Figure 1 (below) is the adjusted diurnal curve utilizing the transient heat-up for the 6-inch siltation levels in combination with 0.75°F allowance for instrument uncertainty (i.e. Maximum peak cooling water temperature - Transient Heat-up Rate - Instrument Uncertainty - 0.25°F adjustment= Adjusted Initial UHS Temperature). This results in the maximum peak cooling Page 7 of 16
ATTACHMENT 1 Evaluation of Proposed Changes water temperature of 107°F under post-accident conditions. The current TS 3.7.3-1 curve is also displayed to show the increased margin obtained from the increase in UHS volume. A 0.25°F adjustment factor was used in generating the curve to ensure that the peak initial UHS temperature does not exceed 106°F which is the highest evaluated temperature for non-safety related systems which is further discussed in Other Considerations below.
Time Initial UHS Maximum Plant Total Transient Temperature Inlet Temperature Heat-Up 0:00 104.53°F 105.21°F 0.68°F 3:00 102.72°F 104.54°F 1.82°F 6:00 102.00°F 103.21°F 1.21°F 9:00 103.19°F 104.42°F 1.23°F 12:00 104.75°F 104.99°F 0.24°F 15:00 104.75°F 104.75°F 0.00°F 18:00 104.75°F 104.75°F 0.00°F 21:00 104.75°F 104.75°F 0.00°F The design analysis utilizes a 0.3 constant wind coefficient in the modeling of the transient heat up which is conservative. Wind sensitivities have shown that when the UHS water surface temperature exceeds 100°F, unstable atmospheric conditions will exist over the UHS, consequently the wind coefficients will remain less than 0.3 for all hours of the day which is shown to reduce the maximum UHS temperature by 1°F for 18-inch sediment levels. This results in additional analytical margin within the analysis that also ensures that the maximum peak cooling water temperature will not exceed 107°F.
Page 8 of 16
107 106 IL. 105 0,
GI (lj-B 104
~
(lj c_ c i!!l (ij 103 E
c:
(/)
- x:
10h 104 1°'1 1S:oo 18:00 103_/
Figure 1: New UHS Diurnal Temperature Curve compared to Current Diurnal Temperature Curve As shown, the 6-inch sedimentation temperature switch from 6 am to 3 am is driven by the larger temperature response between the two times where the temperature response rise is dependent on the limiting start time for a given sedimentation level (effective volume)_
Modeling Changes Affected The analytical modeling of the UHS is not affected by the change in siltation levels from 18 inches to 6 inches. This is because the 18 inches case provides the most limiting results for all cases and bounds all other cases and is therefore conservative. Effects on mixing, transit time, and worst weather analysis have been reviewed and are summarized below:
UHS Mixing - Sensitivity studies were performed on UHS mixing. The studies determined that the highest maximum UHS temperature occurs when no mixing zone is considered for the 18 inches of sedimentation case. Therefore, current modeling remains bounded and conservative.
Higher UHS Temperature - The worst weather evaluation for the initial lake temperature was set to 100°F and does not influence the results of the analysis.
Page 9 of 16
ATTACHMENT 1 Evaluation of Proposed Changes Therefore, the use of a higher UHS initial temperature would not affect the worst weather evaluation.
Transit Time - Shorter transit times were considered to not miss a short span of bad weather whereas the change from 18 inches to 6 inches will increase the transit time.
The screenings also considered higher initial temperatures and concluded essentially the same worst average periods. The 18-inch sedimentation case (approximately 33-hour transit time) was considered the most limiting case. The Ryan wind function will dominate at higher lake temperatures.
Temperature Response - Heat sources contributing to the cooling pond, higher initial water surface temperatures will result in a decrease in net incident radiation (based on the same weather input data) and an increase in net rate of heat loss. This results in a reduced initial temperature response rise due to the heat loss. Using a lower initial temperature response rise of a lower initial temperature with the higher initial temperature is conservative.
