ML20197G943

From kanterella
Jump to navigation Jump to search
Monthly Operating Rept for May 1984
ML20197G943
Person / Time
Site: Nine Mile Point 
Issue date: 05/31/1984
From: Lempges T, Roman T
NIAGARA MOHAWK POWER CORP.
To:
NRC OFFICE OF ADMINISTRATION (ADM), NRC OFFICE OF INSPECTION & ENFORCEMENT (IE)
References
NUDOCS 8406180217
Download: ML20197G943 (16)


Text

'.

OPERATING DATA REPORT 50-220 DOCKET NO.

DATL June b, 1984 COMPLETED BY Thomas W. Rom n TELEPHONE l3i6)JW-2422 OPERATING STATUS Nine Mile Point Unit #1 Notes

1. Unit Name:
2. Reporting Period:

5/1/84 thru 5/31/84

3. Licensed Thermal Power (MWt):

1850 640

4. Nameplate Rating (Gross MWe):
5. Design Electrical Rating (Net MWe):

630 620

6. Maximum Dependable Capacity (Gross MWe):

610

7. Maximum Dependable Capacity (Net MWe):
8. If Changes Occur in Capacity Ratings (Items Number 3 Through 7) Since Last Report. Give Reasons:
9. Power Level To Which Restricted,if Any (Net MWe):
10. Reasons For Restrictions,if Any:

This Month Yr..to.Date Cumulatise

11. Hours In Reporting Period 744 3288.5 127.079.2
12. Number Of Hours Reactor Was Critical 0

1828.5 88,130.2

13. Reactor Reserve Shutdown Hours 0

0 1204.2

14. Hours Generator On.Line 0

1828.5 85313.8

15. Unit Reserve Shutdown Hours 0

0 20.4

16. Gross Thermal Energy Generated (MWil) 0 3.062.522.0 141.156.962.0
17. Gross Electrical Energy Generated (MWH) 0 1,034,284.0 46,666.065.0
18. Net Electrical Energy Generated (MWHy 0

1,001,923.0 45,196,682.0

19. Unit Service Factor 0

41.6 66.2

20. Unit Availability Factor 0

~41.6

-66.2

21. Unit Capacity Factor (Using MDC Net) 0 37.4 57.5
22. Unit Capacity Factor (Using DER Net) 0 36.8_

56.5

23. Unit Forced Outage Rate 0

0.0 17.1

24. Shutdowns Scheduled Over Next 6 Months (Type. Date.and Duration of Each):

Unit shutdown for biennial refuel and overhaul. Shutdown 3/16/84 scheduled for startup 6/10/84.

25. If Shut Down At End Of Report Period. Estimated Date of Startup:
26. Units In Test Status (Prior to Commercial Operation):

Forecast AchieSed INITIAL CRITICALITY INITIAL ELECTRICITY COMMERCIAL OPERATION (9/771 I

8406180217 840531 PDR ADOCK 05000220 R

PDR 1

~

1 AVER AGE D AtLY UNITPOWER LEVEL DOCKET NO. 50-220 9 Mile Pt. Unit #1 UNIT 6/5/84 DATE CO\\1PLETED fly Thomas W. Roman TELEPIIONE (315) 349-2422 ay 1984-AlONTH DAY AVER AGE DAILY POWER LEVEL.

DAY AVERACE DAILY POWER LEVEL (31We-Net)

(MWe Net) 17 0

2 0

0 IS 3

-0 19 0

4 0

20 0

s 0

21 0

'O 6

22 0

0 7

0 23 8

0 24 0

0 9

25 0

10 0

26

'O II O

27 0

12 0

2S 0

13 0

29 0

14 0

30 0

15

'0 0

31 0

16 t

INSTRUCTIONS l

On this for:nat.hst the aserage daily unit piswer lesel in MWe.Nei riit #d'j' d3F I" the 'cPunF in >nili. C.iiiiputs ti the nearest whole megaws t.

er (9/77) i

s 50-220 UNITSHUTDOWNS AND POWER REDUCTIONS DOCKET NO.

