GPU Nuclear Corporation Nuclear

=== 388 Forked River, New Jersey 08731-0388 609 971-4000 Writer's Direct Dial Number:

March 15, 1985 Mr. John A. Zwolinski, Chief Operating Reactors Branch No. 5 Division of Licensing U.S. Nuclear Regulatory Commission Washington, DC 20555

Dear Mr. Zwolinski:

Subject:

Oyster Creek Nuclear Generating Station Docket No. 50-219 Environmental Qualification of Certain Electrical Components Important to Safety l

This letter documents our March 8,1985 telephone conversation with Mr. J. Donohew, NRC Project Manager for Oyster Creek, concerning the staff's questions raised during our recent discussion (February 28, 1985) on certain Justifications for Continued Operation (JC0-0C-85-2, 4, 24 and 43) which l

were transmitted by GPUN letter dated February 22, 1985.

In the discussion, the NRC staff stated that the four JC0s listed above required revision and requested GPUN to modify the JCOs or qualify equipment l

within 10 days (by March 10, 1985). Our re-evaluation of the JCOs has l

resulted in the following hardware modifications which have been completed.

1.

The unqualified components in motor operated valves V-21-5,11,13, 15,17, and 18 in the Containment Spray System which are discussed in JC0-0C-85-2 and 4 have been replaced with qualified components.

2.

All of the key lock control switches discussed in JC0-0C-85-24 and 43 have been disconnected. This action (disconnecting the key lock control switches) results in operator inconvenience, however, it will neither affect safety system operation to bring the plant to a safe shutdown condition nor the mitigation of any of the design basis accidents. Qualified key lock switches will be installed at a later date to facilitate operator convenience.

Based on these modifications, it is concluded that JC0-0C-85-2, 4, 24 and 43 are no longer needed and are therefore rescinded by this letter.

Enclosed are revised Attachments I and II to our letter of February 22,1985 to reflect these changes.

4 l

8503250017 850315

\\

1 l

PDR ADOCK 05000219 t

P PDR l

l GPU Nuclear Corporation is a subsidiary of the General Pubiic Utikties Corporation o

Please note that an additional change has been made to Attachment I.

Previously, it was. reported that DC-2 Motor Control Center (MCC) was expected to be qualified by analysis before March 31, 1985.

However, in the process of preparing the qualification documentation, we have recently concluded that a schedular extension for this item is required. The JC0, (JC0-0C-85-21), for this component has been revised and is attached.

It was also reported in Attachment I that additional time was required to establish qualification status or to specify replacement parts (Note 6) of limit switches for motor operated valves V-1-110 and V-1-111 in the Main Steam System.

A recent plant walkdown established qualification status of the limit switches and specified replacement parts. Therefore, Note 6 of Attachment I has been deleted and the current status of the limit switches are provided in Attachment I.

Should you have any question, please contact M. Laggart - Manager, BWR Licensing (201) 299-2341.

Very truly yours, V_-

4.,)

P te iedler Vice President and Director Oyster Creek PBF/ dam PBF/dh/rj

  1. 0927A cc: Dr. Thomas E. Murley, Administrator Region I U.S. Nuclear Regulatory Commission 631 Park Avenue King of Prussia, PA 19406 NRC Resident Inspector Oyster Creek Nuclear Generating Station Forked River, NJ 08731 4

+

,.-.w

--m

..---.<---,,,n.----ww--

--,---,-----e

ATTACHMENT I OYSTER CREEK ENVIRONMENTAL QUALIFICATION STATUS COMPONENT SCHEDULAR REASON FOR COMPONENT TER QUALIFICATIDN JC0 EXTENSIDN EXTENSION QUALIFICATION SCHEDULE FOR TAG NO.

GENERIC NAME MANUFACTURER gQ.

STATUS MQ.

REDUESTED REQUESTED METHOD OUALIFICATIDN Emeraency Condenser System IB05-Al Differential Barton 58 Qualified Pressure Switch IB05-A2 Differential Bartop 58 Qualified Pressure Switch IB05-B1 Differential Barton 58 Qualified Pressure Switch 1805-B2 Differential Barton 58 Qualified Pressure Switch IB11-Al Differential Barton 58 Qualified Pressure Switch IB11-A2 Differential Barton 58 Quallfled Pressure Switch IB11-B1 Differential Barton 58 Qualified Pressure Switch 1811-B2 Differential Barton 58 Qualified Pressure Switch IG06-A Level Transmitter GE/MAC 42 OC-85-7 Yes Notes Ib&2 Replace Next Refueling outage IG06-B Level Transmitter GE/MAC 42 DC-85-7 Yes Notes Ib&2 Replace Next Refueling Outage V-14-1 Limit Switch Micro Switch DC-85-26 Yes Notes la&2 Replace Note 2 V-14-5 Limit Switch Micro Switch DC-85-26 Yes Notes la&2 Replace Note 2 U-14-19 Limit Switch Micro Switch DC-85-26 Yes Notes la&2 Replace Note 2 V-14-20 Limit Switch Micro Switch DC-85-26 Yes Notes la&2 Replace Note 2 V-14-30 Motor Operator Limitorque 8

Replaced / Qual.

V-14-31 Motor Operator Limitorque 9

Replaced / Qual.

V-14-32 Motor Operator Limitorque 8

Replaced / Qual.

V-14-33 Motor Operator Limitorque 9

Replaced / Qual.

(See Page 20 for Notes.)

04480/p1 Rev. 1

. ~ -. - -

ATTACNMENT I 0YSTER CREEK ENVINDNMENTAL QUALIFICATION STATUS COMPONENT SCHEDULAR REASON FOR COMPONENT TER QUALIFICATION JC0 EXTENSION EXTENSION QUALIFICATION SCHEDULE FOR TAG NO.

GENERIC MAM MANUFACTURER STATUS REDUESTED REQUESTED METHOD OUALIFICATION Emeraency Condenser System (Cont'd)

U-14-34 Motor Operator Limitorque 9

Replaced / Qual.

