Amend 162 to License DPR-65,incorporating Addl Fire Dectection & Suppression Sys to TS Resulting from 10CFR50, App R,Design Changes & Mods & Providing Consistency W/Gl 87-09
ML20114C017
Person / Time
Site: Millstone 
Issue date: 08/26/1992
From: Stolz J
Office of Nuclear Reactor Regulation
To:
Northeast Nuclear Energy Co (NNECO), Connecticut Light & Power Co, Western Massachusetts Electric Co
Shared Package
ML20114C018 List:
References
DPR-65-A-162, GL-87-009 NUDOCS 9209010101
Download: ML20114C017 (14)


Text

- - - _ _...

p* ** 00

?

UNITED STATES t

n 5

.I NUCLEAR REGULATORY COMMISSION

[

W ASHINGTON. D.C. 20E66

'4 f

4 e. **

h(LRIllEAST NUCLEAR ENERGY COMPANY JBE CONNECTICVT LIGHT AND POWER COMPANY THE WESTERN MASSACHUSETTS ELECTRIC COMPANY DOCKET NO. 50-336 MILLSTONE NUCLEAR POWER STATION. UNIT NO. 2 AMENUMENT TO FACILITY OPERATING LICENSE Amendment No.

162 License No. DPR-65 1.

The Nuclear Regulatory Comission (the Comission) has found that:

A.

The application for amendment by Northeast Nuclear Eneigy Comaatiy, et al. (the licensee), dated March 18, 1991, as supplemented

)y letter dated December 23, 1991, complies with the standards u.d requirements of the Atomic Energy Act of 1954, as amended (the Act),

and the Comission's rules and regulations set forth in 10 CFR Chapter I; B.

The facility wis. vpeine in conformity with the application, the provisions of the Act, and the rules and regulations of the Comission; C.

There is reasonable assurance (i) that the activities authorized by this amendment can be conducted without endangering the health and safety of the public, and (ii) that such activities will be conducted in compliance with the Comission's regulations; D.

The issuance of this amendment will not be inimical to the comon defense and security or to the health and safety of the public; and E.

The issuance of this amendment is in accordance with 10 CFR Part 51 of the Comission's regulations and all applicable requirements have been satisfied.

I 92o9010101 920826 PDR ADOCK 05000336 P

PDR

l 2.

Accordingly, the license is amended by changes to the Technical Specifications as indicated in the attachment to this license amendment, and paragraph 2.C.(2) of facility Operating License No. DPR-65 is hereby amended to read as follows:

(2) Inchnical Specifications The Technical Specifications contained in Appendix A, as revised through Amendment No.162, are hereby incorporated in the license.

The licensee shall operate the facility in accordance with the Technical Specifications.

3.

This license amendment is effective as of the date of issuance, to be implemented within 30 days of issuance, rvK THE NUCLEAR REGULATORY COMMISSION J n

. Stolz, Director ro ct Directorate I-4 sion of Reactor Projects - f/II Office af Nuclear Reactor Regulation Attachmit:

Changes to the Technical Specifications Date of Is;-uuice:

August 26, 1992 e

7

]

ATTACHMENT TO LICENSE AMENDMENT NO. 162 FACILITY OPERATING LICENSE NO. OPR-65

)

DOCKET NO. 50-336 Replace the following pages of the Appendix A Technical Specifications with the enclosed pages. The revised pages are identified by amendment number and contain vertical lines indicating the areas of change.

Remove Insert VIII Vill i

3/4 3-44 3/4 3-44 3/4 3-45 3/4 3-45 3/4 3-45a 3/4 7-37 3/4 7-37 3/4 7-40 3/4 7-40 3/4 7-41 3/4 7-41 3/4 7-42 3/4 7-42 3/4 7-43 3/4 7-44 6-19(b) 6-19(b) i l

1

lI

.lf@El j

LIMITING CONDITIONS FOR OPERATION AND SURVEILLANCE RE0VIREMENTS SECTION

fMf, 1

3/4.7 PLANT SYSTEMS i

3/4.7.1 TURBINE CYCLE..........................................