UNIT NAME 9 Mlle Pt. Unit #1 DATE 6/5/84 May 1984 COMPLETED 8Y Thomas W. Roman REPORT MONT11 TELEPHONE (315) 349-2422 "i

g '1, Cause & Corrective

=

e.

3

.E _e E

gsX Licensee gg a

c

$3 Action to N"-

l'* ' c C::

35 5

_E s E Event u '?

$E E

j5g Report ar

<50

]U Prevent Recurrence 6

i 84-6 840317 S

C 1

Unit shutdown for Biennial Refuel and overhaul.

t I

2 3

4 F: Forced Reason:

Method:

Exhibit G - Instructions S: Ssheduleil A Equipment Failure (Explain) 1 Manual for Preparation of Data B Maintenance of Test 2-Manual Scram.

Entry Sheets foi Licensee C Refueling 3 Automatic Scram.

Event Report (LER) File (NIJREG-D-Regulatory Restriction 4 Other (Explain) 0161)

E-Operator Training & License Examination F-Administrative 5

G-Operational Error (Explain t Exhibit i Same Source 08/77)

Il4)ther (Explain)

NIAGARA M0 HAWK POWER CORPORATION NINE MILE POINT NUCLEAR STATION UNIT #1 NARRATIVE OF OPERATING EXPERIENCE MAY 1984 The station has been shutdown since March 17th for scheduled refueling and overhaul. During the month of May the station experienced a series of cold shutdown scrams.

On 5/9/64 a spurious trip of IRM 11 and 16.

On 5/13/84 During power board switching a loss of power to RPS MG Sets.

On 5/21/84 High Pressure Scram during vessel hydrostatic testing.

On 5/24/84 A loss of scram header air pressure during a containment spray air test resulted in a scram dump instrument volume High Level Trip.

The station is scheduled to return to service in e6rly June 1984.

m m

.-. -m-

CLASS I WORK - MECHANICAL MAINTENANCE - MAY 1984 WR #26138 CRD #71635, Rebuilt CRD WR #25129 05-03 Emer. Cond. Vent Valve, repacked and adjusted WR #25335 CRD 46-31, uncoupled drive WR #25334 CRD 46-23, uncoupled drive WR #25329 CRD 22-35, uncoupled drive WR #24450 CRD 38-15, uncoupled drive WR #25321 CRD 38-19, uncoupled drive WR #23315 EC Valve #05-01, replaced packing and lap WR #25337 CRD 06-23, uncoupled drive WR #25322 CRD 38-27, uncoupled drive-WR #25332 CRD 30-31, uncoupled drive WR #25331 CRD 30-27, uncoupled drive WR #25327 CR0 30-19, uncoupled drive WR'#25333 CRD 22-31, uncoupled drive WR #25326 CRD 22-19, uncoupled drive WR #25324 CRD 14-27, uncoupled drive WR #25330 CRD.22-23, uncoupled drive WR #25325 CRD 14-19, uncoupled drive WR #25336 CRD 06-31, uncoupled drive WR #25972 CRD 34-31, uncoupled drive WR #25323 CR0 38-25, uncoupled drive WR #25328 CRD 30-35, uncoupled drive WR #24449 CRD 14-15, uncoupled drive WR #25973 CRD 42-31, uncoupled drive WR #25975 CRD 22-03, uncoupled drive WR #23445

  1. 14 Rx Recirc Pump-removed and replaced mechanical seal WR #26135 CRD #71634, Rebuilt Drive WR #26137 CRD #71719, Rebuilt Drive WR #26473 CRD(106)26-27 Charging Water Valve installed stem, seat ring, and packing WR #264.76 CRD(106)22-31 Charging Water Valve installed stem, seat ring, and packing WR #26427 CRD(106)26-19 Charging Water Valve installed stem, seat ring, and packing WR #26428 CRD(106)18-23 Charging Water Valve installed stem, seat ring, and packing WR #26031 CR0 #71640 Rebuilt Drive WR #26486 CRD(106)26-35 Charging Water Valve installed stem, seat ring, and packing WR #26505 CRD 10-31 replaced uncoupling pin WR #26033 CRD #71563 Rebuilt Drive WR #23460 Control Rod Drives-Leak Rate Tested listed CRD's

