t D CVNER'S DATA REPORT FOR INSERVICE INSPECTION EDWIN I. HATCH NUCLEAR PLANT UNIT 2 Q
]
JANUARY 1988 - MARCH 1988
]
O i
h!k SOOCK h6
- - 9
W O
TABLE OF CONTENTS PAGES I.
ASME NIS-1 FORM AND SUPPLEMENTARY INFORMATION 1-7 II. ABSTRACT 8-14 Y
III. EXAMINATION
SUMMARY
A.
CLASS 1 EXAMINATIONS 15-49~
B.
CLASS 2 EXAMINATIONS 50-60 C.
PRESSURE TESTING 61-63 D.
COMPONENT SUPPORTS 64-74 E.
REACTOR PRESSURE VESSEL INTERNALS75-104 F.
REPAIRS AND REPLACEENTS 105-106
]
l l
l 1 O if l
l
O.
~
NOTE: Portions of this report are. compiled from Southern Company Services issued report; "Nondestructive Examination Of Selected Class 1, 2, and 3 Components", for the Winter 1988 Refueling Outage at E.I.
Hatch Nuclear Plant, Unit 2.
This report will be available for review in the Records Management Department at the plant site.
N d
3
!O iii
LIST OF ABBREVIATIONS
-q ANI/AN!!
Authorized Nuclear Inspector / Authorized Nuclear Inservice I
kJ Inspector ASME American Society of Mechanical Engineers ASNT Americati Society for Nondestructive Testing BC Branch Connection BWR Boiling Water Reactor CH Closure Head CONT Containment CPI Containment Purge and Inerting System CRD Control Rod Drive Systen CS Core Spray System CU Cleanup C&L Cramer and Lindell Engineers DCR Design Change Request ET Eddy Current Examination EPRI Electric Power Research Institute FB Flange Bolting 9C Fuel Pool Cooling System FW Feedwater System
]
GE General Electric GPC Georgia Power Company HL Hanger Lug a
HPCI High Pressure Coolant Injection System INF Indication Notification Fom IGSCC Intergranular Stress Corrosion Cracking ISI Inservice Inspection ITL International Testing Laboratories LD Longitudinal Seam Weld Extending Downstream LD-I longitudinal Weld Downstream on Inside of Elbow LO-O Longitudinal Weld Downstream on Outside of Elbow LHT Lanbert, MacGill, and Thomas, Inc.
Lo Zero Reference location LU Longitudinal Seam Weld Extending Upstream LU-I Longitudinal Weld Upstream on Inside of Elbow LU-0 Longitudinal Weld Upstream on Outside of Elbow iv
MSIV lhin Steam Isolation Valve MS liain Steam System MSA fiain Steam Auxiliary System ITT fiagnetic Particle Examination ifWO Maintenance Work Order NDE Nondestructive Examination NI No Indication NRC Nuclear Regulatory Commission NRI No Recordable Indication OL Overlay PL Pipe Lug PLT Plant PR Pipe Restraint PROD Product
?
PS Pipe Support
~
PSW Plant Service Water System PT Liquid Penetrant Examination OC Quality Control (GPC)
RC Reactor Recirculation System RCIC Reactor Core Isolation Cooling System RHR Residual Heat Removal System RI Recordable Indication
)
RINTSA Recirculation Inlet Nozzle Themal Sleeve Attachment' Welds RL Refracted Longitudinal RL Restraint Lug RPV Reactor Pressure Vessel RX Reactor RWCU Reactor Water Cleanup System SBLC Standby Liquid Control System SCS Southern Company Services SER Service SRV Safety Relief Yalve SWRI Southwest Research Institute TDP Torus Drainage and Purification System TSB TurMne Steam Bypass System UT Ultrasonic Examination l
VLV Valve VT Visual Exanination This list is comprised of standard abbreviations used in Inservice Inspection Documentation.
All of these abbreviations may not appear in this report.
v
._..__J
TOTAL NUMBER OF SHEETS 105 FORii NIS-1 7
FORf1 NIS-1 OWNERS' DATA REPORT FOR INSERVICE INSPECTIONS As Required By the Provisions Of The ASME Code Rules 1
Owner Georgia Power Company, 333 Piedmont Ave., NE P.O. Box 4545 Atlanta j
Georgia 30302 i
2.
Plant Edwin I. Hatch Nuclear Plant, Route 1, Box 278, Baxley, Ga.
31513 3.
Plant Unit 2
4.
Owner Certificate of Authorization (if req.)
N/A 5
Commercial Service Date 09/05/79, 6.
National Board No. for Unit N/A_
j 7.
Components Inspected:
Component or Manufacturer State or 3
Appurtenance Manufacturer or Installer Province National or System or Installer Serial No.
Number Board No.
E=323E=32EEE 33=E=333EE=3 333E===E=333 EMEEEE=E E==3EEEEE Rx. Pressure Vessel Combustion Eng.
70101 N/A 11570 Rx. Pressure Vessel Combustion Eng.
70201 N/A 11570 2821 lbin Steam Pullman Power Prod.
N/A 2B21 Feedwater Pullman Power Prod.
N/A 2321 M.S. Relief Pullman Power Prod.
N/A 2B31 Rx. Recirc Pullman Power Prod.
N/A
)
2B31 Recire Pump Byron Jackson N/A 2C11 CRD Pullman Power Prod.
N/A 2041 SBLC Pullman Power Prod.
N/A 2E11 RHR Pullman Power Prod.
N/A 2E21 Core Spray Pullman Power Prod.
N/A 2E41 HPCI Pullman Power Prod.
N/A l
Note: Supplemental sheets in form of lists, sketches, or drawings may be used provided (1) size is 8 1/2 in. x 11 in., (2) infomation in items 1 through 6 on this data report is included on each sheet, and (3) each sheet is numbered and the number of sheets are recorded at the top of this forn. **
Spo'1 piece or fitting numbers too numerous to list for each specific o
system.
f taterial certifications for all piping, fittings, etc., are available for review in the Records Management Department at the plant site.
Exception taken to note 2 O
7 Components Inspected (continued):
FORM NIS-1 (Continued)
C5mponent or Manufacturer State or Appurtenance Manufacturer or Installer Province National or System or Installer S2 rial No.
Number Board No.
t
==
=======ummam
==
==
=
2G31 RWCU Pullman Power Prod.
N/A 2G41 FPC & CU Pullman Power Prod.
N/A 2 Nil M S Auxilia ry Pullman Power Prod.
N/A 2P41 Plt Serv Water Pullman Power Prod.
N/A
- Spool piece or fitting numbers too numerous to list for each specific system.
Material certifications for all piping, fittings, etc., are e"ailable for review in the Records Management Department at the plant h
2.
d a
1 l
l l
l (2)
P Q,
FORM NIS-1 (Back)
- 8. Examination Dates 01/04/88 to 03/23/88
/^)T
(_
- 9. Inspection Interval from 01/86 to 01/96,
- 10. Abstract of Examinations.
Include a list of examinations and a statement concerning status of work required for current interval.
- 11. Abstract of Conditions Noted.
- 12. Abstract of Corrective Heasures Recommended and Taken.
We certify that the statements made in this report are correct and the examinations and corrective measures taken conform to the rules of the ASME Code,Section XI.
Date
\\~ c.
19 hr Signed Georgia Power Company By7 <;~~)L, &
Owner Certificate of Authorization No. (if applicable) N/A Expiration Date 'N/A I
CERTIFICATE OF INSERVICE INSPECTION l
l l
l I, the undersigned, holding a valid commission issued by the National Board l l of Boiler and Pressure Vessel Inspectors and/or the State or Province of l
(~5 i
GA.
and employed by of Hartford, CT have inspected the l
'/
l components described in this Owners' Data Report during the period 01 /88 l
]
l to 03/88. and state that to the best of my knowledge and belief, the Owner l l has performed examinations and taken corrective measures described in this I
l Owners' Data Report in accordance with the requirements of the ASME Code, I
l Section XI.
I I
I I By signing this certificate neither the Inspector nor his employer makes anyl I warranty, expressed or implied, concerning the examinations and corrective i
I measures described in this Owners' Data Report.
Furthermore, neither the I Inspector nor his employer shall be liable in any manner for any personal I
I injury or property damage or a loss of any kind arising from or connected l
I with this inspection.
I I
I l Date Lv.
6, 19 68 l
2h Comissions Georgia 201 l& InspeCror" s 5f gna)6re National Board, 5*. ate, Province, 8 No. l 1
I The following NIS-1 Forn supplementary infonnation and report includes the responses to NIS questions #10, #11, and 412.
Hartford Steam Boiler Insurance and Inspection Company.
O
NIS-1 Form Supplementary Information Owner's Data Report for Inservice Inspection s
Date: June 1, 1988 Owner Name & Address:
Georgia Power Company 333 Piedmont Avenue, N.E.
P.O. Box 4545 Atlanta, Georgia 30302 Name & Address of Nuclear Generating Plant:
Edwin I. Hatch Nuclear Plant Route 1, Box 278 Baxley, Georgia 31513 Name Assigned to Nuclear Plant Station:
h-Edwin I. Hatch Nuclear Plant Unit 2 Commercial Service Date: September 5, 1979 Gross Generating Capability:
2436 MWt, 817.3 fiWe State, Province, or Municipality Assigned Number:
f.-
N/A
~
National Board Number Assigoed'by Manufacturer:
N/A Name of Component or Part of Component ISI Involved:
Representative samples of the following components and areas were examined 5
with nondestructive testing techniques.
Class 1 Reactor Pressure Vessel Standby Liquid Control System Reactor Pressure Vessel Closure Head High Pressure Coolant Injection Syst<
l'ain Steam Piping Systen Reactor Core : solation Cooling Syster Feedwater Piping System Residual Heat Removat System Control Rod Drive Systen Reactor Recirculation System Core Spray System O
aeector water c'eea"o siste=
Yalve Internal Surfaces Valve Bolting
Class 2 RHP. System Core Spray System f]
HPCI System Control Rod Drive System Reactor Water Cleanup System Main Steam Auxiliary Piping System Hydrostatic Testing Class 2 Residual Heat Removal System (ISI Hydros 2E11-HT-2, 2E11-HT-3, 2E11-HT-6, 2E11-HT-14, 2 Ell-HT-23, and a
2E11 -HT-24 )
9 Class 3 Plant Service-Water System (ISI Hydros 2P41-HT-13, 2P41-HT-28, and 2P41-HT-29)
System Pressure / Leakage Tests O
System Class Test Required-'
)
Reactor Pressure Vessel and 1
Leakage Associated Piping and Components
( 2B21-LT-1 )
Residual Heat Removal Service 3
Inservice Water System (2E11-IT-1) p' Pipe Support & Hanger Examination Class 1 Main Steam System High Pressure Coolant Injection System Reactor Recirculation System I
Class 2 Core Spray Systen High Pressure Coolant Injection System Residual Heat Removal System O
4 nein Steem,ux4nery Syste, C
Class 3 fiain, Steam Safety / Relief Yalve Discharge System RHR Service Water System
(
Plant Service Water System V.
Fuel Pool Cooling System Name & Address of Manufacturer of Components:
1 Reactor Pressure Vessel and Closure Head:
Combustion Engineering, Inc.
Chattanooga, TN 3.
Piping (Classes 1, 2, and 3)
- a. Pellman Power Products Division of Pullman-Kellogg Williamsport, PA i
- b. General Electric Company San Jose, CA Note:
Piping purchased by General Electric and Pullman and installed by Pullman.
Material certifications and manufacturer information are available for review in the Records Management Department at the Hatch Plant Site.
3.
Piping Supports and Hangers (Classes 1, 2, and 3)
(V~3
- a. Bergen-Paterson Pipe Support Corporation Laconia, NH
]
- b. ITT Grin'nell Corporation i
Providence, Rhode Island 1
- c. Pacific Scientific Anaheim, CA 4
Yalves, Pumps, and Heat Exchangers
- a. Byron-Jackson, Inc.
Los Angeles, CA
- b. Crane New York, NY
- c. Wm. Powell Company Cincinnati, OH
- d. General Electric San Jose, CA O
Y
- Date of Inservice Inspection:
January 1988 - March 1988-Completion Date of Inservice Inspection:
'()
March 23,1988
- Name of Inspector: Charles F. Toegel, Jr. ( AN!/ANII)
Name & Mailing Address of Inspector's, Employer:
The Hartford Steam Boiler Inspection and Insurance Company 1117 Perimeter Center West Suite E 301 Atlanta, Georgia 30338 4
6 1
- Small portion of pressure test 2E11-IT-1 was not completed until 05-03-88 due to required valve line up.
Majority of test was completed prior to 03-23-88 and is beng included in this report.
O 7
ABSTRACT An Inservice Inspection of selected Class 1, 2, and 3 components of Georgia Power Company's Edwin I. Hatch Nuclear Plant Unit 2 was performed during the Winter 1988 Maintenance / Refueling Outage.
The components were examined in accordance with the applicable outage plan, including any changes made during the ISI as approved by Georgia Power Company.
The nondestructive examinations were performed using VT, PT, HT, AND UT examination techniques.
SCS personnel and their contractors; SWRI and EBASCO
In addition, CTS assisted SCS personnel with YT examinations of selected RPV internal components.
SCS, SWRI, and EBASCO personnel performed Class 1, 2, and 3 examinations.
SCS and SWRI procedures were used to perform the NDE Examinations.
EBASCO y
personnel were qualified to the applicable SCS procedures prior to performance N
of examinations.
EPRI qualified inspectors were utilized for examinations involving IGSCC susceptible materials.
In addition to NDE testing of Class 1 and 2 welds and components, pressure testing, visual examination of Class 1 valve internal surfaces and visual examination of pipe supports and hangers were also performed.
GPC QC Personnel perfonned the Class 1 Valve Internal s Inspections and supplied copies of the examination reports to SCS for inclusion in the final report.
Third party review (e.g. an ANII) was utilized' for the ISI.
Selected components were examined in accordance with the following documents:
]
Section XI of the American Society of Mechanical Engineers (ASME) Boiler and Pressure Vessel Code, "Rules for Inservice Inspection of Nuclear Power Plant Cmponents," 1980 Edition with Addenda through Winter 1981 United States Nuclear Regulatory Commission, NUREG 0313, Revision 2,
(Dra f t), "Technical Report on Material Selection and Processing Guidelines for BWR Coolant Pressure Boundary Piping".
United States Nuclear Regulatory Connission, NUREG 0619, "BWR Feedwater Nozzle and Control Rod Drive Return Line Nozzle Cracking".
United States Nuclear Regulatory Connission IaE Bulletin 80-13 Visual Examination of Core Spray Spargers.
General Electric Company Service Information Letter-330, Jet Pump Beam Inspection.
General Electric Company Service Information letter-420, Inspection of det Punp Sensing Lines.
General Electric Company Service Information Letter-433, Shroud Head Bolting Inspection.
SCS "Second Ten-Year Examination Plan, Edwin I. Hatch Nuclear Plant, Unit 2", Pev. 1.
SCS "Inservice !nspection Outage Plan, Edwin I.
Hatch Nuclear Plant, Unit 21988 Winter Refueling Outage", Revision 1 and Deviation 001.
l
Representative samples of the following systems, conprised of selected Class 1,
2, and-3 components, were examined using various NDE techniques, in accordanct with the above documents:
Class 1 Q(>
Reactor Pressure Vessel (2811) fiain Steam System (2821)
Feedwater System (2821)
Reactor Recirculation System (2831)
Control Rod Drive System (2C11)
Standby Liquid Control System (2C41)
Residual Heat Removal Systen (1E11)
Core Spray System (2E21)
High Pressure Coolant Injection System (2E41)
Reactor Core Isolation Cooling System (2E51)
Reactor Water Cleanup System (2G31)
Valve Internals Valve Bolting Class 2 f
Residual Heat Removal System (2E11)
Core Spray System (2E21)
High Pressure Coolant Injection System (2E41)
Control Rod Drive System (2C11)
Reactor Water Cleanup System (2G31)
Hain Steam Auxiliary System Piping (2N11)
Main Steam Relief Yalve Discharge Piping (2B21)
Class 3 Service Water System (2E11) (2P41)
O eve' eoo' coo'$os siste- (2841)
Main Steam Safety / Relief Yalve Discharge System (2R21)
Other (Non-ASME Related)
UT thickness measurements were performed on selected components in the Extraction Steam, Auxiliary Vents and Drain, and Condensate Feedwater Piping Systems.
A portion c-these components were selected due to their similarity in design and operating conditions to components involved with the "Surry Pipe Break Incident".
A separate report for these examinations was prepared by SCS and was submitted to GPC engineering.
O 4
I CLASS 1 EXAMINATIONS RPV Shell Welds (SWRI Mechanized UT)
OV liechanized UT was utilized to examine four (4) circumferential welds and twelve (12) longitudinal welds.
A minimum of 5% of each circumferential weld and 10% of each longitudinal weld was examined.
These examination lengths neet the requirements of the ASME Section X: Cade,1974 Edition with Addenda through Summer 1975.
No reportable indications were detected.
RPY Examinations (UT)
Five (5) nozzle-to-shell welds and four (4) nozzle inner radius welds were examined using manual UT techniques.
No reportable indications were detected.
The RPV closure head-to-flange weld was examined due to indications detected during a previous outage.
There was no significant change in the indications and they were deemed acceptable, h
Nineteen (19) closure head studs and eighteer (18) vessel flange ligaments were examined.
No reportable indications were detected.
RPY Examinations (MT & YT)
Nineteen (19) closure head S ts were MT examined and the corresponding nineteen (19) washers were VT examined.
No reportable indications were detected.
RPV Internal Examinations (UT & VT)
All twenty (20) jet pump hold down beams were UT examined per GE SIL-330 Jet pump beam #20 was found to have a crack like indication and was removed and a
repl aced. The replacement beam was UT examined and found to be acceptable.
All thirty-six (36) shroud head hold down bolts were UT examined per GE SIL-433.
Eight (8) bolts were found to have crack like indications (#6, #10,
- 13, #17, #24, #32, #34, and #36).
Six (6) bolts were replaced (#6, #10, #17,
- 24, #32, and #36).
The remaining two (2) bolts were evaluated and deemed to be acceptable by GE.
Per IE Bulletin 80-13, the core spray sparger and associated piping was VT examined.
No reportable indications were detected.
Per AStiE Section XI, selected RPV internals were examined using remote visual examination techniques.
YT of the steam dryer revealed forty-five (45) indications in the support ring, two (2) indications in the vertical vane welds and forty-five (45) indications in the steam dryer support brackets.
Indications were evaluated and found to be acceptable by GE, Visual examination of the jet pump mixing nozzles revealed evidence of erosion in the throat area.
The erosion was evaluated by GE and deened acceptable with recomendations for additional monitoring in future outages.
Other Class 1 Examinations (UT, MT, PT, & VT1 Sixty-three (63).
of the welds was per NUREG-0619, fi f ty-si x (56 ) welds welds were examined using volumetric and surface NDE techniques.
One (1) eq were per NUREG-0313 and the remaining six (6) were for ASME Section XI U
requirements.
One (1) HT indication was reported to GPR.
This indication was evaluated by UT and found to be acceptable.
One (1 ) weld was being re-examined due to previous indications.
There was no significant change in the indication and it was deemed acceptable.
Twenty-three (23) integral attachments were examined using surface NDE techniques.
One (1) attachment had unacceptable indications and required surface conditioning to remove indications.
Five (5) RINTSA welds were UT examined per NUREG-0313 and all were found to be acceptabl e.
Bolting on recirculation pump 2831-C001 A was UT examined and no reportable indications were detected.
Thirteen (13) components were examined using VT for bolting and valve body examination requirements of ASME Section XI.
No reportable indications were detected.
CLASS II EXAMINATIONS Seventy-two (72) welds were examined using surface and volumetric NDE techniques.
These examinations included piping welds and integral attachment welds.
Three (3) of these were examined for GPC augmented comitments, three h
(3) were examined per NUREG-0619 and the remaining sixty-six (66) were examined for ASME Section XI requirements.
Four (4) indications were reported to GPC.
These indications were repaired and re-examined and found to be acceptable.
PRESSURE TESTING Six (6) Class 2 and three (3) Class 3 hydrostatic test, one (1) Class 3 Inservice Tests and a Class 1 Leakage Test were perfomed during the Outage.
See the Pressure Test Section of this report for specific infomation.
COMPONENT SUPPORT EXAMINATIONS (CLASS 1, 2, AND 3)
One hundred and sixty-five (165) component supports were VT examined during the outaoe.
Twenty-th ree (23) exaninations revealed unacceptable resul ts.
These supports were either repaired and re-examined or evaluated by engineering and found to be acceptable as is.
REPAIRS AND REPLACEMENTS (CLASS 1 AND 2)
Ho major repairs or replacements were perforned during the outage.
Some minor repairs to valves and component supports were perfomed due to ISI O
examinations, six shroud head hold down bolts, and one,iet pump hold down beam were replaced.
See Repair and Replacement Section of this report for sp0Cific infomation.
//
REPORTABLE INDICATIONS Following is an itemized list of all welds and components which were reported
'p to contain indications or were. considered unacceptable due, to ISI v
examinations.
All of these items were either repaired or evaluated and then deemed acceptable.