Evaporative Losses The UHS must be designed to provide cooling water to maintain the two units in a safe shutdown condition for a 30-day period. In addition to the temperature limit discussed above, evaporative losses must be considered in the design of the UHS; the volume of water must be verified to be adequate for 30 days following the accident to provide adequate NPSH to the required pumps.
With the increase in the UHS starting temperature, the change in evaporative losses is small.
The safety related cooling water pumps and fire protection pumps have been evaluated for a water temperature of 107°F and the reduced UHS volume. Furthermore, the available NPSH for the CSCS and FP pumps has been verified to be adequate with evaporative losses as high as 5 ft and 2.3 ft, respectively, with a cooling water temperature of 107°F.
Other Considerations The non-safety related fuel pool cooling heat exchangers have been evaluated for a cooling water temperature of 106°F. With the cooling water temperatures at 106°F, the fuel pool cooling heat exchangers are able to maintain the fuel pool temperature below the maximum normal (batch offload) design basis limit of 140°F. Other non-safety related heat exchangers cool plant equipment that is directly related to power production. These heat exchangers have also been qualified for a cooling water temperature of 106°F. Non-safety related heat exchangers cannot be credited to mitigate any design basis events due to the lack of safety related power and safety related cooling water. Therefore, qualification beyond 106°F is not necessary.
Additionally, controls are in place to monitor for fish kill. Procedure EN-LA-402-0005 directs operations to monitor the lake screen house trash basket twice per hour for indications of a fish kill. If a fish kill is observed, appropriate notifications are made and actions to remove the dead fish are initiated.
Page 10of16
ATTACHMENT 1 Evaluation of Proposed Changes
5.0 REGULATORY ANALYSIS
5.1 Applicable Regulatory Requirements/Criteria The design of the UHS satisfies the requirements of 10 CFR 50.36, "Technical Specifications,"
paragraph (c)(2)(ii), Criterion 3. This criterion states the following:
(ii) A Technical Specification Limiting Condition for Operation (TS LCO) of a nuclear reactor must be established for each item meeting one or more of the following criteria:
Criterion 3. A structure, system, or component that is part of the primary success path and which functions or actuates to mitigate a design basis accident or transient that either assumes the failure of or presents a challenge to the integrity of a fission product barrier.
The proposed change does not remove or relocate the CSCS pond temperature limits from TS 3.7.3, "Ultimate Heat Sink;" therefore, Criterion 3 of 10 CFR 50.36(c)(2)(ii) continues to be met.
General Design Criteria 2, "Design bases for protection against natural phenomena," and General Design Criteria 44, "Cooling water," of Appendix A to 10 CFR Part 50, "General Design Criteria for Nuclear Power Plants," provides design considerations for the UHS. Regulatory Guide (RG) 1.27, "Ultimate Heat Sink for Nuclear Power Plants," Revision 2, dated January 1976, provides an acceptable approach for satisfying these criteria. The basis provided in RG 1.27, Revision 2, was employed for the temperature analysis of the LSCS UHS.
General Design Criteria 5, "Sharing of structures, systems and components," of Appendix A to 10 CFR Part 50 also provides design criteria applicable to the UHS, a shared system between LSCS Units 1 and 2. The proposed change was evaluated consistent with the existing methodology which considers a DBA event (i.e., a LOCA with LOOP) along with the safe non-accident shutdown and cooldown of the opposite unit. Therefore, GDC 5 criteria continue to be met by raising the TS temperature limit of the cooling water supplied to the plant from the UHS to continue varying with the diurnal cycle while accounting for an average sediment limit of 6 inches.
The proposed changes continue to ensure the maximum temperature of the cooling water supplied to the plant during the UHS design basis event remains :s: 107°F, LSCS current safety-related cooling water design temperature. Therefore, there is no impact of this change on LSCS safety analyses.