CLASS I WORK - MECHANICAL MAINTENANCE - MAY 1984 Cont'd WR #26139 CRD #7054 Rebuilt Drive WR #26140 CRD #71682 Rebuilt Drive WR #23442

  1. 12 CRD Pump-Rebuilt pump WR #26136 CRD #71678 Rebuilt Drive WR #24613 N2 Purge & Fill Valve #20112-33. Disassembled, repaired, repacked, reassembled WR #26032 CRD #71627 Rebuilt Drive WR #24736
  1. 13 Rx Recirc Pump-removed and replaced mechanical seal WR #26134 CRD #71457 Rebuilt Drive WR #26548 CRD 107 Valve) 38 replaced washer WR #26501 CRD Accum BV 111 Valve 14-23) - repaired seat and packing WR #26487 CRD 106 Valve 34-19, Replaced ball and set screw WR #26471 CRD 106 Valve 10-35 Replaced set screw WR #26426 CRD 106 Valve 18-03, Replaced ball and packing WR #26683 CRD 106 Valve 22-31, Replaced ball and packing WR #26483 CRD 106 Valve 38-35, Replaced ball and packing WR #26425 CRD 106 Valve 42-31, Adjusted nut on stem WR #26685 CRD 106 Valve 18-23, Adjusted handle WR #26508 CRD 106 Valve 42-39, Replaced ball, packing and set screw WR #26472 CRD 106 Valve 14-43, Adjusted nut on stem WR #26682 CRD 106 Valve 26-27, Adjusted nut on stem, replaced ball WR #26681 CRD 106 Valve 26-35, Adjusted nut, reassembled WR #26684 CR0 106 Valve 26-19, Replaced ball and reassembled WR #26430 CRD 106 Valve 06-35, Replaced ball, spring WR #26475 CRD 106 Valve 02-27, Replaced shaft, ball, spring WR #26433 CRD 106 Valve 02-35, Replaced shaft, ball, spring WR #26423 CRD 106 Valve 46-27 Replaced ball, spring WR #26421 CR0 106 Valve 34-51, Replaced ball, spring WR #26432 CRD 106 Valve 18-51. Replaced ball, spring WR #26431 CRD 106 Valve 06-39, Replaced ball, spring WR #26429 CRD 106 Valve 14-15, Replaced ball, spring WR #26424 CRD 106 Valve 26-51, Replaced ball, spring WR #26299 Liquid Poison Valve 42.1-03, replaced center section WR #26343 CR Door #41 repaired latch WR #26045 CR0 #71560 Rebuilt Drive WR #26595 Hanger Clamp-39-HS, Installed stud and nuts, tightened WR #26592 Hanger Clamp-39-H12, Installed stud and nuts, tightened WR #26463 Spring loaded Clamps-39-H29-Installed stud and nuts, tightened WR #26452 Spring loaded Clamps-39-H21-Installed stud and nuts, tightened WR #26046 CRD #71338 Rebuild Drive WR #26300 Liquid Poison Valve 42.1-02, replaced Chk Valve WR #23446
  1. 12 Rx Recirc Pump-removed and replaced mechanical seal WR #26549 CRD(107 Valve)46-35,replacedstemandrepacked

t D

CLASS I WORK - MECHANICAL MAINTENANCE - MAY 1984 Cont'd WR #26422 CRD 106 Valve 46-39, Changed ball, welded new body in place WR #26438 PSV 81-11 Core Spray 12 Loop Relief Valve, removed PSV 81-11 installed in #11 Core Spray Loop WR #26444 Weld #40-SW-498, took boat samples, ground crack and welded-WR #25751

  1. 01-06 warm up Valve #112, removed Valve, installed plug, reinstalled valve, welded limit switch.