RPV Internals 92 linear indications in steam dryer (VT)
Deficiency Card 2-88-0465 8 Moisture Separator Shroud Head Hold Down Bolts (UT)
Deficiency Card 2-88-0477 (Bol ts 6,10,13,17, 24, 32, 34, 36 )
MWO 2-88-0065 (Bolts 6,10,17, 24, 32, 36 )
Jet Pump Hold Down Beam #20 (UT)
Deficiency Card 2-88-0464 y
MWO 2-88-0659 Jet Pump Inlet Mixing Nozzles - all 20 (VT)
Deficiency Card 2-88-0583 Class 1 Welds 2E41-1HPCI-10-0-8 (MT)
Deficiency Card 2-88-0466 MWO 2-88-0565
)
2821-IMS-24A-GPL-2 (MT)
Deficiency Card 2-88-0644 MWO 2-88-0727 Class 2 Welds 2E11-2RHR-8-FPS-8 (tit)
Deficiency Card 2-88-1058 ffWO 2-88-1159 2 Ell-2RHR-208-0-3 (MT)
Deficiency Card 2-88-1059 MWO 2-88-1160 2N11-2MSA-248-IPS-1 (fit)
Deficiency Card 2-88-0942 tiWO 2-88-1020 2 Nil-2fiSA-248-IPS-2 (tit)
Deficiency Card 2-88-0942 MWO 2-88-1020 O
l'
Component Sti 90 (Class 1, 2, AND 3)
SUPPORT DEFICIENCY CARD MWO
'N 2821-MS-H3 2-88-0860 2-88-0970
'2821-MSRV-H7 2-88-0860 2-88-0970
-2821-MSRV-H26 2-88-0860 2-88-0970 2B21-MSRV-R55 2-88-0614 2-88-0703 2E11 -RHP,-A58 2-88-0817 2-88-0929 2E11-RHR-H57 2-88-0864 2-88-0975 2E11-RHR-H175 2-88-0864 2-88-0975 2E11-RHR-H181 2-88-0864 2-88-0975 2E11-RHR-H182 2-88-0864 2-88-0975 2E11-RHR-H183 2-88-0864 2 88-0975 g
2E11-RHR-H193 2-88-0864 2-88-0975 2E11-RHR-R298 2-88-0817 2-88-0930 2E11-RHR-R299 2-88-0817 2-88-0928 2E11-RHR-R300 2-88-0817 2-88-0931 2E11-RHR-H314 2-88-0864 2-88-0975 2E41-HPCI-H31 2-88-0227 2-88-0287 2E41-HPCI-H71 2-88-0887 2-88-1006
~
2E41-HPCI-H98 2-88-0835 2-88-1120
)
2-88-0584 2-88-0672 2E41-HPCI-H108 2-88-0887 2-88-1006 2E41-HPCI-HR710 2-88-0835 2-88-1120 2-88-0584 2-88-0672 2E41 -HPCI-P.102 2-88-0835 2-88-1120 2E41-HPCI-R104 2-88-0835 2-88-1120 2-88-0584 2-88-0672 2P41-SW-H265 2-88-0888 2-88-1007 O
/A
.c
~
The following sections of. this ' NIS-1 Report contain the summary of the-NDE Examinations performed, provides additional information and gives 'results of i
those examinations.
i O
f
+
h I
4 3
t 5
y f
i h
p
[
6 i
i 1.
l t
I
(
/4 ~
O SUMARY OF CLASS 1 COMPONENTS O
]
l O
4
O O
EdwinI.HahhUnit2 1988 Winter Refueling Outage Class 1 Components Page 1 of 34 ASMC SECTlota XI EXAM EXAM ISE EXAM / CAL.
RI REMARKS /8ASIC CAT. NO.
FIG. NO.
EXAMINATION / AREA METHOD PROCEDURE SHEET NO.
NI NRI GEOM /0TER CALIBRATION BLOCK HPV EXAMINATIONS bl.Il A-1/04 2C-2 Mech SwRI Please see SwRI Report PL-CSCL-5.875-62-H B-A Upper Shell-To-Upper Middle Shell Bl.11 A-1/04 2C-3 Mech SwRI Please see SwRI Report PL-CSCL-5.875-62-H B-A Upper Middle Shell-To-Lower Middle Shell 31.11 A-1/04 2C-4 Mech SwRI Please see SwRI Report PL-CSCL-5.875-62-H B-A Lower Middle Shell-To-Lower Shell Weld B1.11 A-1/04 2C-5 Mech SwRI Please see SwRI Report PL-CSCL-5.875-62-H B-A Lower Shell-To-Bottom Head Torus Bl.12 A-1/04 2C-1-A Mech SwRI Please see Sidt! Report PL-CSCL-5.875-62-H B-A Longitudinal Weld on Upper Shell Bl.12 A-1/04 2C-1-B Mech SwRI Please see SwRI Report PL-CSCL-5.875-62-H B-A Longitudinal Weld on Upper Shell S
g 3
v y
O b
O Edwin I. Hatch Unit 2 1988 Winter Refueling Outage Class 1 Components Page 2 of 34 C
ASME SECTIOfA XI EXAM EXAH NDE EXAM / CAL.
RI REMARKS /8ASIC CAT. NO.
FIG. NO.
EXAMINATION / AREA MFTHOD PROCEDURE SHEET NO.
E _NRI GEOM /0THER CALIBRATION BLOCK RPV EXAMINATIONS (Cont'd) 81.12 A-1/04 2C-1-C Mech SwRI Please see SwRI Report PL-CSCL-5.875-62-H B.A Longitudinal Weld on Upper Shell 31.12 A-1/04 2C-2-A Mech SwRI Please see SwRI Report PL-CSCL-5.875-62-H B-A Longitudinal Weld on Upper Mid Shell ut.12 A-1/04 2C-2-B Mech SwRI Please see SwRI Report PL-CSCL-5.875-62-H B-A Longitudinal Weld on Upper Mid Shell 61.12 A-1/04 2C-2-C Mech SwRI Please see Sdl Report PL-CSCL-5.875-62-H B-A Longitudinal Weld on Upper Mid Shell 01.12 A-1/04 2C-3-A Mech Sd!
Please see SwRI Report PL-CSCL-5.875-62-H B-A Longitudinal Weld on Lower Mid Shell 81.12 A-1/Or 2C-3-B Mech Sd!
Please see Sd ! Report PL-CSCL-5.875-62-H 8-A Longitudinal Weld on Lower Mid Shell ut.12 A-1/04 2C-3-C Mech Sd!
Please see SwRI Report PL-CSCL-5.875-62-H B-A Longitudinal Weld on Lower Mid Shell
\\
N
g
-.p -
O Q
O Edwin I. Hatch Unf t 2 1988 Winter Refueling Outage Class 1 Components Page 3 of 34 A *.,ME SECTIOfJ XI EXAM EXAM NDE EXM/ CAL.
RI REMARKS / BASIC CAT. NO.
FIG. NO.
EXAMINATION / AREA METHOD PROCEDURE SHEET NO.
NI NRI
_ GEOM /0THER CALIBRATION BLOCK RPV EXAMINATIONS (Cont'd) 81.12 A-1/04 2C-4-A Mech SwRI Please see SwRI Report PL-CSCL-6. 875-61 -il 11-A Longitudinal Weld on Lower Shell U1.32 A-l/04 2C-4-B Mech SwRI Please see SwRI Report PL-CSCL-6. 875-61 -ti 11-A Longitudinal Weld on Lower Shell 81.12 A-1/04 2C-4-C Mech SwRI Please see StRI Report PL-CSCL-6.875-61-H B-A Longitudinal Weld on Lower Shell 31.40 A-3/03 2HC-2 MT MT-H-500/2 588H2M048 x
PL-CS-4. 5-64-H B-A Closure liead-To-fig UT UT-H-410/4 588H2U132 x
Indications Centerline Stud 1 S88H20143 x
detected during to Stud 20 (CW) 588H2U145 x
previous outage.
588H20041 UT Cal.
See INF 186H2010.
S88H20052 UT Cal.
Acceptable per S88H20053 UT Cal.
u s.w A-l/04 2N2A UT UT-H-410/4 588H2U169 x
PL-CSCL-6.875-61-H U-U B Loop Recirculation S88H2U176 x
Inlet Nozzle To Shell
$88H2U177 x
$88H2C073 UT Cal.
S88H20074 UT Cal.
588H20075 UT Cal.
S 4
.; c Edwin I. Hatch Unit 2 1988 netnter Refueling Outage Class 1 Components Page 4 of 34 ASME 8
SECTION XI EXAM EXAM NDE EXAM / CAL.
RI REMARKS / BASIC CAT. NO.
FIG. NO.
EXAMINATION / AREA METHOD PROCEDURE SHEET NO.
g NRI GE0H/0THER CALIBRATION BLOCK RPV EXAMINATIONS (Cont'd) 83.90 A-1/04 2N2D UT UT-H-410/4 588H2U172 x
PL-CSCL-6. 875-61 -H B-D B Loop Rec 1rculation 588H2U175 x
Lasinar indication.
Inlet Nozzle to Shell
$88H20178 x
Acceptable per
$88H20073 UT Cal.
IWB-3511 -2.
$88H20074 UT Cal.
S88H20075 UT Cal.
UJ.90 A-1/04 2N2G UT UT-H-410/4
$88H2U171 x
PL-CSCL-6.875-61-il B-U A Loop Recirculation
$88H20173 x
Inlet Nozzle to Shell
$88H2U179 x
588H20073 UT Cal.
588H20074 UT Cal.
588H2C075 UT Cal.
83.90 A-I/04 2N2K UT UT-H-410/4 S88H2U170 x
PL-CSCL-6.875-61-H B-D A Loop Rectrculation S88H20174 x
Inlet Nozzle to Shell
$88H2U180 x
$88H20073 UT Cal.
S88H20074 UT Cal.
588H20075 UT Cal.
83.90 A-1/04 2N4D UT UT-H-410/4 588H20214 x
PL-CSCL-5.875-62-H B-D B-D Loop Feedwater S88H2U215 x
Inlet Nozzle to Shell
$88H2U216 x
588H2U217 x
$88H2009G UT Cal.
S88H20091 UT Cal.
S88H20092 UT Cal.
gfy g-O 4
U
,m Edwin I. Hatch Unit 2 1988 Winter Refueling Outage Class 1 Components Page 5 of 34 8
ASML SECTION XI EXAM EXAM MDE EXAM / CAL.
RI REMARKS / BASIC CAT. NO.
FIG. NO.
EXAMINATION / AREA METH00 PROCEDURE SHEET NO.
NI NRI GEOM /0TER CALIBRATION BLOCK HPV EXAHINATIONS (Cont'd) 83.1w A-1/04 2N2A UT UT-H-480/3 588H2U188 U-D D Loop Recirculation x
PL-CSCL-6.875-61-il S88H20077 UT Cal.
Inlet Nozzle IR 83.100 A-1/04 2N2D UT UT-H-480/3 588H20187 B-U 8 Loop Recirculation x
PL-CSCL-6.675-61-H S88H20077 UT Cal.
Inlet Nozzle IR B3. IW A-1/04 2N2G UT UT-H-480/3 588H20186 B-U A Loop Recirculation x
PL-CSCL-6.875-61-H
$88H2C077 UT Cal.
Inlet Nozzle IR UJ.100 A-1/04 2N2K UT UT-H-480/3
$88H2U185 B-0 A Loop Recirculation x
PL-CSCL-6.875-61-H S88H20077 UT Cal.
Inlet Nozzle IR 86.10 A-33/01 2 NUT-1 MT MT-H-501/2 S88H2M063 x
B-G-1 Closure Head Nuts (16. 1 0 A-33/01 2 NUT-2 MT MT-H-501/2
$88H2M063 x
B-G-1 Closure Ibad Nuts tu,. s o A-JJ/UI 2NUI-J MT MT-H-501/2
$88H2M063 x
B-6-1 Closure Head Nuts lib.10 A-33/01 2 NUT-4 MT MT-H-501/2 S88H2M063 x
D-G-1 Closure akad Nuts i
I o
)
~
w n
3 i
-rg.
,h,
~ C/ '
I i
4 4
Edwin I Hatch Unit 2 1988 Winter Refueling Outage Class 1 Components Page 6 of 34 s
ASME SECTION XI EXAM EXAM MDE EXAM / CAL.
RI REMARKS /8ASIC CAT. NO.
FIG. NO.
EXAMINATION / AREA METH00 PROCEDURE SHEET NO.
g NRI
_ GEOM /0THER CALI8 RATION BLOCK RPV EX.4MINATIONS (Cont'd)
Ub.10 A-33/01 2 NUT-5 MT MT-H-501/2 588H2M063 x
B-G-1 Closure Head Nuts Ub.10 A-J3/01 2 NUT-6 MT MT-H-501/2 588H2M063 x
B-G-1 Closure Head Nuts 86.10 A-33/01 2 NUT-29 MT MT-H-501/2
$88H2M063 x
8-G-1 Closure Head Nuts bb.10 A-33/01 2WUT-45 MT MT-H-501/2 588H2M064 x
8-G-1 Closure 14ad Nuts D6.10 A-33/01 2 NUT-46 MT MT-H-501/2 588H2M064 x
b-G-1 Closure llead Nuts 80.IO A-33/01 2 NUT-47 MT MT-H-501/2 588H2M064 x
B-G-1 Closure Head Nuts 80.10 A-33/01 2 NUT-48 MT MT-H-501/2 S88H2M063 x
B-G-1 Closure Head Nuts B6.10 A-33/01 2 NUT-49 MT MT-H-501/2 588H2MC62 x
U-G-1 Closure Head Nuts bb.10 A-33/01 2 NUT-50 MT MT-H-501/2 588H2M064 x
11 1 Closure head Nuts b
s
.~.
O O
O
)
Edwin I. Hatch Unit 2 1988 Winter Refueling Outage Class 1 Components Page 7 of 34 ASME SECTION XI EXAM EXAM NDE EXAM / CAL.
RI REMARKS / BASIC CAT. NO.
FIG. NO.
EXAMINATION / AREA METHOD PROCEDURE SHEET NO.
NI NRI GEOM /0TER CALIBRATION BLOCK kPV EXAMINATIONS (Cont'd) 86.10 A-33/01 2 NUT-51 MT MT-H-501/2 588H2M064 x
B-G-1 Closure Head Nuts 80.10 A-33/01 2 NUT-52 MT MT-H-501/2 588H2M062 x
B-G-1 Closure Head Nuts Ub.10 A-33/01 2 NUT-53 MT MT-H-501/2 588H2M062 x
B-G-1 Closure Head Nuts 80.10 A-33/01 2WUT-54 MT MT-H-501/2
$88H2MD62 x
B-G-1 Closure Head Nuts l'
Bb.10 A-33/01 2 NUT-55 MT MT-H-501/2
$88H2M064 x
B-G-1 Closure Head Nuts
~
Ub.10 A-33/01 2 NUT-56 MT MT-H-501/2 588H29064 x
l B-G-1 Closure Head Nuts 86.30 A-33/01 2 STUD-1 UT UT-H-421/2 588H2U227 x
23-H B-G-1 Closure Head Studs S88H20099 UT Cal.
Ub.JU A-33/01 2 STUD-2 UT UT-H-421/2 588H2U227 x
23-H U-b-1 Closure Head Studs
$88H2C099 UT Cal.
Ub.30 A-33/01 2 STUD-3 UT UT-H-421/2 588H2U227 x
23-H B-G-1 Closure Head Studs
$88H20099 UT Cal.
.y
]
- M
/
(_5 7U' O
O O
Edwin I. Hatch Unit 2 1988 Winter Refueling Outage Class 1 r
,_._..ts Page 8 of 34 A5ME i
SEC' ION XI EXAM EXAM NDE EXAM / cal..
R1 REMARKS / BASIC CAT. NO.
FIG. NO.
EXAMINATION / AREA METH00
/ROCEDURE SHEET NO.
NI NRI GEOM /0TER CALIBRATION BLOCK RPV EXAMINATIONS (Cont'd) 80.J0 A-33/01 2 STUD-4 UT UT-H-421/2 588H2U227 x
23-H B-G-1 Closure Head Studs
$88H20099 UT Cal.
86.30 A-33/01 2 STUD-5 UT UT-H-421/2
$88H2U227 x
23-H B-G-1 Closure Head Studs
$88H20099 UT Cal.
80.30 A-33/01 2 STUD-6 UT UT-H-421/2 588H2U227 x
23-H U-G-1 Closure liead Studs 588H20099 UT Cal.
Ub.30 A-33/01 2 STUD-40 UT UT-H-421/2 588H2U227 x
23-H B-G-1 Closure Head Studs
$88H20099 UT Cal.
Bb.JO A-33/01 2 STUD-45 UT UT-H-421/2 588H2U227 x
23-H B-G-1 Closure Head Studs 588H20099 UT Cal.
Ob.30 A-33/01 -
2 STUD-46 UT UT-H-421/2 588H2U227 x
23-H B-G-1 Closure liead Studs
$88H20099 UT Cal.
Ub.JU A-33/01 2 STUD-47 UT UT-H-421/2 588H2U227 x
23-H B-G-1 Closure Head Studs
$88H20099 UT Cal.
Bb.JU A-J3/01 2 STUD-48 UT UT-H-421/2 588H2U227 x
23-H B-G-1 Closure Head Studs
$88H20099 UT Ca1.
Ub.JU A-33/UI 2 STUD-49 UT UT-H-421/2 588H20227 x
23-H B-G-1 Closure Head Studs
$88H20099 UT Cal.
9 y
At
LJ W1.
O O
11 q
l Edwin I. Hatch Unit 2 I
1988 Winter Refueling Outage Class 1 Components Page 9 of 34 A5ME SECTION XI EXAM EXAM HDE EXAM / CAL.
RI REMAPJCS/ BASIC e CAT. NO.
FIG. NO.
' EXAMINATION / AREA METHOD PROCEDURE SHEET NO.
NI NRI
_ GEOM /0THER CALIBRATION BLOCK RPV EXAMINATIONS (Cont'd)
Ub.30 A-33/01 2 STUD-5U UT UT-H-421/2 588H2U227 x
23-H B-G-1 Closure Head Studs S88H20099 UT Cal.
Ub.30 A-33/01 2 STUD-51 UT UT-H-421/2
$88H2U227 x
23-H B-G-1 Closure Head Studs
$88H20099 UT Cal.
Bb.30 A-33/01 2 STUD-52 UT UT-H-421/2 S88H2U227 x
23-H B-6-1 Closure Head Studs
$88H20099 UT Cal.
80.30 A-33/01 2 STUD-53 UT UT-H-421/2 588H2U227 x
23-H B-G-1 Closure llead Studs
$88H2C099 UT Cal.
Ub.30 A-33/01 2 STUD-54 UT UT-H-421/2 588H2U227 x
23-H B-G-1 Closure Head Studs 588H20099 UT Cal.
e6.30 A-33/01 2 STUD-55 UT UT-H-421/2 588H2U227 x
23-H B-G-1 Closure Head Studs 588H20099 UT Cal.
80.30 A-33/01 2 STUD-56 UT UT-H-421/2 588H2U227 x
23-H B-G-1 Closure Head Studs 588H20099 UT Cal.
Ub.40 A-33/01 2LIG-1 UT UT-H-419/0
$88H2U226 x
23-H B-G-1 Flange Ligaments 588H20098 UT Cal.
p g
g Edwin I. Hatch Unit 2 1988 Winter Refueling Outage Class 1 Components Page 10 of 34 ASt1L SELTION XI exalt EXAM NDE EXAM / CAL.
RI REMARKS / BASIC CAT. NO.
F IG. 140.
EXAMINATION / AREA METHOD
_ PROCEDURE SHEET NO.
NI NRI GEOM /0THER CALIBRATION BLOCK RPV EXAMINATIONS (Cont'd) vo.40 A-33/01 2LIG-2 UT UT-H-419/0 S88H2U226 x
23-H B-b-1 Flange Ligaments S88H20098 UT Cal.
86.40 A-33/01 2LIG-41 UT UT-H-419/0 S88H2U226 x
23-H B-G-1 Flange Ligaments S88H20098 UT Cal.
80.40 A-33/01 2LIG-42 UT UT-H-419/0 S88H2U226 x
23-H B-G-1 Flange Ligaments
$88H20098 UT Cal.
Ub.40 A-33/01 2LIG-43 UT UT-H-419/0 588H2U226 x
23-H B-G-1 Flange Ligaments S88H20098 UT Cal.
86.40 A-33/01 2LIG-44 UT UT-H-419/0 588H2U226 x
23-H B-G-1 Flange Ligaments S88H2C098 UT Cal.
06.40 A-J3/UI 2LIG-45 UT UT-H-419/0 588H2U226 x
23-H B-G-1 Flange Ligaments 588H20098 UT Cal.
Ub.40 A-J3/01 2LIG-46 UT UT-H-419/0 588H2U226 x
23-il b-b-i Flange Ligaments
$88H20098 UT Cal.
Ub.40 A-33/UI 2LIG 47 UT UT-H-419/0 S88H20226 x
23-H B-G-1 Flange Ligasents 588H20098 UT Cal.
bb.40 A-33/01 2LIG-48 UT UT-H-419/0 588H20226 x
23-H B-G-1 Flange Ligaments S88H20098 UT Cal.
S A
y g-O-
O i
4 Edwin I. Hatch Unit 2 1988 Winter Refueling Outage
~
i Class 1 C ;:ur.ts Page 11 of 34 4
A$ti SECTION XI EXAM EXAM ISE EXAM / CAL.
RI REHARKS/8ASIC CA1. NO.
FIG. NO.
EXAMINATION / AREA ETHOD PREEDURE SHEET HO.
NI HRI GESI/0TER
. CALIBRATION BLOCK RPY EXAMINATIONS (Cont'd) 80.40 A-33/01 2LIG-49 UT UT-H-419/0
$88H2U226 x
23-H B-G-1 Flange Ligaments
$88H20098 UT Cal.
86.40 A-33/01 2LIG-50 UT UT-H-419/0 588H2U226 x
23-H B-G-1 Flange Ligaments 588H20098 UT Cal.
80.40 A-33/01 2LIG-51 UT UT-11-419/0 588H2U226 x
23-H B-G-1 Flange Ligaments 588H20098 UT Cal.
86.40 A-33/01 2LIG-52 UT UT-H-419/0 588H2U226 x
23-H B-G-1 Flange Ligaments
$88H20098 UT Cal.
Ub.40 A-33/01 2LIG-53 UT UT-N-419/0 588H2U226 x
23-H B-G-1 Flange Ligaments
$88H20098 UT Cal.
80.40 A-33/01 2LIG-54 UT UT-H-419/0 588H2U226 x
23-H B-G-1 Flange Ligaments S88H20098 UT Ca1.
86.40 A-33/01 2LIG-55 UT UT-H-419/0 588H2U226 x
23-H B-G-1 Flang Ligaments
$88H20098 UT Cal.
116. 4 0 A-J3/01 2LIG-5G UT UT-H-419/0 S88H2U226 x
23-H B-G-1 Flange Ligaments 588H20098 UT Cal.
Bo.bu A-33/01 2 WASHER-1 VT VT-H-710/2 588H2V183 Satisfactory u-G-1 Closure Head Washers i
i b
l i
e I,9
!+
_g O
O O
EMn I. istch Unit 2 1968 Winter Refueling Outage.
Class 1 Ceeponents Page 12 of 34 A91E SECTION XI EXAM EXAM IRIE EXAN/CAC.
RI R3 WIKS/8ASIC CAT. NO.
FIG. NO.
EXAMINATION / AREA METH0G PROCEDURE SHEET 100.
WI
- NRI, GEON/0TER CALIBRATION BLOCK.