U-14-35 Motor Operator Limitorque 9

Replaced / Qual.

V-14-36 Motor Operator Limitorque 10 Replaced / Qual.

4 V-14-37 Motor Operator Limitorque 10 Replaced / Qual.

Core Sorav and Automatic Deoressuri2ation System i

IA83A Pressure Switch Dresser /Barksdale 49 OC-85-1 Yes Notes-la&2 Replace Next Refueling Outage j

and Controllers i

IA83B Pressure Switch Dresser /Barksdale 49 OC-85-1 Yes Notes la&2 Replace Next Refueling Outage and Controllers i

IA83C Pressure Switch Dresser /Barksdale 49 OC-85-1 Yes Notes laS2 Replace Next Refueling Outage and Controllers ZA830 Pressure Switch Dresser /Barksdale 49 OC-85-1 Yes Notes la&2 Replace Next Refueling Outage and Controllers i

3A83E Pressure Switch Dresser /Barksdale 49 OC-85-1 Yes Notes la&2 Replace Next Refueling Outage and controllers NR-108A Solenoid Valve Dresser 37 Qualified NR-108B Solenoid Valve Dresser 37 Qualified i

NR-108C Solenoid Valve Dresser 37 Qualified NR-108D Solenoid Valve Dresser 37 Qualified NR-108E Solenoid Valve Dresser 37 Qualified i

NICIA Pump Motor General Electric 67 Qualified NZO18 Pump Motor General Electric 67 Qualified NZOIC Pump Motor General Electric 67 Qualtfled N201D Pump Motor General Electric 67 Qualified NZO3A Pump Motor General Electric 69 Qualified (See Page 20 for Notes.)

i Rev. 1 04480/p2 i

ATTACMMENT I OYSTER CREEK ENVIRONMENTAL QUALIFICATI0F STATUS COMPONENT SCHE'ijLAR REASON FOR COMPONENT TER QUALIFICATIDN JC0 EXTE4SIDN EXTENSION QUALIFICATIDN -SCHEDULE FOR TAG NO.

GENERIC NAME MANUFACTURER STATUS REQLl2STED REQUESTED METHOD OUALIFICATION Core Sorav and Automatic Deorescurization Svstam (Cont'd)

NZ038 Pump Motor General Electric 68 Qualified NZO3C Pump Motor General Electric 69 Qualified N203D Pump Motor General Electric 68 Qualified RE17A Pressure Switch Barksdale 55 Qualified RE178 Pressure Switch Barksdale 55 Qualified RE17C Pressure Switch Barksdale 53 Qualified RE17D Pressure Switch Barksdale 53 Qualified RV26A Flow Transmitter GE/MAC 43 DC-85-11 Yes Notesib&&

Replace Next Refueling Outage RV26B Flow Transmitter GE/MAC 43 DC-85-11 Yes Notesib&2 Replace Next Refueling Outage RV29A Pressure Switch Mercoid 51 DC-85-9 Yes Note la' Replace.

Before 11/30/85 RV208 Pressure Switch Mercoid 51 DC-85-9 Yes Note la Replace Before 11/30/85 RV29C Pressure Switch Mercold 51 OC-85-9 Yes Note la Replace Before 11/30/85 RV29D Pressure Switch Mercold 51 DC-85-9 Yes Note la Replace Before 11/30/85 RV40A Diff. Press. Switch SOR 52 Replaced / Qual.

RV40B Diff. Press. Switch SOR 51 Replaced / Qual.

RU40C Diff. Press. Switch SOR 52 Replaced / Qual.

RV40D Diff. Press. Switch SOR 51 Replaced / Qual.

RV46A Pressure Switch Barton 48 Qualified RV468 Pressure Switch Barton 48 Qualified RV46C Pressure Switch Barton 48 Qualified RV460 Pressure Switch Barton 48 Qualified V-20-3 Motor Operator Limitorque DC-85-42 No Replace Before 3/31/85 Limit Switch (See Page 20 for Notes.)

l Rev. 1 04480/p3

ATTACHMENT I OYSTER CREEK ENVIRONMENTAL QUALIFICATION STATUS COMPONENT

-SCHEDULAR REASON FOR COMPONENT TER QUALIFICATION JC0 EXTENSION EXTENSION QUALIFICATION SCHEDULE FOR TAG NO.

GENERIC NAME MANUFACTURER HQ, STATUS MQ.

REQUESTED REQUESTED METHOD OUALIFICATION Core Sorav and Automatic Deorcssurization System (Cont'd)

V-30-4 Motor Operator Limitorque DC-85-42 No Replace Before 3/31/85 Limit Switch V-20-15 Motor Operator Limitorque 2

Qualified V-20-21 Motor Operator Limitorque 2

Qualified V-20-32 Motor Operator Limitorque DC-85-42 No Replace Before 3/31/85 Limit Switch U-20-33 Motor Operator Limitorque DC-85-42 No Replace Before 3/31/85 Limit Switch U-20-40 Motor Operator Limitorque 2

Qualified V-20-41 Motor Operator Limitorque 2

Qualified 9-20-92 Limit Sw. itch (2)

Namco DC-85-25 Yes Note la Replace Before 11/30/85 V-20-93 Limit Switch (2)

Namco DC-85-25 Yes Note la Replace Before 11/30/85 V-20-94 Limit Switch (2)

Namco DC-85-25 Yes Note la Replace Before 11/30/85 V-20-95 Limit Switch (2)

Namco DC-85-25 Yes Note la Replace Before 11/30/85 Containment Soray System IP03A Flow Transmitter General Electric 45 Note 4 OC-85-12 Yes Notes Ib& 2 Replace Next Refueling Outage IP03B Flow Transmitter General Electric 44 Note 4 OC-85-12 Yes Notes Ib&2 Replace Next Refueling Outage IPISA Pressure Switch Barton 48 Qualified IP158 Pressure Switch Barton 48 Qualified IP15C Pressure Switch Barton 48 Qualified IP150 Pressure Switch Barton 48 Qualified IP18A Temperature Switch Ashcroft Note 4 OC-85 19 Ves Note la Replar,e Before 11/30/85 IP18B Temperature Switch Ashcroft Note 4 DC-85-19 Yes Note la Replace Before 11/30/85 (See Page 20 for Notes.)