3/4 7-1

)

Iafety Valves..........................................

3/4 7-1 Auxiliary feedwater Pumps..............................

3/4 7-4 l

Condensate Storage Tank................................

3/4 7-6 Activity...............................................

3/4 7-7 j

1 Main Steam Line Isolation Valves.......................

3/4 7-9 j

3/4 7.2 iTEAM GfNERATOR PRESSURE / TEMPERATURE LIMITATION........

3/4 7-10 1

3/4.7.3 fliACTOR BUILDING CLOSED COOLING WATER SYSTEM...........

3/4 7-11 j

3/4.7.4 SERVICE WATER SYSTEM...................................

3/4 7-12 i

3/4.7.5 FLOOD LEVEL............................................

3/4 7-13 l

3/4.7.6 CON 1ROL ROOM EMERGENCY VENTILATION SYSTEM..............

3/4 7-16 3/4.7.7 SEALED SOURCE CORTAMINATION............................

3/4 7-19 3/4.7.8 SNUBBERS...............................................

3/4 7-21 3/4.7.9 FIRE SUPPRESSION SYSTEMS...............................

3/4 7-33 Fire Suppression Water System..........................

3/4 7-33 i

Spray and/or Sprinkler Systems.........................

3/4 7-37 j

F i re Ho s e St at i o n s.....................................

3/4 7-39 Halon fire Suporession Systems.........................

3/4 7 41 3/4.7.10 PENETRATION FIRE BARRIERS..............................

3/4 7 42 3/4.7.11 ULTIMATE HEAT SINK.....................................

3/4 7-44 l

3/4.8 ELECTRICAL POWER SYSTEMS 3/4.8.1 A.C. SOURCES...........................................

3/4 8 1 l

Operating..............................................

3/4 8 1 Shutdown...............................................

3/4 8-5 1/4.8.2 ONSITE POWER DISTRIBUTION SYSTEMS......................

3/4 8-6 A.C. Distribution - Operating..........................

3/4 8-6 A.C. Distribution - Shutdown...........................

3/4 8-7 D.C. Distribution - Operating..........................

3/4 8 8 D.C. Distribution - Shutdown...........................

3/4 8-10 MILLSTONE - UNIT 2 VIII Amendment No. //, ;IE, SE, Jpf, oco JfE 162'

. = _.. -

~

TABLE 3.3-10 i

i FIRE DETECTION INSTRUMENTS ex 3;

11 eat Smoke i

~g d

Minimum Minimum i5; Total No.

Channels Total No.

Channels 7

Instrument location (lone) of Channels Operable of Channels Operable l

1 c-5 1.

Containment East Penetration (37)--FLP 3-3 7

5 i

l West Penetration (31)--FLP 3-7 7

5 i

2.

Control Room Vent Duct (42) Z-2 1

1 Control Room Vent Duct (2) Z-1 1

1 6

3.

Cable Vaults & Areas t

Aux. Bldg Cable Vault (25') (10) 5 4

16 12 t

Turbine Bldg. Cable Vault (25') (22) 34 34 l

Turbine Bldg Cable Vault Area (45') (21) 8 6

1 Y

lunch Room Cable Chase Area (36'6") (24) 4 3

l 2

l 4.

4.16 & 6.9 kV Switchgear Room (54'6") (40) 4 3

4.16 kV Switchgear Room (31'6") (18) 4 3

2 I

480 V West Switchgear Room (36'6") (18) 480 V East Switchgear Room (36'6") (28) 2 1

k East DC, Equipment Room (43 Alarm) (FLP-5) 6 6

West DC Equipment Room (45 Alarm) (FLP-6) 6 6

2 East Cable Vault Ventilation Opening 1

1 E

(44) (FLP 7)

West Cable Vault Ventilation Opening 1

1

[

2 (44) (FLP 7) y l

3" 5.

Battery Rooms u?

West Battery Room (14'6") (39) 1 I

East Battery Room (14'6") (39) 2 1

w r

g 6.