I RPV EXAMINATIONS (Cont'd) 80.50 A-33/01 2WA5etER-2 VT VT-H-710/2 588H2V183 Satisfaclory B-G-1 Closure Head Washers 86.50 A-33/01 2 WASHER-3 VT VT-H-710/2
$88H2V183-Satisfactory D-G-1 Closure Head Washers ub.bu A-33/01 2 WASHER-4 VT VT-H-710/2 588H2V183 Satisfactory B-G-1 Closure Head Washers 86.50 A-33/01 2 WASHER-S VT VT-H-710/2 588H2V183 Satisfactory B-G-1 Closure Head Washers 86.50 A-33/01 2 WASHER-6 VT VT-H-710/2 588H2V183 Satisfactory B-G-1 Closure Head Washers ub.60 A-33/01 2 WASHER-29 VT VT-H-710/2 588H2V183 Satisfactory B
-I Closure Head Washers 86.50 A-33/01 2WA91ER-45 VT VT-N-710/2 588H2V183 Satisfactory B-G-1 Closbre Head Washers Ub. $0 A-33/01 ZWA91LR-46 VT VT-H-710/2 588H2V183 Satisfactory B-G-1 Closure Head Washers 8b.50 A-33/01 2 WASHER-47 VT VT-H-710/2 588H2V183 Satisfactory B-L-1 Closure Head Washers N
O O
O Edwin I. Hatch Unit 2 1988 Winter Refueling Outage Class 1 Components Page 13 of 34 e
ASML SECTION XI EKAM EXAM ISE EXAM / CAL.
RI REMARKS /E*. SIC CAT. NO.
FIG. NO.
EXAMINATION / AREA METHOD PROCEDUPI SHEET NO.
NI NRI GEOM /0THER CALIBRATION BLOCK HPV EXAMINATIONS (Cont'd) bb.bu A-JJ/01 2WAsilER-48 V!
VT-H-710/2 588H2V183 Satisfactory B-G-1 Closure Head Washers U6.to A-33/01 2 WASHER-49 VT VT-H-710/2 588H2V183 Satisfactory B-G-1 Closure Head Washers 80.$U A-33/UI 2 WASHER-50 VT V! -N-710/2 588H2V183 Satisfactory B-G-1 Closure Head Washers 89.$U A-J3/01 2WA91ER-51 VT VT-H-710/2 588H2V183 Satisfactory B-G-1 Closure Head Washers be.bu A-J3/01 2WA5fiER-52 VT VT-N-710/2 588H2V183 Satisfactory B-G-1 Closure Head Washers 80.50 A-33/01 2 WASHER-53 VT VT-N-710/2 588H2V183 Satisfactory B-G-1 Closure Head Washers B6.50 A-33/01 2 WASHER-54 VT VT-H-710/2
$88H2V183 Satisfactory B-G-1 Closure Head Washers I
B6.SU A-33/01 2 WASHER-55 "I
VT-H-710/2 588H2V183 Satisfactory B-G-1 Closure Head Washers no.LU A-J3/01 2WA9sER-56 VT VT-H-710/2 588H2V183 Satisfactory B-G-1 Closure 'iead Washers 1
o G
C Edwin I. Hetch Unit 2 1988 Winter Refueling Outage Class 1 Components Page 14 of 34
'4 A5ME SECTIou XI EXAM EXAM ISE EXAM / CAL.
RI REMARKS / BASIC CAT. NO.
TIG. NO.
EXAMINATION / AREA METHOD PROCEDURE SHEET 100.
{
NRI GE0H/0THER CALIBRATION SLOCK.
RPV EXAMINATIONS (Cont'd) i U13.10 RTV Examination of VT VT-H-750/1
$88H2V115 x
Visual exas renaled U-N-1 Ve 21 Interior crack 11ke indications See INF 188H2003.
Acceptable per GE Letter G-GPC-8-053.
Visual exam revealed signs of erosion in all 20 jet pumps. See INF 188H2006. No corrective action required at this outage.
UlJ.20 RPV Exastnation of VT VT-H-750/1
$88H2V115 x
B-U-2 Interior Attachments Within Beltline Reg.
DI3.21 RPV Examination of VT VT-H-750/1 588H2V115 x
B-N-2 Interior Attachments Beyond Beltitne Reg.
Bi3.22 RPW Examination of VT VT-H-750/1 588H2Y115 x
B-N-2 Core Support Structure U15.10 Class 1 Pressure VT VT-H-720/1 See Pressure Test Section of Report B-P Retaining Boundary Leakage Test
~
O
g-g Edwin I. Ha+.ch Unit 2 1988 Winter Refueling Outage Class 1 Components Page 15 of 34 s
AMIL SECTION XI EXAM EXAM NDE EXAM / CAL.
-RI REMARKS / BASIC CAT. NO.
FIG. NO.
EXAMINATION / AREA METil0D PROCEDURE SHEET NO.
NI NRI GEOM /0THER CALIBRATION BLOCK MAIN STEAM SYSTEM B10.10 A-6/04 2B21-1MS-24A-SPL-2 MT MT-H-S00/2 S88H2M046 x
Linear indication B-K-1 Device 2821-MS-H1 588H2M052 x
detected. See INF S88H2M061 x
188H2009. After grinding, weld was re-examined an<1 deemed acceptable.
B10.10 A-b/04 2821 -1MS-24A-SPL-3 MT MT-H-500/2 S88H2M047 y
B-K-1 Device 2821-MS-H1 ulo.10 A-6/04 2B21 -1MS-24A-SPL-4 MT MT-H-500/2 S88H2M047 x
B-K-1 Device 2821-MS-H1 89.31 A-7/05 2821 -1MS-248-8BC-2/
MT MT-H-500/2 S88H2M036 x
24-CS-80-1.218-69-H B-J 2821 -1MS-88-BSR UT UT-H-400/7 S88H2U208 x
Pipe to Branch S88H2U209 x
Connection S88H2C086 UT Cal.
S88H2C087 UT Cal.
B 10.10 A-7/05 2B21 -1MS-24B-8P L-1 MT MT-H-500/2 588H2M030 x
B-K-1 Device 2B21-MS-RS3 010.10 A-7/05 2B21 -1MS-248-8PL-2 MT MT-H-500/2 588H2M030 x
B-K -1 Device 2B21-MS-RS3 B10.10 A-7/US 2821 -1HS-248-8PL-3 MT MT-H-500/2 588H2M030 x
B-K -1 Device 2821-MS-RS3 D
g y
CD Gx 0
Edwin I. Hatch Unit 2 1988 Winter Refueling Outage Class 1 Components Page 16 of 34 ASML SECTION XI EXAM EXAM NDE EXAM / CAL.
RI REMARKS / BASIC-CAT. NO.
FIG. NO.
EXAMINATION / AREA METEDD PROCEDURE SHEET NO.
NI NRI GE0M/0THER CALIBRATION BLOCK MAIN STEAM SYSTEM (Cont'd) 4 1110.10 A-7/05 2821 -lMS-248-8PL-4 MT MT-H-500/2 588H2M030 x
t Il-K -1 Device 2B21-MS-R53 1;10.10 A-7/05 2821-1MS-248-8PL-5 MT MT-H-500/2 S88H2M030 x
li-K -1 Device 2B21-MS-R53 1110.10 A-7/05 2B21 -1MS-248-8PL-6 MT MT-H-500/2 S88H2M030 x
i li-K - 1 Device 2821-MS-RS3 810.10 A-7/05 2821-1MS-248-8PL-7 MT MT-H-500/2 588H2M030 x
B-K-1 Device 2821-MS-RS3 B10.10 A-7/05 2821 -1MS-248-8PL-8 MT MT-H-500/2 588H2M030 x
B-K-1 Device 2821-MS-R53 i
B10.10 A-8/06 2821 -1MS-24C-SPL-1 MT MT-H-500/2 S88H2M060 x
B-K-1 Device 2821-MS-H7 B10.10 A-8/06 2B21 -1MS-24C-SPL-3 MT MT-H-500/2 S88H2M060 x
B-I;-1 Device 2821-MS-H7 ulo.10 A-b/06 2821 -1MS-24C-SPL-4 MT MT-H-500/2 S88H2M060 x
B-K-1 Device 2821-MS-H7 09.;s1 A-8/06 2821-1MS-24C-8BC-3/
MT MT-H-500/2 588H2M029 x
24-CS-80-1.218-69-H B-J 2821 -1MS-8C-CSR UT UT-H-400/7 S88H2UO39 x
Pipe to Branch S88H2U207 x
Connection S88H2C002 UT Cal.
S88H20085 UT Cal.
2 (4
w
g-O Q
Edwin I. Hatch Unit 2 1988 Winter Refueling Outage Class 1 Components Page 17 of 34 8
ASME SICTION XI EXAM EXAM NDE EXAM / CAL.
RI REMARKS /8ASIC C.tT. NO.
FIG. NO.
EXAMINATION / AREA METHOD PROCEDURE SHETT NO.
NI NRI GEOM /0THER CALIBRATION BLOCK' MAIN STEAM SYSTEM (Cont'd)
B ).11 A-9/05 2821 -1MS-240-9 MT MT-H-500/2 S88H2M056 x
24-CS-80-1.218-69-H B4 Elbow to Pipe UT UT-H-400/7 S88H2U197 x
S88H20081 UT Cal.
B 10.10 A-9/05 2821 -1MS-24D-9PL-2 MT MT-H-500/2 588H2M031 x
B-K-1 Device 2821-MS-R37 810.10 A-9/05 2821-1MS-24D-9PL-6 MT MT-H-500/2
$88H2M031 x
B-K-1 Device 2821-MS-R37 810.10 A-9/05 2821 -1MS-240-9PL-7 MT MT-H-500/2 588H2M031 x
B-K -1 Device 2821-MS-R37 U10.10 A-9/05 2821 -1MS-24D-9PL-8 MT MT-H-500/2 S88H2M031 x
B-K-1 Device 2B21-P.S-R37 strACTOR coot ANT PilMPS Bb.180 2RC-A Pump Bolt UT UT-H-420/4 S88H2U224 x
28-H B-G-1
- Pump Bolting S88H20097 UT Cal.
I through 5 Bo.200 2RC-A Pump-Nuts VT VT-H-710/2 S88H2V203 Satisfactory B-G-1 and Washers 1 through 16 U 10. 20 A-4/02 2RC-A Pump Lug-1A2 PT PT-H-600/2 S88H2P060 x
Acceptable per B-K-1 Restraint Lug IWB-3516-2 J
- A
O Oq
~
O.v Edwin I. Hatch Unit 2 1988 Winter Refueling Outage Class 1 Components Page 18 of 34 s
ASME SECTion XI EXAM EXAM NDE EXAM / CAL.
RI REMARKS /8ASIC CAT. NO.
FIG. NO.
EXAMINATION / AREA METHOD PROCEDURE SHEET NO.
NI NR GEOM /0THER CALIBRATION BLOCK REACTOR COOLANT PUMPS (Cont'd) i 810.20 A-4/02 2RC-A Pump Lug-3A2 PT PT-H-600/2 S88H2P021 x
B-K-1 Restraint Lug 810.20 A-4/02 2RC-A Pump Lug-382 PT PT-H-600/2 S88H2P021 x
B-K-1 Restraint Lug U10.20 A-4/02 2RC-A Pump Lug-3C2 PT PT-H-600/2 588H2P021 x
B-K-1 Restraint Lug B10.20 A-4/02 2RC-A Pump Lug-302 PT PT-H-600/2 S88H2P021 x
i B-K-1 Restraint Lug RESIDUAL HEAT REMOVAL SYSTEM 87.50 A-20/02 2E11-1RHR-9A-HS-lF8 VT VT-H-710/2 S88H2V244 Satisfactory B-G-2 Flange Bolting CORE SPRAY SYSTEM l
8 9.11 A-25/03 2E21 -1 CS-108-13 MT MT-H-500/2 S88H2M039 x
54-H l
B-J Elbow to Pipe UT UT-H-400/7
$88H2U161 x
l S88H20066 UT Cal.
l HIGH PRESSURE COOLANT IlOECTION SYSTEll B9.11 A-26/03 2E41 -1 HPCI-10-D-7 MT MT-H-500/2 S88H2M037 x
10-CS-100-0. 719-54-H B-J Pipe to Elbow UT UT-H-400/7 S88H2U194 x
UT-H-460/1 S88H20195 Weld Profile 588H20079 UT Cal.
I i
g
g, g
O q
O Edwin I. Hatch Unit 2 1988 Winter Refueling Outage Class 1 Components Page 19 of 34 ASME a
SECTIOu XI EXA.,
RI REMARKS / BASIC CAT. NO.
FIG. NO.
EXAMINATION / AREA METHOD PROCEDURE SHEET NO.
E NRI GE0M/0THER CALIBRATION BLOCK HIGH PRESSURE COOLANT INJECTION SYSTEM (Cont'd) b9.11 A-20/03 2 E41 -l HPCI-10-D-8 MT MT-H-500/2 S88H2M035 x
10-CS-100-0. 719-54-H H-J Elbow to Pipe UT UT-H-400/7 S88H20165 x
Linear indication UT-H-460/1 588H20183 Weld Profile detected. See INF S88H2U184 x
188H2007. Acceptable 588H2U206 Ind. Eval, per IWB-3514-2.
S88H2C070 UT Cal.
S88H2C076 UT Cal.
VALVE BOLTING B7.70 A-d/01 2B21 -F013F VT VT-H-710/2 S88H2V216 Satisfacte.y B-G-2 Valve Bolting B7.70 A-5/01 2821 -F013G VT VT-H-710/2 588H2V217 Satisf actory B-G-2 Valve Bolting 67.70 A-b/01 2B21 -F013H VT VT-H-710/2 S88H2V218 Sati sfactory li-G-2 Valve Bolting 117. 70 A-b/01 2821-F013K VT VT-H-710/2 S88H2V219 Satisfactory U-G-2 Valve Bolting B 7. 70 A-5/01 2821 -F013L VT GPC-450C-MWO 2-87-3163 Satisinctory Exam performed B-G-2 Valve Bolting INS-010-OS/0 by GPC B7.70 A-5/01 2821 -F013M VT VT-H-710/2 588H2V220 Satisfactory H-G-2 Valve Bolting s
- A y
. @ ;.nn
-~=..
y
O O
Edwin I. Hat 6 Unit 2 1988 Winter Refueling Outage Class 1 Components Page 20 of 34 a
ASME SECTION XI EXAM EXAM NDE EXAM / CAL.
RI REMARKS / BASIC CG. NO.
FIG. NO.
EXAMINATION / AREA METHOD PROCEDURE SHEET NO.
NI NRI GEOM /0THER CALIBRATION BLOCK VALVE BULTING (Cont'd) n l. 70 A-28/03 2G31 -F004 VT VT-H-710/2 S88H2V198 Satisfactory ll-G-2 Valve Bolting 01.70 A-28/03 2G31-F027 VT VT-H-710/2 588H2V157 Satisfactory B-G-2 Valve Bolting VALVE BODIES 812.50 2821-F0220 VT VT-H-730/3 NA Satisfactory Exas Perfonned B-M-2 Valve Bodies By GPC ul2.bu 2821-F0280 VT VT-H-730/3 NA Satisfactory Exam Performed B-M-2 Valve Bodies By GPC CORE SPRAY SPARGER SYSTEM 2NSA Sparger VT VT-H-750/1 588H2V115 x
IEB-80-13 A-A Loop Nozzle 2NSB Sparger VT VT-H-750/1 S88H2Vil5 x
IEB-80-13 A-B Loop Nozzle LOTE: Va!ve 2B21-F010A was disassembled for maintenance, however only a limited visual examination was perfonned. Valve 7 t71-r0101s was esisasseneled and visustly examined duririg the Fall 1986 outage, therefore the requirement of ASML Section XI, IWB-2500-1. Examination Category B-M-2 has been satisfied (See NIS-1, Page 156).
t i
+s.
ti U
~
.dtt O
O Edwin I. Hatch Unit 2 1988 Winter Refueling Outage Class 1 Components Page 21 of 34 A$t4L a
SECTION XI EXAM EXAM NDE EXAM / CAL.
RI REMARKS / BASIC CAT. NO.
FIG. NO.
EXAMINATION / AREA METHOD PROCEDURE SHEET NO.
NI NRI GEOM /0THER CALIBRATION BLOCK NUREG-0313 EXAMINATIONS 2N2F UT UT-H-415/2 588H2U190 x
RINTSA-125-H RINTSA Weld S88H20078 UT Cal.
2N2G UT UT-H-415/2
$85H20193 x
RINTSA-125-H RINTSA Weld S88H2C078 UT Cal.
2N2H UT UT-H-415/2 588H20191 x
RINTSA-125-H RINTSA Weld S88H20078 UT Cal.
2N2J UT UT-H-415/2 S88H20192 x
RINTSA-125-H RINTSA Weld S88H2C078 UT Cal.
2N2K UT UT-H-415/2 S88H20189 x
RINTSA-125-H RINTSA Weld S88H20078 UT Cal.
B5.10 A-37/00 2B31 -1 RC-4JP-A-1 PT PT-H-600/2 S88H2P047 x
5.437-SS-X-0. 813-121 -H B-f Nozzle 2N8A to UT UT-H-409/3 588H2U119 x
Safe-End UT-H-400/7 S88H2U147 x
S88H2CO37 UT Cal.
S88H20055 UT Cal.
B 9.11 A-37/00 2831 -1 RC-4JP-A-2 PT PT-H-600/2 S88H2P034 x
. 4-SS-80-0.337-80-H B.-J Safe End to UT UT-H-401/6 S88H20117 x
Penetration Seal 588H2CO36 UT Cal.
O
i u
e o
g O.
I Edwin I. Hatch Unit 2 1988 Winter Refueling Outage Class 1 Components j
Page.22 of 34 e
ASME SECTION XI EXAM EXAM NDE EXAM / CAL.
RI REMARKS / BASIC.
CA1. NO.
FIG. No.
EXAMINATION / AREA METHOD PROCEDURE SHEET NO.
NI NRI GEOM /0THER-CALIBRATION BLOCK NUREG-0313 EXAMINATIONS (Cont *d) 115.10 A-37/00 2831 -lRC-4JP-B-1 PT PT-H-600/2 588H2P035 x
5.437-SS-X-0.813-121-H.
B-F Nozzle 2N88 to UT UT-H-409/3
$88H2U120 x
Safe-End UT-H-400/7 S88H20146 x
$88H2CO38 UT Cal.
S88H20054 UT Cal.
89.11 A-37/00 2831 -1 RC-4JP-B-2 PT PT-H-600/2 S88H2P036 x
4-SS-80-0.337-80-H B-J Safe End to UT UT-H-401/6 S88H2' 118 x
J Penetration Seal S88H2CO36 UT Cal.
69.11 A-14/02 2831 -1RCM-12AF-3 PT PT-H-600/2 S88H2P023 x
12-SS-0. 792-132-H B-J Pipe to Safe-End UT UT-H-401/6 588H2U109 x
588H2U111 x
S88H20033 UT Cal.
S88H2CO34 UT Cal.
B9.12 A-14/02 2831 -1 RCM-12AF-3LU PT PT-H-600/2 S88H2P022 x
12-SS-0. 792-132-H B-J Longitudinal Seam UT UT-H-401/6 S88H2U106 x
Weld Extending S88H2CO33 UT Cal.
Upstream
- n. I l A-14/02 2831 -l RCM-12AG-2 PT PT-H-600/2 588H2P013 x
12-SS-0. 792-132-H B -J Pipe to Safe-End UT ~
UT-H-401/6 S88H20067 x
S88H2UO68 x
S88H2OO69 Weld Profile S88H20014 UT Cal.
S88H20015 UT Cal.
E Q
m.
o
,e O
O' Edwin I. Hatch Unit 2 1988 Winter Refueling Outage Class 1 Components Page 23 of 34 s
ASME SECTION XI EXAM EXAM NDE EXAM / CAL.
RI REMARKS / BASIC CAT. NO.
FIG. N3.
EXAMINATION / AREA METHOD PROCEDURE SHEET NO.
NI NRI GE0M/0THER CALIBRATION BLOCK NUREG-0313 EXAMINATIONS (Cont'd) u9.11 A-14/02 2831 -1RCM-12AH-2 PT PT-H-600/2 S88H2P031 x
12-SS-0. 792-132-H B-J Pipe to Safe-End UT UT-H-401/6 S88'f2U108 x
S88H20110 x
S88H2CO33 UT Cal.
S88H20034 UT Cal.
B9.11 A-14/02 2831 -1 RCM-12AJ-2 PT PT-H-600/2 S88H2P012 x
12-SS-0. 792-132-H B-J Pipe to Safe-End UT UT-H-401/6 S88H20070 x
S88H20071 S88H20072 We u cofile S88H2C016 UT ral.
S88H2C017 UT La1.
89.12 A-14/02 2831 -1RCM-12Al-2LU PT PT-H-600/2 588H2P033 x
12-SS-0.792-132-H B-J Longitudinal Seam UT UT-H-401/6 S88H20107 x
Weld Extending S88H2CO33 UT Cal.
Upstream B9.11 A-14/02 2B31 -1RCM-12AK-3 PT PT-H-600/2 S88H2P014 x
12-SS-0.792-132-H B-J Pipe to Safe-End UT UT-H-401/6 S88H20065 x
l S88H2UO66 x
588H20012 UT Cal.
S88H20013 ~
UT Cal.
89.11 A-15/02 2B31 -1 RCM-12BA-3 PT PT-H-600/2 S88H2P030 x
12-SS-0.792-132-H U-J Pipe to Safe-End UT UT-H-401/6 S88H2UO73 x
$88H20074 x
S88H20018 UT Cal.
S88H20019 UT Cal.
6
+
g O
e O
Edwin I. Hatch Unit 2 1988 Winter Refueling Outage Class 1 Components Page 24 of 34 ASin.
SECTION XI EXAM E
RI REMARKS /8ASIC CAT. NO.
FIG. NO.
EXAMINATION / AREA METHOD PROCEDURE SHEET NO.
NI NRI GE0M/0THER CALIBRATION BLOCK NUREG-0313 EXAMINATIONS (Cont'd) 89.11 A-15/02 2831 -1RCM-1288-2 PT PT-H-600/2 588H2P032 x
12-SS-0. 792-132-H B-J Pipe to Safe-End UT UT-H-401/6 588H2UO76 x
S88H20077 x
S88H20020 UT Cal.
S88H20021 UT Cal.
89.11 A-IS/02 2831 -1RCH-12BC-2 PT PT-H-600/2 S88H2P024 x
12-SS-0.792-132-H B-J Pipe to Safe-End UT UT-H-401/6 S88H20063 x
S88H2UO64 x
S88H20010 UT Cal.
S88H20011 UT Cal.
B9.11 A-15/02 2831 -1RCM-12BD-2 PT PT-H-600/2 S88H2P025 x
12-SS-0.792-132-H B-J Pipe to Safe-End UT UT-H-401/6 S88H2U101 x
S88H2U103 x
588H2CO31 UT Cal.
S88H2CO32 UT Cal.