N I 04480/p4

ATTACHMENT I OYSTER CREEK ENVIRONMENTAL QUALIFICATIDN STATUS COMPONENT SCHEDULAR REASON COR COMPONENT TER QUALIFICATION JC0 EXTENSION EXTENSIJN QUALIFICATION SCHE'JULE FOR TAG NO.

GENERIC NAME MANUFACTURER STATUS REOUESTED REQUEEID._

METHOD OUALIFICATION Containment Sorav System (Cont'd) l V-21-1 Motor Operator Limitorque 6

Replaced / Qual.

Limit Switch U-21-1 Key Lock Control General Electric 6

Note 5 Switch V-21-3 Motor Operator Limitorque 6

Replaced / Qual.

Limit Switch V-21-3 Key Lock Control General Electric Note 5 Switch V-21-5 Motor Operator Limitorque 7

Replaced / Qual.

V-21-5 Key Lock Control General Electric Note 5 Switch U-21-7 Motor Operator Limitorque 6

0C-85-41 No Replace Before 3/31/85 Limit Switch V-21-7 Key Lock Control General Electric Note 5 Switch V-21-9 Motor Operator Limitorque 6

OC-85-41 No Replace Before 3/31/85

-Limit Switch U-21-9 Key Lock Control General Electric Note 5 Switch V-21-11 Motor Operator Limitorque 7

Replaced / Qual.

V-21-11 Key Lock Control General Electric Note 5 Switch V-21-13 Motor Operator Limitorque 13 Replaced / Qual.

V-21-13 Key Lock Control General Electric Note 5 Switch U-21-15 Motor Operator Limitorque Replaced / Qual.

V-21-15 Key Lock Control General Electric Note 5 Switch (See Page 20 for Notes.)

04480/p5 Rev. 1

ATTACHMENT I OYSTER CREEK ENVIRONMENTAL QUALIFICATION STATUS COMPONENT SCHEDULAR REASON FOR COMPONENT TER QUALIFICATION JC0 EXTENSION EXTENSION QUALIFICATION SCHEDULE FOR TAG NO.

GENERIC NAME MANUFACTURER NQ.

STATUS NQ.

REDUESTED REQUESTED METHOD OUALIFICATIDN Containment Sorav System (Cont'd)

V-31-17 Motor Operator Limitorque 15 Replaced / Qual.

V-31-17 Key Lock Control General Electric Note 5 Switch V-31-18 Motor Operator Limitorque Replaced / Qual.

V-31-18 Key Lock Control General Electric Note 5 Switch 1-1 Pump Motor General Electric 70 Qualified 1-2 Pump Motor General Electric 70 Qualifted 1-3 Pump Motor General Electric 70 Qualified 1-4 Pump Motor General Electric 70 Qualified Drywell & Sunoression System DPS-66A Differential ITT Barton Note 4 DC-85-15 Yes Notes la&2 Replace Note 2 Pressure Switch DPS-66B Differential ITT Barton Note 4 OC-85-15 Yes Notes la&2 Replace Note 2 Pressure Switch LT-37 Level Transmitter Rosemount Qualified LT-38 Level Transmitter Rosemount Qualified PT-53 Pressure Transmitter Rosemount Qualified PT-54 Pressure Transmitter Rosemount Qualified q

RE04A Pressure Switch Static-0-Ring 50 Note 4 OC-85-5 Yes Notes la&2 Replace Note 2 RE04B Pressure Switch Static-0-Ring 50 Note 4 OC-85-5 Yes Notes la&2 Replace Note 2 RE04C Pressure Switch Static-0-Ring 50 Note 4 0C-85-5 Yes Notes la&2 Replace Note 2 RE04D Pressure Switch Static-0-Ring 50 Note 4 OC-85-5 Yes Notes la&2 Replace Note 2 TE-109A Temperature Element Pyco Note 4 OC-85-34 Yes Note la Replace Before 11/30/85 (See Page 20 for Notes.)

04480/p6 Rev. 1

ATTACHMENT I OYSTER CREEK ENVIRONMENTAL QUALIFICATION STATUS COMPONENT SCHEDULAR REASON FOR COMPONENT TER QUALIFICATION JC0 EXTENSIDN EXTENSIDN QUALIFICATIDN SCHEDULE FOR TAG NO.

GENERIC NAME MANUFACTURER MQ, STATUS RQ2 REQUESTED REQUESTED METHOD OUALIFICATIDN Drywell & Sucoression System (Cont'd)

TE-109B Temperature Element Pyco Note 4 DC-85-34 Yes Note la Replace-Before 11/30/85 TE-109C Temperature Element Pyco Note 4 DC-85-34 Yes Note la Replace Before 11/30/85 TE-1090 Temperature Element Pyco Note 4 DC-85-34 Yes Note la Replace Before 11/30/85 Tip Ball Solenoid Valves General Electric DC-85-39 Yes Analysis Before 11/30/85 Valves V-5-147 Motor Operator Limitorque 14 DC-85-3 Yes Note 2 Partial Replemt.

Note 2 V-5-166 Motor Operator Limitorque 11 Qualified V-5-167 Motor Operator Limitorque 14 DC-85-3 Yes Note 2 Partial Replemt.

Note 2 V-6-395 Limit Switch Namco Qualified V-15-1 Motor Operator Limitorque 3

Replaced / Qual.

V-16-2 Motor Operator Limitorque 4

Replaced / Qual.

V-16-14 Motor Operator Limitorque 4

Replaced / Qual.

V-16-61 Motor Operator Limitorque 4

Qualified V-17-1 Motor Operator Limitorque 5

Replaced / Qual.

V-17-2 Motor Operator Limitorque 5

Replaced / Qual.

V-17-3 Motor Operator Limitorque 5

Replaced / Qual.

V-17-19 Motor Operator Limitorque 3

Replaced / Qual.

