ML20154F586

From kanterella
Jump to navigation Jump to search
Application for Amend to License NPF-39,revising Tech Specs to Increase Min Spray Pond Water Level to Relect Spray Pond Vol Requirements
ML20154F586
Person / Time
Site: Limerick 
Issue date: 09/07/1988
From: Gallagher J
PECO ENERGY CO., (FORMERLY PHILADELPHIA ELECTRIC
To:
Shared Package
ML20154F559 List:
References
NUDOCS 8809200058
Download: ML20154F586 (7)


Text

.

BEFORE THE UNITED STATES NUCLEAR REGULATORY COMMIS$!0N in the Matter of Docket No. 50-352 PHILADELPHIA ELECTRIC COMPANY l

APPLICATION FOR AMENDMENT l

OF FACILITY OPERATING LICENSE NPF-39 i

i l

l I

Eugene J. Bradley

[

2301 Market Street i

Philadelphia, Pennsylvania 19101 I

Attorney for Philadelphia Electric Company SG09200058 690914 l

PDR ADOCK 05000352 l

p FDC J

BEFORE THE

?

UNITED STATES NUCLEAR REGULATGRY COMMIS510N i

l

(

In the Matter of Docket No. 50 352 PHILADELPHIA ELECTRIC COMPANY APPLICATION FOR AMENDMENT Of FACILITY OPERATING LICENSE NPf 39 l

l Philadelphia Electric Company, Licensee under facility Operating License hPf 39, for Limerick Generating Station Unit No.1, hereby requotts that I

the Technical Specifications contained in Appenjix A to the Operating License be f

amended as indicated by the vertical bar in the margin of the attached page 3/4 7-6.

The amendment of Technical Spccification 3.7.1.3.a requested herein will increase the spray pond water minimum level to a r.ean sea level elevation I

of 250'10" from the present requirement of elevation 250'0".

The proposed f

change is required to support two unit operation and is consistent with the

{

i I '

r t

original spray pond requirements described in FSAR, Section 9.2.6 and approved by the NRC for two unit operation in SER Section 9.2.5 and Supplements 3 and 4.

Licensee requests that the proposed changes become effective upon the issuance of an operating license for Limerick Unit 2.

t' 4

System Discussion:

The ultimate heat sink (VHS), a spray pond, serves the safety-related functions of providing tooling water, and acting as a heat sink for the 1

Emergency Service Water (ESW) system and the Residual Heat Removal Service Water (RHRSW) system during accident conditions. The UHS is designed to provide sufficient cooling water to the ESW and RHR$W systems, permitting simultaneous safe shutdobi and cooldown of both units, and maintaining them in a safe shutdown con 'It ton. Further system description, design and operation information can be found in LGS FSAR Section 9.2.6.

l l

Description of Changes:

Licensee proposes a change in Technical Specification 3.7.1.3.a spray i

pond level requirements from 250'0" to 250'10" above mean sea level. The LGS FSAR Section 9.2,6 specifies that the spray pond level required for two unit operation is a volume of 28.92 X 106 l

gallons or 250'10".

The volume t

associated with the current level of 250'0" provides design cooling requirements I

for only a single unit and was put in place originally to avoid operating restrictions associated with maintaining a water volume for two unit operation while only a single unit was licensed. The purpose of the proposed change is to i

I 4

l 2

I c

revise the Technical Specifications '.o reflect the spray pond level requirement which was previously approved for two unit operation.

i Safety Discussion:

f a

A spray pond level of 250'10" reflects the minimum two unit volume l

requirement of 26.92 x 106 2

gallons. The analysis supporting 250'10" is L

presented in FSAR Section 9.2.6 and demonstrates the ability of the spray pond r

j to provide a 30 day cooling supply below the maximum pond temperature limit I

without make-up or blowdown, considering the design basis heat input and

[

meteorlogical conditions.

The NRC approval of the spray pond is set forth in SER Section 9.2.5 (NUREG 0991) and Supplements 3 and 4.