89.11 A-15/02 2831 -1RCM-12BE-3 PT PT-H-600/2 S88H2P026 x
12-SS-0.792-132-H B-J Pipe to Safe-End UT UT-H-401/6 S88H2U100 x
$88H20102 x
S88H2CO31 UT Cal.
S88H20032 UT Cal.
4 e
4
t1 o
O Edwin I. Hatch Unit 2 1988 Winter Refueling Outage Class 1 Components Page 25 of 34 8
AME SECTION XI EXAM EXAM NDE EXAM / CAL.
RI REMARKS /8ASIC CAT. NO.
FIG. NO.
EXAMINATION / AREA METHOD PROCEDURE SHEET NO.
NI NRI GEOM /0THER CALIBRATION BLOCK NUREG-0313 EXAMINATI0hS (Cont *d) 89.11 A-17/02 2831 -1RCM-28AD-1 PT PT-H-600/2 S88H2P002 x
22-SS-1.184-128-H B-J Pump to Pipe UT UT-H-401/6 588H2P051 x
Linear and rounded S88H20094 x
indications. After S88H20097 x
flapping, weld was 588H20029 UT Cal.
found to be S88H2CO30 UT Cal.
acceptable.
D 9.11 A-l//U2 2031-lRCM-28AD-2 PT PT-H-600/2 588H2P003 x
28-SS-1.184-128-h B-J Pipe to Valve UT UT-H-401/6 S88H20095 x
588H20098 x
S88H20029 UT Cal.
S88H2CO30 UT Cal.
89.11 A-17/02 2831 -1 RCM-28AD-3 PT PT-H-600/2 588H2P004 x
28-SS-1.184-128-H li-J Valve to Elbow UT UT-H-401/6 S88H20096 x
S88H2U099 x
$88H20029 UT Cal.
S88H2CO30 UT Cal.
H 9.11 A-Ib/03 21131 -1 RCM-28AS-2 PT PT-H-600/2 588H2P028 x
28-SS-1.184-128-11 U-J Safe-End to Elbow UT UT-H-401/6
$88H20083 x
S88H20089 x
S88H20024 UT Cal.
588H20026 UT Cal.
89.12 A-16/03
-2831 -1 RCM-28AS-2LD-I PT PT-H-600/2 588H2P027 x
28-SS-1.184-128-H H-J Longitudinal Weld UT UT-H-401/6 S88H20084 x
Downstream on S88H20024 UT Cal.
Inside of Elbow
4-Edwin I. Hatch linit 2 1988 Winter Refueling Outage Class 1 Components Page 26 of 34 AM4L SECTION XI EXAM EXAM NDE EXAM / CAL.
RI REMARKS /8ASIC CA1. NO.
F IG. NO.
EXAMINATION / AREA METHOD PROCEDURE SHEET NO.
NI NRI GEOM /0THER CALIBRATION B80CK NUREG-0313 EXAMINATIONS (Cont'd) h9.12 A-16/UJ 2U31-1RCH-28AS-2LD-0 PT PT-H-600/2 S88H2P029 x
28-SS-1.184-128-H B-J Longitudinal Weld UT UT-H-401/6 588H2UO8S x
Downstream on S88H20024 UT Cal.
Outside of Elbow 89.11 A-10/03 2831-1RCM-28AS-8 PT PT-H-600/2 588H2P039 x
28-SS-1.184-128-H B-J Elbow to Valve UT UT-H-401/6 S88H2UO78 x
S88H20086 x
S88H20024 UT Cal.
SS8H20025 UT Cal.
89.12
'13 2831 -1 RCH-28AS-8LU-I PT PT-H-600/2 S88H2P038 x
28-SS-1.184-128-H B-J Longitudinal Weld UT UT-H-401/6 S88H2UO79 x
Upstream on S88H2C024 UT Cal.
Inside of Elbow 89.12 A-16/03 2831-1RCM-28AS-8LU-0 PT PT-H-600/2 S88H2P040 x
28-SS-1.184-128-H B-J Longitudinal Weld UT UT-H-401/6 588H2UO80 x
Upstream on S88H20024 UT Cal.
Outside of Elbow u 9.11 A-Ib/UJ 2uJi-IRCM-28AS-9 PT PT-H-600/2 S88H2P015 x
28-SS-1.184-128-H B-J Valve to Elbow UT UT-H-401/6 S88H20081 x
S88H20087 x
S88H20024 UT Cal.
S88H20025 UT Cal.
i
~
i
- u iw Edwin I. Hatch Unit 2 1988 Winter Refueling Outage Class 1 Components Page 27 of 34 Asrtt SECT 10tl XI EXAM EXAM NDE EXAM / CAL.
RI REMARKS /8ASIC CAT. NO.
FIG. No.
EXAMINATION / AREA METHOD PROCEDURE SHEET NO.
NI NRI GEOM /0THER CALIBRATION BLOCK NUREG-0313 EXAMINATIONS (Cont'd) 89.11 A-16/03 2831 -1 RCH-28AS-10 PT PT-H-600/2 S88H2P016 x
28-SS-1.184-128-H B-J Elbow to Pump UT UT-H-401/6 S88H2UO82 x
$88H20088 x
S88H20024 UT Cal.
S88H20025 UT Cal.
89.11 A-19/02 2831 -1RCM-2WD-1 PT PT-H-600/2 588H2P017 x
28-SS-1.184-128-il U-J Pump to Pipe UT UT-H-401/6 588H20056 x
S88H20058 x
S88H20006 UT Cal.
S88H20008 UT Cal.
89.12 A-19/02 2831 -I RCM-28BD-lLD PT PT-H-600/2 588H2P018 x
28-SS-1.184-128-H B-J Longitudinal Seam UT UT-H-401/6 S88H20057 x
Weld Extending 588H2C007 UT Cal.
Downstream B9.11 A-19/02 2831 -1RCM-288D-2 PT PT-H-600/2 S88H2P019 x
28-SS-1.184-128-H B-J Pipe to Valve UT UT-H-401/6 S88H20055 x
S88H2UO75 x
S88H20005 UT Cal.
S88H20008 UT Cal.
O m
._ w
-~~~
(
Edwin I. Hatch Unit 2 1988 Winter Refueling Outage Class 1 Components Page 28 of 34 A$ME SECTION XI EXAM EXAM NDE EXAM / CAL.
RI REMARKS / BASIC CAT. NO.
FIG. H0.
EXAMINATION / AREA METHOD PROCEDURE SHEET NO.
NI NRI GE0M/0THER CALIBRATION BLOCK NUREG-0313 EXAMINATIONS (Cont'd) 89.11 A-19/02 2831 -lRCM-2880-3 PT PT-H-600/2 S88H2P020 x
28-SS-1.184-128-H B-J Valve to Elbow UT UT-H-401/6 S88H20159 x
$88H20160 x
S88H20064 UT Cal.
588H2C065 UT Cal.
39.11 A-18/03 2831 -l RCM-2mS-2 PT PT-H-600/2 S88H2P041 x
28-SS-1.184 -128-H B-J Safe End to Elbow UT UT-H-401/6 S88H20090 x
S88H2UO91 x
588H2C027 UT Cal.
S88H2C028 UT Cal.
89.12 A-18/03 2831 -l RCM-28BS-2LD-I PT PT-H-600/2 588H2P042 x
28-SS-1.184-128-H B-J Longitudinal Weld UT UT-H-401/6 588H20092 x
Downstream on S88H2C028 UT Cal.
Inside of Elbow U 9.12 A-18/03 2B31 -l RCH-28BS-2 LD-0 PT PT-H-600/2 S88H2PO43 x
28-SS-1.184-128-H B-J Longitudinal Weld UT UT-H-401/6 588H20093 x
Downstream on S88H2CO28 UT Cal.
Outside of Elbow 09.11 A-18/03 2831 -l RCM-28BS-7 PT PT-H-600/2 588H2P007 x
28-SS-1.184-128-H B-J Elbow to Valve UT UT-H-401/6 588H2U122 x
S88H2Ul27 x
588H20022 UT Cal.
S88H20023 UT Cal.
AW
y
.m-Edwin I. Hatch Unit 2 1988 Winter Refueling Outage Class 1 Components Page 29 of 34 I
e ASME SECTION XI EXAM EXAH NDE EXAM / CAL.
RI REMARKS /8ASIC CAT. NO.
FIG. NO.
EXAMINATION / AREA METHOD PROCEDURE SHEET NO.
M NRI GEOM /0THER CALIBRATION BLOCK NUREG-0313 EXAMINATIONS (Cont'd) 89.11 A-18/03 2831 -1RCM-2WS-8 PT PT-H-600/2 S88H2P0C8 x
28-SS-1.184-128-H B,0 Valve to Elbow UT UT-H-401/6 588H2U123 x
S88H20128 x
S88H2C022 UT Cal.
S88H20023 UT Cal.
89.11 A-18/03 2831 -1 RCM-2WS-9 PT PT-H-600/2 588H2P011 x
28-SS-1.184-128-H U-J Elbow to Pump UT UT-H-401/6 S88H20124 x
$88H20129 x
S88H20022 UT Cal.
S88H2C023 UT Cal.
89.12 A-18/03 2831 -1RCM-28BS-9LU-I PT PT-H-600/2 S88H2P010 x
28-SS-1.184-128-H B-J Longitudinal Weld UT UT-H-401/6 S88H2U125 x
Upstream on Inside S88H2C022 UT Cal.
of Elbow I
89.12 A-18/03 2831 -lRCM-288S-9LU-0 PT PT-H-600/2 588H2P009 x
28-SS-1.184-128-H j
B-J Longitudinal Weld UT UT-H-401/6 S88H2U126 x
i Upstream on Outside S88H20022 UT Cal.
i of Elbow B 5. 50 A-21/03 2E?l-1RHRM-20RS-3 PT PT-H-600/2 S88'f2P057 x
20-SS-0. 879-130-H B-F Elbow to Pipe UT UT-H-401/6 S86H2P061 x
Linear indication.
S8flH2U166 x
Acceptable af ter 588H20071 UT Cal.
surface preparation.
o 0
Edwin I. Hatch Unit 2 1988 Winter Refueling Outage Class 1 Components Page 30 of 34 8
ASML SECTION XI EXAM EXAM NDE EXAM / CAL.
R1 REMARKS / BASIC CAT. NO.
FIG. NO.
EXAMINATION / AREA METHOD PROCEDURE SHEET NO.
NI NRI GEOM /0THER CALIBRATION BLOCK NUREG-0313 EXAMINATIONS (Cont'd) 89.12 A-21/03 2E11-1RHRM-20RS-3LU-I PT PT-H-600/2 588H2P005 x
20-SS-0. 879-130-H B -J Longitudinal Weld UT UT-H-401/6 S88H20168 x
Upstream on Inside 588H2C072 UT Cal.
of Elbow B9.12 A-21/03 2E11-1RHRM-20RS-3LU-0 PT PT-H-600/2 S88H2P006 x
20-SS-0. 879-130-H B-J Longitudinal Weld UT UT-H-401/6 588H2U167 x
Upstream on Outside S88H20072 UT Cal.
of Elbow 05.50 A-22/03 2E11 -1R!!RM-24 A-10 PT PT-H-600/2 S88H2P044 x
24-SS-1.186-131-H B-F Pipe to Elbow UT UT-H-401/6 -
588H20158 x
588H20063 UT Cal.
B $. 50 A-23/03 2E11 -1RHRM-248-10 PT PT-H-600/2 588H2P062 x
24-SS-1.186-131-H B-F Pipe to Elbow UT UT-H-401/6 S88H2U210 x
Acceptable per S88H2C088 UT Cal.
IWB-3514-3 B 5. 60 A-24/03 2E21 -1CS-10A-20 PT PT-H-600/2
$88H2P037 x
B-F Pipe to Safe-End UT UT-H-400/7 S88H2U199 x
10-9-IN-X-0. 600-79-H 588H2C082 UT Cal.
b$.10 A-24/03 2E 21 -1 CS-10A-21 PT PT-H-600/2 S88H2P045 x
13.2-IN-X-1.200-78-H B-f Safe-End to Nozzle UT UT-H-400/7 S88H2P055 x
Rounded indication.
UT-H-409/3
$88H20149 x
Acceptable after S88H20150 x
surface preparation.
S88H2U151 Weld Profile S88H2C048 UT Cal.
S88H20056 UT Cal.
e s'.-
o Q
O Edwin I. Hatch Unit 2 1988 Winter Refueling Outage C1 css 1 Components Page 31 of 34 p5gg SECTION XI EXAM EXAM NDE EXAM / CAL.
RI REMARKS / BASIC CAT. NO.
FIG. NO.
EXAMINATION / AREA METHOD PROCEDURE SHEET NO.
NI NRI GE0M/0THER CALIBRATION BLOCK NUREG-0313 EXAMINATIONS (Cont'd)
U5.$0 A-25/U3 2E21 -1 CS-108-19 PT PT-H-600/2 S88H2P056 x
10-9-IN-X-0. 600-79-H B -F Pipe to Safe-End UT UT-H-400/7
$88H20198 x
$88H20082 UT Cal.
hS.10 A-25/U3 2E21 -1CS-100-20 PT PT-H-600/2 S88H2P048 x
13.2-IN-X-1.200-78-H 8F Safe-End.., Nozzle UT UT-H-400/7 S88H2U138 x
UT-H-409/3 588H2U139 Weld Profile S88H20148 x
$88H20047 UT Cal.
S88H20056 UT Cal.
10.11 A-28/03 2G31 -lHWCUM-6-D-17 PT PT-H-600/2 588H2P050 x
2-H U-J Valve to Penetration "JT UT-H-400/7 S88H2U154 x
$88H2U155 x
$88H20059 UT Cal.
S88H20060 UT Cal.
D *>.12 A-28/0J 2G31 -I RWCUM-6-D-6 PT PT-H-600/2 588H2P053 x
6-SS-0.432-133-H B-J Pipe to Valve UT UT-H-401/6
$88H2U134 x
S88H2U135 x
S88H20043 UT Cal.
S88H2C044 UT Cal.
U 9.12 A-28/03 2G31 -1RWCUM-6-D-6LU PT PT-H-600/2 S88H2P052 x
6-SS-0.432-133-H B-J Longitudinal Seam UT UT-H-401/6
$88H2U1.33 x
Weld Extending 588H2C042 UT Cal.
Upstream
U m'hN O
Q C
Edwin I. Hatch Unit 2 1988 Winter Refueling Outage Class 1 Components Page 32 of 34 ASML SECT 10N X1 EXAM EXAM NDE EXAM / CAL.
RI REMARKS /8ASIC.
CAT. NO.
FIG. NO.
EXAMINATION / AREA METHOD PROCEDURE SHEET NO.
NI NRI GE0M/0THER CALI8 RATION BLOCK NUREG-0313 LXAMINATIONS (Cont'd) 89.11 A-28/03 2G31 -l RWCtf4-6-D-7 PT PT-H-600/2
$88H2P051 x
6-SS-0.432-133-H B-J Valve to Pipe UT UT-H-401/6
$88H20136 x
S88H2U137 x
$88H20045 UT Cal.
588H20046 UT Cal, b9. l l A-28/03 2G31 -l HWCUM-6-D-14 PT PT-H-600/2 S88H2P049 x
6-SS-0.432-133-H 8-J Pipe to Valve UT UT-H-401/6 S88H2U156 x
$88H2U157 x
$88H20061 UT Cal.
S88H20062 UT Cal.
39.11 A-28/03 2G31 -lRWCUM-6-D-15 PT PT-H-600/2 S88H2P065 x
6-SS-0.432-133-H B-J Penetration to Pipe UT UT-H-401/6 588H2U219 x
588H2U221 x
S88H20094 UT Cal.
S88H2C095 UT Cal.
39.11 A-28/03 2G31 -lRWCUM-6-D-16 PT PT-H-600/2 588H2P063 x
6-SS-0.432-133-H B-J Pipe to Valve UT UT-H-401/6 S88H20220 x
588H2U222 x
588H20094 UT Cal.
S88H20095 UT Cal.
u9.12 A-28/03 2G 31 -lRWCUM-6-D-16LU PT PT-H-600/2 S88H2P064 x
6-SS-0.432-133-H b-J J
Longitudinal Seam UT UT-H-401/6 S88H2U223 x
Weld Extcading 588 HIC 096 UT Cal.
Upstream G
tr M
a-ww.
O O>
Q Edwin I. Hatch Unit 2 1988 Winter Refueling Outage Class 1 Components Page 33 of 34 s
ASME SECIlON XI EXAM EXAM N0E EXAM / CAL.
RI REMARKS / BASIC CAI. NO.
FIG. NO.
EXAMINATION / AREA METHOD PROCEDURE SHEET NO.
NI NRI GEOM /0THER CALIBRATION BLOCK NUREG-Ubl9 EXAMINATIONS B9 ll A-10/03 2821 -1FW-12AA-12 MT MT-H-500/2 588H2M038 x
16-CS-100-1.031-53-H B-J Transition Piece UT UT-H-400/7 S88H2U162 x
No significant change To Nozzle S88H20163 in length or depth x
588H20164 x
when compared to 588H2C067 UT Cal.
past outages.
S88H2C068 UT Cal.
S88H2C069 UT Cal.
JET PUMP BEAM EXAMINATIONS RPV UT UT-H-414/2 S88H2U130 x
JPB-124-H Jet Pump Beams S88H2C040 UT Cal.
Crack-like indi-No. 1-20 cation in. jet pump beam #20. See INF 188H2004. Jet pump beam was removed and replaced.
JPB-124-H Jet Pump Beams S88H2U218 x -
Replacement Beam No. 20 S88H20080 UT Cal.
Baseline Exam.
S88H20093 UT Cal.
- N*-
l l
Edwin I. Hatch Unit 2 1988 Winter Refaeling Outage Class 1 Components Page 34 of 34 e
A5ME SECTION XI EXAM EXAM NDE EXAM / CAL.
RI REMARKS / BASIC CAT. NO.
FIG. NO.
EXAN*MATION/ AREA METil0D PROCEDURE SHEET N0.
NI NRI GE0M/0THER CALIBRATION BLOCK SHROUD HEAD BOLTS Shroud llead Bolts UT UT-H-418/0 588H2UO36 x
INC-ShB-136-H 1 thru 36 588H2C001 UT Cal.
Crack-like indi-cations found. See INF 188H2002. Six of the 8 cracked bolts were removed and re-l placed. No re-exam required at this time per GE MDE 39-0286.
Re-exam next outage.
Exam figures referenced throughout these tables are a part of the SCS-ISI Examination Plan and can be reviewed at the Plant Site.
It.Fs ref erenced throughout these tables are part of the SCS Final Report and may be reviewed at the Plant Site.
1 s
O I
1
)
h l
SUPNARY OF l
CLASS 2 COMPONENTS
,!0
{
l l
l O
t-t
u
,m
/7
{}%
%,) ~
Ns' Edwin I. Hatch Unit 2 1988 Winter Refueling Outage Class 2 Components Page 1 of 10 ASiiE SECTION XI EXAM EXAM NDE EXAM / CAL.
RI REMARKS / BASIC CAT. NO.
FIG. NO.
EXAMINATION / AREA METil0D PROCEDURE SHEET NO.
NI NRI GEOM /0THER CALIBRATION BLOCK RESIDUAL HEAT REMOVAL SYSTEM Cb.10 B-2/02 2E11-2RHR-PMI-A MT MT-H-500/2 S88H2M015 x
Limited MT Exam.
C-G RilR Pump A VT-H-710/2 S88H2V048 Sati sfactory Supplemented by VT.
Inlet Nozzle Weld to.lu u-2/02 2El l-2idlR-POP-A-1 MT MT-H-600/2 S88H2M011 x
C-G Flange to Elbow RilR Pump A Co.10 U-2/02 2E11-2RHR-POP-A-18C/
MT MT-H-500/2 588H2M012 x
C-G Shaf t-Elbow to BC RHR Pump A Cb.10 B-2/02 2E11-2RHR-POP-A-2 MT MT-H-500/2 588H2M013 x
C-G Elbow to Flange RHR Pump A L$.11 B-23/03 2E11-2RHR-8-FPS-8 MT MT-H-500/2 S88H2M067 x
Linear indication.
C-F 45-Degree Elbow to 588H2M070 x
See INF 188ti2016, 45-Degree Elbow After grinding, weld was re-examined ano found to be acceptable.
C 5.11 B-23/03 2E11-2RHR-8-FPS-21 MT MT-H-500/2 588H2M050 x
C-F Elbow to Pipe L3.40 B-14/05 2El l-2RHR-16 A-DS-7APS-1 MT MT-H-500/2 588H2M044 x
C-C Device 2E11-RHR-H321 e-ae e-
,L E
43 0 m
(y J'
l Edwin I. Hatch Unit 2 1988 Winter Refueling Outage Class 2 Congonents Page 2 of 10 t
ASML i
StCTIou X1 EXAM EXAM NDE EXAM / CAL.
RI REMARKS / BASIC CAT. NO.
FIG. NO.
EXAMINATION / AREA METHOD PROCEDURE SHEET NO.
NI NRI GEOM /0THER CALIBRATION BLOCK l
RESIDUAL HEAT REMOVAL SYSTEM Cont'd) l C3.40 B-14/05 2E11 -2RHR-16A-DS-7 APS-2 MT MT-H-500/2 S88H2M045 x
C-C Device 2E11-RitR-H321 l
C5.11 B-14/05 2E11 -2RilR-16A-DS-8 MT MT-H-500/2 S88H2M043 x
C-F Pipe to Elbow Ca.40 B-29/03 2 Ell-2RilR-16A-PD-C-3PL-1 MT HT-H-500/2 588H2M014 x
l C-C Device 2E11-RHR-H180 1
C3.40 B-29/03 2 Ell-2RliR-16A-PD-C-3PL-2 MT
'i-H-500/2 588H2M014 x
- i C-C Device 2E11-RHR-H180 l
l LJ.40 B-29/03 2E11 -2RilR-16A-PD-C-3PL-3 MT MT-H-500/2 S88H2M014 x
l C-C Device 2E11-RHRAll80 C3.40 B-29/03 2 Ell-2RilR-16A-PD-C-3PL-4 MT MT-H-500/2 S88H2M016 x
Linear indication.
C-C Device 2E11-RHR-H180 588H2M020 x
After flapping, weld was re-examined and found to be acceptable.
Cb.11 B-36/02 2E11-2RiiR-20B-D-3 MT MT-H-500/2 S88H2M068 x
Linear indication.
C-F Pipe to 45-Degree S88H' WJ59 x
See INF 188H2017.
I Elbow After grinding, I
weld was re-examined and found to be acceptable.