V-17-54 Motor Operator Limitorque 1

Replaced / Qual.

V-17-55 Motor Operator Limitorque 5

OC-85-40 No Replace Before 3/31/85 Limit Switch V-17-56 Motor Operator Limitorque 5

DC-85-40 No Replace Before 3/31/85 Limit Switch V-17-57 Motor Operator Limitorque 5

OC-85-40 No Replace Before 3/31/85 Limit Switch V-22-1 Limit Switches (2)

Namco Qualified (See Page 20 for Notes.)

Rev. 1 04480/p?

ATTACHMENT I OYSTER CREEK ENVIRONMENTAL QUALIFICATION STATUS COMPONENT SCHEDULAR REASON FOR COMPONENT TER QUALIFICATION JC0 EXTENSION EXTENSION QUALIFICATIDN SCHEDULE FOR TAG NO.

GENERIC NAME MANUFACTURER HQ.

ETATUS 90.

REQUESTED REQUESTED METN00 00ALIFICATIDN Drywell & Sunoression System (Cont'd)

V-22-2 Limit Switches (2)

Namco Qualified U-22-28 Limit Switches (2)

Namco Qualified V-22-29 Limit Switches (2)

Namco Qualified V-23-13 Limit Switches (2)

Micro Switch DC-85-30 Yes Note la Replace Before 11/30/85 U-23-14 Limit Switches (2)

Micro Switch DC-85-30 Yes Note la Replace Before 11/30/85 V-23-15 Limit Switches (2)

Micro Switch DC-85-30 Yes Note la

  • Replace Before 11/30/85 U-23-16 Limit Switches (2)

Micro Switch DC-85-30 Yes Note la Replace Before 11/30/85 V-23-17 Limit Switches (2)

Namco DC-85-30 Yes Note la&2 Replace Note 2 V-23-18 Limit Switches (2)

Namco DC-85-30 Yes Note la&2 Replace Note 2 V-23-19 Limit Switches (2)

Namco Qualified V-23-20 Limit Veitches (2)

Namco Qualified V-23-21 Limit Switches (2)

Namco DC-85-30 Yes Notes la&2 Replace Note 2 V-23-22 Limit Switches (2)

Namco DC-85-30 Yes Notes la&2 Replace Note 2 U-26-16 Limit Switches (2)

Micro Switch Qualified U-26-18 Limit Switches (2)

Micro Switch Qualified V-27-1 Limit Switches (2)

Micro Switch DC-85-28 Yes Note la Replace Before 11/30/85 V-27-2 Limit Switches (2)

Micro Switch DC-85-28 Yes Note la Replace Before 11/30/85 V-27-3 Limit Switches (2)

Namco DC-85-28 Yes Note la Replace Before 11/30/85 V-27-4 Limit Switches (2)

Namco DC-85-28 Yes Note la Replace Before 11/30/85 U-28-17 Limit Switches Namco DC-85-32

- 15 Note la Replace Before 11/30/85 U-28-18 Limit Switches Namco DC-85-32 Yes Note la Replace Before 11/30/85 V-28-47 Limit Switches (2)

Namco DC-85-32 Yes Note la Replace Before 11/30/85 U-31-2 Limit Switch Namco 0C-85-45 Yes Note la Replace Before 11/30/85 (See Page 20 for Notes.)

04420/p8 Rev. 1 4

ATTACHMENT I OYSTER CREEK ENVIRONMENTAL QUALIFICATION STATUS COMPONENT SCHEDULAR REASON FOR COMPONENT TER QUALIFICATION JC0 EXTENSIDN EXTENSIDN QUALIFICATIDN SCHEDULE FOR TAG ND.

GENERIC NAME MANUFACTURER STATUS REQUESTED REDUESTE3.

METHDD OUALIFICATION Main Steam System IB10A Temperature Switch Fenwal 65 Qualified 1810B Temperature Switch Fenwal 65 Qualified IB10C Temperature Switch Fenw 65 Qualified 18100 Temperature Switch Fenwal 65 Qualified IB10E Temperature Switch Fenwal 65 Qualified IB10F Temperature Switch Fenwal 65 Qualified IB10G Temperature Switch Fenwal 65 Qualified IB10H Temperature Switch Fenwal 65 Qualified 1B10J Temperature Switch Fenwal 65 Qualified IB10K Temperature Switch Fenwal 65 Qualified IB10L Temperature Switch Fenwal 65 Qualified IB10M Temperature Switch Fenwal 65 Qualified IB10N Temperature Switch Fenwal 65 Qualified ZB10P Temperature Switch Fenwal 65 Qualified IB100 Temperature Switch Fenwal 65 Qualified IB10R Temperature Switch Fenwal 65 Qualified RE22A Differential Press. Barton 57 Qualified Indicating Switch RE23B Differential Press. Barton 57 Qualified Indicating Switch RE22C Differential Press. Barton 57 Qualified Indicating Switch RE22D Differential Press. Barton 57 Qualified Indicating Switch (See Page 20 for Notes.)

N8 '

04400/p9

ATTACHMENT I OYSTER CREEK ENVIRONMENTAL QUALIFICATION STATUS COMPONENT SCHEDULAR REASON FOR COMPONENT TER QUALIFICATION JC0 EXTENSION EXTENSION QUALIFICATION S'HEDULE FOR

_IAG NO...

GENERIC MAME MANUFACTURER STATUS REQUESTED REOUESTED METHDD OUALIFICATION Main Ste&m System (Cont'd)

RE22E Differential Press. Barton 57 Quallfled Indicating Switch RE22F Differential Press. Barton 57 Qualified Indicating Switch RE22G Differential Press. Barton 57 Qualified Indicating Switch RE22H Differential Press. Barton 57 Qualified Indicating Switch RE23A Pressure Switch Meletron 46 Qualified RE23B Pressure Switch Heletron 46 Qual,1 fled RE23C Pressure Switch Heletron 46 Qualified RE230 Pressure Switch Heletron 46 Qualified NS03A Limit Switches Namco Replaced / Qual.

