ML20115G518

From kanterella
Jump to navigation Jump to search
Proposed Tech Specs,Revising Limiting Condition for Operation 3.8.1.1, AC Sources - Operating
ML20115G518
Person / Time
Site: Beaver Valley
Issue date: 10/06/1992
From:
DUQUESNE LIGHT CO.
To:
Shared Package
ML20115G465 List:
References
NUDOCS 9210260193
Download: ML20115G518 (32)


Text

DPR-66 314.-9 ELECTRICAL DOWER SYSTEMS 3/4.8.J A.C. SOURCES

'2PERATING LIMITING CONDITION FOR OPERATION 3.8.1.1 As a minimum, the following A.C. electrical power sources shall be OPERABLE:

a. Two physically independent circuits between the offsite transmission network and the onsite Class 1E dist-ibution system, and
b. Two separate and independent diesel generators each with:
1. Separate day and engine-mounted fuel tanks containing A minimum of 900 gallons of fuel,
2. A separate fuel storage system-containing a minimum of 17,500 gallons of fuel, and
3. A separate fuel transfer pump. , j APPLICABILITY: MODES 1,2,3 and 4. NMb

~_

ACTION:

a. With either an offsite circuit or diesel generator
  • of the above required A.C. electrical power sources inoperable, denonstrate the OPERABILITY of the remaining A.C. sources by performing Surveillance Requirements 4.8.1.1.1.a and 4.8.1.1.2.a.5 within one hour and at least once per 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br /> thereafter; restore at least two offsite circuits and two diesel generators to OPERABLE status within 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> or be in COLD SHUTDOWN within the next 36 hours4.166667e-4 days <br />0.01 hours <br />5.952381e-5 weeks <br />1.3698e-5 months <br />,
b. With one offsite circuit and one diesel generator
  • of the above required A.C. electrical power sources inoperable, demonstrate 'the OPERABILITY of the remaining A.C. sources by performing Surveillance Requirements 4.8.1.1.1.a and 4.9.1.1.2.a.5 within one hour and at least once per 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br /> thereafter; restore at least one of the inoperable sources to OPERABLE status within 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> or be in COLD SHUTDOWN within the next 36 hours4.166667e-4 days <br />0.01 hours <br />5.952381e-5 weeks <br />1.3698e-5 months <br />. Restors at least two offsite circuits and two diesel generators to OPERABLE status within 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> from the time of initial loss or be in COLD' SHUTDOWN within the next 36 hours4.166667e-4 days <br />0.01 hours <br />5.952381e-5 weeks <br />1.3698e-5 months <br />.

1 I

BEAVER VALLEY - UNIT 1 3/4 8-1 9210260193 921006 DR ADOCK 0500 4 (f Wym

a RICAL POWER SYSTEMS hh ACTION (Continued)  :

ith two of the above required Offsite A.C, circuits inoperable, demonstrate the OPERABILITY of two diesel generators by performing Surveillance _ Requirement 4.8.1.1.2.a 5 within one hour and at least once per 8-hours thereafter, unless the diesel generators are already

,~

operating; restore at least one of the inoperable offsite sources to OPERABLE Status within 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> or be in at least HOT STANDBY wi thin the next 4 hours4.62963e-5 days <br />0.00111 hours <br />6.613757e-6 weeks <br />1.522e-6 months <br />. With only one offsite source restored, restore at least two offsite circuits to OPERABLE status within 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> from time of initial loss or be in COLD SHUTDOWN within the next 36 hours4.166667e-4 days <br />0.01 hours <br />5.952381e-5 weeks <br />1.3698e-5 months <br />,

d. With two of the above required diesel generators

circuits by performing Surveillance Requirement 4.8.1.1.1.a within one hour and at least once per 8-hours thereafter; restore at least one of the inoperable diesel generators to OPERABLE status within 2 hours or be in COLD SHUTDOWN within the next 36 hours4.166667e-4 days <br />0.01 hours <br />5.952381e-5 weeks <br />1.3698e-5 months <br />. Restore at least two diesel generators to OPERABLE status within 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> from tima of.

initial loss or be in COLD SHUTDOkN within the next 26 hours3.009259e-4 days <br />0.00722 hours <br />4.298942e-5 weeks <br />9.893e-6 months <br />.

SURVEILLANCE REQUIREMENTS 4.8.1.1.1 Two physically independent circuits between the offsite transmission network and the onsite Class 1E distribution system shall be:

a. Determined OPERABLE at least once per 7 days by verifying correct breaker alignments, indicated power availability, and
b. Demonstrated OPERABLE at least once per 18 months by transferring (manually and automatically) unit power supply from the unit circuit to the system circuit.

4.S.1.1.2 Each diesel generator shall be dr.onstratad OPERABLE:

a. At least once per 31 days on a STAGGERED TEST BASIS by:
1. Verifying the fuel level in the day and engine-mounted fuel tank,
2. Verifying the fuel level in the fuel storage tar.k,

$YE Fuel oil contained in the storage tanks not meeting the l properties in accordance with 4.8.1.1.2.d.2 or 4.8.1.1.2.e shall be brought within the specified limits within 7 days.

/

BEAVER VA1LEt - UNIT 1 3/4 8-2 Amendment No.

REPLAG W ITN n SERT'We e g sey % ry g 1

R inghment to A.c.:Sournen - On91311ns 1 1

Insert " A" j

~ACI12H: )

a. With one offe.:te circrir of 3.8.1.1.a _ inoperable,- j demonstrate -the OPERABILITY of the remaining A.C. sources; by performing Surveillanc Requirement 4.8.1.1.1.a'within 11 ~i hour and at least once por 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br /> thereafter. If either diesel generator has not been successfully' tee" .d within the past 24 hours, demonstrate its OPERAbtLITY: by; performing Surveillance Requirement 4.8.1.1.2.a.S separately for each such diesel generator within 24: hours.

Restore the offs!.c. circuit to OPERADLE status within 72-

-hours or bo in at least HOT STAND 9Y within the next 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> and COLD SHUTDOWN within the following 30 hours3.472222e-4 days <br />0.00833 hours <br />4.960317e-5 weeks <br />1.1415e-5 months <br />.

b. Wich one diesel generator (1)- of 3.8.1.1.b inoperable, demonstrate the OPERABILITY of the A.C. offsite sources by performina surveillance Requirement 4.8.1.1.1.a - within 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> and at least once per 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br /> thereafter; and if the diesel generator became inoperable due to any cause other than testing or preplanned preventative maintenance, demorrtrate the OPERABILITY of the remaining OPERABLE diesel generator by Requirement 4.8.1.1.2.a.5 wit'iin performinghours(gyrveillanc" 24 N; restore the -diesel generator to OPERABLE status within 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> or be in at least HOT STANDBY within the next 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> and in COLD SHUTDOWN within the following 30 hours3.472222e-4 days <br />0.00833 hours <br />4.960317e-5 weeks <br />1.1415e-5 months <br />.
c. With one offsito_ circuit and one diesel generator (1) inoperable, demonstrate the OPERABILITY of the reraining A.C. sources by performing Surveillance Requirement 4.8.1.1.1.a within one hour and at least once per;8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br /> thereafter; and if the diasal generator became inoperable-due to any cause other than testing or proplanned preventative maintenance, demonstrate the OPERABILITY of the remaining OPERABLE diesel generator- by perforg Surveillance Requirement 4.8.1.1.2.a.5 within 8 hc urs t jpg 1; .

restore one of the inoperable sources to OPERABLE status-within 12 -hours or be in at least HOT STANDBY within the next 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> and in COLD SHUTDOWN within the following 30 hours3.472222e-4 days <br />0.00833 hours <br />4.960317e-5 weeks <br />1.1415e-5 months <br />. Restore the other A.C.- power: source _(offsite circuit or diesel generator) to OPERABLE status in

-accordance with the provisions of Section 3.8.1.1 Action' Statement- a or b, as appropriate with the time requirement of that Action Statement based on-.the time of initial loss-of- the remaining inoperable n.C. power source. _ A successful test cf diesel OPERABILITY per _ Surveillance Requirement 4.8.1.1.2.a.5 performed under this Action-Statement- for an OPERABLE diesel or a restored-to OPERABLE

. diesel satisfies the- diesel generator test requirement of Action Statement a or.b.