5.2 No Significant Hazards Consideration In accordance with 10 CFR 50.90, "Application for amendment of license or construction permit," Exelon Generation Company, LLC (EGC) is requesting a change to the Technical Specifications (TS) of Renewed Facility Operating License Nos. NPF-11 and NPF-18 for LaSalle County Station (LSCS), Units 1 and 2.
The Ultimate Heat Sink (UHS) for LSCS, Units 1 and 2 provides a heat sink for process and operating heat from safety related components during the UHS design basis event. The Page 11 of 16
ATTACHMENT 1 Evaluation of Proposed Changes Residual Heat Removal Service Water (RHRSW) system and Diesel Generator Cooling Water (DGCW) system utilize the UHS to reject heat from safety related plant loads. The UHS consists of an excavated pond integral with the cooling lake. The volume of the pond is sized to permit the safe shutdown and cooldown of both LSCS units for a 30 day period design basis event with no additional makeup water source. The current maximum safety-related cooling water design temperature at LSCS has been evaluated to be 107°F.
The proposed changes modify the acceptance criteria in TS Surveillance Requirement (SR) 3.7.3.1 and SR 3.7.3.2. The proposed TS SR 3.7.3.1 will contain a diurnal curve with new temperature limits in TS Figure 3.7.3-1 to verify the cooling water temperature supplied to the plant from the UHS. The current TS SR 3.7.3.2 verifies sediment level less than or equal to 1.5 feet in the intake flume and the CSCS pond. The proposed TS SR 3.7.3.2 will account for averaging the sedimentation level measurement in the intake flume and the CSCS pond. The current TS SR 3.7.3.3 verifies CSCS pond bottom elevation is less than or equal to 686.5 feet.
The proposed change would delete TS SR 3.7.3.3 because the requirement to ensure adequate long term cooling can be maintained through verification of average sedimentation level as proposed in TS SR 3.7.3.2.The use of average sedimentation depth of no greater than 6 inches ensures that a sufficient UHS volume remains for use during a design basis accident.
Additionally, TS 3.7.3 is being modified to address a discrepancy with the TS rules of usage.
Condition B of TS 3.7.3 is being deleted and the SR 3.7.3.1 Frequency is being revised to encapsulate performance of SR 3.7.3.1 (i.e., once per hour) that is directed by Condition B of TS 3.7.3. This is an administrative change that maintains the intent of conditions that require performance of the SR. The proposed change ensures performance of SR 3.7.3.1 once per hour with CSCS pond temperature~ 101 ° F.
The analysis performed to support the proposed license amendment demonstrate that the maximum temperature of the cooling water supplied to the plant during the UHS design basis event remains:::; 107°F, which is LSCS, Units 1 and 2 current safety-related cooling water design temperature.
According to 10 CFR 50.92, "Issuance of amendment," paragraph (c), a proposed amendment to an operating license involves no significant hazards consideration if operation of the facility in accordance with the proposed amendment would not:
(1)
Involve a significant increase in the probability or consequences of an accident previously evaluated; or (2)
Create the possibility of a new or different kind of accident from any accident previously evaluated; or (3)
Involve a significant reduction in a margin of safety.
In support of this determination, an evaluation of each of the three criteria set forth in 10 CFR 50.92 is provided below:
- 1.
Does the proposed change involve a significant increase in the probability or consequences of an accident previously evaluated?
Response: No.
Page 12of16
ATTACHMENT 1 Evaluation of Proposed Changes The proposed change makes no physical changes to the plant, nor does it alter any of the assumptions or conditions upon which the UHS is designed. These assumptions and conditions include failure of the cooling lake dike, a loss of offsite power, and a OBA loss of coolant accident (LOCA) on one unit and a normal shutdown of the other unit.