(V-1-7)

A,B.D NS-03A-L1 Solenoid Valve Asco 17 Qualified (V-1-7)

ES-03A-L2 Solenoid Valve Asco 17 Qualified (V-1-7)

NS-03A-L3 Solenoid Valve Asco 17 Qualified (V-1-7)

NS03B Limit Switches Namco Replaced / Qual.

(V-1-8)

A.B.D NS-03B-L1 Solenoid Valve Asco 18 Qualified (V-1-8)

NS-03B-L2 Solenoid Valve Asco 18 Qualified (V-1-8)

(See Page 20 for Notes.)

1-8)

(See Page 20 for Notes.)

Rev. 1 04482/p10

ATTACHMENT I OYSTER CREEK ENVIRONMENTAL QUALIFICATION STATUS COMPONENT SCHEDULAR REASON FDR COMPONENT TER QUALIFICATIDN JC0 EXTENSIDN EXTENSION QUALIFICATION SCHEDULE FOR TAG NO.

GENERIC NAME MANUFACTURER STATUS REQUESTED REQUESTED METNOD OUALIFICATION Main Steam System (Cont'd)

NS-03B-L3 Solenoid Valve Asco 18 Qualtfled (V-1-8)

NSO4A Limit Switches Namco 64 Replaced / Qual.

(V-1-9)

A,B,D NSO4B Limit Switches Namco 64 Replaced / Qual.

(V-1-10)

A,B,0 V-1-106 Motor Operator Limitorque 12 DC-85-44 Yes Notes la&2 Partial Replemt.

Note 2 Limit Switches U-1-107 Motcr Operator Limitorque 12 DC-85-44 Yes Notes la&2 Partial Replcat.

Note 2 Limit Switches V-1-110

. Motor Operator Limitorque DC-85-44 Yes Notes la&2 Partial Replomt.

Note 2 Limit Switches V-1-111 Motor Operator Limitorque DC-85-44 Yes Notes la&2 Partial Replemt.

Note 2 Limit Switches V-6-2679 Solenoid Valve Asco 19 Qualified (NS-048-L1)

U-6-2680 Solenoid Valve Asco 19 Qualified (NS-04BL2)

V-6-2681 Solenoid Valve Asco 19 Quallfled (NS-04BL3)

U-6-2683 Solenoid Valve Asco 20 Qualified (NS-04A-L1)

V-6-2685 Solenoid Valve Asco 20 Qualified (NS-04A-L2)

V-6-2685 Solenoid Valve Asco 20 Qualified (NS-04A-L3)

(See Page 20 for Notes.)

Rev. 1 04480/pil

9

~ATTACNMENT I OYSTER CREEK ENVINONMENTAL QUALIFICATION STATUS Col #0NENT SCNEDULAR REASON FOR COMP 0NENT TER QUALIFICATION JC0 EXTENSION EXTENSION QUALIFICATION SCNEDULE FOR TAG NO.

GENERIC NAME MANUFACTURER E

STATUS E

REDUESTED REQUESTED METH00 OUALIFICATION Condensate Transfer Svstam V-6-457 Solenoid Valve Asco 32 Replaced /Oual.

(Fcr V-11-34) v-6-458 Solenoid Valve Asco 32 Replaced /Oual.

(Fcr V-11-36)

V-11-34 Limit Switch Fisher Governor Co.

DC-85-31 Yes Note la Replace Before 11/30/85 V-11-36 Limit Switch Fisher Governor Co.

OC-85-31 Yes Note la.

Replace Before 11/30/85 Onernency Service Water Systan V-3-87 Control Switch General Electric Note 5 V-3-88 Control Switch General Electric Note 5 Reactor Plant Instr e ntation System IA-90A Differential Press. Rosemount OC-85-37 Yes Notes Ib&2 Replace Note 2 Transmitter IA-908 Differential Press. Rosemount DC-85-37 Yes Notes ib&2 Replace Note 2 Transmitter IA-91A Differential Press. General Electric OC-85-37 Yes Notes Ib&2 Replace Note 2 Transmitter IA-918 Differential Press. General Electric OC-85-37 Yes Notes Ib&2 Replace Note 2 Transmitter IA-92A Pressure Transmitter Rosemount OC-85-37 Yes Notes Ib&2 Replace Note 2 IA-92B Pressure Transmitter Rosemount OC-85-37 Yes Notes ib&2 Replace Note 2 ID13A Level Transmitter General Electric 41 OC-85-8 Yes Notes Ib&2 Replace Next Refueling Outage ID13B Level Transmitter General Electric 41 OC-85-8 Yes Notes Ib&2 Replace Next Refueling Outage ID46A Pressure Indicating GE/MAC 38 OC-85-6 Yes Notes IbE2 Replace Next Refueling Outage Transmitter ID46B Pressure Indicating GE/MAC 38 OC-85-6 Yes Notes Ib&2 Replace Next Refueling Outage Transmitter (See Page 20 for Notes.)

04480/p12 Rev. 1

ATTACNMENT I OYSTER CREEK ENVIRONMENTAL QUALIFICATION STATUS COMPONENT SCNEDULAR REASON FOR COMPONENT TER QUALIFICATION

.'00 EXTENSION EXTENSIDN QUALIFICATION SCHEDULE FOR

. LAG _MQm GENERIC NAME MANUFACTURER E

STATUS E

REQUESTED REQUESTED METHOD OUALIFICATION Reactor Plant Instrumentation System (Cont'd)