BEAVER VALLEY - UNIT 1 (Proposed Wording)

Attachndnt to A.C. Sources - Opprpiing Lrige rt "A" ( Cont i nued_),~
d. With two of the required of; site A.C. circuits inoperable,.

demonstrate the OPERABILITY of- two diesel generators by Requirement sLquentially performing Surveillance 4.8.1.1.2.a.5 on- both -diesels 'within 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br />, unless the diesel generators are already operating; restore one of the inoperable offsite sources to OPERABLE status within 24-hours or be in at least HOT STANDBY within the next 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br />. Following restoration of one offsite source, follow- >

Action Statement a with the time requirement of'that Action Statement based on the' time of initial loss of the remaining inoperable offsite A.C. circuit. A successful test (s) of diesel OPERABILITY per Surveillance Requirement 4.8.1.1.2.a.5 performed under this Action Statement for the OPERABLE diesels satisfies the diesel generator test requirement of Action Statement a.

e. With two of the above required diesel generators (1) inoperable, demonstrate the OPERABILITY of two offsite A.C.

circuits by performing Surveillance Requirement 14.8.1.1.1.a within one hour and at least once per 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br /> tho eafter; restore one of the inoperable diesel generators t- sPERABLE status within 2 hours2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br /> or be in at least HOT STnNDBY within the next 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> and in COLD SHUTDOWN within the following 30 hours3.472222e-4 days <br />0.00833 hours <br />4.960317e-5 weeks <br />1.1415e-5 months <br />. Following restoration of one diesel generator unit, follow Action Statenont b with the time requirement of that Action statement based on the time of initial loss of the remaining inoperable diesel generator.

A successful test- of diesel OPERABILITY per Surveillance Requirement 4.8.1.1.2.a.S performed under this Action Statement far a restored to OPERABLE diesel satisfies the diesel gerarator- -

test requirement of Action Statement b.

(1) Fuel oil contained in the storage tanks not meeting the properties in accordance with 4.8.1.1.2.d.2 or 4.8.1.1.2.e shall be brought within the specified limits within 7 days.-

(2) This test is required to be completed regardless of when the inoperable diesel generator is restored to OPERABILITY.

t l-1:

BEAVER VALLEY UNIT 1 (Proposed Wording)

. , . . . .... . . - . . . . . . . - . _ - . - . . . .- . . . ~ . .. .... .. .

. ATTACHMENT A-2 i Beaver Valley Power Station, Unit.No. 2

- Proposed Technical Specification change No. 67 Revise the Technical Specification as follows:

Ennove Paans Insert Panes 3/4 8-1 3/4 8-1 3/4 8-2 3/4 8-2 3/4 8-3 3/4 8-3 3/4 8-5 3/4 8-5 l~

W -

e w - .- -*- w

^iPF l 4 3/4.8 ELECTRICAL' POWER SYSTEMS-(3/4.811- A;C. SOURCES'

-OPERATING LIMITING CONDITION FOR OPERATION

3. 8.1.1 As a minimum, the following A.C. electrical power-sources shall be  ;

OPERABLE: '

a. Two physically independent circuits between the offsite transmission network.and the onsite Class 1E distributi_on system, cnd
b. Two separate and independent diesel generators each with:
1. Separate day _ tank containing a minimum of 350-gallons of fuei.
2. A separate fuel storage system containing a minimum of 53,225-gallons of fuel,
3. A separate fuel transfer pump,-
4. Lubricating oil storage =containing a minimum total volume'of 504 gallons of lubricating oil, and
5. Capability to transfer lubricatin'g oil-from storage to the '

diesel generator unit.

n4

@PLPG WTTR TMERT 8

~

APPLICABILITY: mores 1, 2, 3 and 4.

a. With either an offsite circuit or diesel generator
  • of_the above re-quired A.C. electrical (power sources-_ inoperable, demonstrate the1 OPERABILITY of_the remaining A.C._ sources by performing Surveillance

, Requirements 4.8.1.1.1.a and 4.8.1,1.2.a.5 within one hour and at least once per 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br /> thereaf ter; restore at_ least two offsite:cir-

.cuits and two diesel generators =to OPERABLE status within-72 hours-or be in COLD SHUTDCWNLwithin the next 36 hours4.166667e-4 days <br />0.01 hours <br />5.952381e-5 weeks <br />1.3698e-5 months <br />.

L b. With one offsite circuit-and one diesel-generator

  • of the above re-L quired A.C. electrical: power sources-inoperable, demonstrate the.
  • l 0PERABILITY of the remaining A.C. sources by performing Surveillance 1 Requirements-4.8.1.1.1.a and 4.8.1.1.2.a.5 within one~ hour and at-least once per 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br /> thereafter;_ restore at least one of the in-operable sources to OPERABLE status within 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> or be in' COLD SHUTOOWN within:the-next 36 hours4.166667e-4 days <br />0.01 hours <br />5.952381e-5 weeks <br />1.3698e-5 months <br />. Restore at least two offsite

~

l' circuits and two diesel generators to OPERABLE status within 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> from the time of initial loss or be in-COLD-SHUTDOWN within the next

! 36 hours4.166667e-4 days <br />0.01 hours <br />5.952381e-5 weeks <br />1.3698e-5 months <br />.

c L

BEAVER VALLEY -. UNIT 2 3/4 8-1 UropoScb U otb

NPF-73

.4 ELECTRICAL POWEP SYSTEMS

@fLACE bhN Mbb b LIMITIN(LCONDTTION FOR OPERATION (ContinueL _

c. With two of the above required offsite A.C. circuits inoperable, demonstrate the OPERABILITY of two diesel generators by performing Surveillance Requirements 4.8.1.1.2.a 5 witnin one hour and at least once per 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br /> thereafter, unless the diesel generators are alrtady operating; restore at least one of the inoperable offsite sources to OPERABLE status withi7 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> or be in at least HOT STANDGY within the next 4 hours4.62963e-5 days <br />0.00111 hours <br />6.613757e-6 weeks <br />1.522e-6 months <br />. With only one offsite source restored, restore at least two offsite circuits to OPERABLE status within 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> from time of initial loss or be in COLD SHUTDOWN within the next 36 hours4.166667e-4 days <br />0.01 hours <br />5.952381e-5 weeks <br />1.3698e-5 months <br />.
d. With two of the abova required diesel generators inoperable *, demon-strate the OPERABILITY of two offsite A.C. circuits by performing Surveillance Requirement 4.8.1.1.1.a within one hour and at least once per 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br /> thereafter; restore at least one of the inoperable diesel generators to OPERABLE status within 2 hours2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br /> or be in COLO SHUTDOWN within the next 36 hours4.166667e-4 days <br />0.01 hours <br />5.952381e-5 weeks <br />1.3698e-5 months <br />. Restore at least two diesel gen-erators to OPERABLE status within 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> from time of initial loss or be in COLD SHUTDOWN within the next 36 hours4.166667e-4 days <br />0.01 hours <br />5.952381e-5 weeks <br />1.3698e-5 months <br />.

SURVEILLANCE REOUIREMENTS 4 8.1.1,1. Two physically independent circuits between the offsite trans-mission network and the onsite Class 1E distribution system shall be:

a. Determine OPERABLE at least once per 7 days by verifying correct breaker alignment, indicated power availability, and
b. Demonstrated OPERABLE at least once per 18 months by transferring (manually and automatically) unit power supply from the unit circuit i

to the system circuit.

4.8.1.1.2 Each diesel generator shall be demonstrated OPERABLE:

a. At least once per 31 days on a STAGGERED TEST BAStr by:
1. Verifying the fuel level in the day tank,
2. Verifying the fuel level in the fuel storage tank, r-3 NFueloilcontainedinthestoragetanksnotmeetingthepropertiesin l accordance with 4.8.1.1.2.d.2 or 4.8.1.1.2.e shall be brought within the ecified limits within 7 days.

y RWLACE W)T4 TNSERT Y BEAVER VALLEY - UNIT 2 3/4 8-2 Amendment No.

