ML20148E055
| ML20148E055 | |
| Person / Time | |
|---|---|
| Site: | Davis Besse |
| Issue date: | 01/20/1988 |
| From: | TOLEDO EDISON CO. |
| To: | |
| Shared Package | |
| ML20148E029 | List: |
| References | |
| TAC-66967, NUDOCS 8801250550 | |
| Download: ML20148E055 (6) | |
Text
3/4.8 ELECTRICAL POWER SYSTEMS THEI A hBAP hhnlithPM
(
llj y 3 / 4'. 8.1 A.C. SOURCES FORINFORMATION DN7 LIMITING CONDITION FOR OPERATION 3.8.1.1 As a minimum, the following A.C. electrical power sources shall be OPERABLE:
a.
Two independent circuits between the offsite transmission network and the onsite Class IE distribution system, each consisting of:
1.
Ont OPERABLE 345 KV transmission line, 2.
One OPERABLE 345-13.8 KV startup transformer, and s
3.
One OPERABLE 13.8 KV bus, and b.
Two separate and independent diesel generators each with:
1.
A separate day fuel tank containing a minimum volume of 4000 gallons of fuel, 2.
A separate fuel storage system containing a minimum volume of 32,000 gallons of fuel, and 3.
A separate fuel transfer pump.
l APPLICABILITY: MODES 1, 2, 3 and 4.
ACTION:
a.
With either an of fsite circuit or diesel,tenerator of the above required A.C. electrical power sources inoperable, demonstrate the OPERABILITY of the remaining A.C. sources by perfot ing Surveillance Requirement 4.8.1.1.1.a within one hour and at least once per 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br /> thereaf ter and by performing Surveillance Requirement 4.8.1.1.2.a.4 within 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />.
Restore at least two offsite circuits and two diesel generators to OPERABLE status within 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> or be in at least HOT STANDBY within the next 6
- hours and in COLD SHUTDOWN within the following 30 hours3.472222e-4 days <br />0.00833 hours <br />4.960317e-5 weeks <br />1.1415e-5 months <br />, b.
With one of fsite circuit and one diesel genesator of the above required A.C. electrical power sources inoperable, demonstrate the OPERABILITY of the remaining A.C. sources by performing Surveillance Requirement 4.8.1.1.1.a within one hour and at least once per 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br /> thereaf ter and by performing Surveillance Requirement 4.8.1.1.2.a.4 within 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br />. Restore at least one of the inoperable sources to OPERABLE status within 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> or 1
be in at least HOT STANDBY within the next 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> and in COLD SKUTDOWN within the following 30 t.ours.
Restore at least two l
i i
DAVIS-BESSE, UNIT 1 3/4 8-1 toendment Nc. 4,97 8801250550 900120 1
PDR ADOCK 05000346 P
PER w-.
w
-a.
1 ELECTRICAL POWER SYSTEMS ACTION (Continued) l I
offsite circuits and two diesel generators to OP'ERABLE status within 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> from the time of initial loss or be in at least HOT STANDBY Nithin the next 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> and in COLD SHUTDOWN within the followin;s30 hours3.472222e-4 days <br />0.00833 hours <br />4.960317e-5 weeks <br />1.1415e-5 months <br />.
Wit'a two # the above required of fsite A.C. circuits inoperable, c.
de2onstrate the OPERABILITY of two diesel ger.erators by perforaing Sarveillance Requirement 4.8.1.1.2.a.4 within 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br /> and at least once per 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br /> thereafter, unless the diesel generators are already operating; restore at least one of the inoperable offsite sources to OPERABLE status within 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> or be in at least HOT STANDBY within the next. 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br />. With only one offsite source restored, restore at least two offsite circuits to OPERABLE status within 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> from time of initial loss or be in at least HOT STANDBY within the next 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> and in COLD SHUTDOWN within the following 30 hours3.472222e-4 days <br />0.00833 hours <br />4.960317e-5 weeks <br />1.1415e-5 months <br />.
d.
Withfwo of the above required diesel generators inoperable, demo' strate the OPERABILITY of two offsite A.C. circuits by performing Surveillance Requirement 4.8.1.1.1.a within one hour and at least once per 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br /> thereafter; restore at least one of the inoperable diesel generators to OPERABLE status,within 2 hout:s or be in at least HOT STANDBY within the next f'hstics and in 'OLD SHUTDOWN within the following 30 hours3.472222e-4 days <br />0.00833 hours <br />4.960317e-5 weeks <br />1.1415e-5 months <br />. Restore at ler,st two diesel generators to OPERABLE status within 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> from time of initial loss or be-in at least HOT STANDBY within the next 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> and in COLD SHUTDOWN within the following 30 heurs.