RE03A Level Indicating Yarway 62 Qualtfled Switch RE03B Level Indicating Yarway 62 DC-85-14 Yes Notes la&2 Replace Note 2 Switch RE02C Level Indicating Yarway 62 DC-85-14 Yes Notes la&2 Replace Note 2 Switch RE020 Level Indicating Yarway 62 OC-85-14 Yes Notes la&2 Replace Note 2 Switch RE03A Pressure Switch Barksdale 56 Qualified RE03B Pressure Switch Barksdale 56 Qualified RE03C Pressure Switch Barksdale 56 Qualified RE030 Pressure Switch Barksdale 56 Qualified RE05A Level Indicating Yarway 63 DC-85-22 Yes Notes Ib&2 Replace Next Refueling Outage Switch RE05/19A Level Indicating Yarway 61 DC-85-22 Yes Notes Ib&2 Replace Next Refueling Outage Switch RE058 Level Indicating Yarway 63 DC-85-22 Yes Notes 1b&2 Replace Next Refueling Outage Switch RE05/19B Level Indicating Yarway 61 DC-85-22 Yes Notes Iba2 Replace Next Refueling Outage Switch REI5A Pressure Switch Barksdale 54 Qualified REISE Pressure Switch Barksdale 54 Qualified RE15C Pressure Switch Sarksdale 54 Qualified REISD Pressure Switch Barksdale 54 Qualified RE16A Pressure Switch Barksdale Qualified RE168 Pressure Switch Barksdale Quallfled (See Page 20 for Notes.)

04480/pl3 Rey, 1

--nd

ATTACMMENT I OYSTER CREEK ENVIRONMENTAL QUALIFICATION STATUS COMPONENT SCHEDULAR REASON FOR COMPONENT TER QUALIFICATION JC0 EXTENSION EXTENSION QUALIFICATION. SCHEDULE FOR TAG No.

GENERIC MAME MANUFACTURER STATUS REQUESTED REQUESTED METHOD QUALIFICATI0M Reactor Plant Instrimantation System (Cont'd)

RE18A Level Indicating Barton 60 Qualified Switch RE188 Level Indicating Barton 60 Qualified Switch RE18C Level Indicating Barton 60 Qualified Switch RE18D Level Indicating Barton 60 Qualified Switch TE-50-1A Temperature Element Pyco Qualified TE-57-2A Temperature Element Hy-Cal -

OC-85-37 Yes Note la Replace Before 11/30/85 TE-58-1B Temperature Element Pyco Qualified TE-59-2B Temperature Element Hy-Cal OC-85-37 Yes Note la Replace Before 11/30/85' TE-130-450 Temperature Element Pyco Qualified TE-130-451 Temperature Element Pyco Qualified TE-130-453 Temperature Element Pyco Qualified TE-130-454 Temperature Element Pyco Qualified Rgaetor Protection System R087C Level Switch Magnetrol 59 Replaced / Qual.

R0888 Level Switch Magnetrol 59 Replaced / Qual.

R091A Level Switch Magnetrol 59 Replaced / Qual.

R0920 Level Switch Magnetrol 59 Replaced / Qual.

Safety & Relief Valve Monitor System MS-VE-1 Accelerometers Endevco Note 3 OC-85-16 No Analysis Before 3/31/85 Thre 21 MS-VX-1 Line Driver Uholt2-Dickie OC-85-16 Yes Note 2 Relocate Next refueling outage Thru 21 (See Page 20 for Notes.)

04480/p14 Rev. I

ATTACNMENT I OYSTER CREEK ENVIRONMENTAL QUALIFICATION STATUS COMPONENT SCHEDULAR REASON FOR COMPONENT TER QUALIFICATION JC0 EXTENSION EXTENSION QUALIFICATION SCHEDULE FOR TAG NO.

GENERIC NAME MANUFACTURER H(L STATUS REQUESTED REQUESTED METHOD OUALIFICATION Safety & Relief Valve Monitor Svstan (Cont'd)

TB-NR-28A Terminal Block TRW-Cinch DC-85-16 Yes Note 2 Relocate Next refueling outage Thru H. J Thru N. P Thru R.

TB-NR-108A Thru E.

Hydroaen and Oxvaen Monitorina System

.H /02 Analyzer Consip Inc.

Qualified IT-1A 2

H /02 Analyzer Consip Inc.

Qualified IT-1B 2

V-38-22 Solenoid Valve Asco 29 Replaced / Qual.

V-38-23 Solenoid Valve Asco 29 Replaced / Qual.

V-38-37 Solenoid Valve Target Rock Qualified V-38-38 Solenoid Valve Target Rock Qualified U-38-39 Solenoid Valve Target Rock Qualified V-38-40 Solenoid Valve Target Rock Qualified i

V-38-41 Solenoid Valve Target Rock Qualified i

V-38-43 Solenoid valve Target Rock Qualified V-38-44 Solenoid Valve Target Rock Qualified V-38-46 Solenoid Valve Target Rock Qualified V-40-6 Solenoid Valve Valcor Engineering Qualified SS CPM Selector Switch General Electric Note 4 OC-85-29 Yes Note la Replace /Reloc.

Before 11/30/85 i

6K37X Relay Agastat Note 4 OC-85-29 Yes Note la Replace /Reloc.

Before 11/30/85 i

6K46X Relay Agastat Note 4 DC-85-29 Yes Note la Replace /Reloc.

Before 11/30/85 (See Page 20 for Notes.)

Rev. I 04480/p15

ATTACNMENT I OYSTER CREEK ENVIBONMENTAL QUALIFICATION STATUS COMPONENT SCHEDULAR REASON FOR COMPONENT TER QUALIFICATION JC0 EXTENSION EXTENSION QUALIFICATION SCHEDULE FOR TAG NO.