WR #26479

  1. 12 FW Pump FCV, replaced upper and lower stem, seat rings, gasket WR #25602 MSIV #111-01-01, installed new stem, packing, gasket, lapped r

i WR #24586 CRD #71336 Rebuild Drive WR #26417

  1. 112 Core Spray Topping Pump, replaced nipple on pipe l

WR #26751

  1. 11 CRD Relief Valve, removed Valve and installed blank f

WR #26048 CRD #71578 Rebuild CRD WR #26556 Valve #93-52, repaired cap WR #26457

  1. 39-H-34, Spring absorber, tightened upper and lower jam nut WR #26462
  1. 39-H-23, Shock absorber, tightened loose bolt on clamp WR #26598
  1. 39-H-2, Spring support, tightened loose bolt WR #26456
  1. 39-H-31, Shock absorber, tightened loose bolt WR #26458
  1. 39-H-34, Shock absorber, tightened loose bolt WR #26599
  1. 39-H-22, Shock absorber, tightened loose bolt WR #26455
  1. 39-H-37, spring support, tightened upper & lower clevis nut WR #21209 50-15 Cond. Demin., removed cover, replaced gasket, put cover in place WR #24588 Replaced 01-05 and 01-06 Drain Valves 706, 708, 709, 711, WR #25758 MSIV 01-04, disassembled, lapped and reassembled WR #26748 CRD Water Filter #12, replaced with clean filters WR #26026 DW Post LOCA Flow-Valve 201.1-09, disassembled, cleaned and reassembled WR #26245 Rx Bldg Air Lock, replaced rubber seals on both doors WR #26542 Core Spray Valve 81-11 removed, reset, replaced WR #24458 CRD 42-23, removed CRD 71453, replaced with 71592 WR #24459 CRD 42-27, removed CRD 71361, replaced with 71379 WR #26742 CRD 50-23, Foot Valve replaced worn gaskets WR #26744 CRD 38-31, Foot Valve replaced worn gaskets WR #26752 CRD 18-27, Foot Valve, replaced worn gaskets WR #26745 CRD 22-19, Foot Valve, replaced worn gaskets WR #26743 CRD 38-39, Foot Valve, replaced worn gasket 3

CLASS I WORK - HECHANICAL MAINTENANCE - MAY 1984 Cont'd WR #21222

  1. 12 Cond. Demin 50-12, Inspected WR #26787 CRD 22-51 HCU, replaced packing and 0 rings WR #26785 CRD 38-47 HCU, replaced packing and 0 rings WR #26789 CRD 18-03 HCU, replaced packing and 0 rings WR #26784 CRD 46-27 HCU, replaced packing and 0 rings WR #26563 CRD 50-23 HCU, replaced packing, 0 rings and gasket WR #26456
  1. 39-SC-3 restraint, torqued bolts WR #26596
  1. 39-HS-1 Shock absorber, tightened clamp bolt WR #26451
  1. 39-HS-21 Shock absorber, tightened clamp bolt WR #25607 Torus MUIV, #58.1-01, repaired operator WR #21224 Cont. Vent Post LOCA BV, #201.2-538, installed new packing WR #26170 66-26-10" Vac. Bkr.-polished shaft, replaced 2 bushings, new gaskets WR #21223 Cont. Equip Hatch-Installed new 0 rings, closed hatch WR #26812 Cont Spray Raw Water BV #93-18, disassembled, cleaned, reassembled WR #26827
  1. 12 CRD Pump Bearing, inspection WR #26211 Main Stm (Sys. 66) 4" Vacuum Relief Valve, disassembled, checked internals, reassembled WR #26831 18-07 CRD Scram Outlet Valve (127), repacked, replaced seat, plug, plug guide WR #24975 CRD & Thermal Sleeve 50-19, removed and replaced CRD WR #26687 CRD #7156, leak rate tested WR #25992 Hydraulic Snubber 29-HS-16, overhauled, performed funct. test WR #26132 Hydraulic Snubber SI-HS-5, overhauled, performed funct. test WR #25991 Hydraulic Snubber 29-HS-9, overhauled, performed funct. test WR #25996 Hydraulic Snubber 38-HS-6, overhauled, performed funct. test WR #25998 Hydraulic Snubber 39-HS-2, overhauled, performed funct, test WR #25993 Hydraulic Snubber 30-HS-2, overhauled, performed funct, test WR #25999 Hydraulic Snubber 39-HS-17, overhauled, performed funct. test WR #26260 Hydraulic Snubber 39-HS-32, overhauled, performed funct, test WR #26258 Hydraulic Snubber 39-HS-25, overhauled, performed funct, test WR #26257 Hydraulic Snubber 39-HS-15, overhauled, performed funct. test WR #26253 Hydraulic Snubber 29-HS-13, overhauled, performed funct. test WR #26252 Hydraulic Snubber 29-HS-2, overhauled, performed funct. test WR #25399 CRD #7054. Removed drive, installed thermal sleeve, replaced drive WR #25712 CRD #71635, Removed drive, installed thermal sleeve, replaced drive v

