c. wnirry September 10, 1998 Senior Vice President

& PrincipalNuclear Oficer U. S. Nuclear Regulatory Commission Attn: Document Control Desk i

Washington, DC 20555

SUBJECT:

COMANCHE PEAK STEAM ELECTRIC STATION (CPSES)

DOCKET NOS. 50 445 AND 50 446 TRANSMITTAL OF FIRE PROTECTION REPORT, REVISION 14 Gentlemen:

TV Electric, the owner of CPSES Units 1 and 2 herewith submits Revision 14 of the CPSES Fire Protection Report (FPR).

A page by page description of the changes is attached. The group number assigns a level of significance for eact change made to the Fire Protection Report consistent with TU Electric's letter TXX 88467 ef June 1, 1988.

In addition, all changes have been reviewed under the TU Electric 50.59 process and found not to include any "unreviewed safety questions."

Pages which do not have technical changes but are included in the revision (because a change shifted the existing material to another page or because only editorial changes were made to the Fire Protection Report or pages which are missing and approved earlier by previous FPR revision) are not oiscussed in the Attachment "CPSES FPR Revision 14 Detailed Description." These changes will not adversely affect the ability to achieve and maintain safe shutdown in the event of a fire.

FPR Revision 14 is being issued on September 10, 1998 and will be executed at 12:01 A.M. CST on September 15, 1998.

Enclosed are one signed original and one copy of the CPSES FPR Revision 14.

One copy each has been issued to the Regional Administrator for region IV, the responsible Branch Chief in the Division of Reactor Projects, the responsible Project Manager in the Office of Nuclear Reactor Regulation, and the appropriate NRC Resident Inspector. The remaining seven copies prescribed in 10CFR50.4(b)(6), will be maintained at TV Electric and available upon request for a period of one year following issuance of the amendment.

9909150240 990910 "

PDR ADOCK 05000445 F

PDR 3

),,'

i COMANCilE PEAK STEAM EEECT RIC STATION P.O. Box 1902 Glen Rose, Texas 76043-1002

_. - ~.....

l l

TXX 98200 Page 2 of 2

)

If you should have any questions, please contact Mr. Manu C. Patel at (254)897 0139.

Sincerely.

e. 2. Q C. L. Terry I

By:

M Rog'er'D. Walker Regulatory Affairs Manager MCP/grj Attachment Enclosure c

Mr. E. W. Herschoff Region IV Mr. J. I. Tapia. Region IV Mr. T. J. Polich. NRR Resident Inspector, CPSES i

4 6

i t

I i

l l

___m

_. _ _ _ -. to TXX-98200 Page 1 of 1 UNITED STATES OF AMERICA NUCLEAR REGULATORY COMMISSION In the Matter of

)

)

)

Texas Utilities Electric Company

)

Docket Nos. 50 445

)

50 446 l

(Comanche Peak Steam Electric Station.

)

Units 1 and 2)

)

)

AFFIDAVIT Roger D. Walker being duly sworn, hereby deposes and says that he is the Regulatory Affairs Manager of TV Electric, the licensee herein: that he is duly authorized to sign and file with the Nuclear Regulatory Commission this transmittal of the Fire Protection Report Revision 14: for the captioned facilities: that he is familiar with the content thereof; and that the matters set forth therein are true and correct to the best of his knowledge, e

information and belief.

M Roger D.M alker Regulatory Affairs Manager STATE OF TEXAS

)

COUNTY OF b e # )

. dayof!1' Subscribed and sworn to before me, on this f

L, 1998.

_ ?f l/

7( gj/]dddy

^^^^^^^^-^^^^'

l Gayle R. Peck p l fotaryPublic

/

  • "@M#.iis :

an

.=

_ - -. ~ ~ to TXX-98200 I

CPSES - FIRE PROTECTION REPORT REVISION - 14 DETAILED DESCRIPTION Prefix Page Page 1 (as amended)

Group Description i

I-13 4

Correct the Maximum Permissible Fire Load " low" classification from "160,000 Btu /sq.ft" to "80,000 Btu /sq ft".