9%
\\
O' V
s Edwin I. Hatch Unit 2 1988 Winter Refueling Outage Class 2 Components Page 3 of 10 e
t ASME SECTION XI EXAM EXAM liDE EXAM / CAL.
R1 REMARKS / BASIC CAT. No.
FIG. NO.
EXAMINATION / AREA METHOD PROCEDURE SHEET NO.
NI NRI GEOM /0THER CALIBRATION BLOCK RESIDUAL HEAT REMOVAL SYSTEM Cont'd)
CS.11 0-36/02 2E11-2RHR-208-D-8 MT MT-H-500/2 S88H2M005 x
C-F Elbow to Pipe CS.11 B-38/03 2E11-2RHR-200-D-8 MT MT-H-500/2 588H2M019 x
C-F Pipe to Elbow L.s. 4 0 u-38/03 2El l -2RHR-20D-D-10PL-1 MT MT-H-500/2 S88H2M026 x
C-C Device 2E11-RHR-H174 C3.40 u-38/03 2 Ell-2RHR-200-0-10PL-2 MT MT-H-500/2 S88H2M026 x
C-C Device 2E11-RHR-H174 LJ.40 81-38/03 2E11 -2RHR-200-D-10PL-3 MT MT-H-500/2 588H2M026 x
C-C Device 2E11-RHR-H174 C3.40 B-38/03 2E11-2RHR-200-D-10PL-4 MT MT-H-500/2 S88H2M026 x
C-C Device 2f'l-RHR-H174 C5.11 B-38/03 2E11 -2RHR-200-D-11 MT MT-H-500/2 588H2M025 x
C-F Pipe to Branch Connection LORL SPRAY SYSTEM C 3.4 L, B-53/02 2E21-2CS-10A-TL-15 MT MT-H-500/2 S88H2M049 x
C-C Pipe to Torus Penetration
.o
- - +
.. _ _ 7__
O O
O Edwin I. Hatch Unit 2 1988 Winter Refueling Outage Class 2 Components Page 4 of 10 P
ASME SECTIOra XI EXAM EXAM NDE EXAM / CAL.
RI REMARKS / BASIC CAT. NO.
FIG. NO.
EXAMINATION / AREA METHOD PRZEDURE SHEET NO.
NI NRI GE0M/0THER CALIBRATION BLOCK CORE SPRAY SYSTEM (Cont'd)
C3.40 U-61/03 2E21-2CS-20A-TS-1 VT VT-H-710/2 S88H2V209 Satisfactory Inaccessible for C-C Torus Penetration surface exam X-208A to Pipe C3.40 u-61/03 2E21-2CS-20A-TS-12PS-1 MT MT-H-500/2
$86lt2M021 x
C-C Device 2E21-CS-H708 C3.40 B-61/03 2E21-2CS-20A-TS-12PS-2 MT MT-H-500/2 588H2M022 x
C-C Device 2E21-CS-H708 C3.40 E-t1/03 2E21 -2CS-20A-TS-12PS-2A MT MT-H-500/2 S88H2M027 x
C-C Device 2E21-CS-R41 atIGH PRESSURE COOLANT INJECTION SYSTEM CS.21 8-66/03 2E41 -2HPC I-14-R-37 HT MT-H-500/2 S88H2M028 x
14-CS-80-0. 750-116-H 0-F Pipe to Elbow UT UT-H-400/7 588H2UO59 x
S88H20060 Contour Report S88H20009 UT Cal.
C S. 21 8-b6/03 2E41-2HPCI-14-R-43 MT MT-H-500/2 588H2M059 x
14-CS-100-0. 938-43-H C-F Pipe to Elbow UT UT-H-400/7 588H2U211 x
S88H2C089 UT Cal.
(.ts. I l H-W /OJ 2L41-2HPCI-20TD-8 MT MT-H-500/2 588H2M008 x
C-f Elbow to Pipe s
A
p n
V
's-)
Edwin I. Hatch Unit 2 1988 Winter Refueling Outage Class 2 Components Page 5 of 10 ASMI SECTION XI EXAM EXAM NDE EXAM / CAL.
RI REMARKS / BASIC CAT. NO.
FIG. NO.
EXAMINATION / AREA METHOD PROCEDURE SHEET NO.
NI NRI GEOM /0THER CALIBRATI0t1 BLOCK lilGil PHLSSURE COOLANT INJECTION SYSTEM (Cont'd)
C3.40 0-b9/03 2E41-2HPCI-20-TD-ISPS-1 MT MT-H-500/2 588H2M024 x
C-C Device 2E41-HPCI-R22 C3.40 B-69/03 2E41 -2HPCI-20-TD-I SPS-2 MT MT-H-500/2 S88H2M024 x
C-C Device 2E41-HPCI-R22 4
}
Co.11 8-69/03 2E41-2HPCI-20-TD-19 MT MY-H-500/2 S88112M051 x
i C-F Pipe to Reducer MAIN STEAM SYSTEM C3.40 B-7/03 2N11-2MSA-16A-13PL-1 MT MT-H-500/2 58M2M018 x
C-C Device 2N11-MS-R69 C3.40 0-7/03 2N11-2MSA-16A-13PL-2 MT MT-H-500/2 588H2M318 x
C-C Device 2N11-MS-R69 C3.40 B-7/03 2N11-2MSA-16A-13PL-3 MT MT-H-500/2
$88H2M018 x
C-C Device 2 Nil-MS-R69 C3.40 B-7/03 2 Nil-2MSA-16A-13PL-4 MT MT-H-500/2 S88H2M010 x
C-C Device 2N11-MS-R69 CJ.40 B-7/03 2N11-2MSA-16A-13at-5 MT 18T-H-500/2 588H2M018 x
l C-C Device 2N11-MS-R69 l
h9
y
,y w
7'}
/%
d
([
(/
i Edwin I Natch Unit 2
'938 Winter Refueling Outage Class 2 Components Page 6 of 10 s
A$ML SECTION XI EXAM EXAM NDE EXAM / CAL.
RI REMARKS / BASIC cal. NO.
FIG. NO.
EXAMINATION / AREA METHOD PROCEDURE SHEET NO.
NJ
- NRI, GEOM /0THER CALIBRATION BLOCK MAIN SILAM SYSYEM (Cont *dJ CJ.40 B-7/03 2N11-2MSA-16A-13PL-6 MT MT-H-500/2 S88H2M018 x
C-C Device 2N11-MS-R69 C3.4 0 B-7/03 2N11-2MSA-16A-13PL-7 MT MT-H-500/2 588H2M018 x
C-C Device 2N11-t1S-R69 q
CJ.40 B-7/03 2N11-2MSA-16A-13PL-8 MT MT-H-500/2 588H2M018 x
C-C Device 2N11-MS-R69 i
C5.21 B-7/03 2N11-2MSA-16C-16 MT MT-H-500/2 S88H2M034 x
16-CS-100-1. 031 H C-F Pipe to Pipe UT UT-H-400/7 S88H2U140 x
S88H20050 UT Cal.
C 5. 31 8-9/03 2N11 -2MSA-24A-11BC/
MT MT-H-500/2 588H2M055 x
12-H C-F 2N11-2MSA-6 A-SJ AE UT UT-H-400/7 588H20152 x
Pipe to Branch 588H20153 x
Connection
$88H20057 UT Cal.
S88H20058 UT Cal.
C3.40 8-9/03 2N11-2MSA-24A-11PL-1 MT MT-H-500/2 588H2M023 x
C-C Device 2N11-MS-A60 C3.40 B-9/03 2N11-2MSA-24A-11PL-2 MT MT-H-500/2 S88H2M023 x
C-C Device 2N11-MS-A60
O Cs O
s Edwin I. Hatch Unit 2 1988 Winter Refueling Outage Class 2 Components i
Page 7 of 10 8
ASML SECTION XI LxAM EXAM NDE EXAM / CAL.
RI iEMARKS/ BASIC CAT. No.
FIG. NO.
EXAMINATION / AREA METii0D PROCEDbRE SHEET NO.
NI NRI GEOM /0THER CALIBRATION BLOCK flAIN STEAM SYSTEM (Cont'd)
C3.40 b-9/03 2Ni l-2MSA-24A-11 PL-3 MT MT-H-500/2 S89H2M023 x
C-C Device 2N31-MS~A60 CJ.40 u-9/03 2 Nil-2MSA-24A-11PL-4 MT MT-H-500/2 S88H2M023 x
C-C Device 2 Nil-MS-A60 03.40 B-9/03 2N11-2MSA-24A-llPL-5 MT h!-H-500/2 S88H2M023 x
C-C Device 2 Nil-MS-A60 CJ.40 B-9/03 2N!1-2ilSA-24A-llPL-6 MT MT-H-500/2 S88H2M023 x
C-C Device 2N11-MS-A60 CJ.40 B-9/03 2 Nil-2MSA-24A-11PL-7 MI MT-H-500/2 S88H2M023 x
L-C Device 2 Nil-MS-A60 LJ.40 0-9/03 2hil-2MSA-24A-llPL-8 MT NT-H-500/2 S88H2M023 x
C-C Device 2 Nil-MS-A60 CJ.40 B-10/03 2 Nil-2MSA-24B-IPS-1 MT MT-H-500/2 588H2M057 x
Linear Indications.
C-C Ptpe Support
$88H2MD65 x
See INF 188H2015, S88H2M072 x
After grinding, and
$88H2M073 x
re; air welding, welds found to be acceptable.
4 s2
O
- C Euin I. Hatch Unit 2 1988 Winter Refueling Outage Class 2 Components Page 8 of 10 8
A5ME SECTION XI EXAM EXAM NDE EXAM / CAL.
RI REMARKS /8ASIC CAT. NO.
FIG. No.
EXAMINATION / AREA METHOD PROCEDURE SHEET NO.
NI NRI GEOM /0THER CALIBRATION BLOCK MAIN STEAM SYSTEM (Cont'd)
CJ.40 u-10/03 2N11-2MSA-248-IPS-2 MT MT-H-500/2 S88H2M058 x
~ 8.inear indication.
C-C Pipe Support 588H2MD66
'x See INF 188H2015.
S88H2M071 x
Af ter grinding weld found +- Se acceptable.
CS.21 3-10/03 2N11-2MSA-248-18 MT MT-H-500/2 S88H2M033 x
12-H C-f Tee to Pipe UT UT-H-400/7 S88H2U121 x
588H2CO39 UT Cal.
C3.40 0-11/03 2N11-2MSA-24C-6PL-1 MT MT-H-500/2 S88H2M017 x
C-C Device 2N11-MS-R54 C3.40 B-11/03 2 Nil-2MSA-24C-6PL-2 MT MT-H-500/2 588H2M017 x
C-C Device 2Nll-MS-RS4 C3.40 B-11/03 2N11-2MSA-24C-6PL-3 MT MT-H-500/2 588H2M017 x
C-C Device 2N11-MS-R54 C3.40 0-11 /03 2N11-2MSA-24C-6PL-4 MT MT-H-500/2 S88H2M017 x
C-C Device 2N11-MS-R54 C3.40 0-11/03 2N11-2MSA-24C-6PL-5 MT MT-H-500/2 S88H2M017 x
C-C Device 2N11-MS-R54 03
.y Edwin I. Hatch Unit 2 1988 Winter Refueling Outage Class 2 Components l
Page 9 a
- 10 a
ASME SECTION XI EXAM EXAM NDE EXAM / CAL, etI REMARKS / BASIC CAT. NO.
FIG. No.
EXAMINATION / AREA METHOD PROCEDURE SHEET NO.
NI NRI GEOM /0THER CALIBRATION BLOCK MAIN $ TEAM SYSTEM (Cont'd)
C3.40 B-11/03 2N11-2MSA-24C-6PL-6 MT MT-H-500/2 588H2M017 x
C-C Device 2N11-MS-R54 C3.40 B-11/03 2N11-2MSA-24C-6PL-7 MT MT-H-500/2 588H2M017 x
C-C Device 2N11-MS-R54 C3.40 0-11/03 2N11-2MSA-24C-6PL-8 MT MT-H-500/2 588H2M017 x
C-C Device 2N11-MS-R54 C3.40 B-12/03 2N11-2MSA-24D-8PL-5 MT MT-H-500/2 588H2M054 x
C-C Device 2N11-MS-R51 C3.40 B-12/03 2N11-2MSA-24D-8PL-6 MT MT-H-500/2
$88H2M054 x
C-C Device 2N11-MS-R51 C3.40 B-12/03 2 Nil-2MSA-24D-8PL-7 MT MT-H-500/2 588H2M054 x
C-C Device 2N11-MS-R51 C3.40 B-12/03 2N11-2MSA-24D-8PL-8 MT MT-H-500/2 588H2M054 x
C-L Device 2N11-MS-R51 LS.21 B-12/03 2N11-2MSA-24D-9 MT MT-H-500/2 588H2M032 x
C-F Pipe to Elbow UT UT-H-400/7 588H2U116 x
12-H S88H2CO35 UT Cal.
4 e
D
O-C Edwin I. Hatch Unit 2 1988 Winter Refueling Outage Class 2 Components Page 10 of 10 ASME SECTION XI EXAH EXAM NDE' EXAM / CAL.
RI REMARKS /8ASIC CAT. NO.
F IG. NO.
EXAMINATION / AREA METHOD PROCEDURE SHEET NO.
NI NRI GEOM /0THER CALIBRATION BLOCK AUGMENTED EXAMINATIONS B73A/01 2E41-2HPCI-6-CS-1 PT PT-H-600/2 588H2P001 x
BC to Flange B-73/03 2E41 -2HPCI-16-TS-9 MT MT-H-500/2 588H2M010 x
Pipe to Elbow B-7J/03 2E41 -2HPCI-16-TS-18 MT MT-H-500/2 588H2M009 x
45 Degree Elbow to Tee NUREG-0619 EXAMINATIONS 11-83/02 2G31 -2RWCU-4-2FW-3052 UT UT-H-400/7 S88H2U204 x
4-H Tee to Pipe
$88H2U205 x
$88H20083 UT Cal.
S88H20084 UT Cal.
B-83/02. 2011-2CRD-3-2FW-1611 UT UT-H-400/7 588H2U202 x
4-H Pipe to Reducer S88H2U203 x
$88H20083 UT Cal.
S88H20084 UT Cal.
B-83/02 2011-2CRD-4-2FW-1611 UT UT-H-400/7 588H2U200 x
4-H Reducer to Tec S88H2U201 x
588H2C083 UT Cal.
$88H20084 UT Cal.
Exam Figures referenced throughout these tables are a part of the SCS-ISI Examiution Plan and can be reviewed at the Plant Site.
I INFs referenced throughout these tables are part of the SCS Final Report and may be reviewed at the Plant Site.
,e s
l l
l
(
i O
l
SUMMARY
i 0F CLASS 1, 2, AND 3 PRESSURE TESTS O
]
f O
S/
, PRESSURE TESTING This section of the report provides a discussion of the pressure tests that O
were performed during the Plant Hatch Unit 2 Winter 1988 Refueling Outage.
V These pressure tests were performed for the purpose of in;ervice inspection on selected Class 1, 2,
and 3 piping systems.
The pressure tests and their boundaries are identified in the inservice examination plan prepa red by Southern Company Services, Revision 1.
All pressure tests were performed in accordance with ASHE Section XI, 1980 Edition with Addenda through Winter 1981 All tests were witnessed and/or reviewed by the resident ANI/ANII.
The completed test reports are available for review in the Records Management Department at the plant site.
TESTING Class 1 No class 1 Hydrostatic Tests were performed during this outage.
A Class 1 g
E System Leakage Test, 2821-LT-1, was perfonned prior to unit start-up per ASME XI, Section IWA-5211(a).
This test was performed using GPC Proce. dure 42IT-TET-006-2S under Mainterance Work Order 2-87-3043.
The pressure and examination boundary was in accordance with ASME Section XI, Table IWB-2500-1 Examination Category B-P, Note 1.
Only minor leakage was detected during YT-2 examination and after some repair work the Class 1 System was deemed acceptable by plant engineering.
Any Class 1
system Components not examined during performance of C.
42tr-Ter-ooe-2s were exe 4#ed ovr4#9 riemt ster +-en
- s4#9 cec arocedure 42IT-TET-001-0S.
The pressure boundary was in accordance with ASME Section
}
XI, Table IWB-2500-1 Examination Category B-P, Note 1.*
Class 2 Six Class 2 Hydrostatic Tests were performed during the outage.
These g
hydrostatic tests were perfonned per ASME XI, IWA-5211 (d ).
The tests were performed in accordance with GPC procedure 42IT-TET-001-0S.
Listed below are the Class 2 Hydrostatic Tests and accompanying Maintenance Work Orders:
2E11-HT-2 MWO 2-87-3034 2E11 -HT-14 INO 2-87-3045 l
2 Ell-HT-3 fNO 2-87-3035 2 Ell-HT-23 tiWO 2-87-3039 l
2 Ell-HT-6 ffWO 2-87-3037 2 Ell-HT-24 FWO 2-87-3036 Only minor leakage was detected during YT-2 examination and all tests results were deemed acceptable by plant engineering.
l
- Valve 2821-F001 and 2B21-F002 were disassembled prior to test, however, l
during test they were both in their normally closed position.
As a result, valve 2821-F002 did not experience test pressure.
J G?
Class 3 Three Class 3 Hydrostatic tests were performed during the ou tage.
These
' (]-
hydrostatic tests were performed per ASME XI, IWA-5211 (d) and in accordance
-with GPC Procedure 42IT-TET-001-0S.
Only minor leakage was detected and after engineering evaluation all tests results were deemed acceptable.
Listed below are the Class 3 Hydrostatic Tests and accompanying Maintenance Work Orders:
2P41-HT-13 tiWO 2-87-3041 2P41-HT-28 HWO 2-87-3040 2P41-HT-29 HWO 2-87-3042 Class 3 Inservice Test One Class 3 Inservice Test was performed per ASME XI, IWA-5211(c).
A special l
purpose procedure, 42SP-011388-0W-1-2S, was written to perform the test.
This
. test was on the Residual Heat Removal Service Water System and is identi,fied as test 2E11-IT-1.
O
]
s O
dd O
as
O i
'S SlHiARY OF VISUAL EXAMINATIONS CLASS 1, 2, AND 3 COMPONENT SUPPORTS O
J O
q O
ca
COMPONENT SUPPORT EXAMINATIONS p) -
This section of the report provides a discussion of the visual examinations
'v performed on selccted component supports on Hatch Unit 2.
The subject examinations were performed prior to and during the Refueling / Maintenance Outage.
Examinations were perfonned using SCS Procedure VT-H-730 (VT-3).
The procedure and all examination data sheets are available for review at the plant site.
Examinations Class 1 Twenty-eight (28) component supports from the Main Steam.
Reactor Recirculation, and HPCI Systems were visually examined.
Two reportable indications were found.
Class 2 Fifty-two (52) component supports from the following systems were vistially examined:
Residual Heat Removal, Core Spray, HPCI,. Main Steam Auxiliary.
Seventeen (17) of these Class 2 component supports were found unacceptable.
Class 3 Eighty-five (85) component supports from the following Class 3 systems were visually examined:
Main Steam Relief Valve, Fuel Pool Cooling, RHR Service g.Q Water, and Plant Service Water.
Four (4) of these Class 3 component supports were found to be unacceptable.
]
O
Summary of Visual Examinations This section of the report presents an explanation of the Summary of Component
.r Support Examinations (Summary Table).
The Summary Table provides information
\\
for the visual examinations performed prior to and during the 1987 Unit 1 Refueling / Maintenance Outage to satisfy the requirements of ASME Section XI and contains the results of each visual examination perfomed.
1.
ASME Class The purpose of this column is self-explanatory.
2.
Support This column is for -the number assigned to a particular device on a given system.
For example, 2B21-MS-H4 indicates that the mark number for that particular Unit 2 main steam device is H4.
3.
Figure Number The number given is the ISI Figure Number on which the location of the pipe support or hanger is depicted.
These drawings are found f ri the Southern Company Services-issued long-term inservice examination plans for Class 1, 2, and 3 Components at Edwin I. Hatch Nuclear Plant Unit 2.
4 Type The type is divided only into
- spring, snubber (hydraulic or mechanical), and simple-type hangers, d
V
- 5. -10. Examina tion Resul ts,
]
These columns give the examination resul ts,
INFs generated, MWO numbers, and re-examination results if applicable.
11.
Remarks Comments will be made in this column which describe any deficiency identified during the examination along with infomation concerning any T
additional evaluation performed.
l 0
Fage le.
1 1968 E.I. Mim UNIT 2 PlPE StWORTS
/~T'
'D R X SUFM RT FIGURE TYPE REStLTS RENRT NO.
!W NO.
MWO NO.
RES11TS RENRT NO.
IkMRKS ttASS NUMER 1
2B21-MS-H3 A-6 SPRING U
Se&2V093 188H2012 2-88-0970 A 58& lye'4 1MREER SPRIE CANSETTING 1
2B21-MS-R45 A4 SNUBER A
$88KN091 NA NA M
M M
i 2B21-MS446 A-6 SHER A 588HN092 M
M M
M NA 1
2B21-MS-R2 A4 SPRING A
S88KN107 NA NA NA M
M 1
2B21-MS-N1 A4 SPRING A
S88KN154 M
M 14 M
M k
1 2B21-MS-R47 A4 SMJBER A S88H2Y094 m
M NA NA NA 1
2B21-MS-R48 A4 SMJBER A S88K'.4095 NA M
NA NA NA 1
2B31-SSA21 A-16 SMJBBER A
$88KN222 M
NA M
M NA 1
2831-SSA22 A-16 SHER A
$88}EV223 M
M M
M M
i 2B31-SSA8 A-16 SMJBBER A
$88H2V057 M
NA NA M
M 4
1 2B31-SSA7 A-16 SMDBER A
$88H2V058 NA M
M NA NA
]
1 2831-SSA6 A-16
. 9dJBER A S88H2V059 M
M M
M M
tj
,1 2831-HB5 A-18 SPRING A
S88H2V060 M
M NA M
M 1
2831-HB6 A-18 SPRING A
588H2V061 NA NA NA M
NA 1
2831-HB7 A-18 SPRING A
S88H2V062 M
NA M
M NA 1
2831-SSB2 A-18 SMJBER A
$88H2V063 m
M NA M
M 2B31-SSB3 A-18 SMKR A 586fGV064 NA M
M M
NA 1
2B31-SSB4 A-18 SMER A
$88KN065 h-M NA M
M 1
2831-ESB5 A-18 SMJPEER A 588H29066 NA M
P4 M
NA 1
2B31-SSB6 A-18 SNUBBER A SSSKN067 14 NA M
M M
1 LE41-PCI-R110 A-25 SMKR A E86HiV096 M
M NA
'A M
1 EE414CI-H103 4-26' SPRING V
$88H2'M7 188K?013 2-SS-1006 A 588H2V237 IMROPER SPRING CAN KTTING 1
21414Ci-Fit! A-26 SMJEKR A 3&M N093 NA NA M
V M
1 iE41-ICl-Ell 2 A-26 SNUEi(R A iM GYO99 G
h4 NA W
M G
I ge i+0.