(fropsch Wofb

- . . . . _ _ . . _ . . .~ - --. - - - - - . - -

.Attachme:nt to-A.C. Sources - Operqting '

l l Lg 3 x g " B "' ^

ACTION:-- ,

a. With one offsite circuit of 3.8.1.1.a , inoperable,.

demonstrate the OPERABILITY of_the remaining A.C.. sources by performing Surveillance Requirement 4.8.1.1.1.a within 1 hour and at least once per 8. hours thereafter. If either.

diesel generator has- not' been successfully tested within the past. 24 hours, demonstrate its OPERABILITYL by performing Surveillance Requirement 4.8.1.1.2.a.5.

coparately for each such diesel generator within 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />.

Restore the offsite circuit to OPERABLE status within 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> or be'in at least HOT STANDBY within the next 6 hour6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br />s-and COLD SHUTDOWN within the following-30 hours,

b. With one diesel generator (l)- of 3.8.1.1.b inoperable, demonstrate the OPERABILITY-of the A.C. offsite sources lar

~

performing Surveillance Requirement 4.8.1.1.1.a within 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> and at least once per 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br /> thereafter; and if the diesel generator became inoperable 1due to any cause other than testing or preplanned preventative ~ maintenance, demonstrate the OPERABILITY of the remaining OPERABLE diesel generator by 91r Requirement 4.8.1.1.2.a.5 within. performing 24' hours (b ;veillance restore the diesel generator to OPERABLE status within 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> or be.in at least HOT STANDBY within the next 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> and in COLD SHUTDOWN within the following 30 hours3.472222e-4 days <br />0.00833 hours <br />4.960317e-5 weeks <br />1.1415e-5 months <br />,

c. With one offsite circuit and one diesel generator (1) inoperable, demonstrate the OPERABILITY of the' remaining' A.C. sources by performing Surveillance Requirement 4.8.1.1.1.a within one hour and at-least once per 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br /> thereafter; and if the diesel generator became inoperable due to any cause other than- testing or preplanned preventative maintenance, ' demonstrate the OPERABILITY of the remaining OPERABLE diesel generator hf perforg Surveillance- Requirement 4.8.1.1.2.a.5 within-8 hours){pg;.

restore one of. the inoperable sources to OPERABLE status.

-within 12' ' hours or be in at least HOT STANDBY within the next 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> .and in. COLD SHUTDOWN within the following 1K) hours. Restore the other A.C. power-- source (offsite circuit or -diesel generator) to . OPERABLE status in-accordance with the provisions of Section-3.8.1.1' Action Statement a c r b, as appropriate with the time requirement' of that Action Statement' based on the time of initial loss of the remaining inoperable A.C. power ~ source. . .A.

-successful test of diesel' OPERABILITY per Surveillance Requirement -4.8.1.3.2.a.S performed ~ under- this Action Statement for an OPERABLE diesel or a restored to OPERABLE.

diesel- satisfies the diesel generator test requirement of Action Statement a or b.

BEAVER VALLEY - UNIT 2 (Proposed Wording)

._ - _ -- _. _ _ _ . ._ .. . . . _ > m_ . . _ .

, Attachment to Ad'., Sou_rggs - Oneratilag Jnsert "B" (Continuedl

d. With two_ of.the required offsite A.C. circuits. inoperable, demor. strate the OPERABILITYz of two diesel generators:by-sequentially performing Surveillance Requirement 4.8.1.1.2.a.5 on both diesels within 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br />, unless the diesel generators are already operating; restore one of the inoperable offsite sources to OPERABLE status within 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> or be in at least HOT STANDBY within the next 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br />. Following restoration of one offsite source, follow Action Statement a with the time requirement-of that' Action Statement based on the time of initial loss- of the

. remaining inoperable offsite A.C. circuit. A successful

-test (s) of diesel OPERABILITY per Surveillance-Requirement 4.8.1.1.2..a.5 performed under this Action Statement for the OPERABLE diesels satisfies the diesel generator test requirement of Action St cement a.

e. With two of the above required diesel generators (1h inoperable, demonstrate the OPERABILITY-of two offsite-A.C.

circuits by performing Surveillance Requirement 4.8.1.1.1.a within one hour and at least once por 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br /> thereafter; restore one of the inoperable diesel generators to OPERABLE status within 2 hours2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br /> or be in at least HOT STANDBY within the next 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> and-in COLD SHUTDOWN within:the following 30 hours3.472222e-4 days <br />0.00833 hours <br />4.960317e-5 weeks <br />1.1415e-5 months <br />. Following -rectoration of one diesel generator-unit, follow Action Statement b with the time requirement of that Action Statement based on the time of initial loss-of the remaining inoperable diesel generator. A successful test of diesel- OPERABILITY- per Surveillance Requirement 4.8.1.1.2.a.5 performed under this Action Statement for-a-restored to OPERABLE diesel. satisfies the diesel generator.

test requirement of Action Statement b.

1

1) Fuel oil contained in the stotage tanks not meeting the-properties in accordance with 4.8.1.1.2.d.2 or 4.9.1.1.2.e shall be brought within the specified limits within 7 days.'

(2L This test is required to be completed regardless of when-the inoperable diesel generator is restored to OPERABILITY, BEAVER VALLEY - UNIT 2 (Proposed Wording)

11PF-i3 -

ELECTRICAL POJER SYSTEMS Luys!.LutLREZLLE M L &mti w 1

3. (Deleted) 4 Verifying the fuel transfer pump can be started and transfers fuel from the storage system to the day tank,
5. Verifying the diesel starts frra ambient condition,
6. Verifying the generator is synchronized, loaded to 3, 4,238 kw, and operates for at least 60 minutes,
7. /erifying the diesel generator is aligned te provide standby power to the associated emergency busses, and On.ETE m 8. verifying the lubricating oil inventory in storage,
b. Atleastonceper18monthNduringshutdownby:
1. Subjecting the diesel to an inspection in accordance with pro-cedures prepared in conjunction with its manufacturer's recom-mendations for this class of standby service,
2. Verifying the generator :apability te reject a load of > 825 kw without tripping,
3. Simulating a loss of offsite power in conjunction witt, a safety injection si taal, and:

a; Verify.iig de-energization of she eurgency busses and load shedding from the emergency busses, b) Verifying the diesel starts from ambient condition on the auto-start signal, energirr. the emergency busses with per-manently connected loads, snc.*gizas the auto-connected emergency loads through the load sequencer and operates for

> 5 minutes while its generator is loaded with the emergency Toads.

4. Verifying that on a loss of power to the emergency busses, all gg7Em diesel generatot trips, except engine overspeed, backup phase 4 fault detect 16i$ generator differential current, and gene ator overexcitation are automatically disabitd.

"The specified 10-month surveillance interval during the first fuel cycle may be extended to coincide wi' nmpletion of the first refueling outage.

  1. This item (backup phase fs dJ M *'on) is to be implemented no later than startup from the second rerueling . age.

-- o E LETE.

BEAVER VALLEY - UNIT 2 3/4 8-3 Amendment No.

hopo.%b urch

I tiPF-73  !

ELECTRICA,L POWER SYSTEMS EV1 41M M .E RE0VIREMENT5 (Continued .__,

-i

e. At least once every 31 days by obtaining a sample of fuel oil from the storage tanks and day tanks in accordance with ASTM 02276-78, and verifyie- that total particulate contamination is less than 10 mg/ liter when checked in accordance with ASTM 02276-78, Method A
f. At least once per 10 years or af ter any *nodifications which could affect diesel generator interdependence by starting" oth diesel generators simultaneously, during' shutdown, and verifying -

that both diesel generators accelerate to at least 514 rpm in less than or equal to 10 seconds, g, At least once per 10 years by:

1) Oraining each main fuel oil storage tank, removing the accumu-lated sediment, and cleaning the tank using a sodium hypochlorite solution or other appropriate cleaning solution, and
2) Performing a pressure test, of those portions of the diesel fuel oil system designed to Section III, subsection ND of the ASHE Code, at a test pressure equal to 110% of tne system design pressure, i l

1 (3)

    • This test shall be conducted in accordance with the manufacturer's rect'- .-

dations regarding engine prelube and warmup procedures, and as applic/

l regarding loading recommendations. ,

BEAVER VALLEY - UNIT 2 3/4 8-5 Amendment No.