CLASS I WORK - MECHANICAL MAINTENANCE - MAY 1984 Cont'd WR #26248 Hydraulic Snubber 40-HS-6, reset snubber to 2 3/4" WR #26249 Hydraulic Snubber 37-HS-1, reset snubber to 3 1/2" WR #26250 Hydraulic Snubber 36-HS-2, reset snubber to 3 1/16" WR #24976 CRD Housing 50-19, rolled drive housing WR #26000 Hydraulic Snubber 39-HS-28, overhauled, performed funct. Test WR #25398 CRD 71457, removed drive, installed thermal sleeve, replaced drive WR #26764

  1. 13 Recirc Pump, tightened union WR #25124 31-01 FW Check Valve, replaced check valve

-WR #21226 Emerg. personnel hatch (DW) replaced DW side hatch with new gasket WR #23448

  1. 12 Core Spray Ck Vlv 40-03, disassembled WR #24752
  1. 11 IA Comp, 94-34 BV, Disassembled, cleaned seat, installed new internals reassembled WR #24640
  1. 12 IAC BV 94-35, installed new valve WR #26025 DW Post LOCA Flow to Emerg. Vent, 201.1-11-Disassembled valve, cleaned WR #26958 Cont. Spray Nozzles Valve 40-09, replaced 2 new nozzles WR #26765 Retainer CRD 42-39 to IRM, installed and adjusted retainer clip WR #26768 40-12 IV, tightened body bonnet flange and took up on packing WR #25340 CRD #71634, removed drive and thermal sleeve and reinstalled CRD WR #26758 Core Spray Check VIV 81-CS-C-3, disassembled, checked internals, assembled valve WR #24460 CRD 30-33, drive uncoupled, replaced with rebuilt CRD WR #24452 CRD 14-39, drive uncoupled, replaced with rebuilt CRD WR #25922 CRD 22-39, drive uncoupled, replaced with rebuilt CRD WR #25921 CRD 42-35, drive uncoupled, replaced with rebuilt CRD WR #25923 CRD 22-47, drive uncoupled, replaced with rebuilt CRD WR #24456 CRD 18-51, drive uncoupled, replaced with rebuilt CRD WR #24453 CRD 14-35, drive uncoupled, replaced with rebuilt CRD WR #24454 CRD 34-15, drive uncoupled, replaced with rebuilt CRD WR #26528 CRD 06-39, drive uncoupled, replaced with rebuilt CRD WR #26129 CRD 22-23, drive uncoupled, replaced with rebuilt CRD WR #25971 CRD 10-31, drive uncoupled, replaced with rebuilt CRD WR #25397 CRD 34-07, drive uncoupled, replaced with rebuilt CRD WR #25339 CRD 30-07, drive uncoupled, replaced with rebuilt CRD WR #25394 CRD 14-11, drive uncoupled, replaced with rebuilt CRD WR #25400 CRD 42-39, drive uncoupled, replaced with rebuilt CDD WR #25396 CRD 46-27, drive uncoupled, replaced with rebuilt C M WR #25711 CRD 46-39, drive uncoupled, replaced with rebuilt CRD WR #23267 CRD 22-27, drive uncoupled, replaced with rebuilt CRD WR #26259 Hydraulic Snubber 39-HS-30, overhauled, performed funct, test WR #25994 Hydraulic Snubber 33-HS-1, overhauled, performed funct. test i

