ML20199H361

From kanterella
Jump to navigation Jump to search
Proposed Tech Specs Table 4.1-2 Re Local Power Range Monitor (LPRM) Signal Calibr
ML20199H361
Person / Time
Site: FitzPatrick 
Issue date: 01/15/1999
From:
POWER AUTHORITY OF THE STATE OF NEW YORK (NEW YORK
To:
Shared Package
ML20199H342 List:
References
NUDOCS 9901250187
Download: ML20199H361 (11)


Text

.._ _ - -.

r

. to JPN-99-002 PROPOSED TECHNICAL SPECIFICATION PAGES LPRM CAllBRATION (JPTS-99-001) l i

l I

l New York Power Authority JAMES A. FITZPATRICK NUCLEAR POWER PLANT Docket No. 50-333 DPR-59 l

9901250187 990115 i

PDR ADOCK 05000333 P

PDR._

JAFNPP 4.1 BAMS (cont'd)

The individual sensor response time may be B. The MFLPD is checked once per day to determine measured by simulating a step change of the if the APRM scram requires adjustment.

Only a particular parameter.

This method provides a small number of control rods are moved daily conservative value for the sensor response and thus the MFLPD is not expected to change time, and confirms that the instrument has significantly and thus a daily check of the retained its specified electromechanical MFLPD is adequate.

characteristics.

When sensor response time is measured independently, it is necessary to also LPRM gain settings are determined from the measure the remaining portion of the response local flux profiles measured by the Traversing time in the logic train up to the time at which Incore Probe (TIP) System.

This establishes the scram pilot valve solenoids de-energize.

the relative local flux profile for The channel response time must include all appropriate representative input to the APRM component delays in the response chain to the System.

The 1000 MWD /T frequency is based on ATTS output relay plus the design allowance for operating experience with LPRM sensitivity RPS logic system response time.

A response

changes, time for the RPS logic relays in excess of the design allowance is acceptable provided the overall response time does not exceed the response time limits specified in the UFSAR.

The basis for excluding the neutron detectors from response time testing is provided by NRC Regulatory Guide 1.118, Revision 2, section C.S.

The sensors for the Reactor High Pressure and Reactor Water Level - Low (L3) trip functions are exempted from response time testing based on analyses provided in NEDO-32291-A, " System Analyses for the Elimination of Selected Response Time Testing".

Two instrument channels in Table 4.1-1 have not been included in Table 4.1-2.

These are: mode switch in shutdown and manual scram.

All of the devices or sensors associated with these scram functions are simple on-off switches and, hence, calibration during operation is not applicable.

Amendment No. ' 1, 99, 131, I S 3, 227, 233, 235, 38 m

m..

r m-

JAFNPP TABLE 4.1-2 REACTOR PROTECTION SYSTEM (SCRAM) INSTRUMENT CALIBRATION MINIMUM CAllBRATION FREQUENCIES FOR REACTOR PROTECTION INSTRUMENT CHANNELS Instrument Channel Group (1)

Calibration Frecuency (2) lRM High Flux C

Comparison to APRM on W

Controlled Shutdowns APRM High Flux Output Signal B

Heat Balance D

Flow Bias Signal B

Internal Power and Flow Test R

with Standard Pressure Source LPRM Signal B

Every 1000 MWD /T average core exposure l

Higa Reactor Pressure B

Standard Pressure Source (Note 6)

High Drywell Pressure B

Standard Pressure Source (Note 6)

Reactor Low Water Level B

Standard Pressure Source (Note 6)

High Water Levelin Scram A

Water Column (Note 5)

R (Note 5)

Discharge instrument Volume High Water Levelin Scram B

Standard Pressure Source Q

Discharge instrument Volume Main Steam Line Isolation A

(Note 4)

(Note 4)

Vcive Closure Turbine First Stage Pressure B

Standard Pressure Source (Note 6)

Permissive Amendment No. 42,13, S2,75, SP,15,193,207,233, 46

Attschm::nt li to JPN-99-002 SAFETY EVALUATION.

4 LPRM CAllBRATION (JPTS-99-001) l New York Power Authority l.

JAMES A. FITZPATRICK NUCLEAR POWER PLANT Docket No. 50-333 DPR-59

Attechment ll to JPN-99-002 SAFETY EVALUATION LPRM CAllBRATION 1.

DESCRIPTION This section provides a description of the proposed changes to the Technical Specifications (TS). Minor changes in format, such as type font, margins or hyphenation, are not described in this submittal. The proposed TS changes remove the Local Power Range Munitor (LPRM) signal calibration methodology from TS Table 4.1-2. Inclusion of this calibration method in the TS is not required because it does not meet any of the criteria for retention in the TS in accordance with 10 CFR 50.36(c)(2)(ii), in addition, the units for LPRM signal calibration Frequency on TS Table 4.1-2 and the TS Bases regarding LPRM calibration are changed. The above noted changes adopt the applicable provisions of the Standard Technical Specifications (STS) (Reference 1). The specific changes are as follows:

1.