GENERIC NAME MANUFACTURER STATUS E

KQ G Q REQUESTED METHOD OUALIFICATION 4160 Volt System 1A Non-Emergency General Electric DC-85-47 Yes Note 10 Analysis Before 11/30/85 Switchgear IB Non-Emergency General Electric DC-85-47 Yes Note 10 Analysis Before 11/30/85 Switchgear 1C Emergency Switchgear General Electric OC-85-47 Yes Note 10 Analysis Before 11/30/85 1D Emergency Switchgear General Electric DC-85-47 Yes Note 10 Analysis Before 11/30/85 160 Volt System STD Static Time General Electric OC-85-49 Yes Note 10 Analysis Before 11/30/85 Delay Unit for USS 1A1, BKR 011B STD Static Time General Electric DC-85-49 Yes Note 10 Analysis Before 11/3/085 Delay Unit for USS IBl. BKR 021B 1A1 460V Unit Substation General Electric DC-85-48 Yes Note 10 Analysis Before 11/30/85 1A11 460V MCC General Electric DC-85-51 Yes Note 9 Analysis Before 11/30/85 1A13 460V MCC General Electric DC-85-51 Yes Note 9 Analysis Before 11/30/85 1A31A 460V MCC General Electric DC-85-51 Yes Note 9 Analysis Before 11/30/85 1A31B 460V MCC General Electric 73 OC-85-51 Yes Note 9 Analysis Before 11/30/85 1AB2 460V MCC General Electric 74 DC-85-52 Yes Note 9 Analysis Before 11/30/85 181 460V Unit Substation General Electric OC-85-48 Yes Note 10 Analysis Before 11/30/85 1813 460V MCC General Electric DC-85-51 Yes Note 9 Analysis Before 11/30/85 1821A 460V MCC General Electric 74 OC-85-52 Yes Note 9 Analysis Before 11/30/85 1B21B 460V MCC General Electric 74 DC-85-52 Yes Note 9 Analysis Before 11/30/85 135 Volt Station DC System Battery Batteries Gould Inc.

Qualified Bac3 C C-1 Battery Charger Power Conversion Qualified Products (See Page 20 for Notes.)

04480/p16 Rev. 1

ATTACHMENT I OYSTER CREEK ENVIRONMENTAL QUALIFICATION STATUS COMPONENT SCHEDULAR REASON FOR CDNPONENT TER QUALIFILATION JC0 EXTENSION EXTENSION QUALIFICATION SCHEDULE FOR

__IAG NO.

GENERIC NAME MANUFACTURER STATUS REQUESTED REQUESTED METHOD OUALIFICATION 125 Volt Station DC System (Cont'd)

C-2 Battery Charger Power Conversion Qualtfled Products DC-C Distribution Center Gould Inc.

Qualified DC-1

. Hotor Control Center General Electric 73 OC-85-52 Yes Note 9 Analysis Before 11/30/85 i

DC-2 Motor Control Center ITE Gould 75 Note 3 OC-85-21 Yes Note la Partial Replemt Before 11/30/85 Comon Items Cah

Anaconda Qualified Cable Boston Insulated Qualified Wire Cat' General Electric 78 Qualified (Power)

Cable General Electric 79 Qualified (Control)

Cable Kerite FR 82 Qualified Cable Kerite HT 82 Qualified l

Cable Rockbestos EP 80 DC-85-20 Yes Note 8 Test Note 8 Cable Rockbestos DC-85-20 Yes Note 8 Test Note 8 Firewall III Cable Tenso11te 81 Qualified Electrical ITT Cannon 76 Qualified Connectors Electrical ITT Cannon 77 Qualified Connectors Electrical General Electric 72 OC-85-50 Yes Note 10 Analysis Before 11/30/85 Penetration Splice Raychem WCSF-N 83 Qualified Spilce Raychem NPKV Qualified (See Page 20 for Notes.)

04480/p17 Rev. 1

ATTACNMENT I OYSTER CREEK ENVIRONMENTAL QUALIFICATION STATUS COMPONENT SCHEDULAR REASON FOR COMPONENT TER QUALIFICATIDN JC0 EXTFNSION EXTENSION 00ALIFICATION SCHEDULE FOR TAG NO.

GENERIC NAME MANUFACTURER STATUS REOUESTED REQUESTED METHOD OUALIFICATIQR Comon Items (Cont'd)

Cable Dkonite (Dkozel)

Qualified Terminal Blocks General Electric Qualified Terminal Blocks Weidmuller 71 Qualified Wire Terminals AMP-PIDG, Qualified Plasti-Grip Wire Terminals Thomas and Betts Qualified 1

i Terminal Block Marathon Qualified Terminal Block Buchanan Qualified Coaxial Cable Endevco DC-85-16 Yes Note 2 Replace Next refueling outage Cable Okonite (X-01ene)

Qualified Standby Gas Treatment / Reactor Buildina Ventilation System VE2G-6A Temperature Element Weed Qualified TE28-6B Temperature Element Weed Qual t fled TE28-7A Temperature Element Weed Qualified TE28-78 Temperature Element Weed Qualified V-6-578 Solenoid Valve Asco Qualified V-6-580 Solenoid Valve Asco Qualified V-28-9 Limit Switches (2)

Namco DC-85-33 Yes Note la Replace Before 11/30/85 V-28-10 Limit Switches (2)

Namco DC-85-33 Yes Note la Replace Before 11/30/85 V-28-11 Limit Switches (2)

Namco DC-85-33 Yes Note la Replace Before 11/30/85 V-28-12 Limit Switches (2)

Namco DC-85-33 Yes Note la Replace Before 11/30/85 V-28-13 Limit Switches (2)

Namco DC-85-33 Yes Note la Replace Before 11/30/85 V-28-14 Limit Switches (2)

Namco DC-85-33 Yes Note la Replace Before 11/30/85 (See Page 20 for Notes.)

Rev. 1 04480/pl8

-ATTACHMENT I OYSTER CREEK ENVIRONMCTAL QUALIFICATION STATUS I

COMPONENT SCHEDULAR REASON FOR COMPONENT TER QUALIFICATION JC0 EXTENSION EXTENSION QUALIFICATION SCHEDULE FOR 4

TAG NO.