l

l l

CLASS I WORK - MECHANICAL MAINTENANCE - MAY 1984 Cont'd t

WR #23463 Hydraulic Snubber 01-HS-2, functional tested and rebuilt, retested i

WR #26131 Hydraulic Snubber 40-HS-9, functional tested and rebuilt, retested WR #26133 Hydraulic Snubber 66-HS-9, functional tested and rebuilt, retested WR #26254 Hydraulic Snubber 30-HS-5, functional tested and rebuilt, retested WR #26251.

Hydraulic Snubber 01-HS-4, functional tested and rebuilt, retested WR #26256 Hydraulic Snubber 39-HS-8, functional tested and rebuilt, retested WR #25995 Hydraulic Snubber 36-HS-5, functional tested and rebuilt, retested i

WR #26255 Hydraulic Snubber 38-HS-8, functional tested and rebuilt, retested WR #21419 DW Cooling Fans, #11, 13, 14, Set blade angle WR #23444

  1. 15 Rx Recirc Pump, removed, replaced mechanical seal WR #26029
  1. 63-05 Post Accid. Sample Return, tightened packing glands WR #26969 replaced Cont. Spray Nozzles WR #21591 42.1-R1 Liquid Poison, reinstalled U-bolt WR #23449 Shoot out steel, installed WR #23457 Rx 340' disassembled and reassembled

+

WR #26847 CRD Scram inlet 18-07, replaced valve seat WR #26849 CRD HCU 18-07 (106 viv), replaced ball, spring, repacked valve WR #26261 Mech. Snubber #7544, replaced, attached bracket WR #23465 Mech, Snubber 51-MS-1, removed, tested, replaced snubber WR #23464 Mech. Snubber 40-MS-12, removed, tested, replaced snubber WR #23466 Mech. Snubber 32-MS-28, removed, tested, replaced snubber WR #23467 Mech. Snubber 32-MS-16, removed, tested, replaced snubber WR #23468 Mech. Snubber 32-MS-10, removed, tested, replaced snubber WR #24977 CRD & Thermal Sleeve, 50-19, Installed thermal sleeve and CRD WR #25997 Hydraulic Snubber 38-HS-12, functional tested, overhauled, retested WR #23469 Sta. Mech Snubbers, performed visual inspection per memo WR #26506

  1. 12 CRD Pump, rebuilt pump WR #26027 63-04, Post Accid. Sample, Return IV, reinstalled new valve WR #24615 63-05, Post Accid. Sample, Return IV, changed air lines for testing WR #23447
  1. 11 Rx Recirc Pump, replaced mechanical seal.

WR #21432 121 Core Spray Topping Pump Seal, replaced impeller wear rings, cosing rings, mechanical seal i

WR #24911 122 Core Spray Topping Pump Seal, Completely rebuilt pump WR #26691

  1. 122 Core Spray Pump, replaced pump WR #27003 Cond. Torus Makeup 58.1-04, installed premanent packing l

WR #23461 Torus Manway - removed and installed torus manway covers WR #27001 Cond. Torus Makeup 58.1-07, Changed spectacle flange WR #24616 Spectacle Flange 81-100 changed to blanked off position r

re CLASS 1 WORK - MECHANICAL MAINTENANCE - MAY 1984 Cont'd WR #26992 Spectacle Flange 81-99, changed to blanked off position WR #22369