Electrical Penetration Rooms 5

East (14'6") (20) 3 2

West (14'6") (17) 2 r

l

s TflBLE 3.3-10 (Continued)

~

FIRE DETECTION INSTRUMENTS exy Heat Smoke Minimum Minimum e'

Total No.

Channels Total No.

Channels Instrument location (Zone) of Channels Operable of Channels Operable E

Z 7.

Diesel Generators m

Diesel 1221 (12) 8 8

Diesel 1321 (13) 8 8

8.

Main Exhaust Equipment Room and B52 Enclosure 3

3 Room (El 33'6") (5) 9.

Auxiliary Building - 45 (FLP-1) w 3

2 1

Gveral Area (48) 2 1

5 A.

Safe Guards Room (48) 2 1

I.

8.

Safe Guards Room (48)

I I

l C.

Safe Guards Room (48) s

10. Auxiliary Building - 25 (FLP-?)

E 9

7 g

Ceneral Area - 25 (52) 5 3

Charging Pump Rooms - 25 (52) 8

11. Containment Building FLP-3 (37) 5 RCP "A" - (FLP 3-1) 5 3

g RCP "B" - (FLP 3-2) 5 3

RCP "C" - (FLP 3-5) 5 3

't_

RCP "D*'- (FLP 3-6) 5 3

t

12. Auxiliary Building (-5'/14'6") (FLP-4) 9 7

?

Auxiliary Building General Area 14'6" (41) g Auxiliary Building West Piping Penetration (41) 2 I

N Room -5' Auxiliary Building

-5' (41) 13 10 l

i

TABLE 3.3-10 (Continued)

FIRE DETECTION INSTRUMENTS

.j%

Heat Smoke

- r-O l'inimum Minimum E

Tntal No.

Channels Total No.

Channels 7

Instrument location (Zone) of Channels Operable of Channels Operable E

Z

13. Hydrogen Seal Oil (31) 6 6

j n

14.

Intake Structure (6) 10 10

15. Motor Driven Aux. Feed Pump Rm (22) 2 2

w Y

O.

it a

.\\

n E

~

PLANT SYSTEMS SPRAY AND/OR SPRINKLER SYSTEMS LIMITING CONDITION FOR OPERATION i

3.7.9.2 The following spray and/or sprinkler systems shall be OPERABLE:

i a.

Diesel Generator Rooms j

b.

Diesel Generator Day Tank Rooms c.

Cable Vault (Aux. Building)

Sprinkler (in tray) level) 1.

Sprinkler (ceiling 2.

d.

Cable Vault (Turbine Building) 1.

Automatic Wet Pipe Sprinkler System (45'0')

2.

Automatic Deluge System (vertical cable shaft and elevation 25'0' cable vault) e.

Hydrogen Seal Oil Unit f.

Turbine Building Northeast Corner g.

Turbine Building 31'6*/14'6" - North h.

Turbine Building 31'6'/14'6' - South i.

Lube Oil Room j.

Aux. Building (-45'6") General Area k.

Aux. Building (14'6') Truck Access 1.

Turbine Bearing m.

Steam Generator feed Pumps n.

Aux. Bldg. (14'6*) at MCC R G1 o.

Aux. Bldg. (-25'6') at Charging Pump Cubicle p.

Aux Bldg. (14'6') General Area APPLICABILITY: Whenever equipment in the spray / sprinkler protected areas is required to be OPERABLE.

ACTION:

a.

With one or more of the above required spray and/or sprinkler systems inoperable, establish a continuous fire watch with backup fire suppression equipment for the unprotected area (s) within 1 i

hour; restore the system to OPERABLE status within 14 days or, in lieu of any other report required by Specification 6.6.1, prepare and submit a Special Re> ort to the Commission pursuant to Specification 6.9.2 wit 11n the next 30 days outlining the action taken, the cause of the inoperability and the plans and schedule for restoring the system to OPERABLE status.

b.

The provisioi.s of Specification 3.0.3 are not applicabic.