(Pr y esed M '

ATTACHMENT H Beaver Valley Power Station, Unit Hos. 1 and e Proposed Technical Specification Change No. 200 and 67 REVISION OF SPECIFICATION 3.8.1.1 TITLED "A. C. SOURCES - OPERATING" A. DESCPIPTION OF AMENDMENT REOUEST The prcposed changes would revise the action statements of Limiting Condition of Operation (LCO) 3.8.1.1, titled "A.C.

Sources-Operating." The proposed Action Statement "a" would provide actions to be taken with one offsite circuit of the required A.C. electrical power sources inoperable. The actions required when one diesel generator (D/G) is inoperable are being separated from this action statement and incorporated in? ~S jndividual Action Statement "b". The present requiremer 4.;

Action Statement "a" to perform surveillance requirement rPj 4.8.1.1.2.a.5 within one hour and at least once por 8 '.oere thereafter would be altered to require that SR 4.8.1.1.2.a.5 bc performed once within 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> of declarina the offsite circuit inoperabic unicus previously tested within the past 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />.

The proposed Action Statement "b" would provide actions to be taken with one D/G inoperable. The pntformance of SR 4.8.1.1.2.a.S, will be performed once within 24 hours on the remaining D/G. This test is required to be performed regardless of when the inoperable D/G is restored to operability. A provision would be added to not require performance of SR 4.8.1.1.2.a.5 if the D/G has been rendered inoperable due to proplanned maintenance or surveillance testing.

The proposed Action Statement "c" would provide actions to be taken with one offsite circuit and one D/G inoperable. In the exist 3ng LCO 3.8.1.1 specifjcation, this is Action Statement "b" with the following revisions. Surveillance requirement 4.8.1.1.2.a.5 will be performed on the remaining D/G within 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br /> of declaring one D/G inoperable. The existing Action Statement "b" requires SR 4.8.1.1.2.a.5 to be performed within one hour anu at least once per 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br /> thereafter. A provision would be added to not require performance of SR 4.8.1.1.2.a.5 if the D/G has been rendered inoperable due to preplanned maint enance or surveillance testing. Also, guidance would be provided to enter the appropriate Action Statement "a" or "b" once either a D/G or offsite circuit has been restored to operable status.

The proposed Action Statement "d" would provide actions to be taken when two offsite power circuits are declared inoperable.

In the existing LCO 3.8.1.1 specification, this is Action Statement "c" with the following revisions. Surveillance requirement 1.8.1.1.2.a.5 will be performed nn both diesels within 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br /> of declaring both offsite circuits inoperable.

The existing Action Statement "c" requires SR 4.8.1.1.2.a.5 to be performed within one hour and at least once per 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br />

, A T T A Cl! M l!N T B , continued

Proposed Technical Specification Change Hos. 200 and 67 Page 2 thereafter. -The requirement to-b( in Hot Standby with the next 4 i hours would be changed to require the plant to be in llot Standby with the next 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br />. Also, guidance'would be provided to enter Action Statement "a" once a single offsite circuit has been restored to operable status.

The proposed Action Statement "e" would provide action to be taken when two diesel generators are declared inoperable. In the existing LCO 3.8.1.1 specification, this is Action Statement "d" with the addition of a statement which refers back to Action-Statement "b" once one D/G is restored to operable status.

A new footnote would be added which applies to testing of the diesel generators. The footnote would require starting of the remaining diesel generator regardless of when the inoperable diesel generator is restored to operable status. The existing footnotes would be designated by numbers inste,d of symbols to I ensure correct application. On DVPS-Unit No.-2 only, 'ho two footnotes contained on the present page 3/4 8-3 would be acleted

since -they no longer apply. These two footnotes were only applicable for the first and second fuel cycle. DVPS Unit 2'is currently on its fourth fuel cycle.

l

b. BACKGROUND Beaver Valley Power Station (BVPS) Unit th). 1 and 2 each have two emergency diesel generators. Two diesels are fully dedicated to each plant, with- one diesel assigned to each of the-redundant electrical pruar divisions of each plant. There is no sharing of diesel generators between units. Power from one diesel to one electrical division of each plant is sufficient to provide either for safe shutdown loads or for accident loads. The D/G's at BVPS~

Unit I are manufactured by General Motors Electro-Motive Division and BVPS Unit 2-D/G's are manufactured by Fairbanks Morse Engine Division of Colt Industr2es.

Our present technical specifications require starting the operable diesel _ w ithin 1_ hour and every_8 hours thereafter when specific conditions exist. Generic Letter (GL) f 84-15, " Proposed _

Staff- Actions to Improve and Maintain- Diesel Generator i Reliability," provides guidance for revising stare frequencies for diesel generators under _certain conditions to- improve reliability. This proposed change incorporates NRC guidance intended to improve diesel generator reliability,

i. _ __ _

l C. JUSTIFICATION The ' proposed revisions to LCO. 3.8.1.1 action statements are ,

consistent with-the action statements approved for Virginia, Power Company North _ Anna Unit 1 and 2 and similar to those appr,ved.for-Northea,t Utilities Mi'llstone Unit 2. The proposed revisions are l also_similar to those' contained in_ App 3ndix A of GL 84-15.

l I

l

, _ _ _ _ _ . . . . . _ . , _ . . . _ _ - _ . _ . _ _ _.a u_.

l

. ATTACliMENT B, continued I proposed Technical Specification Change Nos. 200 and 67 Page 3 The following is a discussion on the provision that would be added to not require performance of SR 4.8.1.1.2.a.5 if the D/G has been rendered inoperable due to proplanned maintenance or

, surveillance testing. This provisjon would be added to the proposed Action Statements "b" and "c". The current. wording requires that the alternate train testing be performed, i.e.,

statting of the opposite train D/G, to provide a positive demonstration that a loss of nafety function has not occurred.

There are situations where reduced operability testing on the l remaining diesel can exist when a diesel is made inoperable due i to preventative maintenance or testing. The purpose far testing the remaining dicsol is to assure a common mode failure does not i exist. Since the reason for D/G inoperability is known, i.e.,

preventative maintenance or testing, then a common modo failure on the remaining D/G does not exist. The NRC staff- has ,

recommended, por a memorandum dated February 11, 1991, (Entry -

Into A Technical Specification LCO During Performance of Surveillance Testing) ' that licensees- change their current technical specification wording to eliminate the need for such testing if a D/G is taken out of service for proplanned-preventative ma ntenance or testing. Therefore, the provision that would bot require that performance of SR 4.8.1.1.2.a.5, if the D/G has been rendered inoperable due to preplanned maintenance or surveillance testing, is proposed to be added to Action Statements "b" and "c".

The present Action Statement "a" would be divided into two separate action statements based on GL 84-15. The present requirement to start each D/G within one hour and every 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br /> thereafter, due to a loss of an offsite power source, we believe i is excessive and will lead to accelerated.D/G wear. This action is . intended to verify the availability of a backup power source.

The D/Gs are designed and are intended to be standby power sources. Under the present wording, in just one 72 hour8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> period'a total of nine D/G tests would be required por D/G. This repetitive type testing introduces accelerated D/G wear and

-provides little additional assurance of D/G availability than what was provided in the previous successful test. A test frequency of one' D/G test in the first 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> of one offsite source being inoperable, unless the D/G has been tested.in the e previous 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />, is proposed to minimize repetitive testing.

This test frequency will provide assurance of _ tarting. capability '

and also provide additional ~ time for inspaction and prolube and' other pre-start activities recommended by the manufacturca-to minimize- the- mechanical stress -and- wear on the D/Gs.

Furthermore,- 24 hours . permits sequential testing of the D/G5 rather than the simultaneous testing of both. Repetitive testing increases the likelihood of a D/G failure rather than providing continued assurance of starting capability especially since loss of an offsite _ power source does not directly imply a failure of the D/Gs.

The proposed Action Statement "b" provides the appropriate responses when declaring one D/G inoperable.- The present wording requires that the opposite train be tested within 1-hour and at *

. ATTACHMEllT B, continued proposed Technical Speci12 cation Change lion. 200 and 67 Page 4 least once per 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br /> thereafter. The reason to perform a diesel test following the loss of one diesel is to ensure that the remaining diesel will be operabic and capable of starting as designed. Specifically, an operability test of the remaining diocol provides assurance that the remaining operable diesel is not subject to the same failure (i.e., common mod 6 failure).