2 l
1988 E.I. MTCH LNii 2 PlFE Suf90RTS
/~]
O ASME SUF90RT FIGURE TYPE RESLLTS REPORT NO.
INF NO.
MWO NO.
RESILTS REPORT N0.
REMRKS CLASS NLMIER LE41-HPCI-R113 A-26 SNUBBER A 588H2V100 W
NA NA M
M 1
2E41-f0Cl-R114 A-26 SNUBBER A
$88KN101 M
NA NA NA M
i 2E41-HFCI-R115 A-26 SNJBf(R A
$88H2V102 M
NA NA M
M 1
2E41-HPCI-H109 A-26 SPRING A
$88KN155 NA NA M
M M
2 2N!!-W3-R65 B-6 HANER A
S88HWO46 M
NA NA NA M
t 2
2N11-f9S-R67 B-6 SWBBER A S88H2V116 NA NA M
NA NA h
2 2N!!-W3-R68 B-6 SWERR A S88H2Y045 M
NA NA NA NA 2
ENil-MS-R48 B-9 SWBER A S88KN044 M
NA NA NA NA 2
2 Ell-RHR-H195 B-15 SPRING U
S88KN034 188H2011 2-88-0975 A
$88H2V228 IMR0fER SPRIE CM SETTING 2
2 Ell-RHR-H318 B-17 SPRING A
S88KN121 m
NA M
M M
2 2E!!-RHR-R382 B-18 SMJBBER A S88H2V152 M
NA NA M
M
]
2 2 Ell-RHR-R124 B-18 RESTMINT A S88H2V173 NA NA M
NA M
.y 2
2 Ell-RHR-H57 B-18 SPRING U
588KN174 188H20ll 2-88-0975 A S88H2V233 1490ffR SPR12 CAN SETTING LOOSE JAM MJT 2
2E!!-RHR-R123 B-18 SMJEBER A S8882V175 M
NA M
M NA A+
E lill-RHR-458 B-18 ACOR U
588H2V171 188H2010 2-88-0929 A S88HN213 LOOSE NJT 2
2 Ell-M -R125 B-18 SNUEICR A SG8KN172 NA NA NA NA M
2 2 Ell-M -R38!
B-18 RESTFAINT A S88HN153 M
M NA NA M
2 2E11-PhR+46 B-21 SPRING A
48KN119 M
NA NA NA M
i ZEll-M -K!C5 6-22 SPRING A
588HN182 M
M M
M M
2 Ell-M -R279 B-22 RESTRAINT U SB8H2V185 IB8H2010 2-S8-0?28 A S$8H;V212 LOOSE E
[
LEll-M -R298 B-22 FISTRAINT U S!2MN124 IB8H1910 2-68-0930 A 586H2V214 EENT FISi;AINT 2 Ell-N+46 3-23 Wr0ER A
$88KN215 V
NA M
M M
V 2E!!-%R-H175 B-26 SPRING V
SiSBN032 188H2011 2-88-0975 A S!5HN229 IMPR0ffR 5H 195 CAN SETTis3 Gf
Page ho.
3 1988 E.I. HAfDi LNii 2 Nif SUFMRIS
[,)
ASE SUPPORT FIGURE TYPE RESlLTS REFORT NO.
!!f W.
NWO NO.
RESLLTS REFORT NO.
REMD.S Q. ASS NLM(R 2
EEll-RHR-H182 B-28 SPRING V
588KN033 IS$f0li 2-88-0975 A
$88KN231 IMR0fiRSPRIM CAN SETTING 2
2 Ell-M -H181 B-28 SPRING U
S88KN031 188H2011 2-88-0975 A S88HN230
!MR0fER SPRIE CAN SETTING 2
2 Ell-M -H179 B-29 SPRING A
S88K4030 M
M M
NA M
2 2 Ell-RHR-H183 B-30 SPRING V
Se8H2V027 188HNil 2-88-0975 A 588H2VE32 IMROF(R SPRIE OW SETTING 2
2 Ell-RHR-H186 B-31 SPRING A
S88KN025 NA NA NA M
NA 2
Efil-RHR-H187 B-33 SPRING A
588K?V024 te NA NA M
NA 2
2 Ell-RHR-H314 8-39 SPRIM3 U
S88KN104
[88KNil 2-88-0975 A S88HN227 IMA@ER SPRilEi CAN SETTING 2
2 Ell-RHR-R317 B-39 RESTRAINT A S88KN103 70 NA M
NA M
l 2
2 Ell-RHR-HR149 B-44 liiR-EST A
$88H2V!20 NA M
M M
NA 2
2E21-CS-H109 8-64 SPRING A
S88f0026 NA NA M
M M
2 2E41 M Cl-H31 B-65 MMsER U
S88H2V029 188H2001 2-86-0287 A S88H2V208 GAP KTEEN MJTS
[
l AND BREATE L
2 2E41 M CI-R53 B-65 RESTRAINT A S88KN188 NA NA M
NA iM 2
2E41 MCI-H28 B-65 HfNGER A
588HNIE6 PM M
NA M
NA l
2 2E41 MCI-H29 B-65 HAMiER A
588KN187 NA iM M
M NA 2
2E41 4 Cl-A709 B-66 ANDOR A
S86H29062 PA M
M NA SEE ALSO S88KNii3 2
2E41-HPCI-HR710 IK 6 NGR-REST U S88h3'083 186KE5 2-8M72 A S&BKN242 EGSEPLWc SEPARAT':N SEE ALS:
586W;il AND 188KKC'A l
l 2
2E41-4CI-H33 B-66 MtC{R U
S86H2V076 ISSKM5 2-ES-0672 A 588H2V241 LO23E WJi EEE ALK SS8KN132 AND 18&OX'A 2
EE414CI-H93 B-66 Hin3ER A
ESKN073 M
M M
V 5EE f(E iSLHis:M l
l G1
Pee Ib.
4
~ 1988 E.I. MICH LN1T 2 PlfE SlMORTS (G
U ASE SUPPORT FIGUE
-TYPE RESULTS EFORT NO.
!W N0.
NWO N0.
ESl1TS REPORT NO.
ENARKS CLASS W.mKR 2
2E41-tCl-R104 6-66 RESTMINT U S88KN075 188K005 2-BS-0672 U*
S88H2V243 LODSE NUT SEEALSO S88H2V200 AM 188H2005A
+6PC ENSIEERil6 ACCEPT AS IS 2
2E41-t9CI-HR101 B-66 HGR-EST A S88KV160 M
M M
NA NA 2
2E41-tFCl-R107 B-66 RESTMINT A S88E4078 M
NA M
M SEE ALSD S88WV201 5
2 2E41-}FCl-A102 S-66 RESTMINT U S88RV199 188K2005A2-88-1120 A S88KN238 STRUCTUR$.
'l
[(6RADAT10N
}
2 2E41-HPCI-tf97 B-66 HANGER A
S88H M 80 NA NA M
M SEE ALSO 588H2Vl95 2
2E41-tPCI-R106 B-66 RESTMINT A 588H2V161 M
M M
M NR i
i 2
E41-WCl-H96 P-66 F#NiER A
SC2Y081 M
NA NA NA SEE ALSO 6
S68H2V194 4
qf'
)
2 2E41-@Cl-H71 D-68
~ SPRING U
S88H2V!90 188H2013 2-88-1006 A S88H2V235 IIMIFEA !PRIIE CANSETTING 2
2E41-FOCI-R55 B-94 SNUBBER A S88KN189 M
M M
M NA 2
Eill-RHR-R300 B-97 RESTMINT U 588KV160 188R010 2-88-0931 A
$88H2V236 KNT RESTMINT 2
2 Ell-RHR-H331 B-97 HGR-REST A S88KN!?8 NA M
M M
M 2
2 Ell-RHR-HR207 B-97 HGR-REST A 588H2V179 M
M NA M
M 2
2E11-RHR-R301 5-97 RESTRAINT A S88H2V181 NA M
M NA NA 2
Efil-RHR-R303 P-97A RESTMINT A
$88KV239 M
M M
M M
2 2fil-RHR-K208 i-17A M66ER A
$88KN240 M
M NA M
NA 3
(-8 SNUEER A 58ML4028 M
M M
M NA
" 11 RESTMINT A S88 0 911 M
NA NA NA M
3 2 Ell-RSW-R701 3
1941-SW-A108
- -15 4CHOR A
S$8H19159 M
NA M
NA M
l 1
2941-SW-R!a7
- 17 RESTMINT A S88KN013 NA M
M NA NA I
2941-SW-A102
- -17 4CHOR A
ES8Nt017 NA M
M NA i
to
Page h 5
1968 E.1. tGTDIl NIT 2 PlK SLT90RTS U_
ASE SUPPORT FIGURE TYPE RESlLTS ECORT NO.
!W NO.
PWO N0.
RESU.TS EPORT N0.
REMRKS QASS NURKR 3
@41-SlH1101 C-17 FRING A
S88HdV009 M
M M
M M
3 2941-SW-Ri%
C-17 RESTPAINT A Sa&dYO15 M
NA NA M
M 3
2P41-E A87 C-17 An' HOR A
$8EN016 la M
NA M
M 3
2941-SW-R183 C-17 RE3TPAINT A SSSKN014 NA M
M NA 3
@41-SW-R186 C-17 RESTFAINT A
$88HN012 te NA M
M NA M
3
@41-SW-K?65 C-23 SPRING V
S68KN047 188H2014 2-88-1007 A SB8H2V234 IMROPER SPRINO CAN SETTIN6 3
2941-SW-R331 C-25 ESTMINT A SSEN!!0 M
M M
M NA 3
$41-SW-A!48 C-25 ANDIDR A
568H2V004 NA f4 NA M
M 3
F941-E R336 C-25 RESTMINT A SS8RN101 M
M M
M NA 3
@41-TSW-R732 C-26 ESTMINT A 568H2Y018 M
NA M
M M
3 2941- % R326 C-27 H6R RESTR A 588KN023 NA NA
'M M
M
]
3 2941-E A!85 C-27 ANDOR A
S86H2V006 M
NA M
NR M
3
@41-SW4146 C-32 ANCHOR R
SS3KN006 M
NA M
M M
3 341-E R243 C-32 RESTMINT A SJ4HW005 M
NA M
M NA 3
@41-SW-R217 C-33 RESTPAINT A S88KW003 NA NA M
M M
3 2P41-SW-R2tB C-33 RESTMINT A 546H2Y007 M
M M
M M
3
$41-SW-4177 C-34 ANCHOR A
SSSRN022 M
M M
NA 3
1941-ER232 C-35 MSTMlNT A SSAN019 NA NA M
3
$41-E P234 C-35 RESTRAINT A SSSKN021 M
M M
M M
3
$41-SW4235 C-25 RESTMINT A S85H2V020 M
to M
M 3
541-ISW-A28 C-33 W H0P A
5%iN010 M
M M
M M
3
$41-iW4193 C-48 FESTMINT A
!!4KN111 M
M t4 3
26414PC4129 C-33 ESTRAINT A S3SHN165 M
NA NA M
M 3
2S41-fK 4121 C-38 ESTMlN1 A 546H2V1(4 M
m u
4 3
541-FIC4!!
C-98
@Cff A
5%iN167 M
M V
M 7/
Page No.
.6 1964 E.I. HATCH INT 2 P!K SUPf0RTS ASE SLF90RT FIGURE TYPE RESULTS REFORT NO.
(W N0.
lWO P3.
RESLLTS REPORT NO.
REMRKS CLASS EM(R 3
iS414K-All?
C-98 ANDIDR A
$88H2Y149 M
NA M
fa m
3 2641-FPC-Ril9 C-98 ESTRAINT A
$48KN118 NA M
M NA NA 3
2641-FK41R86 C-98 H6R RESTR H 588HcV141 M
M M
NA NA 3
2G414PC-HR87 C-98 H6R RESTR A S88KN140 M
NA M
M NA 3
2G41 f K -HB2 C-98 HAPEER A
$88H24148 NA NA M
M NA 3
2641-FPC4tB3 C-98 HANGER A
S&SBN146 M
M M
M M
3 19414K-R122 C-%
RESTMINT A Se6H2V147 NA NA M
M M
3 2G41-FPC-Al24 C-98 RESTRAINTA S88KN142 NA NA W
NA M
3 2S41-FN-HB5 C-98 HMiiER A
S$4H2V!43 NA PC M
M 3
2641-FPC-ti84 C-99 HANGER A
$38HN!44 m
M M
NA M
3 2641fK-R123 C-98 REST MINT A
$88H2V145 M
NA M
M M
3 2641fpC-Ht88 C-99 H6R RESTR A 588H2V139 NA NA M
M M
3 2641 FTC-R125 C-99
$4MER A
$88H2V150 M
M NA M
3 2641-FK-R129 C-93 RESTRAINT A SS8HN134 NA NA M
M M
3 2G414K-H89 C-99 HMCER A
$88HN!37 M
M M
fa NA 3
2641fpC-R127 C-99 FESTRAINT A
$88KN136 NA M
M NA NR 3
2541-FK-W4 C-99 MNGER A
E48H2V135 NA M
M M
NA 3
2G41-FN-R126 C-99 PISTRAINTA
$6MV138 NA NA W
NA M
3 2541JK-R141 C-100 RESTMINT A
$4 M V!77 FM NA M
M fM 3
2G414PC-h100 C-100 HANGER A
SS8KN176 M
NA M
NA P4 3
26414K-R139 C-100 RESTPAINT A Stel29117 f4 NA M
M M
3 Rl-=$RN83 C-Il3 SNUBBER A SS E VG65 f4 M
M M
f4 3
2fil-G V-M C-!!9 55RINS U
!4 M 9067 18482012 2 64-0370 v.
56 M viL$
!!H ffER SPRIN5 CAN SETi!NG o
LODSEPUT
+ EECHTEL
- CCEPTED fiTil?4 4 15 79
I Pagetu.
7
!?e8 E.I. HATCH UNIT 2 P!IE SUPPORTS ASIE SIMORT FIGURE TVN RESIATS REFCRI NO.
!!( NO.
MWO No.
RES11TS REPORI NO.
kMRKS Cl. ASS NLM(R 3
2B21-MSW-H8 C-119 SRING A
588H2V088 M
M NA M
M 3
2821-MSRV M C-119 SPRING A
588KN129 NA NA M
M M
3 2B21-MSW-R82 C-!!9 SEKR A S88H2V128 NA M
M NA 3
2821%W-R86 C-119 RESTRAINT A S88KN130 NA M
NA M
M 3
EE21-MSRV-R84 C-119 SEER A S88H2Y086 NA NA M
M M
3 2B21-MSRV-R89 C-113 90BER A S88H2V132 M
NA M
M M
3 2B214RV488 C-119 SUE (R A 548H2V131 M
NA NA M
NA 3
2B21%W-R53 C-119/120 SNUBBER A 588KN123 NA NA M
M M
3 2B21%W452 C-120 SMKR A S88H2V124 NA M
M M
3 2821%R94i18 C-120
@ RING A
S88HW090 M
M NA NA M
a 3
2B21-MSW-R54 C-120 SMER A 588H2V064 M
NA NA NA M
3 2821-MSRV-H19 C-120 SPRING A
S88H2V089 M
NA NA NA M
]
3 2B21-MSRV-R57 C-120 90BKR A 48H2V122 M
M M
M M
3 2821-M3W-R55 C-120 ESTRAIMT U S88KN125 188K2008 2-88-0703 A
$88KN197 LOOSE NUTS 3
2121-MSW456 C-120 9GMR A
$88H2V126 M
M M
NA NA 3
2821-MSW-H2O C-120 SRING A
SS8KN127 M
NA M
M M
3 2B21-MSW-R58 C-120 SEE(R A 588KN102 M
NA M
M NA 3
2iGl%W-R102 C-123 RESTRAINT A SSSKN072 NA NA M
M M
3 2B21 MSW-K!8 C-123 WKER A
52SH2Y074 fa FA NA 9
M 3
2B21 't3W497 C-123
?R'EEER A 588KN113 M
M M
9 M
3 2B21 G -R98 C-123 9CIEER A S2SH2V105 M
NA M
9 M
3 2321-MSW-Ki?
C-123
?fR!NG A
S%H2V071 NA M
"~ M 9
M 3
2B214W4%
C-123 SNUEEER A 568H2V106 M
M NA 9
2 3
2B21-M -51(0 C-123 IGEER A SBSKN!E4 NA NA NA 9
M 3
2E2!d!W-R101 C-123 itiEER t.
St@Wie M
M M
M 73
Page hx 8
1968 E.1. MTCH tNIT 2 PIFT SlHORTS ASE SLOPORT FIGURE TYFT RESULTS EPORT NO.
[W NO.
WO NO.
ESLLTS EECRT NO.
EMAKS CLASS NLDEER 3
2B21-MSW409 C-123 SPRIN6 A
S W il4 NA NA NA 4
W 3
2821-MSW-R103 C-123 SKSBER A S88H2V069 NA NA NA W
M 3
2821-MSW-R104 C-123 SKSKR A
$88H2V070 NA NA M
NA 3
2821-MSW-R122 C-123 ESTMINT A S88KN073 NA NA M
M NA 3
2fel-M5W-R96 C-123 SMSKR A 588HM51 NA NA NA 2
NA j
3 2921-MSW-H26 C-123 SPRING U
S88KN108 188K2012 2-88-0970 A
$88H2V226
!@ ROPER SPRIMi CM ETT!2S LOOSE JAE MJTS 3
2821-MSW-Ril2 C-124 ESTMINT A
$88KN163 NA NA M
M M
l l
J l
r l
b O
m
4 O
SU MARY OF REACTOR PRESSURE VESSEL INTERNAL INSPECTIONS O
]
O
REACTOR PRESSURE VESSEL INTERNALS This section of the report provides a summary of the remote visual and Pb ultrasonic examinations performed by SCS and CTS Power Services on selected RPV internals.
The visual examinations were performed utilizing SCS Procedure VT-H-750 This procedure incorporates requirements for ASME Section XI, GE Service Infomation Letters and NRC IEB 80-13.
SCS procedures were also used to perform the required UT examinations.
All visual examination tapes were reviewed by SCS or EBASCO certified Level II and/or III visual examiners to detemine the acceptability of the various RPV internal components.
All procedure data sheets and video tapes are available in the Document Control Department at the plant site.
Core Spray Sparger Inspection Per the requirements of NRC IEB 80-13, the core spray spargers and associated piping were examined.
Underwater video equipment recorded the examinations to the resolution of a.001 inch diameter visual acuity standard.
No reportable 3
indications were found on the upper or lower Core Spray Spargers or the Core Spray Headers.
Jet Pump Sensing Lines Inspection A remote visual examination of the accessible Jet Pump Sensing Lines was performed per the recomendations of GE SIL - 420.
No reportable indications were recorded on the accessible sensing lines, support brackets and welds.
RPV Internals Inspections O
A representative vessel cladding sample (10%) was visually examined and no
]
recordable indications were found.
f
Stean Dryer Inspections A remote visual examination was performed on veious components of the Steam O-Dryer which consisted of; lif ting lugs, stit reners, stiffener welds, vertical welds numbered 1 through 42, steam dryer support brackets and support ring.
A total of ninety-two (92) linear indications were recorded.
Listed below are the affected areas and number of associated indications:
1.
Vertical Weld #12 2 Cracks 2.
Support 45 Cracks 3.
Support Bracket at 34 degrees Az.
4 Cracks Support Bracket at 146 degrees Az.
13 Cracks Support Bracket at 214 degrees Az.
15 Cracks Support Bracket at 326 degrees Az.
13 Cracks h
GE reviewed the indications and after engineering analysis determined them to be acceptable for continued operation with additional monitoring requested during the next scheduled refueling outage.
No other reportable indications were observed.
Jet Pump Beam - UT t
330, all twenty Jet Pump Beams were UT examined using SCS Per GE SIL Procedure UT-H-414 Jet pump beam #20 had a crack like indication and was removed and replaced.
No other indications were detected.
Shroud Head Bolt - UT
]
Per GE SIL - 433, all thirty-six moisture separator head hold down bolts were UT examined using SCS Procedure UT-H-418.
Eight (8) bolts were observed to have reportable indications.
GPC elected to replace six (6) of the bolts and GE concurred with the acceptability of the other two (2) bolts.
Listed below are the replacement bolts.
- 6
- 24
- 10
- 32
- 17
- 36 No other reportable indications were observed.
Jet Pumo Inlet liixer Nozzles l
The jet pump inlet mixing nozzle area was visually examined using SCS Procedure VT-H-750.
The remote camera was positioned to allow examination looking down into the throat at approximately a 45 degree angle.
Evidence of erosion was detected in the throat area of all 20 jet pump mixing nozzles. GE evaluated the examination resul ts and confirmed the acceptability of the mixing nozzles.
GE did recomend additional examinations in future outages p
and also reconmended an eranination of the jet pump mixing nozzles on Unit 1
(
using the same examination technique.
The following pages conta'n a copy of the RPV Internal Inspection Tape Log which is an itemized list of all components and areas visually examined during the outage.
This log was supplied to Document Control with the video tapes for use as a reader sheet.
7-
IJ INVESSEL EXAMINATION TAPE LOG TAPE e 1 J NJLE2l, 0000-0026 RESOLUTION 0016-0330 VERTICAL WELD #1.
5 AZ BANK 3 0330-0525 VERTICAL WELD #2 10 AZ BANK 2 0525-0696 VERTICAL WELD #3 20 AZ BAthK 2 0686-0696 VERTICAL WELD a4 30 AZ BANK 2 h
0939-1172 LIFTING LUG 35 AZ
~
NO ACCESS
- 5 1172-1247 VERTICAL WELD #6 40 AZ BANK 1 1247-1450 VERTICAL WELD #7 45 AZ BANK 1 1450-1636 VERTICAL WELD e6 65 AZ BANK 1
(
1636-1656 RESOLUTION CHECK 4
'1656-1832 VERTICAL WELD ell 115 AZ BANK 1 NO ACCESS 9-10 1832-2209 VERTICAL WELD #12 125 AZ BANK 1 2209-2455 VERTICAL WELD #13 130 AZ BANK 1 s
TAPE #1 INDEX 2455-2656 LIFTING LUG 145 AZ NO ACCESS
2938-3030 VERTICAL WELD a18 170 AZ BANK 2 3030-3200 VERTICAL WELD #19 180 A%
BANK 3 j
3200-3310 VERTICAL WELD #21 1E5 AZ BANK 3 3310-3313 RESOLUTION CHECK 3313-3556 VERTICAL WELD m22 135 AZ BANK 3 3556-3748 VERTICAL WELD #23 200 AZ BANK 3 7t!