SURVEILLANCE REQUIREMENTS 4.8.1.1.1 Each of the above required independent circuits between the offsite transmission network and the onsite Class IE distribution system shall be:
Determined OPERABLE at least once per 7 days by verifying correct a.
breaker alignments and indicated power availability, and b.
Demonstrated OPERABLE at least once per 18 months during i
shutdown by transferring (manually and automatically) unit power supply to each of the 345 KV transmission lines.# f 4.8.1.1.2 Each diesel generator shall be demonstrated OPERABLE:
a.
At least once per 31 days on a STAGGERED TEST BASIS, if Survstilance Requirement 4.8.1.1.2.c has not been performed withi s the previous 31 days, by:
i I
DAVIS SESSE, UNIT 1 3/4 8-2 Amendment No. 97 l
l
--r
TH S SAGE PROVIDED E,LECDtICAL PWER SYSTEMS, SE EILI.ANCE REQUIREiKNTS (Continued) 1.
Verifying the fuel level in the day fuel tank.
2.
Verifying the fuel level in the fuel storage tank.
3.
Verifying the fuel transfer pump can be started and trans-fers fuel from the storage system to the day tank.
4.
Verifying the diesel starts and accelerates up to 900 rpm, preceded by an engine prelube and/or appropriate other warmup procedures.
5.
Verifying the generator is synchronized, loaded to 1 1000 kw, and operates for 160 minutes, l
6.
Verifying the diesel generator is aligned to provide standby power to the associated essential busses.
7.
Verifying that the automatic load sequenec-timer is OPERABLE with each load sequence time within i 10% of its required
- value, b.
At Itast once per 92 days by verifying that a sample of diesel fuel from the fuel storage tank is within the acceptable limits specified in Table 1 of ASTM D975 68 when checked for viscosity, j
water and sediment.
c.
At least once per 184 days on a STAGGERED TEST BASIS by:
1.
Verifying the fuel level in the day fuel tank.
2.
Verifying the fuel level in the fuel storage tank.
3.
Verifying the fuel transfer pump can be started and transfers fuel from the storage sysic. to the day tank, i
4.
Verifying the diesel starts from ambient coadition and accelerates to at least 900 rpm in < 10 seconds.
5.
Verifying the generator is synchronized, loaded to 3 1000 kw, and operates for 1 60 minutes.
l 6.
Verifying the diesel generator is aligned to provide standby power to the associated essential busses.
1 7.
Verifying that the automatic load sequence timer is OPERABLE with each load sequence time within i 10% of its required
- value, i
DAVIS-BESSE, UNIT 1 3/4 8-3 Amendment No. 75, 77, 105
ELECTRICAL POVER SYSTEMS SURVEILLANCE RIQUIREMENTS (Continued) d.
At least once per 18 months during shutdown by:
1.
Subjecting the diesel to an inspection in accordance with procedures prepared in conjunctica with its manufacturer's recommendations for this class of standby service,*
2.
Verifying the generator capability to reject a load equal to the largest single emergency load supplied by the generator witbout tripping.
3.
Simulating a loss of offsite power in conjunction with a safety features actuation system (SFAS) test signal, and:
(a) Verifying de-energization of the essential busses and load shedding from the essential busses, (b) Verifying the diesel starts f rom ambient condition on the auto-start signal, energizes the essential busses with permanently connected loads, energizes the auto-connected essential loads through the load sequencer and operates for 1 5 minutes while its generator is loaded with the essential loads.
(c) Verifying that all diesel generator trips, except engine overspeed and generator differential, are automatically bypassed upon loss of voltage on the essential bus and/or an STAS test signal.*
4.
Verifying the diesel generator operates for 160 minutes while loaded to 1 2000 kw.
5.
Verifying that the auto-connected loads to each diesel generator do not exceed the 2000 hour0.0231 days <br />0.556 hours <br />0.00331 weeks <br />7.61e-4 months <br /> rating of 2838 kw.
The 18 month surveillance wnich is due on January 3,1988 for EDG l-1 and December 10, 1987 for EDG l-2, may be delayed for EDG l-1 until March 31, 1988 and EDG l-2 until March 20, 1988.