Testing within 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> provides timely assurance of diesel operability while providing the additional time for inspection prior to testing As stated in the discussion for the proposed Action Statement "a", repetitive testing every 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br /> following the initial confirmation of diesel operability is unnecessary.

This change to require D/G testing within 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> is consistent with GL 84-15. _

The proposed Action Statement "c" provides the appropriate response- to be taken upon declaring one offsite circuit and one diesel generator inoperable. Consistent with the proposed changes to Action Statements "a" and "b", the proposed changes to Action Statement "c" provide adequate assurance of diesel operability by one-time testing while eliminating repetitive testing. The performance of the D/G test within 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br /> provides adequate assurance of the availability of the remaining D/G while eliminating excessive starts and also providing added time for inspection prior to testing. Since the allowable outage period for .this action is 12 hours, follow-up D/G starts are not applicable.

  • 1he proposed Action Statement "d" provides the appropriate responses to be taken upon declaring two offsite power circuite inoperable. The proposed change is consistent with those made for Action Statements "a", "b", and "c". As noted in the discussion for Action Statement "a",_ loss of anLoffsite circuit does not suggest tl.at the diesels have become less reliable than demonstrated by previous surveillance tests. Given the significance of losinc both offsite circuits, one operability test per diesel within 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br /> provides adequate assurance of

-diesel reliability.

The proposed Action Statement- "e" provides the appropriate responses to be- taken upon-declaring both D/Gs inoperable.--The proposed change is the same as existing Action Statement "d".

The only difference in the proposed change is the use of distinct action statements based on the number of D/Gs inoperablo (either one or both).

The addition of the new footnote will ensure that the remaining.

operable. diesel generator -is started regardless of when the inoperable diesel generator'is restored to operable status.1 This action . will verify that a common mode failure does not exist on tne- remaining operable diesel. _ The change to the existing footnotes, by designating _them with_ numbers instead of symbols, along -with the deletion of two footnotes on Page 3/4 8-3 for BVPS Unit fio . 2, is administrative in nature and does not affect plant safety, y

1

.-- __-. __ -1

ATTACHMENT B, continued Proposed Technical Specification Change Nos. 200 and 67 Page 5  !

D. SAFETY ANALYSIS The A.C. electrical power sources are designed to provide sufficient capacity, capability, redundancy, and reliability to-ensure tla availability of necessary power to engineered safety features (ESP) systems so that the fuel, reactor coolant system, and containment design limits are not exceeded. The proposed changes to LCO 3.8.1.1 action statements will continue to ensure that the A.C. electrical power sources will perform au designed.

The capacity, capability, and reaundancy of the alectrical power sources is not affected by this proposed change. The specific number of offsite circuits and diesel generators that are required to be operable remains unchanged. The length of time  !

and number of components that can be inoperable for continued  !

plant operation remains unchanged. The specific parameters, contained in the surveillance requirements, that each component must meet to be determined operable, remains unchanged. The-proposed changes are intended to enhance diesel generator reliability by eliminating excessive testing which can lead to premature diesel failures. When n D/G is made inoperable.due to preplanned maintenance or surveillance tonting, there is not a concern that a common mode failure exists on the remaining D/G.

The reason for D/G inoperability is known. Therefore, requiring the starting of the remaining D/G within 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> and at least once ,

per 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br /> thereafter, provides no additional safety benefits and can lead to premature diesel failures. Also, the present requirement to perform nine D/G starts in a 72 hour8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> period does ,

not provide any additional safety benefits. This repetitive type testing introducer accelerated D/G wear and provides little additional assurance of D/G availability than what was provided in the previous successful test. A one time start of a D/G, l while~ in an action statement, is sufficient ~to ensure a loss of safety function has not occurred.

Therefore, this change is considered safe based on continued-ability of the A.C. electrical power sources to provide sufficient capacity, capability, redundancy, and reliability to ensure the availability of power to ESF cystems. The proposed changes are. InterAod to enhance D/G reliability by eliminating ,

excessive testing. The overall result of this change is to

  • enhance the ability of ...C, electrical power sources to perform as originally designed to ensure continued safe plant operation.

E. NO SIGNIFICANT HAZMDS EVALUATION The no significant_ hazard considerations involved with- the oroposed amm.ument have been evaluated, focusing on the three sJandard, set forth in 10 CFR 50.92(c)fas quoted below: )

The Commission. may make a final determination, pursuant to l the procedures-in paragraph 50.91, that a. proposed _ amendment to an operating license for a facility licensed under paragraph 50.21(b) or paragraph 50.22 or for a testing i facility involves no significant hazards' consideration, if

l

. ATTACHMENT B, continued .

Proposed Technical Specification Change Hos. 200 and 67 l Page 6 l i

operation of the facility in accordance with the proposed  !

amendment would nott (1) Involve a significant increast in the probability or consequences of an accident previously evaluated; or (2) Create the possibility of a new or different-kind of '

accident from any accident previously evaluated; or  :

(3) Involve a significant reduction in a margin of safety.

The following evaluation is provided for the no significant hazards consideration standards. .

1. Does the change involve a significant increase in the- '

probability or consequences of an accident previously evaluated?

The probability of occurrence of a previously evaluated accident is not increased because the allowable outage times for the offsite circuits and diesel generators remains unchanged. The consequences of an accident previously evaluated is not increased because reducing the diesel generator test frequency is intended to enhance diesel.

reliability. By eliminating excessive testing,.which can Icad to prenature diesel failures, the diesel generator reliability is increased. This . proposed change.does not affect the availability or reliability of the offsite circuits.

Therefort, this change will not increase the probability or ,

consequences of an accident previously evaluated due to the continued availability and reliability of the A.c.

electrical power-sources.

2. Does the change create the possibility of a new or different kind of accident from any accident previously evaluated?

The proposed changes do not alter the method af operating the plant. The changes do-not introduce any new failure-modes and are intended. to increase the diesel generator reliability. The revision to the various action statements provido assurance that the diesel generators will be able to power their respective safety . systems if required. The proposed changes do not impact the performance of any safety sv3Lem.

Therefore, this. proposed. change does- not create the possibility of a new or different kind of accident from any accident previously evaluated.

3. Does- the change involve a significant-reduction in a margin of safety?

The margin of safety is not reduced because the A.C.

electrical. power sources will continue to provide sufficient

, - , , , - . - - ,_.- - -. -- . - - - , - - , . = - . a-

A T T A tll M sti T B , continued Propond Technical Specification Change 11os. 200 and 67 page i capacity, capability, redundancy, and re13 ability to ensure availability of necousary power to ESP systems. The ESP systems will continue to function, as assumed in the safety analyses, to ensure that the fuel, reactor :oolant system.

and containment design limits are not exceeded. Tne ulimination of excessive testing on the diesel generators is intended to increase reliability by reducing. wear on the diesel. The increased reliability of the diescis adds.to the ability of A.C. electrical power source to provide power to ESF systems.

Therefore, this proposed change does not involve a significant reduction in a margin of safety.

F. 110 SIG!11 FICA 11T llAZARDS CONSIDERATIO!1 DETERMINATIO!1 Based on the considerations expressed above, it is concluded that the activities assocjated wi.th this license amendment request satisfies the no significant hazards consideration standards of 10 CFR 50.92(c) and, accordingly, a no significant hazards consideration finding is justified.

5 i

I-r l- t l

l l1

. - - - . . . - , . , . _,, . . . . , - ..,,..m. -

y,-s_v,.~.~...~,---,m...m,  : mm. , ..,mm...m._-~.,,y.--,,,..,-,

ATTACll!4EllT C-1 Beaver Valley Power "tation, Unit No. 1 Proposed Technical Specification Chango llo. 200

5 Typod Pages 3/4 8-1 3/4 8-2 3/4 0-3 1

3/4 8-4 3/4 8-4a k

e 1

i

, . - - + . . . . . . . - , . . - - - - . ..; ,- ,  :.- . -  :..... - . . - . - _ _ . . . . . - . . - . - , . . . - - - . _ - . - , . . . = - , - . , , . . . .