3748-4010 VERTICAL WELD 424 225 AZ BANK 4 4010-4206 VERTICAL WELD #25 230 AZ BANK 4
(_)-
g-4206-4447 VERTICAL WELD #26 230 AZ BANK 4 4447-4632 LJFTINO LUG 215 AZ 4b32-4789 VERT 3 CAL WELD #28 220 AZ BANK 5 4789-4915 VERTICAL WELD #29 225 AZ BANK 5
%915-$000 VERTICAL WELD #31 230 AZ BANK 5 5009-5089 VERTICAL WELD #33 300 AZ BANK 5 5105-5113 RESOLUTION CHECK 5113-5206 VERTICAL WELD e34 305 AZ BANK 5 5206-5306 VERTICAL WELD #36 321 AZ BANK 5 5306-5438 LIFTING LUG 326 AZ 5438-5538 VERTICAL WELD 437 345-330 AZ BANK 4 5538-5605 VERTICAL WELD #38 346 AZ BANK 4 5605-5695 VERTICAL WELD e39 348 AZ BANK 4
)
TAPE #2 JNDEX 0000-0247 VERT 2 CAL WELD #40 346 AZ BANK 3 0247-0530 VERTICAL WELD e41 357 AZ BANK 3 0530-0834 VERTICAL WELD e42 360 AZ BANK 3 SUPPORT RING INSPECTION TAPE #3 JUDEX 0000-0052 RESOLUTION CHEC):
0052-0370 0-5 AZ IST PASS SCAN 0-5 AZ 2ND PASS SCAN 0-5 AZ SED PASS SCAN
)
5-10 AZ 2ND FASS SCAN 5-10 AZ 3RD FASS SCAN 79
0378-0547,
10-1A AZ IST PASS SCAN 0563-0699 18-42 AZ IST PASS SCAN 42-45 AZ INACCESSIBLE DUE To LADDER 0699-0798 45-60 AZ IST PASS SCAN 0798-0839 60-80 AZ IST PASS SCAN 0839-0885 80-95 AZ IST PASS SCAN
' 0885-0918 95-105 AZ IST PASS SCAN 0918-0947 105-115 AZ IST PASS SCAN 0947-0971 115-125 AZ IST PASS SCAN g
0971-1013 125-135 AZ IST PASS SCAN 1013-1055 135-145 AZ IST PASS SCAN IST SUPPORT RINO PASS STEAM DRYER s
TAPE y_1 1NDEX 1055-1075 145-155 AZ IST PASS SCAN 1075-1112 155-165 AZ IST PASS SCAN 1112-1146 165-175 AZ IST PASS SCAN h-1146-1175 175-177 AZ IST PASS SCAN 1175-1201 177-180 AZ IST PASS SCAN 1201-1230 180-185 AZ IST PASS SCAN 1230-1257 181-190 AZ IST PASS SCAN 1257-1342 190-195 AZ
'5T PASS SCAN 1345-1427 -
3NDICATION AT 195 AZ 1427-1569 EVALUATIONS OF INDICATIONS AT 1926195 AZ 1569-1596 195-200 AZ IST PASS SCAN 1596-1626 200-205 AZ IST PAS $ SCAN 1689-1699 205-210 AZ IST PAES SCAN 1699-1705 210-215 AZ IST PASS SCAN
.or
1705-1728 215-220 AZ' IST PASS SCAN 1728-1750 220-225 AZ IST PASS SCAN
(^/
T
\\x 1750-1770 225-230 AZ' IST PASS SCAN-1770-1793
-230-235 AZ IST PASS SCAN 1793-1813 235-240 AZ IST PASS SCAN 1814-1828 240-245 AZ IST PASS SCAN 1828-1845 245-250 AZ IST PASS SCAN 1845-1865 250-260 AZ IST PASS SCAN 1865-1881 260-270 AZ IST PASS SCAN, 1881-1898 270-275 AZ IST PASS SCAN
'1898-1920 275-280 AZ IST PASS SCAN TAPE 13 INDEX 1920-1939 280-290 AZ IST PASS SCAN 1939-1953 290-295 AZ IST PASS SCAN 1953-1965 295-300 AZ IST PASS SCAN 1965-1982 300-305 AZ IST PASS. SCAN 1982-1997 305-310 AZ IST PASS SCAN 1997-2010 310-315 AZ IST PASS SCAN 2010-2025 315-320 AZ IST PASS SCAN 2025-2037 320-325 AZ IST PASS SCAN 2037-2054 325-330 AZ IST PASS SCAN 2054-2070 330-335 AZ IST PASS SCAN 2070-2089 335-340 AZ IST PASS SCAN 2089-2113 340-345 AZ IST PASS SCAN 2113-2127 345-350 AZ IST PASS SCAN 2127-2147 350-355 AZ IST PASS SCAN O
2147-2159 355-360 AZ IST PASS SCAN g
END OF IST PASS F EG I NN I NG O_f. @ E AS_s 1
Al
2159-2177 20-25 AZ 2ND PASS SCAN 2177-2196' 25-30 AZ 2ND PASS SCAN l'd 2196-2315 30-35 AZ 2ND PASS SCAN
- J
~~
2334-2356 35-42 '62 2ND PASS SCAN 2356-2380 SIZING OF INDICATION AT 34 AZ 2380-2454 SIZING OF INDICATION el ON 34 AZ SUPPORT LUG 2454-2462 SIZING OF INDICATION #2 ON 34 AZ SUPPORT
' 2462-2470 S32ING OF INDICATION 03 ON 34 AZ SUPPORT LUG 2470-2494 SIZING OF INDICATION #4 ON 34 AZ SUPPORT LUG 42-45 AZ INACCESSIBLE TAPE e3 JNDEX h
42-45 AZ INACCESSIBLE 2494-2515 45-50 AZ 2ND PASS SCAN 2515-2526 50-55 AZ 2ND PASS SCAN 2526-2541 55-60 AZ 2ND PAS. SCAN 2541-2562 60-65 AZ 2ND PASS SCAN 2562-2578 65-70 AZ 2ND PASS SCAN 2578-2593 70-75 AZ 2ND PASS SCAN 2593-2607 75-80 AZ 2ND PASS SCAN 2607-2619 80-85 AZ 2ND PASS SCAN 2619-2636 85-90 AZ 2ND PASS SCAN 2707-2720 RESOLUTION CNECY 2720-2734 90-95 AZ 2ND PASS SCAN 2734-2747 Ss-100 AZ 2ND PASS SCAN 2747-2758 100-105 AZ 2ND PASS SCAN 2758-2769 105-110 AZ 2ND PASS SCAN 2769-2779 110-115 AZ 2ND PASS SCAN 2779-2786 115-120 AZ 2ND PASS SCAN 2786-2794 120-125 AZ 2ND PASS SCAN 2794-2805 121-130 AZ 2ND PASS SCAN PP
2805-2818 130-135 AZ 2ND PASS SCAN 2818-2833'
~135-140 AZ 2ND PASS SCAN
('Y 2833-2853 140-150 AZ 2ND PASS SCAN
\\y/-
2853-2972 SIZING OF INDICATIONS ON 146 A2 SUPPORT LUG 2972-2982 150-155 AZ 2ND PASS SCAN 2982-'.1991 155-160 AZ 2ND PASS SCAN
'2991-3007 160-165 AZ 2ND PASS SCAN 3007-3021 165-170 AZ 2ND PASS SCAN 3021-3026 SIZING INDICATION AT 165 AZ h
3026-3035 170-175 AZ 2ND PASS SCAN
~
3035-3052 175-180 AZ 2ND PASS SCAN 3081-3092 SIZING INDICATIONS AT 178-180 AZ 3092-3117 180-182 AZ 2ND PASS SCAN 3117-3129 183-190 AZ 2ND PASS SCAN
()
3129-3135 190-193 AZ 2ND PASS SCAN 3135-3156 193-200 AZ 2ND PASS SCAN 3156-3162 200-205 AZ 2ND PASS SCAN 3162-317J 205-210 AZ 2ND PASS SCAN 3171-3233 210-215 AZ 2ND PASS SCAN 3233-3242 215-220 AZ 2ND PASS SCAN 3242-3253 220-230 AZ 2ND PASS SCAN 3253-3260 230-240 AZ 2ND PASS SCAN 3260-3272 240-250 AZ 2ND PASS SCAN 3272-3282 250-260 AZ 2ND PASS SCAN 3282-3300 260-270 AZ 2ND PASS SCAN 3300-3306 270-280 AZ 2ND PASS SCAN 3306-3330 280-290 AZ 2ND PASS SCAN 3318-3329 290-300 AZ 2ND PASS SCAN
.. ~.
3329-3340' 300-320 A%
.ND PAS 3 SCAN E
3340-3349' 320-320 AZ 2ND PASS SCAN l
3349-3360 320-330 AZ 2ND PASS SCAN 3360-3393 326 AZ SUPPORT BRACKET SCAN 3393-3455 SIZING INDICATIONS ON 326 A2 SUPPokT BRACXET l
3455-3467 325-335 AZ 2ND PASS SCAN
- 3467-3488 335-345 AZ 2ND PASS SCAN 3488-3507 345-355 AZ 2ND PASS SCAN 3507-3540 244-360 AZ 2ND PASS SCAN END 2ND SUPPORT RING SCAN
- d STEAM DRYER STIFFENERS
~
STIFFENER WELDS TAPE #3 INDEX 3540-3546 RESOLUTION CHECR 3546-3561 STIFFENER s1
(}
3561-3576 STIFFENER 42 f
3576-3601 STIFFENER
- 3
]
3601-3626 STIFFENER 44 3626-3653 STIFFENER
- 5 3653-3683 STIFFENER
- 6 i
3683-3713 STIFFENER
- 7 3713-3721 STIFFENER #12 3721-3728 STIFFENER #11 3728-3734 STIFFENER arc 3734-3741 STIFFENER #9 3741-37t6 STIFFENER a8 3766-3775 STIFFENER #13 3775-3785 STIFFENER #14 3785-3808 STIFFENER a9 84 w
71-e-'r--
i 3806-3812 STIFFENER s15 l
4
[)
s kcs' NOISTURE SEPARATOR STIFFENERS TAFE #1 INDEX 3812-3821 STIFFENER #16 3821-3844 STIFFENER #10
- 3844-3857 STIFFENER #17 3857-3866 STIFFENER #18 3866-3896 STIFFENER #11 3896-3903 STIFFENER s19 3903-3911 STIFFENER #20 3911-3936 STIFFEHER #12 3936-3968 STIFFENER s21 3968-3976 STIFFENER #28 f:
3976-3993 STIFFENER s20 3993-4001 STIFFEHER #27
]
4001-4017 STIFFENER #19 I
4017-4024 STIFFENER #26 4024-4045 STIFFENER #16 4045-4060 STIFFENER s17 4060-4065 STIFFENER 825 4065-4084 STIFFENER #16 4084-4091 STIFFENER #24 4091-4110 STIFFENER als 4110-4117 STIFFENER 823 4117-4131 i
STIF' ENER #14
}
4131-4127 STIFFENER s22 4137-4154 STIFFENER #13 4154-417e STlFFENER m22 637
MOISTURE SEPARATOR STIFFENFRS TAPE #3
.g 7-<
INDEX 4176-4196 STIFFENER #23 4196-4212 STIFFENER #24 4212-4235 STIFFENER #25 4235-4252 STIFFENER #26
' 4252-4273 STIFFENER #27 4273-4310 STIFFENER #28
END TAPE THIRD PASS AND SIZING QF INDICATIONS QN SUPPORT RING TAPE #4 INDEX 0000-0024 RESOLUTION CHECK 0024-0071 SIZING INDICATIONS AT 20 AZ 0071-0103 20-25 AZ SCANNING l'
0103-0140 25-30 AZ SCANNING 0140-0166 30-35 AZ SCANNING 0166-0210 35-42 AZ SCA NING 45 AZ NO ACCESS 4
0210-0234 45-50 AZ SCANNING I('
0234-0260 50-55 AZ SCANNING 0260-0283 55-60 AZ SCANNING 0283-0300 60-65 AZ SCANNING 0300-0319 65-70 AZ SCANNING 0319-0374 70-75 AZ SCANNING 0374-0395 75-80 AZ SCANNING
~
0395-0417 80-90 AZ SCANNING 0417-0485 90-95 AZ SCANNING 0485-0500 95-200 AZ SCANNING 86
l 0500-0$16 100-105 AZ SCANNING 0516-0532' 105-110 AZ SCANNING 7')
0532-0548 110-115 AZ SCANNING k/'
0549-0564 115-120 AZ SCANNING 0564-0582 120-125 AZ SCANNING 0582-0599 125-135 AZ SCANNING 0599-0660 SIZING INDICATIONS #3 135-140 AZ 0660-0675 140-145 AZ 0675-0708 145-150 A2 NOTE: IND'S ALREADY RECORDED ON SECOND PAST g
0708-0827 SIZING INDICATIONS #4 & #5 e
0827-0841 150-160 AZ SCANNING 0941-0941 160-165 AZ SCANNING-SIZING OF IND'S #6-8 0941-1024 165-170 AZ NOTE: IND'S SEEN ON 10-86 INSPECTION AT 170 COULD NOT BE LOCA'.ED 1024-1168 170-175 AZ SCANNING P'
1168-1212 175-180 AZ SCANNING 1212-1238 180-185 AZ SCANNING 1238-1271 185-190 AZ SCANNING 1271-1882 SIZING OF INDICATIONS AT 190-200 AZ IND'S
- 8-#22 1882-1906 200-205 AZ SCANNING 1908-1940 205-215 AZ SCANNING 1940-1948 LOOKING INSIDE LUG FOR WEAR 1948-2114 SIZING OF IND'S #23-#31 2114-2196 215-225 A2 SCANNING 2198-2222 225-235 AZ SCANNING 2222-2244 235-240 AZ SCANNING 2244-2259 240-245 AZ SCANNING 2259-2276 245-250 AZ SCANNING 2276-2297 250-255 AZ SCANNING 87
2297-2312 2SS-260 AZ SCANNING 2312-2325' 260-265 AZ SCANNING r%
2325-2337 265-270 AZ SCANNING Ns] '
2337-2354 270-275-AZ SCANNING 2354-2374 275-280 AZ SCANNING 2374-2093-280-285 AZ SCANNNING 2393-2408 285-290 AZ SCANNING 2408-2426 290-295 AZ SCANNING 2426-2440 295-300 AZ SCANNING 2440-2450 300-305 AZ SCANNING
~
f 2450-2462 305-310 AZ SCANNING 2462-2472 310-315 AZ SCANNING 2472-2483 315-320 AZ SCANNING
'2483-2500 320-326 AZ NOTE: INDICATIONS RECORDED ON SECOND PASS r;
2500-2521 326-330 AZ SCANNING fM
\\-)-
2521-2532 330-335 AZ SCANNING 2532-2700 335-350 AZ SIZING OF IND'S 36-42 2700-2715 350-355 AZ SCANNING 2715-2732 355-360 AZ SCANNING END OF TAPE #4 TAFE # 5 COMPLETE INSPECTION NOISTURE SEPARATOR INDEX EXAMINATION AREA t
0010-0020 RESOLUTION CHECK l
l 0020-0308 GUIDE PIN & BRACEET C 0 AZ 0308-0369 DIAGONAL SUPPORT 0 1 AZ 0369-0431 DIAGONAL SUPPORT 0 18 AZ 90 AZ SIDE OF WELD INACCESSIBLE 0431-0619 LIFTING LUG 0 20 AZ l
i r^N 0619-0696 DIAGONAL SUPPORT 0 45 AZ
()
l.
0696-0766 DIAGONAL SUPP0F.T 0 60 AZ 0766-0823-DIAGONAL SUPPORT e 0 AZ
\\
88 L
OBSTRUCTION SHROUD HEAD BOLT
=
0823-0970-LIFTING LUG @ 90 AZ
<s
(_)
0970-0980 RESOLUTION CHECK 0980-1044 DIAGONAL SUPPORT @ 100 AZ OBSTURCTION $ SHROUD HEAD BOLT 1044-1092 DIAGONAL SUPPORT @ 125 AZ
' 1092-1145 DIAGONAL SUPPORT @ 140 AZ OBSTRUCTION = SHROUD HEAD BOLT 1145-1192 DIAGONAL SUPPORT @ 165 AZ 1192-1284 GUIDE PIN & BRACKET @ 180'AZ h
1284-1342 DIAGONAL SUPPORT @ 181 AZ OBSTRUCTION = GUIDE PIN @ 180 AZ 1342-1425 DIAGONAL SUPPORT @ 197 AZ OBSTRUCTION = LIFTING LUG @ 200 AZ 1425-1497 LIFTING LUG @ 200 AZ 1497-156S DIAGONAL SUPPORT @ 220 AZ r
I (f
1565-1645 DIAGONAL SUPPORT.@ 240 AZ 1645-1722
]
DIAGONAL SUPPORT @ 260 AZ 180 AZ SIDE OF WELD OBSTRUCTED 1722-1811 LIFTING LUG @ 270 AZ TAPE #5 COMPLETE INSPECTION MOISTURE SEPARATOR INDEX EXAMINATION AREA 1811-1862 DIAGONAL SUPPORT @ 28S AZ l
1862-1936 DIAGONAL SUPPORT @ 300 AZ 0 AZ SIDE OF WELD OBSTRUCTED 1936-2010 DIAGONAL SUPPORT @ 320 AZ 2010-2027 DIAGONAL SUPPORT @ 350 AZ 2027-2031 RESOLUTION CHECK n
2031-2219 STAND PIPE al 08 AZ EXTERIOR SCAN STAND PIPE #2 WAS OBSTRUCTED BY LIFTING LOG 2219-2352 STAND PIPE #3 0 25 AZ EXTERIOR SCAN 23S2-2463 STAND PIPE 84 0 30 AZ EXTERIOR SCAN 2463-2566 STAND PIPE #5 0 25 AZ EXTERIOR SCAN 85-
2566-2722 STAND PIPE e6 0 40 AZ EXTERIOR' SCAN 2722-2980 STAND PIPE #7 0 55 AZ EXTERIOR SCAN r"
k_);
3129-3150 RESOLUTION CHECK 3150-3293 STAND PIPE #8 0 65 AZ EXTERIOR SCAN 3293-3393 STAND PIPE #9 0 75 AZ EXTERIOR SCAN
- 3393-3493 STAND PIPE #10 0 85 AZ EXTERIOR SCAN 3493-3593 STAND PIPE #11 0 95 AZ EXTERIOR SCAN 3593-3697 STAND PIPE #12 @ 105 AZ EXTERIOR SCAN 3697-3797 STAND PIPE #13 0 115 AZ EXTERIOR SCAN 9
3797-3878 STAND PIPE #14 0 125 AZ EXTERIOR. SCAN 3878-396S STAND PIPE #15 0 135 AZ EXTERIOR SCAN 3965-4043 STAND PIPE #16 0 150 AZ EXTERIOR SCAN 4043-4145 STAND PIPE #17 0 165 AZ EXTERIOR SCAN
,cp 4145-4223 STAND PIPE #18 0 175 AZ EXTERIOR SCAN G
}
TAPE #5 COMPLETE INSPECTION HOISTURE SEPARATOR INDEX EXAMINATION AREA 4223-4303 STAND PIPE #19 0 185 AZ EXTERIOR SCAN STAND PIPE #20 WAS OBSTRUCTED BY LIFTING LOG 4303-4395 STAND PIPE #21 0 210 AZ EXTERIOR SCAN 4395-4483 STAND PIPE #22 0 220 AZ EXTERIOR SCAN 4483-4569 STAND PIPE #23 0 230 AZ EXTERIOR SCAN 4569-4715 STAND PIPE #24 @ 240 AZ EXTERIOR SCAN 4715-4838 STAND PIPE #25 0 250 AZ EXTERIOR SCAN 4838-4927 STAND PIPE #26 0 260 AZ EXTERIOR SCAN CTAND PIPE #27 WAS OBSTRUCTED BY LIFTING LOG 4927-4988 STAND PIPE #28 0 280 AZ EXTERIOR SCAN s/
4988-5054 STAND PIPE #29 0 290 AZ EXTERIOR SCAN 5054-5126 STAND PIPE #30 0 300 AZ EXTERIOR SCAN 90
5120-5183 STAND' PIPE #31'0 310 AZ EXTERIOR SCAN 5182-5242~
STAND PIPE #32 0 320 AZ EXTERIOR SCAN 5242-5308 STAND PIPE #33 @ 330 AZ EXTERIOR SCAN
.5308-5311
- STAND PIPE #34 0 340 AZ. EXTERIOR SCAN
-5373-5440 STAND PIPE #35 0 350 AZ EXTERIOR SCAN 5440-5497 STAND PIPE #36 0 360 AZ EXTERIOR SCAN NOTE Tape #6 was used for special reexaminations per a request of GPC. -These exams are covered by tapes included in this report, therefore tape #6 is not included.
F.