Analyzed accidents are assumed to be initiated by the failure of plant structures, systems, or components. An inoperable UHS is not considered as an initiator of any analyzed events. The increased allowable temperatures can impact the commercial capability of the units; however, this is not considered to impact the probability of any of the Updated Final Safety Analysis Report (UFSAR) postulated events. As such, there is not a significant increase in the probability of a previously evaluated accident. The proposed change will ensure the maximum temperature of the cooling water supplied to the plant during the UHS design basis event remains s 107°F, the current safety-related cooling water design temperature for LSCS, Units 1 and 2.
Therefore, there is no impact of this change on LaSalle safety analyses including the consequences of postulated events. The effects of the proposed change on the ability of the UHS to assure that a 30-day supply of water is available considering losses due to evaporation, seepage, and firefighting has been considered. Sufficient inventory remains available to permit simultaneous safe shutdown and cooldown of both LSCS reactor units and to maintain them in a safe shutdown condition for the required 30-day period.
Therefore, the proposed activity does not involve a significant increase in the probability or consequences of an accident previously evaluated.
- 2.
Does the proposed change create the possibility of a new or different kind of accident from any accident previously evaluated?
Response: No.
This TS amendment request does not propose any changes to the operation, testing, or maintenance of any safety-related, or otherwise important to safety system beyond operating with a UHS initial temperature limit based on the time of day. The UHS temperature does not initiate accident precursors. The impact of increased UHS temperature can affect the commercial operation of the plant, but the change would not create any accident not considered in the LSCS UFSAR.
All systems that are important to safety will continue to be operated and maintained within their design bases. The proposed change will continue to ensure that all associated systems and components are operated reliably within their design capabilities.
The proposed change will ensure the maximum temperature of the cooling water supplied to the plant during the UHS design basis event remains ::5 107°F, the current safety-related cooling water design temperature for LSCS, Units 1 and 2. Therefore, Page 13of16
ATTACHMENT 1 Evaluation of Proposed Changes there is no impact of this change on the LSCS safety analyses including inventory requirements for safety-related systems using the UHS as their cooling water supply.
Because all systems will continue to be operated within their design capabilities, no new failure modes are introduced, nor is the possibility of a new or different kind of accident created through operation in the proposed manner.
- 3.
Does the proposed change involve a significant reduction in a margin of safety?
Response: No.
The proposed change will ensure the maximum temperature of the cooling water supplied to the plant during the UHS design basis event remains :5 107°F, the current safety-related cooling water design temperature for LSCS, Units 1 and 2. The proposed change also ensures that sufficient UHS inventory remains available for the worst 30-day period including losses due to evaporation, seepage, and firefighting to support safe shutdown and cooldown of both LSCS units.
Therefore, there is no impact of this change on LaSalle safety analyses, which ensures that there is no significant reduction in the margin of safety of the plant.
Therefore, the proposed change does not involve a significant reduction in a margin of safety.
Based on the above evaluation, EGC concludes that the proposed change does not involve a significant hazards consideration under the standards set forth in 1 O CFR 50.92(c), "Issuance of Amendment," and, accordingly, a finding of no significant hazards consideration is justified.
5.3 Conclusions In conclusion, based on the considerations discussed above, (1) there is reasonable assurance that the health and safety of the public will not be endangered by operation in the proposed manner, (2) such activities will be conducted in compliance with the Commission's regulations, and (3) the issuance of the amendment will not be inimical to the common defense and security or to the health and safety of the public.
6.0 ENVIRONMENTAL EVALUATION EGC has evaluated this proposed operating license amendment consistent with the criteria for identification of licensing and regulatory actions requiring environmental assessment in accordance with 10 CFR 51.21, "Criteria for and identification of licensing and regulatory actions requiring environmental assessments." EGC has determined that this proposed change meets the criteria for a categorical exclusion set forth in paragraph (c)(9) of 10 CFR 51.22, "Criterion for categorical exclusion; identification of licensing and regulatory actions eligible for categorical exclusion or otherwise not requiring environmental review," and as such, has determined that no irreversible consequences exist in accordance with paragraph (b) of 10 CFR 50.92, "Issuance of amendment." This determination is based on the fact that this change is being proposed as Page 14of16
ATTACHMENT 1 Evaluation of Proposed Changes an amendment to the license issued pursuant to 10 CFR 50, "Domestic Licensing of Production and Utilization Facilities," which changes a requirement with respect to installation or use of a facility component located within the restricted area, as defined in 10 CFR 20, "Standards for Protection Against Radiation," or which changes an inspection or a surveillance requirement, and the amendment meets the following specific criteria:
(i)
The amendment involves no significant hazards consideration.