For one unit operation, the Technical Specification limit was set to a value lower than what is required 4

j for two unit operation to avoid the unnecessary operating restrictions which may 3

j result frcm having to maintain an excess spray pond volume.

I i

The increase in pond level to meet the proposed Technical Specification

  • 111 not affect the design flood calculation.

The original spray pond maximum water elevation calculations were done modeling the spray pond full to its I

l spill ay elevation (251' 0") then adding a probable maximum precipitation event.

l l

causing water to spill from the emergency spillnay,

)

No Significant Ha?ards Consideration; l

1 (1) The proposed change does not involve a significant increase in the i

probability or consequer<es of an accident previously evaluated.

Raising the minimum level to 250'10" is within the bounding conditions 4

]

for the accident / design analysis referred to in FSAR section 9.2.6 and

)

3 i

1 a

accepted by the NRC in Section 9.2.5 of the Safety Evaluation Report i

(SER) and Supplements 3 and 4 for Limerick Generating Station. The requiremant to provide a 30 e tg supply for two unit operation while complying with all tt requirements of the Standard Review Plan (as discussed in SER S u,n 9.2.5 and Supplements 3 and 4) is provided by raising the minimum level to 250'10". The cooling supply is designed to accommodate:

1) single unit LOCA avd safe thutdown of the other unit.
11) safe shutdown of both units, i

The design basis accident analyses described in FSAR Chapter 15 are l

unaffected, therefore there is no significant ir. crease in the i

probability or consequences of an accident presiously evaluated.

(2) The proposed change does not change or c.1 ate the possibility of a new or (ifferent kind of accident previously evaluated.

As discussed in criterion one, the requested change provides spray pond level requirements within the scope of the accepted FSAR analysis, j

Therefore, the proposed change does not create the possibility of a new 1

or different kind of a:cident previously evaluated.

l (3) The proposed change does not involve a significant reduction in a margin of safety.

l The proposed change raises the miniinum sprt, pond levei to provide a l

margin of safety consistent with that previously approved for two-unit l

l operation in section 9.2.5 of the LGS SER and Supplements 3 and 4 and l

is detailed in FSAR section 9.2.6.

A spray pond level of 250'10" will 4

1

provide a 30 day cooling supply for two unit operation while complying with the design requirements of the Standard Review Plan (as discussed in SER 9.2.5 and Supplements thereto). The current Specification provides the cooling supply for a single unit only. Design requirements are identical for the current Specification and the proposed Specification so that there is no reduction in a margin of safety.

Ensironmental Considerations:

i l

Licensee has determined that the amendment requested in this Application involves no increase in the amouets and no change in the types of any effluents that may be released offsite and has also determined that there is i

l no increase in the individual or cumulative occupational radiation exposure.

l l

Therefore, there is no environmental consideration involved with this Application and consequently an environmental report is not submitted.

Conc lus ion Licensee has reviewed the proposed change to the Technical Specifications and has Concluded it does not involve significant hazards considerations, an unrtviewed safety question or an environmental consideration and will not endanger the health and safety of the public.

l Respectfully submitted, 1

PHILADELPHIA ELECTRIC COMPANY b OaHnb

()Vice Prests4nt

COMM0!TdEALTil OP PPNNSYLVANI A I

as.

COUNTY OF PillLADELPiiI A J. W. Gallagher, being first duly sworn, deposes and says:

That he 1

<> President of Philadelphia Electric Company, the Applicant h

.43 that he has read the foregoing Application fot Amendment of Pacility Operating Licenses, and knows the contents thereof: and that the statements and matters set forth therein are true and correct to the b.

'f his knowledge, information and belief.

%J 00>l&d~

(/

O Vice President Subscribed and sworn to before me this 'F day of 80 tt 1988.

..$ ?h Y ll<t r /. 0,'

Notary Public m y,p. u,wiog Ncsary Mem. % > b 4, comneemm lapree M 38' IM