4 DPR-06 2&.li_ELECTAII' Alt _E93Ltit SY11HliS  ;

llA lt.1- 1LC1.229DECES ,

9PDen!M '

t LIMITING CONDITIO!1 FOR OPERATH N n n_.mw --

3.8.1.1 As a minimum, the following A.C. electrical power sources shall be OPERABLE:

a. Two physically independent circuits between the offsite ,

trannaission network and the onsite Class 1E distribution '

system, and

b. Two separate and independant diesel generators each with: p
1. Separate day and engine-mounted fuel tanks contt.ining a minimum of 900 gallons of fuol,
2. A separate fuel storage system-containing a minimum of 17,500 gallons of fuel, and  ;
3. A separate fuel transfer pump, lWEldCARUtITX: MDDES 1,2,3 and 4. ,

ILCIIQ11: i

a. With one offsite circuit of 3.8.1.1.a inoperabl.o, r demonstrate the OPERABILITY of the remaining A.C. sources by performing Surveillance Requirement 4.8.1.1.1.a within I hour and at least once per 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br /> thereafter. If either diesel generator has not boon successfully tested within the-past 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />, demonstrate its OPERABILITY by. performing Surveillance Requirement 4.8.1.1.2.a.5 separately for each such diesel generator within 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />. Restore the offsite circuit to OPERABLE status within 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> or be in at least ,

HOT STANDBY within the next 6' hours and COLD SHUTDOWN within the following 30 hours3.472222e-4 days <br />0.00833 hours <br />4.960317e-5 weeks <br />1.1415e-5 months <br />,

b. With one diesel Nnerator(1) of 3.8.1.1.b inoperable, demonstrate the OPERABILITY of the.A.C. offsite sources by performing Surveillance Requirement 4.8.1.1.1.a within 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> and ati least -once pe" 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br /> thereafter;.and if the diesel generator became inoperable due to any cauca other ,

than- -testing or- proplanned preventative maintenance, demonstrate the OPERABILITY of the remaining OPERABLE diesel generator by perf orminct Surveillance Requirement 4.8.1.1.2.a.5 within 24 hour2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />sI2); restore the diesel

' BEAVER VALLEY - UNIT 1 3/4 8-1 Amendment No.

(Proposed' Wording) ,

DPR-66 ELECTRICAL POWER FYSTEliS LIMITING CONDITIO!! FOR OPEIV. TION

__ n - _, -- _.

ACTIOtL_(22DLi11RCLR generator to OPERABLE str+un within 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> or be in at least HOT STANDBY within the next 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> and in COLD SHUTDOWN within the following 30 hours3.472222e-4 days <br />0.00833 hours <br />4.960317e-5 weeks <br />1.1415e-5 months <br />. >

c. With one offsite circuit and one diesel generator (1) ,

inoperable, demonstrate the OPERABILITY of the remaining e A.C. sources by performing Surveillance Requiremenc 4.8.1.1.1.a within one hour and at least once per 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br /> thereafter; and if the diesel generator became inoperable due to any cause other than testing and preplanned preventative maintenance, demonstrate the OPERABILITY of the remaining OPERABLE diesel generator by perforg Surveillance Requirement 4.8.1.1.2.a.5 within8hourstjpg i; restore one of the inoperable sources to OPERABLE status within 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> or be in at least HOT STANDBY within the next 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> and in COLD SHUTDOW!1 within the following 30 hours3.472222e-4 days <br />0.00833 hours <br />4.960317e-5 weeks <br />1.1415e-5 months <br />. Restore the other A.C. power source (offsite circuit or diesel generator) to OPERABLE status in accordance with the provisions of Section 3.8.1.1 Action Statement a or b, as appropriate with the time requirement of that Action Statement based on the time of initial loss of the remaining inoperable A.C. power source. A successful test of diesel OPERABILITY per _ Surveillance Requirement 4.8.1.1.2.a.5 performed under this Action Statement for an OPERABLE diesel or a restored to OPERABLE diesel satisfies the diesel generator test requirement of Action Scatement a or b.

a. With two of the required offsite A.C. circuits inoperable, demonstrate the OPERABILITY of two diesel generators by sequentially performing Surveillance Requirement 4.8.1.1.2.a.5 on both diesels within 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br />, unless the dicsel generators are already operating; restore one of the I

inoperable offsite sources to OPERABLE status within 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> or be in at least HOT STANDBY within the next 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br />, rollowing reJtoration of one offsite cource, follow Action Statement a Vith the time requj"ement of that Action Statement based on the time of 14.itial loss of the remaining inoperable offsite A.C. circuit. A successful test (s) of diesel OPEE?lILITY per Surveillance Requirement 4.8.1.1.2.c.5 performed under this Action Statement for the

! OPERABLE diesels satisfies the diesel ' generator test-l requirement of Action Statement a.

i BEAVER VALLEY - UNIT 1 3/4 8-2 Amendment No.

(Proposed Wording) )

)

I l

. _ . . _ _ _ _ _ , _ . , . _ . _ _ _ - __ , _ u_'

DPR-66 ELECIMCl&_f01RILHYETJ]iS LIMITING CONDITIOli FOR OPERATION

-- c .

IkC1LQll_LCSiltinVRdl

e. With two of the above required diesel generators (1) )

inoperabic, demonstrate the OPERABILIT/ of two offsite A.C.

circuits by performing Surveillance Requirement 4.8.1.1.1.a within one hour and at least once per 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br /> thereafter; restore one of the inoperable diesel generators to OPERABLE status within 2 hours2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br /> or be in at least HOT' STANDBY within ,

the next 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> and in COLD SHUTDOWN within the following  !

30 hours. Following restoration of one diesel generator l unit, follow Action Statement b with the time requirement  ;

of that Action Statement based on the time of initial loss 1 of the remaining inoperable diesel generator. A successful l test of diesel OPERABILITY per Surveillance Requirement 4.8.1.1.2.a.5 performed under this Action Statement for a restored to OPERABLE diesel catisfies the diesel generator test requirement of Action Statement b.

SURVEILLANCE REQUIREMENTS m=m=- ._= - -

4.8.1.1.1 Two physically independent circuits between the offsite transmission network and the onsite Class 1E distribution system shall be:

a. Determined OPERABLE at icast once per 7 days by verifying correct breaker alignments, indicated power availability, and
b. Demonstrated OPERABLE at least once per 18 months by-transfer ring (manually and automatically) unit power supply from the uni: circuit to the system circuit.

4.8.1.1.2 Et.ch diesel generator shall be demonstrated OPERABLE:

a. At least once per 31 days on a STAGGERED TEST BASIS by:-
1. Verifying the fuel level in the day and engine-mounted fuel tank,
2. Verifying the fuel level in the fuel storage tank,
3. (Deleted)

(1) Fuel oil contained in the storage tanks not meeting the l properties in accordance with 4.8.1.1.2.d.2 or 4.8.1.1.2.e shall be brought within the specified limits within 7 days.

(2) This test is required to be completed regard 1nss of when the inoperable diesel generator is restored to OPERABILITY, BEAVER VALLEY ~ UNIT i 3/4 8-3 Amendment No.

(Proposed Wording)

1 I

DPR-66 i

- ELECTRICAL POWEP SY.e.Ill.is SURVEILLANCE REQUIREMENTS (Continued)

4. ~ Verifying the fuel transfer pump can be started and transfers fuel from the storage system-to the day and engine-mounted tank, .

i

5. Verifying the diesel starts from ambient condition,
6. Verifying the generator is synchronized, loaded to_ i 21425 kw, and operates for 2 60 minutes, and
7. Verifying the diesel generator is aligned.to provide standby power to the associated emergency busses,
b. At least once per 18 months during shutdown by: ,
1. Subjecting the diesel to an inspection in accordance with procedures prepared in conjunction with its manufacturer's recommendations for this class of standby service, '
2. Verifying the generator capability to reject a' load of 2450 kw without tripping,
3. Simulating a loss of offsite power in conjunction with a safety injection signal, and: ,

a) Verifying de-energization of the emergency busses and load snedding from the emergency busses.

b) Verifyina the diesel starts _ frca ambient condition- on the auto-start signal,nenergizes the emergency busses with permanently connected loads, energizes the - auto-connected emergency.

loads through the load sequencer and operates for , .