As demonstrated in Section 5.2, "No Significant Hazards Consideration," the proposed change does not involve any significant hazards consideration.
(ii)
There is no significant change in the types or significant increase in the amounts of any effluent that may be released offsite.
The proposed change does not result in an increase in power level, does not increase the production nor alter the flow path or method of disposal of radioactive waste or byproducts. The proposed change will ensure the maximum temperature of the cooling water supplied to the plant during the UHS design basis event remains:::; 107°F, LSCS current safety-related cooling water design temperature. Therefore, there is no impact of this change on LSCS safety analyses including the consequences of such events.
Based on the above evaluation, the proposed change will not result in a significant change in the types or significant increase in the amounts of any effluent released offsite.
(iii)
There is no significant increase in individual or cumulative occupational radiation exposure.
There is no net increase in individual or cumulative occupational radiation exposure due to the proposed change. The proposed action will not change the level of controls or methodology used for processing of radioactive effluents or handling of solid radioactive waste, nor will the proposed action result in any change in the normal radiation levels within the plant.
Based on the above information, there will be no increase in individual or cumulative occupational radiation exposure resulting from this change.
Page 15of16
7.0 REFERENCES
ATTACHMENT 1 Evaluation of Proposed Changes
- 1. Engineering Change 632116, Rev 000, "Evaluation of UHS Initial Temperature for Support of License Amendment request for TS 3.7.3"
- 2. Letter from NRC to B. Hanson dated November 19, 2015, "LaSalle County Station, Units 1 and 2, Issuance of Amendment Revising the Ultimate Heat Sink Temperature Limit (CAC Nos. ME9076 and ME9077)" (ML15202A578)
Page 16of16
ATTACHMENT 2 LASALLE COUNTY STATION UNITS 1 and 2 Docket Nos. 50-373 and 50-374 License Nos. NPF-11 and NPF-18 Markup of Proposed Technical Specifications Page Changes REVISED TS PAGE 3.7.3-1 3.7.3-2 3.7.3-3
- 3. 7 PLANT SYSTEMS
- 3. 7. 3 Ultimate Heat Sink (UHS)
LCO
- 3. 7.3 APPLICABILITY :
ACTIONS The Core Standby Cooling System (CSCS) pond sha l l be OPERABLE.
MODES 1, 2, and 3.
- 3. 7.3 CONDITION REQUIRED ACTION COMPLETION TIME A.
cs cs pond inoperable A. 1 Restore cs cs pond to 90 days due to sediment OPERABLE status.
deposition er l:letteFR elevatieA A8t 1.. 1i Ui i A
.+-4-m+-t.
- g.
Goel~ n<:i 1.1ater tl.l Perform SR 3.7.3.1.
Once per hoblr teFF113erat1:Jre 51:lf3f3l i eEI te Uie f3laAt freFR the G~G~ f3 8 A El
- .
- un oP:.
f ll. Required Action and f ll. l Be in MODE 3.
12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> associated Comp l et i on Time of Condition A AND not met.
f._B_. 2 Be in MODE 4.
36 hours4.166667e-4 days <br />0.01 hours <br />5.952381e-5 weeks <br />1.3698e-5 months <br /> OR cs cs pond inoperable for reasons other than Condition A.
LaSalle 1 and 2 3.7.3-1 Amendment No.