SURVE1LLANCE REOUIREMENT 4.7.9.2 Each of the above required spray and/or sprinkler systems shall be demonstrated OPERABLE:

MILLSTONE - UNIT 2 3/4 7-37 Amendment No. #, M, # g fff, 151, ones 162

TABLE 3.7-2 FIRE HOSE STAllDES Hose Station Number Blda/ Elevation arga 201 207 Turbine /14'6" Turbine Building 208-214 (urbine/31'6" Turbine Building 215-221 surbine/54'6" Turbine Building 222 Auxiliary /-45'6" Center of Open Area 223 Auxiliary /-25'6" Near Elevator 224 Auxiliary /-5'0" Near Elevator 225 Auxiliary /14'6" Near Elevator 226 Auxiliary /38'6" Spent Fuel Pool - Northwest corner 227 Auxiliary /14'6" Boric Acid Batch Tank area 228 Auxiliary /14'6" Near MCC 22-lE (B51) 229 Auxiliary /!4'6" Railway access 230 Auxiliary /38'6" Spent Fuel Pool - South Wall 231 Auxiliary /14'6" Outside Diesel Room 234 Auxili:ry/38'6" Southeast corner stairway

'M u Auxiliary /5'0" Southeast corner stairway 241 Auxiliary /25'6" Cable Vault Southeast Entrance 242 Auxiliary /36'6" Control Room Ventilation Area 243 Turbine /45'0" North Entrance of Turbine Bldg. Cable Vaults 250-251 Containment /38'6" East & West Stairwells 248-249 Containment /14'6" East & West Stairwells 244-245 Containment /-22'0" East & West Stairwells MILLSTONE - UNTI 2 3/4 7-40 Arendment No. JE, fd, JJp,162 000?

~

PLANT SYSTEMS HALON FIRE SUPPRESSION SYSTEM LIMITING CONDITION FOR OPERATION 3.7.9.4 The following halon D01 fire suppression systems shall be OPERABLE with:

an intact gas boundary, an operable activation system, and i

a container having a net weight of not less than 95% of full charge weight at 325 psig minimum (corrected to 70*F).

a)

West D.C. Switchgear Room b)

East D.C. Switchgear Room 8PPLICABILITY: At all times.

ACTION:

a.

With one or more of the above systems inoperable, establish a continuous fire watch with backup fire suppression equipment for the unprotected area (s) within I hour; restore the system to OPERABl'.

status within 14 days or, in lieu of any other report required ay Specification 6.6.1, prepare and submit a Special Report to the Commission, pursuant to Specification 6.9.2, within the next 30 days outlining the action taken, the cause of the inoperability and the plans and schedule for restoring the system to OPERABLE statm.

b.

The provisions of Specification 3.0.3 are not applicable.

SURVEILLANCE REQVIREMENTS 4.7.9.4 Each of the above halon fire suppression systems shall be demonstrated OPERABLE:

a.

At least once per 6 months:

1.

By performing a system functional test which includes simulated automatic operation of the system; and:

a.

simulated manual actuation of the system.

b.

verifying that the storage containers have a net weight of not less than 95% of full charge weight at 325 psig (corrected to 70*f).

c.

verifying the associated room dampers close.

b.

At least once per 18 months:

t 1.

By performing a visual inspection of the discharge nozzles to l

assure no blockage.

i 2.

By performing a visual inspection to assure the gas boundary is intact.

MILLSTONE - UNIT 2 3/4 7-41 Amendment No.162 0008 l

i i

PLANT SYSTEMS 3/4.7.10 PENETRATION FIRE BARRIERS LIMITING CONDITIONS FOR OPERATION _,_

3.7.10 All fire rated assemblies (walls, floor / ceilings, cable tray i

enclosures, and other fire barriers) separating safety-related fire areas or j

separating portions of redundant systems important to safe shutdown within a fire area and all sealing devices in fire rated assembly penetrations (fire a

doors, fire windows, fire dampers, cable, piping, and ventilation duct l

penetration seals) shall be OPERABLE.

j APPLICABILITY: At all times unless otherwise determined that the separation l

of safety-related fire areas or separating portions of redundant systems important to safe shutdown within a fire area is not required based on the MODE of operation.