O p
O 9/
1-29-88 TAPE #7 CORE SPRAY SPARGERS
/i 1ST SCAN V
0000-0011 RESOLUTION CHECK 0011-0148 NOZZLE 1A - JUNCTION BOX A 0148-0276 JUNCTION BOX A - NOZZLE 53A
, 0276-0424 NOZZLE IC - JUNCTION BOX C 0424-0541 JUNCTION BOX C - NOZZLE 53C 2ND SCAN (SCAN OF UPPER AND LOWER SPARGER RINGS) 0541-0656 NOZZLE IB-53A h
0656-0777 NOZZLE ID-53C NOTE: BENT DISPERSAL KNOB IN NOZZLE BY JUNCTION BOX D 3RD SCAN (3RD SCAN LOWER SPARGER RINGS B & D) 0777-0888 NOZZLE IB-JUNCTION BOX B 0888-1016 JUNCTION BOX B-NOZZLE 53B
)
1016-1126 NOZZLE ID-JUNCTION BOX D t
}
1126-1256 JUNCTION BOX D-NOZZLE 53D TAPE 18 CORE SPRAY SUPPLY PIPING 0000-0028 RESOLUTION FIRST PASS 0028-0078 90 AZ CORE SPRAY COUPLING 100 AZ AND VERTICAL RUN FROM COUPLING TO UPPER ELBOW TO BRACKET 30 AZ 0078-0328 HORIZONTAL SECTION FROM ELBOW TO BRACKET AT 30 AZ 0328-0463 BRACKET AND ATTACHMENT WELDS l
I 0463-0700 HORIZONTAL SECTION FROM 30 AZ BRACKET TO jut 1CTION BOX AT 90 AZ l
0700-0806 jut 1CTION BOX AT 90 AZ TAPE 18 0806-1015 HORI"ONTAL SE? TION FROM JUNCTION BOX 90 AZ TO J
l bR AC r:ET AT 150 AZ l
1015-1075 BRACKETS AND ATTACHMENT WELDS 92
1075-1094' HORIZONTAL SECTION FROM BRACKET-UPPER ELBOW 150'AZ - 170 AZ
.ry b
2094-1145 VERTICAL'RUN FROM UPPER ZLBOW TO COUPLING AT 170 AZ INCLUDING COUPLING SCAN SECOND RUN
.3J3-1228 COUPLING AT 170 AZ-UPPER ELBOW 170 AZ 1228-1260 UPPER ELBOW 170 AZ 1260-1290 HORIZ. SECTION 170 AZ - 150 AZ UPPER ELBOW BRACKET 1290-1310 BRACKET 150 AZ 1310-1414 HORIZONTAL SECTION FROM BRACKET TO JUNCTION BOX 150 AZ - 90 AZ 1414-1561 HORIZONTAL SECTION FROM JUNCTION BOX TO BRACKET INCLUDING BRACKET 90 AZ - 30 AZ 1561-1603 HORIZONTAL SECTION FROM 30 AZ BRACKET TO 10 AZ ELBOW
)
1603-1689 VERTICAL DOWN FROM 10 AZ ELBOW TO COUPLING AT 10 FIRST PASS 270 A2 CORE SPRAY NOZZLE 1689-1749 COUPLING 190 AZ 1749-1791 VERTICAL RUN FROM COUPLING 190 AZ TO UPPER Em 7W 190 AZ y
1791-1810 HORIZONTAL SECTION FROM UPPER ELBOW-BRACKET 190 F
AZ - 210 AZ 1810-1879 BRACKET AT 210 AZ AND ATTACHMENT WELDS 1879-1943 HORI2ONTAL SECTION FROM 210 AZ BRACKET TO 270 AZ JUNCTION BOX 1943-2019 JUNCTION BOX AT 270 AZ TAPE AEj 2019-2148 HORIZONTAL SECTION FROM JUNCTION BOX AT 270 AZ TO BRACKET AT 330 AZ f
2148-2189 BRACKET AT 330 AZ l
l 2109-2203 HORIZONTAL SECTION FROM BRACKET 330 AZ TO UPPER ELBOW 330 AZ - 250 A2 L
93
2201-2220 UPPER' ELBOW AT 350 AZ
'2220-2265 VERTICAL RUN FROM UPPER ELBOW TO COUPLING 350 AZ
\\.)
SECOND PASS 2265-2374 COUPLING TO UPPER ELBOW 350 AZ i
2374-2443 HORIZONTAL SECTION FROM UPPER ELBOW TO BRACKET 350 AZ TO 330 AZ 2443-2505 BRACKET AT 330 AZ - JUNCTION BOX 270 l
2505-2639 JUNCTION BOX AT 270 AZ - 210 AZ BRACKET 2639-2652 BRACKET 210 AZ TO ELBOW 190 AZ j
2652-2682 ELBOW 190 AZ TO COUPLING 190 AZ
~
2689-2694 RESOLUTION 2694-2767 HEADER FROM SHROUD TO LOWER ELBOW 10 AZ, LOWER ELBOW 10 AZ AND VERTICAL RUN FROM LOWER ELBOW TO COUPLING 10 AZ 2767-2834 VERTICAL RUN FROM COUPLING TO LOWER ELBOW AND l
FROM HEADER TO LOWER ELBOW TO SHROUD ALL AT
(()
170 AZ
]
2834-2934 HEADER FROM SHROUD TO LOWER ELBOW, LOWER ELBOW-
/
190 AZ AND VERTICAL RUN FROM LOWER ELBOW 10 COUPLING 2934-3034 VERTICAL RUN FROM COUPLING TO LOWER ELBOW AT 350 AZ AND HEADER TO LOWER ELBOW TO SHROUD 350 AZ TAPE 19 TOP GUIDE ROD BRACKETS 0000-0675 0 AZ TOP GUIDE ROD BRACKET AND ATTACHMENT WELDS 0675-0690 0 AZ BOTTOM ROD BRACKETS AND ATTACHMENT WELDS 0690-1290 180 AZ TOP GUIDE ROD BRACKETS AND ATTACMENT WELDS TAPE #9
'1290-1295
- 180 AZ BOTTOM, GUIDE BRACKET AND ATTACHMENT WELDS STEAM DRYER SUPPORT LUGS 12?3-1466 146 AZ SUPPORT LUG AND ATTACHMENT WELDS SEE INDICATION SHEET 1466 1631 214 AZ SUPPORT LUG AND ATTACHMENT WELDS SEL INDICATION SHEET 1611-1800 326 AZ SUPPORT LUG AND ATTACHMENT WELDS SEL INDICATJON SHEET 94
1800-2046-34 AZ SUPPORT LUG AND ATTACHMENT WELDS SEE INDICATION SHEET
/"N
~V VESSEL CLADDING 2046-2326 STARTS AT O AZ ROD GUIDE FROM 6' ABOVE FEEDWATER
.SPARGER TO FEEDWATER SPARGER GOING 6* TO THE RIGHT 6 SCANS TAPE #10 SURVEILLANCE SPECIMEN BRACKETS
' 0006-0043 UPPER SURVEILLANCE SPECIMEN BRACKET AND ATTACHMENT AT 30 AZ 0043-0071 LOWER BRACKET AT 30 AZ ON SURVEILLANCE SPECIMEN AND ATTACHMENT WELD 0071-0121 UPPER AND LOWER SURVEILLANCE SPECINEN BRACKETS AND ATTACHMENT WELDS 0121-0154 UPPER AND LOWER SURVEILLANCE SPECIMEN BRACKETS AND ATTACHMENT WELDS TAPE #11 SHROUD SUPPORT RING A.
SUPPORT RING ATTACHMENT WELD TO VESSEL C(}
0000-0025 RESOLUTION CHECK
^
0025-0131 INDICATION FOUND BY ACCIDENT ON RECIRC NOZZLE 28-1A. EVALUATION DONE ON T/.PE #14 FOUND TO BE NOTHING.
0131-0157 AREAS BETWEEN O AZ------JET PUMP #1 0157-0179 AREAS BETWEEN JET PUMP #2------JET PUMP #3 f
0179-0239 AREAS BETWEEN JET PUMP #4------JET PUMP #5 l
0239-0264 AREAS BETWEEN JET PUMP #6------JET PUMP #7 TAPE #11 0264-0419 AREAS BETWEEN JET PUMP #8-----JET PUMP #9 l
NOTE: LINEAR INDICAT:ON SEEN THIS ARE!..
0310-0354 COUNTS 1
l 0419-0475 AREAS BETWEEN JET PUMP #10----180 AZ MANWAY l
~
0475-0538 AREAS"BETWEEN 180 AZ MANWAY---- JET PUMP all 0542-0595 AREAS BETWEEN JET PUMP #12----JET PUMP #J3 0595-0619 AREAS BETWEEN JET PUMP #14----JET PUMP #25
{
0619-0647 AREAS BETWEEN JET PUMP #16----JET PUMP #17 l
NOTE: LIMITED SCAN DUE TO IN"?RUMENT LINES.
0647-0671 AREA 6 BETWEEN JET PUMP #18----JET PUMP M19 95
0671-0689' AREAS BETWEEN JET PUMP N20----O AZ MANWAY (v~)
SUPPORT RING ATTACHMENT WHL TO SHROUD 0689-0725 AREAS BETWEEN O AZ MANWAY----JET PUMP #1 0725-0735 AREAS BETWEEN JET PUMP #2----JET PUMP #3, 0735-0754 APEAS BETWEEN JET PUMP #4----JET PUMP #5 NOTE: AREAS BETWEEN JET PUMP #6 & #7 ARE LIMITED
' 0754-0771 AREAS BETWEEN JET PUMP #8----JET PUNP #9 0771-0791 AREAS BETWEEN JET PUMP #10---180 AZ MANWAY 0791-0806 AREAS BETWEEN JET PUMP #12---JET, PUMP #13 0806-0821 AREAS BETWEEN JET PUMP #14---JET PUMP #15 0821-0836 AREAS BETWEEN JET PUMP #16---JET PUMP #17 ARE LIMITED DUE TO INSTRUMENT LINES 0836-0848 AREAS BETWEEN JET PUMP #18---JET PUMP #19 0848-0878 AREAS.BETWEEN JET PUMP #20--- 0 AZ MANWAY
{}
0879-1023 O AZ SUPPORT RING MANWAY 1023-1180 180 SUPPORT RING MANWAY COVER TAPE #12 SHROUD HEAD HOLD DOWN BRACKET & WELD 0000-0039 BRACKET & WELD 0 5 AZ 0039-0064 BRACKET & WELD 0 15 AZ TAPE #12 0064-0087 BRACKET & WELD 0 25 AZ 0087-0112 BRACKET & WELD 0 35 AZ 0112-0134 BRACKET & WELD 0 45 AZ 0134-0160 BRACKET & WELD 0 55 AZ 0160-0182 BRACKET & WELD 0 65 AZ 0162-0209 BRACKET & WELD 0 75 AZ 0209-0227 BRACKET & WELD 0 SS AZ s
022 -0249 BRACKET & WELD 0 95 AZ (J
0249-0183 BRACKET & WELD 0 105 AZ 0283-0331 BRACKET & WELD 0 115 AZ 96
0331-0383 BRACKET & WELD @ 125 AZ 0383-0406 BRACKET & WELD @ 135 AZ N/
0406-0435 BRACKET & WELD @ 145 AZ 0435-0465 BRACKET & WELD @ 155 AZ 0465-0501 BRACKET & WELD @ 165 AZ 0501-0522 BRACKET & WELD @ 175 AZ
' 0522-0557 BRACKET & WELD @ 185 AZ 0557-0574 BRACKET & WELD @ 195 AZ 0574-0596 BRACKET & WELD @ 205 AZ 0596-0626 BRACKET & WELD @ 215 AZ I
0626-0646 BRACKET & WELD @ 225 AZ 0646-0669 BRACKET & WELD @ 235 AZ 0669'-0695 BRACKET & WELD @ 245 AZ 0695-0733 BRACKET & WELD @ 255 AZ
. h) i 0733-0781 BRACKET 4 WELD @ 265 AZ 0781-0805 BRACKET & WELD @ 275 AZ TAPE #12 0805-0819 BRACKET & WELD @ 285 AZ 0819-0831 BRACKET & WELD @ 295 AZ 0831-0851 BRACKET & WELD @ 305 AZ 0851-0872 BRACKET & WELD 0 315 AZ 0872-0894 BRACKET & WELD @ 325 AZ 0894-0905 BRACKET & WELD @ 335 AZ 0905-0920 -
BRACKET & WELD @ 345 AZ 0920-0945 BRACKET & WELD @ 355 AZ 0945-0952 RESOLUTIO!1 CHECK SHROUD FLAT 4GE SURFACE 0952-1067 0 AZ --- 90 AZ 1067-1152 90 AZ 180 AZ 97
1152-1232 180 AZ --- 270 AZ 1232-1350 270 AZ --- 360 AZ TOP GUIDE HOLD'POWN 1350-1357 HOLD DOWN @ 356 AZ 1357-1364 HOLD DOWN O 86 AZ 1364-1376 HOLD DOWN O 176 AZ
- 1376-1397 HOLD DOWN O 266 AZ TAPE #13 JET PUMP HOLD DOWN BEAMS 0000-0038 JET PUMP #1 BEA11 0038-0076 JET PUMP #2 BEAN s.
b-0076-0109 JET PUMP #3 BEAM 0109-0141 JET PUMP #4 BEAM 0141-0162 JET PUNP #5 BEAM 0162-0180 JET PUMP #6 BEAM O 80-0 6
JET PUMP #7 BEAM O206-0228 JET PUMP #8 BEAM O228-0265 JET PUMP #9 BEAM 0265-0291 JET PUMP #10 BEAM F
O291-0322 JET PUMP #11 BEAM 0322-0354 JET PUMP #12 BEAM 0354-0396 JET PUMP #13 BEAM 0396-0441 JET PUMP #14 BEAN 0441-0482 JET PUMP #15 BEAM 0482-0531 JET PUMP #16 BEAM 0531-0581 JET PUMP #17 BEAM yg 0581-0629 JET PUMP #18 BEAM V
0609 0674 JET PUMP #19 BEAM 0674-070S JET PUMP #20 BEAM 96 i-
TAPE n13
,1ET PUMP INSPECTIONS
. ACCESSIBLE AREA OF JET PUMPS
/~s JET PUMP #1 lst 0707-0741 180 AZ BEND NOZZLE & PARTS OF TRANSITION PIECE 0741-0842 INLET MIXER & JET PUMP RISER BRACE 0842-0913 RESTRAINER 0913-0954 DIFFUSSER SLIP JOINT & RISER NOZZLE
' -0954-1070 DIFFUSER JET PUMP #2 1070-1252 180 AZ BEND NOZZLE & PARTS OF TRANSITION PIECE 1152-1423 INLET MIXEk & JET PUMP RISER BRACE I.
1423-1517 RESTRAINER 1517-1610 DIFFUSER SLIP JOINT 1610-1660 SENSING LINE - DIFFUSER TAPE #13 1660-1665 SENSING LINE UPPER BRACKET 1665-1676 SENSING LINE (f
1676-1695 LOWER SENSING LINE BRACKET 1695-1731 SENSING LINE & COUPLING 1731-1882 DIFFUSER J ET EU M_P_ # 1 1882-1929 180 AZ bet 3D NOZZLE & TRANSITION PIECE 1929-2051 INLET MIXER & RISER BRACE 2051-2153 RESTRAINER 2153 2003 D.1FFUSER ELlP J01NT 2203-2389 DIFFUSER JET EUMP #4 2389-2437 1CO AZ hEllD t102%LE & TRAt1SITION PIECE 2437-2537 2NLET MIXER & RISER BRACE 2537-2599 RESTRAINER 2599-2654 DI FFUSER SL] P J01NT 2654 2691 SENSING LINE 99
I 2691-2697 SENSING LINE-UPPER BRACKET 2697-2715 SENSING LINE 2715-2742 SENSING LINE LOWER BRACKET 2742-2774 SENSING LINE & COUPLING 2774-2945 DIFFUSER JET PUMP #5
- 2945-2996 180 AZ BEND NOZZLE & TRANSITION 2996-3001 INLET MIXER & RISER BRACE 3001-3080 RESTRAINER 3080-3125 DIFFUSER SLIP JOINT TAPE #13 3125-3275 DIFFUSER JET PUNP #6 3275-3300 180 AZ BEND NOZZLE & TRANSITION 3300-3458 INLET MIXER & RISER BRACE
( ')
3458-3501 RESTRAINER 3501-3544 DIFFUSER SLIP JOINT 3544-3568 SENSING LINE 3568-3588 SENSING LINE-UPPER BRACKET P
3588-3606 SENSING LINE 3606-3616 SENSING LINE LOWER BRACKET 3616-3708 SENSING LINE & COUPLING 3708-3768 DIFFUSER JET PUMP,p_'4 376G-3785 180 AZ BEND NOZZLE & TRANSITION 3785-3653 INLET MIXER - RISER BRACE 3853-3894 RESTRAINEk (D
s_/
3894-3910 DIFFUSER SLIP JOINT 3910-3950 CAMERA MISPLACED-RAN OVEk SAME AREA TWICE 3950-4044 SENSING LINE DIFFUSEk
/00 i
4044-4053~
SENSING LINE UPPER BRACKET f 4053-4062 SENSING LINE & DIFFUSER
(-)
4062-4078 LOWER SENSING LINE BRAC):ET 4078-4103 SENSING LINE 4 DIFFUSER & COUPLIllG 4103-4154 180 AZ BENL NOZZLE & TRANSITION 4154-4280 INLET HIXER & RISER BRACE 4280-4300 RESTRAINER 4300-4321 DIFFUSER SLIP JOINT TAPE 2 3-66 4321-4425 DIFFUSER E
^
JET PUMP 19 4425-4446 180 AZ' BEND NOZZLE & TRANSITION 4446-4489 INLET MIXER & RISER BRACE 4489-4509 RESTRAINER 4509-4545 DIFFUSER SLIP JOINT g
t-
\\- -
4545-4557 SENSING LINE 4557-456,0 UPPER SENSING LINE BRACKET 4560-4562 SENSING LINE 4562-4569 LOWER SENSING LINE BRACKET 4569-4576 SENSING LINE & COUPLING e
4576-4632 DIFFUSER JET PUMP alc 4632-4642 180 AZ BEND NOZZLE & TRANSITION 4642-4675 INLET MIXER & RISER BRACE 4675-4692 RESTRAINER 4692-4701 DIFFUSER SLIP JOINT s
4701-4765 DIFFUSER x -
4765-4769 RESOLUTION CHEC):
dhI EUUE.a_i 4769-4770 TOP OF SENS:NG LINE
/0/
3 JET PUMP. M.
E t
4770-4773
~ TOP OF SENSING LINE M
JET PUMP #6 g
a 4773-4775 TOP OF SENSING Aa JET PUMP # 7, 4775-4778 TOP OF SENSING 'LINE 5
- TAPE #1413 $ 2-3'N
{
/
JET PUMP #9 4778-4781 TOP OF SENSING LINE e
E JET PUMP #9 4781-4791 UPPER & LOWER SENSING LINE BRACKBT TAPE WIS RELOOK OF NANWAY COVERS 0000-0015 RESOLUTION CHECK e
0015-0120 0 AZ MANWAY COVER & WELD 0120-0390 180 AZ MANWAY COVER & WELD e
5 TAPE #16 DEI PUMP INSPECTION 0
m4 0000-0018 RESOLUTION CHECK g
"*o JET PUMP all mc 0018-0050 180 AZ BEND N0ZZLE & TRANSITION 55$
0050-0173 JNLET MIXER E"
a0 0173-0227 RESTRAINER E4-EE 0227-0246 DIFFUSER SLIP JOINT "c
$5 0246-0351 DIFFUSER Y"
$8 0351 0365 RISER SRACE "O
$0 JET PUMP =]2
.E 0365-0390 180 AZ BEfid~t10ZZLE & TR AllSITI C :i E"
$ u*
0390-0473 INLET MIXEk & BRACE mI 05 0473-0539 RESTRAINER 4
%3-0539-0564 DIFFUSER SLIP J01NT eO 5:
0564-0702 DIFFUSER 6 S Ells 2 tiG LINE N
~
r"\\
O
\\d 0702-0726 UPPER set 1S]NG LINE BRACKET l
0726-0735 LOWEh S Ellil l1G L]NE ERACMET
/02 1
i 0735-0739' SENSING LINE COUPLING S
.(d.
0739-0767 SENSING LINE JLI PUMP #13 0767-0792 180 AZ BEND N0ZZLE & TRANSITION
' TAPE #16 0792-0851 INLET MIXER
- 0851-0908 RESTRAINT 0908-0937 SLIP JOINT DIFFUSER 0937-1044 DIFFUSER JET PUMP 11
~
1044-1066 180 AZ BEND N0ZZLE & TRANSITION e
1066-1165 INLET MIXER & RISER BRACE 1165-1197 RESTRAINER 1197-1218 DIFFUSER SLIP JOINT 1218-1245 SENSING LINE r
1245-1254 UPPER SE!1 SING LINE BRACKET 1254-1263 SENS'JG LINE 1263-1267 SENSING LINE LOWER BRACKET 1267-1284 SENSING LINE & COUPL]tiG JET PUMP #15 1285-1317 180 BEND N0ZZLE 1317-1400 INLET MIXER & RISER BRACKET 1400-1434 RESTRAINER 2434-1467 DIFFUSER SL]P JOINT 1467-1540 DIFFUSER JET PUMP alt 1540-1597 180 AZ BEND 6 TRAt1SITION 1597-1701 ItiLET MIXER & RISER BRACE 1701-1730 RESTRAINER
,"N 1730-1740 DIFFUSER SLIP JOINT
(.)
1740-1775 S Et1S Il1G LINE & DIFFUSER 1775-1780 SENSING LINE UPPER BRACKET
/03
O 1794-1829 180 AZ BEND & TRANS,ITION PIECE 1829-1950 INLET MIXER 6 RISER BRACE 1950-1979
. RESTRAINER
- 1979-1986 DIFFUSER SLIP JOINT 1986-2016 DIFFUSER & SENSING LINE
'2016-2020 SENSING-LINE BRACKET UPPER
.2020-2031 LOWER SENSING IINE BRACKET 2031-2064 SENSING LINE JET PUMP #18 2064-2084 180 AZ BEND & TRANSITION PIECE 2084-2117 INLET NIXER & RISER BRACE 2117-2131 RESTRAINER 2131-2137 SLIP JOINT DIFFUSER
)
2137-2202
' DIFFUSER JET PUMP #19 2202-2221 180 AZ BEND & TRANSITION PIECE 2221-2280 INLET MIXER & RISER BRACE 2280-2302 RESTRAINER 2302-2318 SLIP JOINT DIFFUSER 2318-2363 DIFFUSER & SENSING LINE & BPACKETS JET PUMP #26 2363-2383 180 AZ BEND & TRANSITION 2383-2455 INLET MIXER & RISER BRACE 2455-2475 RESTRAINER 2475-2500 DIFFUSER SLIP JOIN 7 l
s d
2500-2608 DIFFUSER
/04 L..
6 O
N StIMMARY OF CLASS 1 AND 2 REPAIRS AND REPLACEMENTS Q-
]
l l
l l
O l
/05
REPAIRS AND REPLACEMENTS Repairs and Replacements No significant repairs or replacements were performed during the outage.
As mentioned previously in the report, one (1) Jet Pump Hold Down Beam and six (6) Shroud Head Hold Down Bolts were replaced due to rejectable indications reported from ISI examinations.
Numerous repai rs were initiated or component supports due to indications detected during ISI examination.
These repairs are not described in detail in this report, but Deficiency Card Numbers and HWO Numbers are referenced in the ABSTRACT SECTION and in the EXAMINATION TABLES for additianal infonnation.
Yalves 2821-F001 and 2821-F002 were disassembled and repaired due to leakage detected during perfonnance of the Class 1 System Leakage Test prior to plant s ta rt-up.
These valves were examined after repairs during performance of an isolated leakage inspection that was performed during plant start-up.
5 The ANI/ANII was utilized for review and/or inspection of all repair and/or replacement NDE activities.
3 0