  1. 112 Electromatic Relief Valve 66NR1088, Replaced stem, spring & gaskets WR #25114
  1. 123 Electromatic Relief Valve 66NR108F, Replaced stem, spring & gaskets WR #22358
  1. 121 Electromatic Relief Valve 66NR1080, Replaced stem, spring & gaskets WR #22370
  1. 122 Electromatic Relief Valve 66NR108D, machined parts and lapped WR #26997

_94-23 Blank Flange, removed orifice, installed blank flange WR #26994

  1. 111 Core Spray Topping Pump, tightened packing WR #26993
  1. 81-49, Core Spray Topping Pump #112, tightened packing WR #26995
  1. 81-52, Core Spray Topping Pump #122, tightened packing WR #26979 M.S. Warmup Valve, 01-05, replaced 0 rings in seal bushing WR #26980 M.S. Warmup Valve, 01-06, replaced 0 rings in seal bushing WR #26842 CRD HCU 38-47, 107 valve, disassembled, cleaned, checked seats, installed packing, new plug WR #26841 CR0 HCU 22-31, 107 valve, disassembled, cleaned, checked seats, installed packing, new plug WR #26975 C.U. Relief Disch to Torus 63-04 & 05, inspected and adjusted WR #27036 CR0 #46-27 #111 Foot Valve, replaced stem, packing and 0 rings WR #27035 CRD #22-11 #111 Foot Valve, replaced stem, packing and 0 rings

f CLASS I WORK - ELECTRICAL MAINTENANCE - MAY 1984 WR #25965 Torus Vent & Purge IV 201-09, removed leads and rewired WR #25966 Torus Vent & Purge IV 201-07, removed leads and rewired, checked rotation, cycled valve WR #26319 Aux. Feeder 102, repaired ARC chute with RTV 108 WR #26624 PB 102 supply 416 UV Breaker R1012, burnished contacts and checked resistance WR #26629 Cont. Spray pump 121 4160V Breaker, burnished contacts and checked resistance WR #26628 Core Spray pump 111 4160V Breaker, burnished contacts 1, 1T, 2, 2T, 4 & 4T and checked resistance WR #26622 Cont. Spray pump 111 4160V Breaker, burnished contacts 1, IT, 2, 2T, 4 & 4T and checked resistance WR #26625 PB 102 Aux. Feeder 4160V Breaker R1021, burnished contacts 1, IT, 2, 2T, 4 & 4T, and checked resistance WR #26623 Diesel Gen. 102, 4160V AA Breaker R11022, burnished contacts 1, IT, 2, 2T, 4 & 4T, and checked resistance WR #26627 Cont. Spray pump 112, 4160V Breaker, burnished contacts 1, IT, 2, 2T, 4 & 4T, and checked resistance WR #26626 Cont. Spray RW Pump 111 4168 Breaker, burnished contacts and checked resistance WR #25968 Limit switch Pos 68-01 ILSO, adjusted limit switches and operated valve switches.

WR #25967

'norus/0W Vac. breaker 68-04, adjusted limit switches and cycled valves WR #26634 Core Spray Topping Pump 111, overhauled breaker by GE & MPM-C2 was performed.

WR #26635 Core Spray Sump 112, overhauled by GE & MPM-C2 was performed WR #26636 Core Spray Topping Pump 112, overhauled by GE & MPM-C2 was performed WR #26637 Cont. Spray Raw Water Pump 121, overhauled by GE & MPM-C2 was performed WR #25367 Limit switches on valve 05-05/Pos. 05-03 ILSO 5-03 ILSC, Adjusted limit switches, cycled valves WR #25868 Pos. Valve 05/02, Pos. 05-02 ILS0, 05-02 ILSC, Adjusted limit switches cycled valves WR #26639 Main Steam IV-01-01, disconnected stem coupling and readjusted actuator slate and stem coupling WR #26640 Main Steam IV-01-02, disconnected stem coupling and readjusted actuator slate and reconnected stem ccupling WR #20731 Limitorque valve actuator 39-07, removed spring cartridge cap cover, drilled and tapped cover, installed pipe plug, replaced cover WR #26555 Emergency Condenser valve auto open relay 12K62, replaced time relay coil WR #25211 CAD 02 & H2 sample IV 201.2, 109 & 111, wires have been removed, reconnected wires, installed new flex cond.