2 5 minutes while its_ generator is loaded with the emergenef loads.

4. Verifying that- on a loss - of power to the emergency busses, all- diesel _ g?nerator _ trips , - except--engine L overspeed, generator differential and overcurrent,-are l

automatically disabled.

=t

5. Verifying -the -diesel -generator . operates for 2 60- ,

minutes while loaded to-2 2750 kw.

^

6. Verifying that the aato-connected loads to eachIdiesel

~

generator do not exceed the:2000 hour-rating of;2850; kw.

7. Verifying- that the automatic load sequence timer is
  • OPERABLE with each-load sequence time within 1 10%;of its required-value.

- BEAVER' VALLEY 1- UNIT 1 3/418 Amendment No.

_(Proposed Wording)_

ll l

P* ~ M r.

e- e'- - - - -

. . , . . _ - . - . - . _ . . ~ . - - ~ . - . - - - - -

,DpR-66

' ELECTRICAL PSHER SYSTEMS f SURVEILLANCE REQUIREMENTS (Cont!nued)

c. Check for and remove accumulated water: ,
1. From the day tank, at least onco per 32 days and after f each operation of the diesel where the period of i operation was greater than 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br />, and .

I

2. From the fuel oil storage tank, at least onco per 92 days,
d. By sampling .new fuel oil-in accordance with ASTM D4057-81 privr to addition to the storage tanks and:
1. By verifying in accordance with the tests speciflod in '

ASTM D975-81 prior to addition to the storage tanks that the samplo has: -

l

-a) An API Gravity of within 0.3_dogrees at 60*F or a specific gravity of within .0.0016 at 60/60'F, when compared to tho-supplier's cortificato or an absolute specific gravity at 60/60'F of_ greater-than or equal to 0.83 but less than or equal to 0.89 or an api gravity at 60'F of greater than or equal to 27 degrees'but less than or equal to 39 degrees, t b) A kinematic _ viscosity at 40*C of greater than'or equal to 1.9 contistokes, but= loss than'or equal to 4.1 contistokes, if gravity was not determined ~

by comparison with tho supplier's: certification,.

c) A flash point equal-~to or greater than 125'F,-and d) A cl ar and~ bright appearance with-proper color. '

when tested in accordance with-AbTM D4176--82.

-+

2 .- By verifying within 31 days of obtaining the. sample that the other proporties speciflod in Table 1 of-ASTM ~i D975-81 are mot- when tested in accordance with ASTM.

D975-81_ except -that_ the analysis ~for sulfur-may be performed ~in accordance with ASTM D1552-79 or ASTM ,

D2622-82.

e. At least once every 31-days by-obtaining a sample of fuel ,

oil from the storage tanks and day tanks in.accordance with ASTM- .D2276-78, and verifying that total particulate contamination-'is less than 10 mg/ liter when checked in_ t accordance with ASTM D2276-78, Method A.

BEAVER VALLEY - UNIT 1 3/4 8-4a Amendment No.

(proposed Wording)

^

_. .. _ _ _ _ _ _ . _ _ _ . _ . a a. - _. _ , _ . _ , . . __

.7.-_.------..-----.-..-.....---....

ATTACllMEllT C-2 Belsvor Valley Power Station, Unit 110. 2 Proposed Techni.:al Specification Change llo. 67 i

. 1 l

Typed Pages: 3/4 8-1 ,

3/4 , 8-2 i 3/4 0-3 l

3/4 8-4 3/4 8-4a  !

3/4 d-4b i

~i,

[

b l

.?

I l

l i.

1

-i l +

,..>,--w.- - . . , . - -- = , ~ ~ , - - ,m ,----y,w-.. - e,- ,.,,-.4 e , ., w , ,.e--- .e ,r .=-,.-,-+-w- -=oi-s- , - - 4 ., y -- ,

NPP-73 1/.idL fLECTRLCAL_l>QWER SYS.Tilm 3/4.8.1 A.C. SOURCfJ DERAT.UiG LIMITING CONDITIO!1 FOR OPERATION

n. ,-

--,u,-.= ----w:.

3.8.1.1 As a minimum, the folloaing A.C. electrical power sources chall be OPERABLE:

a. Two physically independent circuits between the offaite i transmission network and the onsite Class 1E distribution i system, and
b. Two coparate and independent diesel generators each with-i
1. Separate day tank containing a minim.m of 350 gallons of fuel, ,

l

2. A separate fuel storage system containing a minimum of l 53,225 galloris of fuel,
3. A separate fuel transfer pump, l
4. Lubricating oil storage containing a minimum total volume of 504 gallons of lubricating oil, and
5. Capability to transfer lubricating oil from storage to the diesel generator u11t.

lilTLIRAILR13"(: MODES 1,2,3 and 4.

hCJ101{:

a. With one offsite circuit cf 3.8.1.1.a inoperable, demonstrate the OPERABILITY of the remaining A.C. sources by performing Surveillance Requiremcnt 4.8.1.1.1.a w3 thin 1 hour and at least once per 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br /> thereafter. If either diesel generator has not - been successfully tested within the past 24 hours, demonstrate its OPERABILITY by-

. performing Surveillance -

Requirement 4.8.1.1.2.a.5 separately- for each such diesel generator within 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />.

Restore the offsite circuit to OPERABLE status within 72-hours or be in at'least HOT STANDBY within the next 6 hour6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br />s-and COLD SHUTDOWN within the following 30 hours3.472222e-4 days <br />0.00833 hours <br />4.960317e-5 weeks <br />1.1415e-5 months <br />, b.- With 'ono diesel- gener6 tor (1) of 3.8.1.1.b inoperable, demonstrate the- OPERABILITY of the A.C. offsite sources by-performing Surveillance Requirement 4.8.1.1.1.a within 1-hour and at laast once por 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br /> thereafter; and if the diesel generator became inope;3ble due to any cause other DEAVER VALLEY - UNIT 2 3/4 S-1 Amendment-No.

(Proposed Wording)

, - ~ _ , -_ - _ _ . - _ - _. _ _ _ _ - . . . - _ . - _ _

~ - - . _ . . _ . -. - ~ _ - - . -

l HPF-73 f1ECTRIChldRDLSYSTE!LS LIMITING-CONDITION FOR OPERATION i

ACTION (Continued)  ;

i than testing or preplanned preventative maintenance, demonstrate the OPcRABILITY of the remaining OPERABLE diesel generator by performJng (Y"prveillance Requirement 4.8.1.1.2.a.5 vithin 24 h aro i; rectore the diesel generator to OFLRABLE status within 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> or be in at least ilOT STANDBY within the next 6' hours and in COLD SHUTDOWN within the following 30 nouls.

l

c. With one offsite circuit and one diesel generator (1) inoperabic, demonatrate the OPERAHILITY of the remaining A.C. sources by perf ornd ng Surveillanco Requirement 4.8.1.1.1.a within one hour and at leaat once per 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br /> thereafter; and if the diosol generator became inoperable due to any cause other than testing or preplanned -

preventative maintenance, demonstrate the OPERABILITY of the remaining OPERABLE diesel generator by perforgjn Surveillance Requirement 4.8.1.1.2.a.5 within 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br /> P)g; restore one of the incperable sourcos to OPERABLE status within 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> or be in at least HOT STANDBY within the next G hours and in COLD SHUTDOWN within the following 30  !

hours. Restore the other A.C. power source (offsite circuit or diesel generator) to OPERABLE status in-accordance with the provisions of Section 3.8.1.1 Action Statement a or b,.as appropriate with the time requirement of that Action Statement based on the time of initial loss of the remaining inoperable A.C. power source. A successful test of diesel OPERABILITY per Surveillance Requirement 4.8.1.1.2.a.b performed _ under this Action Statement for an OPERABLE diesel .cn a re8N red to-OPERABLE diesel satisfies the diesel generator teot requirement of Action Statement a or b.

d. With two of the required offolte A.C. circuits inoperable,.

demonstrate the OPERABILITY of two diesel generators by sequentially performing Surveillance Requirement 4.8.1.1.2.a.5 on both diesels within 8 houre, unless the diesel generators are already operating; restore one of.tbc inoperable offsite sources to OPERABLE status within 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> or be in at leas *- HOT ' STANDBY within the next 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br />. following restoration of one offsite ocurce,-follow Action Statement a with the time requirement of that Action-Statement based on the time of initial loss of the remaining inoperablo offsite A.C. circuit. A successful test (s) of diesel OPERABILITY per Surveillanc0 Requirement 4.8.1.1.2.a 5 parformed under this Action State %ent for the OPERABLE diesels satisfies the diesel generator test requirement of Action Statement a. ,

BEAVER VALLEY - UNIT 2 3/4 8-2 Amendment No.

