ML20154F601

From kanterella
Jump to navigation Jump to search
Proposed Tech Spec Page 3/4 7-5 Reflecting Increased Min Spray Pond Water Level Consistent W/Spray Pond Vol Requirements
ML20154F601
Person / Time
Site: Limerick 
Issue date: 09/07/1988
From:
PECO ENERGY CO., (FORMERLY PHILADELPHIA ELECTRIC
To:
Shared Package
ML20154F559 List:
References
NUDOCS 8809200064
Download: ML20154F601 (2)


Text

'tIMITING CONDITION FOR OPERATION 3.7.1.3 The spray pond shall be OPERABLE with:

A minimum pond water level at or above elevation 250' 10" Mean Sea Level, a.

and 0

L.

A pond water temperature of less than or equal to 88 F.

APPIICABitITY:

OPERATIONAL CONDITIONS 1, 2, 3, 4, 5, and *.

ACil0N:

With the requirements of the above specification not satisfied:

t.

In OPERA 110NAL CONDITION 1, 2, or 3, be in at least H0T SHUTDOWN within 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> and in COLD SHUTDOWN within the next 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />.

b.

In OPERATIONAL CONDITION 4 or 5, declare the RHRSW system and the emergency service water system inoperable and take the ACTION required by Specifications 3.7.1.1 and 3.7.1.2.

(..

In Operational Condition *, declare the emergency service water system inoperable and take the ACTION required by 'pecification 3.7.1.2.

The provisions of Specification 3.0.3 are not applicable.

SURViILLANCE REQUIREMENTS 4./.. 3 The spray pond shall be determined OPERABLE:

a.

By verifying the pond water le. vel to be greater than its limit at least once per 24 hou m Byverifyingthewatersurfacetemperatgre(withintheuppertwofeetofthe h.

surface) to be less than or equal to 88 F:

1.

at least once per 4 hours4.62963e-5 days <br />0.00111 hours <br />6.613757e-6 weeks <br />1.522e-6 months <br /> when the spray pond temperature is greater than or equal to 80 F1 and 2.

at least once per 2 hours2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br /> when the spray pond temperature is greater than or equal to 85 F1 and 3.

atleasgonceper24hourswhenthespraypondtemperatureisgreater than 32 F.

c.

By verifying all piping above the frost line is drained within 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> after being used.

8G09200064 880914 POR ADOCK 05000352 P

PDC llMttlCK - UNIT 1 3/4 7-5

F a

UNITED STATES OF AMERICA

' NUCLEAR REGULATORY COM4ISSION In the Matter of Docket No.:

50-352 PHILADELPHIA ELECTRIC COMPANY (Limerick Generating Station, Unit No. 1)

CERTIFICATE OF SERVICE 1

I hereby certify that copies of the foregoing Application for-1 Amendment of Facility Operating License NPF-39 in the above captioned matter i

j were served on the following by deposit in the United States Mail, first class postage prepaid, on the 14th day of September, 1988.

William T. Russell, Regional Administrator U.S. Nuclear Regulatory Commission Region I 475 Allendale Road King of Prussia, PA 19406 l

t l

T. J. Kenny U.S. Nuclear Regulatory Commission i

Senior Resident Inspector l

P.O. Box 47 r

Sanatoga, PA 19464 l

t Thomas Gerusky, Director l

Bureau of Radiological Protection i

Department of Environmental Resources P.O. Box 2063 Harrisburg, PA 17120 j

Eugen6 J. Bradley

(

j Attorney for l

Philadelphia Electric Company

._ -,... _,~._. _

__...________,_,__--..__,_-._,--~.m..,.-