Editorial Editorial change - Typographical error while processing Fire Protection Report (FPR), Revision 13. This change is consistent with Section 1.2.21.1 (page I-9) of FPR and as such it did not impact the Fire Safe Shutdown Analysis of the plant..

Change Request Number FP 3 Related SER 9.5.1 SSER SER/SSER Impact N

II-83 3

Revise the following for Fire Zone EA43 (paFe 11-83):

)

1) Remove the 45 gallon quantity of Lube Oil for CPI-CICACO-01.
2) Revise quantity of Lube Oil for CPI-CICACO-01 from 6 to 8 gallons.

j

3) Revise quantity of Lube Oil for CP2-CICACO-02 from 6 to 9 gallons.

Revision The service air compressor is non-safety related with no impact upon any safety function required by accident analysis. Verification of component removal and testing of connections removed from senice will ensure a new failure mcxic is not created. The combustible loading for the fire zone EA43 will be decreased as a rosult of the implentation of these activities.

Change Request Number FP 7 Related SER 9.3.I SSER 22 SER/SSER Impact N

1 II-83 3

Revise the following for Fire Zone EA43 (page 11-83) to remove the 45 gallon quantity of Lube Oil for CP2-CICACO-01.

Revision The service air compressor is non-safety related with no impact upon any safety function required by accident analysis. Verification of component removal and testing of connections removed from senice will ensure a new failure mode is not created The combustible loading for the fire zone EA43 will be decreased as a result of the implentation of this activity.

Change Request Number FP 8 Related SER 9.3.1 22

-.- to TXX-93200 CPSES - FIRE PROTECTIOH REPORT REVISIGN -

.4 DETAILED DESCRIPTION Prefix Page Page 2

{as_ amended)

Group Descrintion SER/SSER Impact N

111-3 1 3

Revise Section 4.3.2.4.1 oIFire Protection Report," Operations Department" to change " Auxiliary Operator" to

  • Plant Equipment Operator" and clanfy who directs these operators.

Correction CPSES management decided to combine the organizational positions of

" Auxiliary Operator" and "Radwaste Operator" into a single new organizational I

position of" Plant Equipment Operator". The training programs for the two previous postions were combined and the previous required qualifications and job functions were preserved in the new organizational position responsibilities.

Change Request Number FP 2 Related SER 13.1.2 SSER 12 SER/SSER Impact N

111-4 8 3

Swap the Valves 2-IIV-2452-1 and 2 between main steam lines I and 4.

Update This update is intended to maintain configuration control and to maintain the Licensing Document current.

Change Request Number FP 6 Related SER FPR SSER SER/SSER Impact N

dev 8c-3 4

Figure Add missing page 3 of 3 for FPR Section V, deviation 8c, " Figure Area SK".

Correction Add " Figure Area SK" for deviation 8e (Page 3 of 3), which provides clarification for the 4" coduits supplying power to the Main Steam Isolation Valves identified on Flow Diagram Ml-1924. This figure was missing in the past revisions of Fire Protection Report (FPR), however it does not impact the Fire Safe Shutdown Anflysis of the plant.

Change Request Number FP 3 Related SER 9.5.1 SSER SER/SSER Impact N

1 l

COMANCHE PEAK STEAM ELECTRIC STATION FIRE PROTECTION REPORT INSTRUCTION SHEET The following instructional information is being furnished to help insert Revision 14 into the Comanche Peak Steam Electric Station (CPSES) Fire Protection Report.

Discard the old sheets and insert the new sheets as indicated below.

Remove InscIl Title Page Title Page Report Index Page Report Index Page I-l through I-18 I-l through I-18 11-1 through Il-220 I1-1 through 11-220 III-l through III-82 111-1 through III-82 IV-1 through IV-49 IV-1 through IV-49 V-1 through Appendix D, FPR Figures V-1 through Appendix D, FPR Figures Title Page Title Page VD-1 EPL-0 through EPL-12 EPL-0 through EPL-12