(iib,

\\

O PublicService

-.-m.

Company of Colorado 2420 W. 26th Avenue Suite 100 - D Denver, CO 80211 o;0d,"c580s-m n

(3o3) 571 -7511 April 22, 1985 Fort St. Vrain Unit No. 1 P-85134 h/

7 bbb Regional Administrator Region IV U.S. Nuclear Regulatory Commission MY-3E 611 Ryan Plaza Drive, Suite 1000 Arlington, Texas 76011 j

Attn: Mr. E. H. Johnson

Subject:

Station Battery Capacity to Satisfy Load Profile

Dear Mr. Johnson:

Letter P-85077 (dated 3/11/85), Attachment B-Battery Sizing, states a minimum battery capacity of 1080 amp / hrs would be required to satisfy the FSV emergency DC load profile.

The Exide computer modeling of our load profile requirements shows this number to be 1058 amp / hrs.

The Exide program specifies an FTC-15, 1180 amp /hr battery as sufficient to satisfy our needs, with an 11.5% margin.

This calculates to a requirement of the above-stated 1058 amp / hrs.

This correspondence is to amend the 1080 amp /hr reference in letter P-85077 to 1058 amp / hrs of required battery capacity.

Very truly yours, h JY Wlu d Don W. Warembourg Manager, Nuclear Engineering Division DWW/MR/dh Reviewed by:

b 4

h,e p-anm;;g

/6 eg n,oay ~ b El0