,g
- w. a ~s.svweithnee.,rd::A is As m nea4 t, tWP m*) bc Jalyed udil April I, tu?
DAVIS-BESSE, UNIT 1 3/4 8-4 Amendment No. 91, 105
THIS PAGE PROVIDED-ELECTRICAL POWER SYSTEMS Y
SHUT 00WN LIMITING CONDITION FOR OPERATION 3.8.1.2 As a minimum, the following A.C. electrical power sources shall-be OPERABLE:
a.
One circuit between the offsite transmission network and the onsite Class lE distribution system consisting of; 1.
One OPERABLE 345 XV transmission line, 2.
One OPERABLE 345 KV - 13.8 KV startup transfomer, and 3.
One OPERABLE 13.8 KV bus, and b.
One diesel generator with:
1.
Day fuel tank containing a minimum volume of 4000 gallons of fuel, 2.
A fuel storage system containing a minimum volume of 32,000 gallons of fuel, and 3.
A fuel transfer pump.
APPLICABILITY: MODES 5 and 6.
ACTION:
With less than the above minimum required A.C. electrical power sources OPERABLE, suspend all operai. ions involving CORE ALTERATIONS or positive reactivity changes until the minimum required A.C. electrical power sources are restored to OPERABLE status.
5URVEILLANCE REQUIREMENTS 4.8.1.2 The above required A.C. electrical power sources shall be demonstrated OPERABLE by the perfonnance of each of the Surveillance Requirements of 4.8.1.1.1 and 4.8.1.1.2 except for requirement 4.8.1.1.2.a.5 and 4.8.1.1.2.a.7.
DAVIS-BESSE, UNIT 1 3/4 8-5 Amendment No. 75
3/4.8 ELECTRICAL POVER SYSTEMS e
BASES
$3lh h
g g ; y ( u n w r ur 1
The OPERABILIT'i of the A.C. and D.C. power sources and associated distribu-tion systems during operation ensures that sufficient power will be available to supply the safety related equipment required for 1) the safe shutdovn of the f acility and 2) the mitigation and control of accident conditions within the facility.
The minimum specified independent and l
redundant A.C. and D.C. power sources and distribution systems satisfy the requirements of General Design Criterion 17 of Appendix "A" to 10 CFR 50.
The ACTION requirecents specified for the levels of degradation of the power sources provide restriction upon continued facility operation com=ensurate with the level of degradation.
The OPERABILITY of the power sources are consistent with the initial condition assumptions of the safety analyses and are based upon maintaining at least one of each of the onsite A.C. and D.C. power sources and associated distribution systems OPERABLE during accident conditions coincident with an assumed loss of offsite power and single failure of the other onsite A.C. source.
The OPERABILIT'i of the minimum specified A.C. and D.C. power sources and associated distribution systems during shutdovn and refueling ensures that
- 1) the facility can be maintained in the shutdown or refueling condition for extended time periods and 2) sufficient instrumentation and control capability is available for monitoring and maintaining the facility status.
l The Surveillance Requirements for demonstrating the OPERABILITY of the station batteries are based on the recon:mendations of Regulatory Guide 1.129, "Maintenance Testing and Replacement of Large Lead Storage Batteries for Nuclear Power Plants", February 1978, and IEEE Std. 450-1980, "IEEE
)
Recoe. ended Practice for Maintenance. Testing, and Replacement of Large lead Storage Batteries for Generating Stations and Substations".
Verifying average electrolyte temperature above the minimum for which the battery was sized, total battery terminal voltage on float charge, connec-tion resistance values and the performance of battery service and discharge testa ensures the effectiveness of the charging system, the ability to handle high discharge rates and compares the battery capacity at that time with the rated capacity.
Table 4.8-1 specifies the normal limits for each designated pilot cell and each connected cell for electrolyte level, float voltage and specific gravity.
The limits for the designated pilot es11s float voltage and specific gravity, greater than 2.13 volts and.015 below the manuf acturer's full charge specific gravity is characteristic of a charged cell with adequate capacity. The normal limits for each connected cell for float voltage and specific gravity, greater than 2.13 volts and not more than
.020 below the manufacturer's full charge specific gravity with an average specific gravity of all the connected cells not more than.010 below the manufacturer's full charge specific gravity, ensures the OPERABILITY and capability of the battery.
DAVIS-BESSE, UNIT 1 8 3/4 8-1 Amendment No.100