WR #26753 Core Spray Punp Motor 121, reconnected, retaped, meggered and checked rotation WR #26755 Core Spray Pump Motor 122, reconnected, retaped, meggered and checked rotation

CLASS I WORK - ELECTRICAL MAINTENANCE - MAY 1984 Cont'd WR #26603 DW Vent & Purge limitorque, drilled spring cap cover and installed Pipe plug WR #26604 Emergency Condenser IV Limitorque, drilled and taped spring cap cover to perform movats WR #26606 DW Vent & Purge, removed spring cap cover and installed pipe plug WR #26705 Limit switches on ' valve 68-02, adjusted switches and operated valves several times WR #26704 Limit switches on valve 68-03, adjusted switches and operated valve i

several times WR #26961 SDC IV38-13, removed motor from 38-13 for rewind WR #26902 SDC IV38-01, removed motor from 38-01 for rewind WR #26864 Limitorque actuator IV33-01, removed switches and replaced gaskets with issue attached WR #26971 RPS Transmitters in West Instr. Room, replaced condelet and sealed with i

Kaowool and Bisco Locaseal WR #26972 RPS Transmitters in East Instr. Room, replaced condelet and sealed with Kaowool and Bisco Locaseal l

M.0. 3390 Mark I Containment Low Low Set Point M.0. 3410 Appendix R - ADS Logic M.0. 3938 Feedwater Low Flow Control M.0. 3405 Appendix R - Remote Shutdown Panel

[

M.0. 3384 Feedwater High Level Trip i

M.0. 3411 Appendix R - Core Spray /Rx Head Vent M.0. 1927 Equipment Qualification l

M.0. 3171 Appendix J l

M.0. 2440 containment Vent System, Post LOCA i

M.0. 3406 Appendix R-Emergency Condenser Logic M.0. 2131 Rx Protection System - MG Sets

(

5

. CLASS I WORK -INSTRUMENT & CONTROL - MAY 1984 WR #26126 SRM #13 Reading High (found moisture in connector

- cleaned,-dried, and reconnected)

WR #26564

. Vacuur Breaker Limit Switches 68-02 Out of Adjustment

- Recalibrated per ICP-68-TVB E,-

se>en a nemes afIACES-tNITS NO AUXILIARIES MDNTil - MaV, YEAR 1984 i[aN'a^Nr uself AWA8LA8LE hours REAScess / REPA1RS aut Eensawany pay gas T hen Las AVA IL ASLF HOURS CAP.

1 Rx 3/17/84 0130 3/84-358.5 Plant shutdown for biennial refuel and overhaul.

4/84-719 5/84-744 I

I l

total 1821.5 i

l 4

f i

i.

i I

i l

l 1

l l

N M V NIAGARA RUMOHAWK NIAGARA MOHAWK POWER CORPORATION /300 ERIE BOULEVARD WEST, SYRACUSE. N.Y.13202/ TELEPHONE (315) 474-1511 June 8,1984 Director Office of Inspection and Enforcement U.S. Nuclear Regulatory Commission Washington, DC 20555 Attn:

Document and Control Desk Re: Docket No. 50-220 DPR-63

Dear Sir:

Submitted herewith is the Report of Operating Statistics and Shutdown for May 1984 for the Nine Mile Point Nuclear Station Unit $1.

Also included is a narrative report of Operating Experience for May 1984.

Very truly yours, T.

empges Vice President Nuclear Generation TEL/jkr Attachments cc: Director, Office of I&E (10 copies) 9 i i