TS Bases, Section 4.1.B, Page 38 Replace:

"The sensitivity of LPRM detectors decreases with exposure to neutron flux 1

at a slow and approximately constant rate. This is compensated for in the APRM system by calibrating twice a week using heat balance data and by calibrating individual LPRM's every 1000 effective full power hours, using i

TIP traverse data."

l l

With:

"LPRM gain settings are determined from the local flux profiles measured by the Traversing incore Probe (TIP) System. This establishes the relative local flux profile for appropriate representative input to the APRM system. The 1000 MWD /T Frequency is based on operating experience with LPRM sensitivity changes."

l l

1 l

2.

Line item 4, Table 4.1-2, Page 46 a.

Delete:

"TIP System Traverse" b.

Replace:

i "Every 1000 effective full power hours" With:

"Every 1000 MWD /T average core exposure" 1

4 Page 1 of 4

- - -. - - - =

PURPOSE OF THE PROPOSED CHANGE The Authority has chosen to adopt the applicable provisions of the STS to clarify LPRM calibration requirements.

l l

Ill.

SAFETY IMPLICATIONS OF THE PROPOSED CHANGE l

This change proposes to delete the listed requirements on TS table 4.1-2 for the method of ca!ibration of the LPRM's. Table 4.1-2 identifies the type of test equipment used to perform channel calibration. These details are not necessary because the definition of Instrument Channel Calibration provides the necessary guidance. This change is consistent with STS.

l The proposed change to the Table 4.1-2 LPRM signal calibration frequency units is from "every 1000 effective full power hours" to "every 1000 Megawatt Days per Ton (MWD /T) average core exposure". Both Frequencies consider the LPRM sensitivity changes based on operating history, and represent roughly the same time interval (i.e., for Cycle 14,1000 effective full power hours is approximately 985 MWD /T). The units change allows a more convenient tracking parameter since MWD /T is commonly calculated and recorded by the core monitoring system.

Therefore, this change is consistent with STS.

The change to the Bases does not affect normal plant operation and testing and is consistent with the current licensing basis regarding LPRM signal calibration. This change only replaces Custom TS wording with STS wording. The proposed TS Bases change states that LPRM gain settings are determined from the local flux profiles measured by the Traversing Incore Probe (TIP) System. In conjunction with 3D-Monicore power distribution models, the TIP System data can be from direct readings, symmetrical readings, or calculated data.

i IV.

EVALUATION OF SIGNIFICANT HAZARDS CONSIDERATION Operation of the FitzPatrick plant in accordance with the proposed amendment would not involve a significant hazards consideration as defined in 10 CFR 50.92, since it would not:

1.

involve a significant increase in the probability or consequences of an accident previously evaluated.

This change proposes to remove the listed requirement for the method of calibration of the LPRM Signal from TS Table 4.1-2 because the definition for Instrument Channel Calibration provides the necessary guidance.

Other changes to the bases and adopting signal calibration frequency units of MWD /T vice effective full power hours is consistent with STS.

The proposed changes do not increase the probability of an accident because i

the proposed surveillance requirements still ensure that the LPRM signal is adequately calibrated. The proposed change provides assurance that the Page 2 of 4

Attechmsnt 11 to JPN 99-OO2 SAFETY EVALUATION LPRM CALIBRATION associated Reactor Protection System (RPS) functions are tested consistent with the analysis assumptions. As a result, the consequences of an accident

{

are not affected by this change. This change will not alter assumptions relative to the mitigation of an accident or transient event. Therefore, this change will not involve a significant increase in the probability or j

consequences of an accident previously evaluated.

2.

create the possibility of a new or different kind of accident from any accident previously evaluated.

The proposed changes will not physically alter the plant. As such, no new or different types of equipment will be installed. The methods governing normal plant operation and testing are consistent with current safety analysis assumptions. Therefore, this change will not create the possibility of a new or different kind of accident from any accident previously evaluated.

j 3.

involve a significant reduction in a margin of safety.

The proposed change removes specific calibration method information in Table 4.1-2 regarding the LPRM signal which is adequately addressed in the definition for Instrument Channel Calibration.

Other changes to the Bases and adopting a signal calibration Frequency units I

of MWD /T vice effective full power hours is consistent with STS.

l The proposed changes still provide the necessary control of testing to ensure operability of the RPS instrumentation. The safety analysis assumptions will still be maintained, thus no question of safety exists. Therefore, this change does not involve a significant reduction in a margin of safety.

V.

IMPLEMENTATION OF THE PROPOSED CHANGE This amendment request meets the eligibility criteria for categorical exclusion set forth in 10 CFR 51.22(c)(9) as follows:

(i)

The amendment involves no significant hazards consideration.