SURVEILLANCE REQUIREMENTS SR
- 3. 7. 3. 1 SR
- 3. 7.3. 2
~R J.7.J.J SURVEILLANCE Verify cooling water temperature supplied to the plant from the CSCS pond is with in the limits of Figure 3.7.3-1.
Verify average sediment level is~ 1.9 ftQ inches in the intake flume and the CSCS pond.
Verify c~c~ ~OAd bottom elevatioA is
< 686.9 ft.
- 3. 7.3 FREQUENCY Once per hour when supply from CSCS pond
> 101 °F In accordance with the Survei llan ce Frequen cy Contro l Program In accordance with the Survei l lance Frequency Contro l Program IA accordaAce
- .:i th the
~t:ArveillaAce
~reqbleAcy CoAtrol Pro§ram LaSalle 1 and 2 3.7.3-2 Amendment No.
106.50 106.00 105.50
- t. 105.00
~
- i,
~ 104.50 u
Q.
E 1\\05.32)
\\
\\
u I-104.00 103.50 103.00 0:00 LaSa ll e 1 and 2 I
I Unaccep able Operation
/ I (104.79) I
/
(104.77)
/ (104.la}
(106.00) (106.00) v---
(105.76)
Acceptable Operation (106.00)
~
UH S 3. 7. 3
{105.32) 6:00 9:00 12:00 15:00 18:00 21:00 24:00 Tim e of Day Figure 3.7.3-1 (page1of1)
Temperat11re of Cooling Water Supplied to the Pla nt from the CSCS Pond Versus Time of Day Requirem ents 3. 7.3-3 Amendment No.
ATTACHMENT 3 LASALLE COUNTY STATION UNITS 1 and 2 Docket Nos. 50-373 and 50-37 4 License Nos. NPF-11 and NPF-18 Markup of Proposed Technical Specifications Bases Page Changes - For Information Only REVISED TS BASES PAGES B 3.7.3-2 B 3.7.3-3 B 3.7.3-4 B 3.7.3-5
UHS B 3. 7.3 B 3.7 PLANT SYSTEMS B 3.7. 3 Ultimate Heat Sink (UHS)
BASES BACKGROUND APPLICABLE SA FETY ANALYSES LaSalle 1 and 2 The UHS (i.e., the Core Standby Cooling System CCSCS) Pond) consists of the volume of water remaining in the cooling lake following the failure of the main dike.
This water has a depth of approximately 5 feet and a top water elevation establ i shed at 690 feet.
The volume of the remaining water in the cooling lake i s sufficient to permit a safe shutdown and cool down of the station for 30 days with no water makeup for both accident and normal conditions (Regu latory Guide 1. 27, Ref. 1).
The CSCS Pond provides a source of water to the serv ice water tunnel from which the Residual Heat Removal Serv i ce Water CRHRSW) and Diesel Generator Cooling Water (DGCW) pumps take suct i on.
Th e service water tunnel i s filled from the CSCS Pond by si x inlet lines which connect to the circulat ing water pump forebays.
Prior to enter ing the service water tunnel inlet pipes, the water is strained by the Lake Screen House traveling screens to prevent large pieces of debris from entering the system and blocking flow or damaging equipment.
Howe ver, because t he traveling screens are not safety related, a 54-i nch bypass line around the screens, isolated by a normall y closed manual va lve, i s provided to assure a continuous supply of CSCS Pond water to the service water tunnel.
Additional information on the design and operat ion of the CSCS Pond i s provided in UFSAR, Sect i ons 9.2.1 and 9.2.6 (Refs. 2 and 3).
The excavation slopes of the CSCS Pond and flume are designed to be stable under all condit i ons of emergency operation while providing the capabi lity to supp ly adequate cool ing water to equipment required for safe reactor shutdown.
The vo lume of the CSCS pond is sized to permit the sa fe shutdown and coo ldown of the units for a 30 day period with no additiona l makeup water source available for both normal and accident conditions (Ref. 2).