(Proposed Wording) s)

, . _ _n.

llPF-73 ELECTRhihALTWER SYSTr!45 LI!11 tit 1G CO!!DITIO!J FOR OPERATIO11

. ._-. w, , _.

ARTIOli -(ColitinMill.

c. With two of the above required diesel generators (1) inoperable, demonstrate the OPERABILITY of two offsite A.C.

circuits by performing Surveillance Requirement 4.8.1.1.1.a within one hour and at least once per C hours thereafter; restore one of the inoperable diesel generators to OPERABLE status within 2 hours2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br /> or be in at leact !!OT STA11DBY within the next G hours and in COLD Silb7 DOC 1 withf n the following 30 hours3.472222e-4 days <br />0.00833 hours <br />4.960317e-5 weeks <br />1.1415e-5 months <br />, rollowing restoration of one diesel generator 1 unit, follow Action Statement b with the time requirement  !

of that Action Statement based on the time of initial loss of the remaining inoperable diesel generator. -A successful t e.st of diesel OPERABILITY por Surveillance Requirement 4.8.1.1.2.a.5 performed under this-Action Statement for a restored to OPERABLE diesel batisfles the diesel generator test requirement of Action Statement b.

, SURVEILLAllCE REQUIRE!4EllTS m..__,

-....__m_.._-- , . , .

4.8.1.1.1 Two physically independaat circuits between the offaite transmission network and the onsite Class 1E distribution nyctem shall be:

a. Determined OPERABLE at least once por 7 days by verifying correct breaker alignments, indicated power availability,. ,

and

b. Demonstrated OPERABLE at least once per 18 nonths by transferring (manually and automatically) unit power supply from the unit circuit to the system circuit.

4.8.1.1.2 Each diesel generator shall bo Jomonst;ated OPERABLE:

a. At least once per 31 days on a STAGGERED TEST BASIS by:
1. Verifying the fuel Icvel-in the day tank,-
2. Verifying the fuel level in the fuel storage tank,
3. (Deleted)

(1) I l

Fuel-_ oil contained in the storage tanks _not meeting the l properties in accordance with 4.8.1.1.2.d.2 or 4.8.1.1.2.e

! shall be brought within the specified limits within 7 days.

l (2) This test is required to be completed-regardless of when the, inoperable diesel generator is restored to OPERABILITY. ,

BEAVER VALLEY - Ut1IT 2 3/48-3 Amendment No.-

(Proposed Wording)

NPF-73

  • ELIXTRLCAL POWER SYSIEliS SURVEILLANCE REQUIREMENTS (Continued) _

l

4. Verifying the fuel transfer pump can be started and j transfers fuel from the storage system to the day tank,
5. Verifying the diesel starts from ambient condition,
6. Verifying the generator is synchronized, loaded to 24,238 kw, and operates for at least 60 minutes,
7. Verifying the diesel generator is aligned to provide standby power to the associated emergency busses, and
8. Verifying the lubricating oil inventory in storage.  !
b. At least once per 18 months during shutdown by:
1. Subjecting the diesel to an inspection in accordance with procedures prepared in conjunction with its '

manufacturer's recommendations for this class of standby service, 1

2. Verifying the generator capability to reject a load of 2825 kw without tripping,
3. Simulating a loss of offaite power in conjunction with a safety injection signal, and:

a) Verifying de-energization of the emergency busses and load shedding from the emergency busses.

b) Verifying _ the diesel starts from ambient condition on the auto-start signal, energizes.the emergency busses with permanently connected loads, energizes the auto-connected emergency loads through the load sequencer and operates for 2 S minutes while its generator is loaded with ,

the emergency _ loads.

4. Verifying that on a loss of powta to the emergency busses, all diesel generator trips, except engine overspeed, backup phase fault detection, . generator l differential current, and generator overexcitation are-automatically disabled.

. BEAVER VALLEY - UNIT 2 3/4 8-4 Amendment No.

(Proposed Wording) s

- . ~ ~ ~ .--- - - . - .- -. - .__ _ - .-. - . ~ . - . . - - - . - . . - . .

I 4

,11PF 77

  • JU&CliqqAL POWER SYSTEMS SURVEILLANCE REQUIREME!4TS (Continued)
5. Verifying the diesel generator operates for at lecst--

, 60 minutes while loaded to 2 4,238 kW.

I

6. Verifying that the auto-connected loads ',o each diesel J generator do not exceed the 2000 hour0.0231 days <br />0.556 hours <br />0.00331 weeks <br />7.61e-4 months <br /> rating of 4,S35 kW.  ;
7. Verifying that the autome&ic load sequence timer .is OPERABLE with each load seqacnce time within i 10% of -

its required value,

c. Check for and remove accumulated water:
1. From the day tank, at least once per 31 days and after each operation of *he diesel where the period of .

operation was greater than 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br />, and

2. From the fuel oil storage tank, at least once per 92 days,
d. By sampling new fuel oil in accordance with ASTM D4057-81 prior to-addition to the storage tanks and:
1. By verifying in accordance with the tests specified in ASTM D975-81 prior to addition to the storage tanks that the sample has:

a) An API Gravity of within 0.3 degrees at 60'F or a specific gravity of within 0.0016- at 60/60*F, when compared to the supplier's certificate or an absolute specific gravity at 60/60'F of greater than or equal to 0.83 but.less than or equal to  !

0.89 or an API-gravity at 60'F of greater than-or equal to 27 degrees but less than or equal to 39 degrees, b) A klaematic viscosity at 40'C'of_ greater than or equal to 1.9 concistokes, but less than or equal to 4.1 contistokes, if_ gravity was notldctermined by comp 1r.ison with'the supplicr's certification, c) A flash point equal'to or greater than 125'F, and d) A clear and bright appearance with proper color when tested in accordance with ASTM D4176-82.

L BEAVER VALLEY ' UNIT 2 3/4 8-4a Amendment No.

(Proposed Wording)

)

_ _ _ _ _.-.a,.._-_-.u. . - . - - . . , - _ . .- _ _ ._. _ . ,,

NPP*73

'SJJEIRifAL POWER SYSTEMS SURVEILLANCE REQUIREMENTS (Continued) rm- -

2. Dy verifying within 31 days of obtaining the sample that the other proporties specified in Table 1 of ASTM D975-81 are met when tested in accordance with ASTM D975-01 except that the analysis for sulfur may be performed in accordance with ASTM D1552-79 or ASTM '

D2622-82.

e. At least once every 31 days by obtaining a sample of fuel oil from the storage tanks and day tanks in accordance with ASTM D2276-78, and verifying that total particulate contamination is lens than 10 mg/ liter when checked in accordance with ASTM D2276-78, Method A.
f. At least once per 10 years or after any modifications which could diesel generator inter 3ependence by starting (g{fect -

both diesel generators simultaneously, during shutdown, and verifying that both diosol generators accelerate to at least 514 rpm in less than or equal to 10 seconds.

g. At least once per 10 years by:
1. Draining each main fuel oil storage tank, removing-the accumulated sedir.ent, and cleaning the tank.using a sodium hypochlorite colution or .other appropriate cleaning solution, and
2. Performing a pressure test, of those portions of the diesel fuel oil system designed to Section III, subsection ND of the ASME Code, at a test pressure equal to 110% of the systen design pressure.

i3) This test chall be conducted in accordance with the  !

manufacturer's reconimondations regarding- engine prelube and warmup procedures, and as applicable regarding- loading recommendations.

BEAVER VALLEY - tNIT 2 3/4 D-4b Amendment No.

(Proposed Wording) ,

, , - . m . . s _. _ .. _ _ _ . - . .. _._. . . ._ _. - . _ . . _ _ . _ _ , _ . . .