As described in Section IV of this evaluation, the proposed change involves no significant hazards consideration.

l l

i Page 3 of 4

i Attachmsnt ll to JPN-99-OO2 SAFETY EVALUATION LPRM CAllBRATION (ii)

There is no significant change in the types or significant increase in the amounts of any effluents that may be released offsite.

i l

The proposed change does not involve the installation of any new l

equipment, or the modification of any equipment that may affect the types or amounts of effluents that may be released offsite. Therefore, l

there is no significant change in the types or si0nificcat increase in l

the amounts of any effluents that may be released offsite.

(iii)

There is no significant increase in individual or cumulative Occupational radiation exposure.

l The proposed changes do not involve plant physical changes, or introduce any new mode of plant operation. Therefore, there is no significant increase in individual or cumulative occupational radiation exposure.

Based on the above, the Authority concludes that the proposed changes meet the criteria specified in 10 CFR 51.22 for a categorical exclusion from the requirements of 10 CFR 51.21 relative to requiring a specific environmental assessment by the Commission.

VI.

CONCLUSION The proposed changes will not alter assumptions relative to the mitigation of an i

accident or transient event, and will not adversely affect normal plant operation and i

testing. The proposed changes are consistent with the current safety analysis assumptions and with STS. As such, no question of safety exists.

l The Plant Operating Review Committee (PORC) and Safety Review Committee (SRC) have reviewed this proposed change to the TS and have concluded that it does not involve an unreviewed safety question or a significant hazards consideration and will not endanger the health and safety of the public.

Vll.

REFERENCES 1.

NUREG-1433, " Standard Technical Specifications," General Electric Plants, BWR/4, Revision 1, dated April 1995 Page 4 of 4

Attcchment til to JPN-99-002 MARKED-UP TECHNICAL SPECIFICATION PAGES TRAVERSING INCORE PROBE SYSTEM (JPTS-99-OO1) t l

New York Power Authority JAMES A. FITZPATRICK NUCLEAR POWER PLANT Docket No. 50-333 DPR-59 i

i i

l

. -.. _.. - -... - - - - -. - - - - - -.. - - - - -.. -.. -. -. ~

.-.. -.~ - -

l 4

\\

~

i t

4.1 RASES Icone'dl l

The indmdual eeneer reopense ebne may be -=ed IMr

8. The 8MLpD is cenar*=d ance per day to deoermano M sha I

annedoeng e step shenge of the poesiadan parerneter. TN.

ApgIM steem sagdres e4usessena. Ordy e anneE senesiher of

{

sneehed pretedse e conserweglwe watus for the senser centeel rede ese snowed de5y and this to 88170 le not reopense tisses, and confinne that she homesunnent hee

=W se change i 7 A and sluse a dety ceneck et l

seteined its spoeslead electreenschereest chorectesteence.

= g POisedesgeses, p

1 n --.se ao einesered is spos.desa. a ie r

necessary se stem semeeuse the reensismus persion of the The sensitivity of Lyme doenceere dessesses esteen engeouse response siens in agno legio main esp to eBas times et asheces the to sumussen Bust at e 30eer and oppseedesseely senstant rage.

I screen ytes volve solenoids doenesgles. The charmel TWe le W for ise lhe ApWR4 opetens by eshrating response si must incende es sempeneet essere in me

==.c= a week using heet benense dose and by cashressie roepense cheim se she ATTS auspus reley peue the design inevidual LystaA's owesy 1000 asseceive sig pauper hours.

eseussees per flPS lesic eyotest reopense esses. A respesos using TF troveres does.

i eene ter she nra sagic reseye in escene se she demon g

esewanceis =. n provided she sessed eesponse time g.

does nos sossed she roepense eisne lindes specined in she 1

UF5AR. The hesie Ier seedueng she neutron detectosa fresa r

/

eesponse time seedne is provided by 88ftC Reedstory odde 1.I s a, nedelen 2, seenlan c.s.

LPWI geln settfags are detunteed from the local flux 1

t I(

profiles esasured by the Traverslag lacere Probe (TIP) m m tw seie Meaner 65gh rm and neoctor systes. This establishes the relottwe 1ecal flus profile 1

mw Leest. Leer R.3 istp funcdone are onesepted Grassi for appropriate representative impet to the ArSt Systee.

I roepense einee seesing bosed on aseelvees provided in 8500-th sees l

32291-A, "syneese Anotyssa for she Eliminaden of Selected o/

.n.penas o ne Tes* <.

Two instrunnent channeke in Totte 4.1 1 Dieve not been' inchefed &n Tetfe 4.1-2. These are: snede swin:h in shuHleuwn and seenuel screars. AN es the devices or sensers essecleted evish these acteme functione are senple on-off eevisches end. hence, celsbration spuring opersesen is not opphcende.

~

Asnandmene 90s. 44. "". ? 31, '"122?. ??2.

  • 38 i

4 we-2 l~

i th i

e ll i

G h;

i....

.. d111 !

I i j

!ll0'l

.i!lllj!111lI d

111 1

l 1

1 illih Illi l i l l

I

(

l o

i l

11I!jl L

Illi i

i 13

!i>1>11111 lij l

11

i 1 tim e 3

!