Proposed Tech Spec Table 3.18-1, Fire Detection Instruments
ML20133A245
Person / Time
Site: Crane 
Issue date: 07/31/1985
From:
GENERAL PUBLIC UTILITIES CORP.
To:
Shared Package
ML20133A217 List:
References
NUDOCS 8508050389
Download: ML20133A245 (2)


Text

..

TABLE 3.18-1 FIRE DETECTION INSTRUMENTS Total Number Instrument Location of Detectors Minimum Instruments Operable Heat Smoke Heat Smoke 1.

Control Building Elev. 355' Control Room 0

17 NA 8

Computer Room 0

10 NA 5

HCV Panel 0

2 NA 1

CC & CR Panel 0

3 NA 2

PC & PCR Panel 0

3 NA 2

PL Panel 0

1 NA 1

2.

Control Building Elev. 338' 1D 4160 V SWGR 0

1 NA 1

1E 4160 V SWGR 0

1 NA 1

ESAS Cabinets (CB-3C)

D 3

NA 2

Relay Room 4

1 2

1 3.

Control Building Elev. 322' IP 480V SWGR 0

1 NA 1

IS 480V SWGR1 0

1 NA 1

Battery Room A 0

1 NA 1

Battery Room B 0

1 NA 1

Inverter Room A 0

1 NA 1

Inverter Room B 0

1 NA 1

Remote Shutdown Panel 0

1 NA 1

4.

Control Building Elev. 306' Above False Ceiling 0

10 NA 5

5.

Diesel Generators I

Diesel A 1

0 1

NA Diesel B 1

0 1

NA 6.

Screen House-l General Area (HVAC) 2 0

1 NA Zone 1 0

6 NA 3

Zone 2 0

6 NA 3

7.

Fuel Handling Bldg. Elev. 281' l

General Cable Area (Zone 8) 0 9

NA 5

Lubricant & Storage Area 0

3 NA 2

(Zone 9)

8. Auxiliary Bldg. Elev. 261' I

Decay Heat Removal Pump A 0

3 NA 2

(Zone 6)

Decay Heat Removal Pump B 0

4 NA 2

(Zone 7)

Amendment No. # W' 3-87 DR P

    • e g

TABLE 3.18-1 FIRE DETECTION INSTRUMENTS Total Number Instrument Location of Detectors Minimum Instruments Operable Heat Smoke Heat Smoke 9.

Auxiliary Bldg. Elev. 271' Heat Exchanger Vault (Zone 11) 0 10 NA 5

10. _ Auxiliary Bldg. Elev. 281' l

Pipe Penetration Area (Zone 1) 0 5

NA 3

Makeup & Purification Pumps 0

3 NA 2

(Zone 2)

Valve Gallery (Zone 3) 0 1

NA 1

Cable Gallery (Zone 4) 0 4

NA 2

Hallway (Zone 10) 0 7

NA 4

11. Auxiliary Bldg. Elev. 305' Decay Heat & Nucl. Service Pumps & MCC 1A, 1B (Zone 5) 0 7

NA 4

Ventilation Room 1

1 1

1 12.

Intermediate Bldg. Elev. 295' EF-P-2 A&B Roonis (Zone 1) 0 6

NA 3

Cable Area (Zone 2) 0 2

NA 1

EF-P-1 Room (Zone 3) 0 2

NA 1

Valve Gallery (Zone 4) 0 2

NA 1

13.

Intermediate Bldg. Elev. 305' l

Tank Room (Zone 5) 0 1

NA 1

14.

Reactor Bldg. Elev. 281' l

Exhaust Ducts (Zone 1) 0 3

NA 2

Decay Heat Valve 1 (Zone 2) 0 1

NA 1

Decay Heat Valve 2 (Zone 2) 0 1

NA 1

Cable Tray at Let Down 0

1 NA 1

Cooler (Zone 3) 15.

Reactor Bldg. Elev. 305' l

Exhaust Ducts (Zone 4) 0 5

NA 3

Purge Exhaust (Zone 5) 0 1

NA 1

Cable Tray at Personnel 0

2 NA 1

Hatch (Zone 6)

16. Reactor Bldg. Elev. 346' l

D-Ring Id (Zone 7) 0 6

NA 4

0-Ring le (Zone 8) 0 6

NA 4

17.

Reactor Bldg. Elev. 382' l

Cable Tray (Zone 9) 0 2

NA 1

18.

Reactor Bldg. Elev. 382' i

Elevator Room (Zone 10) 0 1

NA 1

Amendment No. 101 3-87a