TABLE 3.3.10 APPENDIX R ALTERNATIVE SHUTDOWN INSTRUMENTATION AND CONTROLS MINIMUM READOUT CHANNELS INSTRUMENT LOCATION OPERABLE 1.

CTG Unit 1 - Volts H21-P623 1

2.

CTG Unit 1 - Frequency 1

3.

CTG Unit 1 - Watts 1

4.

CTG Unit 1 - Vars 1

5.

Condensate Storage Tank Level 1

6.

Standby Feedwater Flow I

7.

Reactor Water Level 1

8.

Reactor Pressure 1

9.

Torus Water Temperature 1

10. Torus Water Level 1
11. Primary Containment Temperature 1

CONTROL CIRCUITS SWITCH LOCATION TRANSFER (T), CONTROL (C), CMC (CMC),

PUSRBUTTON (PB), SELECTOR (S)

(T) EF1 Supv. Control H21-P623 (T) EF2 System Transfer (C) Voltage Control (C) Governor Control (CMC) CTG 11 Unit 1 Control / Status (C) 120 KV Pos GM Bkr Control (C) 120 KV Pos CK Bkr Control (C) 120 KV Pos CH Bkr Control (C) 120 KV Pos GD Bkr Control (CMC) CTG 11 Pos A2 Bkr Control (CMC) 13.2 KV Pos A7 Outbuilding - TSC Fd Bkr Control (CMC) 13.2 KV Pos A6 SS64 Alt Fd Bkr Control (CMC) SS64 Pri Pos D Bkr Control (CMC) SS66 Pri Pos C Bkr Control (CMC) SS67 Pri Pos B Bkr Control (CMC) Trans 1 Sec Pos A Bkr Control (CMC) SBFW Pump A Bkr Control (CMC) SBFW Pump B Bkr Control (CMC) 4160V Pos V1 Bkr Control (CHC) 4160V Pos V3 Bkr Control (CMC) 4160V Pos W5 Ekr Control (PB) SBFW Flow Control N21-F002 (PB) SBFW Flow Control N21-F003 (PB) SBFW Iso Valve N21-F001 (PB) SRV Line B B21-F013 G 0602050304 e60130 PDR ADOCK 05000341 PDR p

TABLE 3.3.10 (Continued)

APPENDIY R ALTERNATIVE SHUTDOWN INSTRUNENTATION AND CONTROLS CONTROL CIRCUITS SWITCH LOCATION (T) 4160V Pos C9 Tie Breaker Control (Cutoff Switch)

H21-P624 (T) 4160V Circuit Breaker Pos C10 Core Spray Pump C Control (Cut-off Switch)

(T) 4160V Pos CS Circuit Breaker Control (T) 4160V Pos C6 Circuit Breaker Control (T) 4160V Pos C8 Circuit Breaker Control (T) 4160V C11 Circuit Breaker Control (CMC) Residual Heat Removal Pump C (CMC) 4160V Pos C6 Incoming Breaker Control (CMC) 4160V Diesel Gen Bus #12 EB Breaker Control (CMC) ESS Bus 72C Transf R1400S023A Primary Control (T) 43S-5B Transfer Sw Viv. Ell-F004C H21-P625 (T) 43S-6D Transfer Sv Viv. Ell-F048A (T) 43S-5A Transfer Sw Viv. Ell-F003A (T) 43S-5C Transfer Sw Viv. Ell-F006C (T) 43S-6A Transfer Sw Viv. Ell-F047A (T) 43S-6B Transfer Sw Viv. Ell-F068A (T) 43S-7A Transfer Sw V1v. P44-F602A (T) 43S-4D Transfer Sw Viv. P44-F607A (T) 43S-5D Transfer Sw Viv. E11-F016A (T) 43S-9C Transfer Sw Fan T47-C002 (T) 43S-4C Transfer Sw Viv. P44-F606A (T) 43S-3C Transfer Sw Viv. Ell-F009 (T) 43S-3A Transfer Sw Fan T41-B018 (S) 43S-TW TR SW Valve T50-F412A, E41-F400 (PB) Suppr Pool to Pump C Viv. Ell-F004C (PB) RHR Heat Exch A Byp Viv. Ell-F048A (PB) RHR HX A Outlet Ell-F003A (PB) SDC Suction to RHR Pump C Ell-F006C (PB) RHR Heat Exch A Inl Viv. Ell-F047A (PB) RHR SW Control Viv. Ell-F068A (PB) EECW Div I HX Inlet Iso P44-F602A (PB) EECW to Drywl Isolation P44-P607A (PB) Conte Spray Otbd Iso Viv. Ell-F016A l

(CMC) Drywell Cooling Fan 2 (PB) EECW from Drywell'P44-F606A (PB) RHR Suction Cooling Inbd Viv. E11-F009 (S) Drywell Cooling Fan 2 (Low, High Speed)

(CMC) RHR Emergency Equipment Cooler 1 (PB) Torus Water Level' Isolation Valve E41-F400 (PB) Torus Water Level Isolation Valve T50-F412A

~.

r-TABLE 3.3.10 (Continued)

APPENDIX R ALTERNATIVE SHUTDOWN INSTRUMENTATION AND CONTROLS '

CONTROL CIRCUITS SWITCH LOCATION (T) 43S-5A Transfer Switch Viv. Ell-F024A H21-P626 (T) 43S-2A Transfer Switch Viv. Ell-F028A (T) 43S-1AR Transfer Switch Fan T47-C001 (T) 43S-3AR Transfer Switch Viv. Ell-F004A (T) 42S-SDR Transfer Switch Viv. Ell-F611A (PB) Suppr Pool Cooling Test Ell-F024A H21-P626 (PB) Suppr Chab Sp Otbd Iso Viv. Ell-F028A (CMC)Drywell Cooling Fan 1 (PB) Suppr Pool to Pump A Ell-F004A (S)

Dryvell Cooling Fan I (Low, High Speed)

(PB) RHR Recire. Otbd Bypass Ell 50-F611A (T) 43S-1B Transfer Switch V1v. B31-F031A H21-P627 (T) 43S-2B Transfer Switch Viv. E1150-F010 (T) 43S-2C Transfer Switch Viv. Ell 50-F015A (T) 43S-3A Transfer Switch Viv. E1150-F017A (PB) Recirc Pump A Disch Viv. B31-F031A (PB) Crosstie Header Viv. Ell-F010 (PB) RHR to Recire. Inbd Iso Viv. Ell-F015A (PB) RHR Recirc Otdb Iso Viv. Ell-F017A (T) 43S-4B Transfer Switch V1v. P44-F616 H21-P628 (S) EECW from Drywell Inbd Iso P44-F616 (PB) Dedicated Shutdown System Hil-P811

. - -