(cont inued)
B 3.7.3 -1 Revision 29
BASES APPLICABLE SAFETY ANALYSES (continued)
LCO APPLICABILITY LaSalle 1 and 2 62 UHS B 3.7.3 The UHS post-accident temperature is based on heat removal calculations (Ref. 5) that analyze for a maximum allowable post-accident inlet cooling water temperature of 107 ° F.
To account for the worst-case scenario and to apply conservatism, the maximum initial CSCS pond cooling water temperature is reduced by 0. 75°F to account for instrument uncertainty (Ref. 6) and a minimum additional margin of 0.4-2-.2...5.°F, to ensure the cooling water temperature supplied to the plant from the CSCS pond remains~ 107 °F at all times.
There are four temperature measuring devices located in the Circulating Water inlet thermowells (i. e., two per unit).
The 0. 75°F allowance bounds the instrument uncertainty associated with any combination of operable temperature measurement devices.
The UHS satisfies Criterion 3 of 10 CFR 50.36(c)(2)(ii ).
OPERABILITY of the UHS is based on a maximum water temperature being supplied to the plant within the Acceptable Operation region defined by Figure 3. 7.3-1 and a minimum pond water level at or above elevation 690 ft mean sea level.
In addition, to ensure the volume of water available in the CSCS pond is sufficient to maintain adequate long term cooling, average sediment deposition (in the intake flume and in the pond) must be~ 1.9 ft 6 i nches aAd
(~(~ ~OAd bottom elevatiOA m~st be < §Q§.9 ft. ~
In MODES 1, 2, and 3, the UHS is required to be OPERABLE to support OPERABILITY of the equipment serviced by the UHS, and is required to be OPERABLE in these MODES.
In MODES 4 and 5, the OPERABILITY requirements of the UHS are determined by the systems it supports.
Therefore, the requirements are not the same for all facets of operation in MODES 4 and 5.
The LCOs of the systems supported by the UHS will govern UHS OPERABILITY requirements in MODES 4 and
- 5.
(continued)
B 3. 7.3-2 Revision
BASES (continued)
ACTIONS LaSalle 1 and 2 62 UH S B 3. 7.3 If the CSCS pond is inoperable, due to average sediment deposition> 1.5 ft 6 inches (in the intake flume, CSCS pond, or both) or the pond 8ottom elevation > 8@8.5 ft, action must be taken to restore the inoperable UHS to an OPERABLE status within 90 days.
The 90 day Completion Time is reasonable based on the low probability of an accident occurring during that time, historical data corroborating the low probability of continued degradation (i.e., further excessive sediment deposition or pond 8ottom elevation changes ) of the CSCS pond during that time, and the time required to complete the Required Action.
',.'ith 'n'ater temperatl:lre of the Ulol?: §reater than 1Ql°F, ReEJl:li red Action g.1 is provided to monitor the '.:ater temperat1:Jre of the Ulol?: and verify the temperat1:Jre is 11ithin the limits of Fi§l:lre 3.7.3 1 more freEJl:lently.
The once per hol:lr Completion Time takes into consideration l:JH?:
temperat~re variations and the increased monitorin§ freEjl:lency needed to ensl:lre the desi9n basis temperat1:Jre limit of 1Q7°F is not exceeded in this condition.
If the 11ater temperatl:lre of the UH?: exceeds the limits of Fi§l:lre 3.7.3 1, Condition C ml:lst 8e entered immediately.
.C.B.l and.C.B.2 If the CSCS pond cannot be restored to OPERABLE status wit hin the associated Completion Time, or the CSCS pond i s determined inoperable for reasons other than Condition A (e.g., inoperable due to the temperature of the cooling water supplied to the plant from the CSCS pond in the Unacceptable Operation region defined by Figure 3.7.3 -1 ),
the unit must be placed in a MODE i n which the LCO does not apply.