ACTION:

a.

With one or more of the above required fire rated asremblies and/or penetration sealing devices inoperable, within I hour:

1.

Determine that the fire areas / zones on both sides of the affected fire rated assembly and/or penetration sealing device are monitored by either an OPERABLE fire detection or automatic suppression system at the fire barrier and establish a fire I

watch patrol that inspects both areas at least oace per hour, E

2.

Establish a continuous fire watch on at least one side of the t

affected fire rated assembly and/cr penetration seal, E 3.

Temporarily repair the inoperable fire rated assembly and/or sealing device and classify it as temporary.

All temporary or inoperable fire rated assemblies and/or sealing devices shall be permanently repaired within 30 days, or implement ACTION 1 or 2 above.

b.

The provisions of Specification 3.0.3 are not applicable.

SURVEILLANCE RE0VIREMENTS 4.7.10 The above required fire rated assemblies and penetration sealing devices shall be verified to be OPERABLE by a visual insnection:

a.

At least once per 18 months for fire doors and fire dampers.

l MILLSTONE - UNIT 2 3/4 7-42 Anendment No. #, JJp. 15f, noto 162

. =. -

SURVEILLANCE RE0VIREMENTS fContinued) b.

At least once per 18 months for fire barrier pent. ration seals, on at 19ast 10% of the total number of penetratica seals.

If any of the penetration seals in the inspection sample are found to be inoperable, then an additional 10% sample of the total number of penetration seals shall be visually inspected.

Sampling and inspection shall continue until all of the seals in a sample are found OPERABLE or 100% of the seals are inspected.

c.

Prior to returning a fire rated assembly and/or penetration sealing device to OPERABLE status following repairs or maintenance.

)

P gSTONE-UNIT 2 3/4 7-43 Amendment No. #, Up,162

ElANT SYSIEMS 3/4.7-11 ULTIMATE HEAT SINK LiliLTING CONDITION FOR OPERATION 3.7.11 The ultimate heat sink shall be OPERABLE with an average veter temperature of less than or equal to 75'F at the Unit 2 intake structure.

PDfLif. ABILITY: H0 DES 1, 2, 3 AND 4 ACTION:

With the requirements of the above specification not satisfied, be in at least HOT STANDBY within 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> and in COLD SHUTDOWN within the following 30 hours3.472222e-4 days <br />0.00833 hours <br />4.960317e-5 weeks <br />1.1415e-5 months <br />.

SURVEILLANCE RE0VIREMENTS 4.7.11 The ultimate heat sink shall be determined OPERABLt.:

a.

At least ence per 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> by verifying the average water temperature at the Unit 2 intake structure to be within limits.

b.

At least once per 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> by verifying the average water temperature at the Unit 2 intake structure to be within limits when the average water temperature exceeds 70*F.

gSTONE-UNIT 2 3/4 7-44 Amendment No. Jg 162

~.......

I' l

ADMINISTRATIVE CONTROLS c.

Safety Class 1 Inservice Insptttion Program Review, Specification i

l 4.4.10.1.

d.

ECCS Actuation, Specifications 3.5.2 and 3.5.3.

l e.

Fire Detection Instrumentation, Specification 3.3.3.7.

l f.

Fire Suppression Systems, Specifications 3.7.9.1, 3.7.9.2 and 3.7.9.4.

g.

RCS Overpressure Mitilation, Specification 3.4.9.3.

h.

Radiological Effluent Reports required by Specifications j

3.11.1.2, 3.11.2.2, 3.11.2.3 and 3.11.4.

i.

Degradation of containment structure, Specification 4.6.1.6.4.

j j.

Steam Generator Tube Inspection, Specification 4.4.5.1.5.

k.

Accident Monitoring Instrumentation, Specification 3.3.3.8.

i 1.

Radiation Monitoring Instrumentation, Specification 3.3.3.1.

j i

m.

Reactor Coolant System Vents, Specification 3.4.11.

t MILLSTONE - UNIT 2 6-19(b)

Amendment No. JfA 162 0014