GENERIC NAME MANUFACTURER STATUS REQUESTED REQUESTED METHOD OUALIFICATION Standby Gas Treatment / Reactor Buildina Ventilation System (Cont'd)

V-28-15 Limit Switches (2)

Namco DC-85-33 Yes Note la Replace Before 11/30/85 V-28-16 Limit Switches (2)

Namco DC-85-33 Yes Note la Replace Before 11/30/85 V-28-21 Limit Switches (2)

Namco DC-85-36 Yes Note la Replace Before 11/30/85 V-28-22 Limit Switches (2)

Namco DC-85-36 Yes Note la Replace Before 11/30/85 V-28-23 Limit Switch Contrenatics Qualified V-28-24 Limit Switch Contromatics Qualified V-28-27 Limit Switch Contromattes Qualified V-28-28 Limit Switch contromatics Qualified V-28-48 Limito DC-85-36 Yes Note la Replace Before 11/30/85 V-28-23 Limit Switch Contromatics Qualified V-28-24 Limit Switch Contromatics Qualified V-28-27 Limit Switch Contromatics Qualified V-28-28 Limit Switch Contromatics Qualified V-28-48 Limit Switch Contramatics Qualified 4

f I

(See Page 20 for Notes.)

0448:/p19 Rev. 1

ATTACHMENT I OYSTER CREEK ENVIRONMENTAL QUALIFICATION STATUS NOTES:

Note la: This component is expected to be delivered between March 31, 1985 and November 30, 1985.

Note 1b: This component is expected to be delivered after November 30, 1985.

Note 2: Replacement of this component requires a plant shutdown. Next plant shutdown (Cycle 11 refuel outage) is scheduled to consnence sometime after March 1986. However, GPUN will attempt to replace this component during the i

first unscheduled outage of a sufficient length following receipt of the component from the supplier and completion of engineering. Otherwise, the replacement of this component will be accomplished during the Cycle 11 refuel outage.

Note 3 This component has already been qualified at other nuclear plants, and there is a high degree of confidence that qualification will be documented for Oyster Creek. Docunentation is being prepared to complete the EQ file.

Note 4 This component will be deleted if further analysis shows that it is not subjected to a harsh environment for the accident it is required to mitigate.

Note 5 This component was disconnected in March, 1985. It will be reconnected with qualified components.

Note 6 Not Used Note 7 Not Used Note 8 Final qualification of the cable will be confirmed by a supplementary test to be performed by the manufacturer. This test is scheduled to be completed by July 1986.

Note 9 Qualification report is being prepared by vendor for Oyster Creek based on the BWR HCC Qualification Program. Interim letter report concludes that a large majority of the devices are capable of showing qualification. The few remaining devices can be qualified by replacement, similarity analysis, or possibly minor testing. This qualification report will be available by the end of April, 1985 Note 10 Qualification documentation is being prepared by vendor. Interim letter report concludes that there is a high degree of confidence that this component is qualified, i

04480/pg. 20

4 1

JC0-0C-85-2, Rev. 2 March 8,1985 Page 1 of 2 4

0YSTER CREEK NUCLEAR GENERATING STATION JUSTIFICATION FOR CONTINUED OPERATION (JCO) i f

c J

i 9

i t

l-4

,-.c.-,

,,,,--w,n

,---,-mn,n,

,,n-r

-a,--,--

.e--,,.

r,g~.--m m.m--vv--m-n,,nv.,e,

,,m.w ww --w-re

JCO-0C-85-2, Rev. 2 March 8,1985 Page 2 of 2 INTENTIONALLY LEFT BLANK

JC0-0C-85-4, Rev. 2 March 8,1985

' Page 1 of 2 OYSTER CREEK NUCLEAR GENERATING STATION JUSTIFICATION FOR CONTINUED OPERATION (JCO) 4 1

re-e-

p-

,-,-.,..,,--,.y.

-nr.

,.,g, w..-nm.-.-. -.. - - -.,...,-,,.,,.,- -

g.--_.,n,,,

-r,..,..,. -,, -,.., - - - -

JC0-0C-85-4, Rev. 2 March 8,1985 Page 2 of 2 INTENTIONALLY LEFT BLANK k

JC0-0C-85-21, Rev. 2 March 8,1985 Page 1 of 2 OYSTER CREEK NUCLEAR GENERATING STATION JUSTIFICATION FOR CONTINUED OPERATION (JCO)

JC0-0C-85-21, Rev. 2 March 8,1985 Page 2 of 2

. COMPONENTS Tag Numbers DC-2 Description 125V DC Power Supply OBJECTIVE The objective of this discussion is to determine that failure of this component will not degrade other safety systems nor mislead the operator.

COMPONENT LOCATION This power supply is located in the northeast quadrant of the Reactor Building on elevation 75'3".

COMPONENT FUNCTION This component provides power to the vent valves and one of the condensate return valves for one of the isolation condensers.

l EVALUATION The component sees a harsh environment for the isolation condenser break outside the drywell.

If DC-2 supplies power to the affected isolation

. condenser and subsequently failed, it would not result in a degradation of the isolation function of the affected condenser because other redundant AC l

isolation valves which are not powered fran DC-2 will close on an isolation signal.

If the power supply was associated with the intact condenser and subsequently failed, it would at worst cause the condenser to be rendered inoperative. The operator would then make use of alternate decay heat removal systems.

If DC-2 failed prior to satisfying its function, decay heat removal would be through the EMRVs with RPV inventory makeup supplied by Core Spray. This mode could be sustained for a lengthy period due to the large heat capacity of the torus pool. The Containment Spray system could be subsequently used to provide torus pool heat removal, i

The operator would not be misled by the loss of DC-2 since the valve position indicating lights for the valves would inform him of the incorrect i

situation and would allow him to take the appropriate actions.

CONCLUSION The loss of DC-2 will not degrade other plant safety functions and will not provide misleading information to the operator.

4 3

e

JC0-0C-85-24, Rev. 1 March 8,1985 Page 1 of 2 l

OYSTER CREEK NUCLEAR GENERATING STATION JUSTIFICATION FOR CONTINUED OPERATION (JCO) i l

JC0-0C-85-24, Rev. 1 March 8,1985 Page 2 of 2 INTENTIONALLY LEFT BLANK

JC0-0C-85-43, Rev. 1 March 8,1985 Page 1 of 2 0YSTER CREEK NUCLEAR GENERATING STATION JUSTIFICATION FOR CONTINUED OPERATION (JCO)

JCO-0C-85-43, Rev. 1 March 8,1985 Page 2 of 2 INTENTIONALLY LEFT BLANK

~