To achieve this status, the unit must be placed in at least MODE 3 within 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> and i n MODE 4 within 36 hours4.166667e-4 days <br />0.01 hours <br />5.952381e-5 weeks <br />1.3698e-5 months <br />.
The allowed Completion Times are reasonable, based on operating exper ien ce, to reach the required unit conditions from full power conditions in an orderly manner and without chal l enging unit systems.
(cont inued)
B 3. 7.3-3 Revision
BASES (continued)
SURVEILLANCE REQUIREMENTS LaSalle 1 and 2 62 SR
- 3. 7.3. l UHS B 3.7.3 Verification of the temperature of the water supplied to the plant from the CSCS pond ensures that the heat removal capabilities of the RHRSW System and DGCW System are within the assumptions of the DBA analysis.
To ensure that the maximum post-accident temperature of water supplied to the plant is not exceeded (i.e., 107°F evaluated in Ref. 4), the temperature during normal plant operation must be within the limits described by Figure 3. 7. 3-1 (Ref. 3).
This is to account for the CSCS pond design requirement that it provide adequate cooling water supply to the plant (i.e.,
temperature~ 107°F) for 30 days without makeup, while taking into account solar heat loads and plant decay heat during the worst historical weather conditions.
In addition, since the lake temperature follows a diurnal cycle (it heats up during the day and cools off at night),
the allowable initial UHS temperature varies with the time of day.
The allowable initial UHS temperatures, based on the actual sediment level and the time of day have been determined by analysis (Ref. 5).
The limiting initial UHS temperatures determined in this analysis ensure the maximum post-accident temperature of 107°F is not exceeded.
These temperatures are analytical limits that do not include instrument uncertainty or additional margin.
These limiting initial temperatures remain bounded by the SR 3.7.3. l limits described by Figure 3. 7.3-1.
The Surveillance Frequency is controlled under the Surveillance Frequency Control Program.
With water temperature of the UHS greater than or equal to 101°F SR 3. 7.3. 1 is performed once oer hour to monitor the water temperature of the UHS and verify the temperature is within the limits of Figure 3.7.3-1 more frequently.
The once per hour Frequency takes into consideration UHS temperature variations and the increased monitoring frequency needed to ensure the design basis temperature limit of 107°F is not exceeded.
(continued)
B 3. 7.3-4 Revision
BASES SURVEILLANCE REQUIREMENTS (continued )
REFERENCES LaSalle 1 and 2 62 SR 3. 7.3. 2 UH S B 3. 7.3 Thi s SR ensures adequate long term (30 days) cooling can be maintained, by verifying the avera ge sed iment l evel in the intake flume and the CSCS pond is~----+/---..--§- 6 inches feet. ~
Sediment level is determined by a series of so unding cross-sect ion s compa red to as-built soun ding s.
The Surveil lan ce Frequen cy is controlled under the Surveil lan ce Frequen cy Control Program.
SR 3.7.3.3 This SR eAs~res adeq~ate lOA§ term (30 days) cooliA§ caA be maiAtaiAed, by verifyiA§ the CSCS poAd bottom elevatioA is
< §8§.§ feet.
The s~rveillaAce Freq~eACY is COAtrolled
~Ader the s~rveillaAce Freq~eAcy CoAtrol Pro§ram.
- 1.
Regulatory Guide 1. 27, Revision 2, January 1976.
- 2.
UFSAR, Sect i on 9. 2.1.
- 3.
UFSA R, Sect i on 9.2.6.
4.
EC 388666, Rev. 0, "Re vi se Design Analyses f or UHS Temperature of 107° F."
- 5.
L-002457, Rev. 8, "LaSalle County Station Ultimate Heat Sink Analysis."
Q6_,_. __ ter..--L-003230, Rev. lb, "CW Inlet Temperature Uncerta inty Analysis."
fr.7. EC 632116 "Eva l uat i on Of UHS Initia l Tempera t ure for Support of License Amendment Request TS 3. 7.3" B 3. 7.3-5 Revision