Text
.. -, _
PUBLIC SERVICE COMPANY OF COLORADO P.
O. SOX 84o OENVER.
COLORADO 80200 OSCAR H. LEE March 1, 1985 Fort St. Vrain Unit No. 1 P-85069 Regional Administrator
% 9 e[q'y ] T Region IV
)ip-v U. S. Nuclear Regulatory Commission 611 Ryan Plaza Drive MAR - 81985 Arlington, Texas 76011 Attn: Mr. E. H. Johnson
SUBJECT:
Masonry Block Walls
REFERENCES:
Meeting Between Mr. J.R. Reesy (PSC) and Mr. G.L. Plumlee (NRC) on November 27, 1984. Telecon between PSC and NRC on January 16, 1985
Dear Mr. Johnson:
During a meeting between Mr. G.L. Plumlee, SRI, Fort St. Vrain and Mr. J.R. Reesy of PSC, concerning our response to question 14 posed by Mr. Robert Clark's letter dated July 21, 1982 (G-82232),
Mr. Plumlee indicated it would be appropriate that PSC submit a series of sketches indicating how PSC reinforced each of the walls involved in rework as a result of IE Bulletin 80-11. to this letter is a list of the walls requiring rework under IEB-80-11, the detail of the reinforcement, to which side of the wall the reinforcement was installed and sketches indicating the configuration of the reinforcing.
PSC reconnends that your staff review the NRC Safety Evaluation for FSV compliance with IEB-80-11 as the original SER was prepared with the understanding that all walls were reinforced utilizing bar straps installed in a vertical configuration.
8531g[$
J 27 J
eru
,.O g.;uaJ oeMrW f
'6
- q-2GF
I P-85069 Pagn 2
, to this letter is PSC's response to the NRC questions discussed during the telephone conference call between PSC and NRC on January 16, 1985.
PSC believes that since the request for the attached additional information is a direct result of conversations with the SRI and NRC, as referenced on Page 1 of this letter, an oath of affidavit is not required to accompany this letter.
Should you have any questions, please contact Mr. M. H. Holmes at (303) 571-8409.
Very truly yours, O. A $ ~ ly /$. y}%n/
- 0. R. Lee, Vice President Electric Production ORL/MM:pa Attachment
r-
]
~
to.P-85069 Page 1 of 19 MASONRY BLOCK WALL REINFORCING SCHEDULE WALL #
CONSTRUCTION DETAIL SIDE OF WALL APPLIED 2
DETAIL 2 BOTH SIDES 3
DETAIL 3A BOTH SIDES 3a DETAIL 3A BOTH SIDES 4
DETAIL 5 NORTH SIDE DETAIL 11 SOUTH SIDE 6
DETAIL 4A WEST SIDE DETAIL 13A EAST SIDE 7
DETAIL 4 WEST SIDE DETAIL 12 EAST SIDE 8
DETAIL 5A SOUTH SIDE DETAIL 13 NORTH SIDE 9
DETAIL SA EAST SIDE DETAIL 13 WEST SIDE 11 DETAIL 3A BOTH SIDES 12 DETAIL 3A BOTH SIDES 14 DETAIL 1 BOTH SIDES 16 DETAIL 1 BOTH SIDES 20 DETAIL 1 BOTH SIDES 27 DETAIL 3A BOTH SIDES 33*
DETAIL 6 BOTH SIDES OF SOUTH END DETAIL 10 NORTH; SIDE OF WEST END DETAIL 6
. SOUTH' SIDE OF WEST END 49 DETAIL 7 SOUTH SIDE-DETAIL 9 NORTH SIDE 50 DETAIL 1A SOUTH SIDE (CLIP ANGLES AT TOP ONLY)
DETAIL 4A NORTH SIDE 57 DETAIL 7 EAST-SIDE DETAIL 9 WEST SIDE 58 DETAIL 7 EAST SIDE DETAIL 9 WEST SIDE 59 DETAIL 7 EAST SIDE DETAIL 8 WEST SIDE 61 DETAIL 10 WEST SIDE DETAIL 6 EAST SIDE 62 DETAIL 8 WEST SIDE DETAIL 7 EAST SIDE 64 DETAIL 8 NORTH SIDE DETAIL 7 SOUTH SIDE 65 DETAIL 10 WEST SIDE DETAIL 6 EAST SIDE 69 DETAIL 7 EAST SIDE DETAIL 9 WEST SIDE 70 DETAIL 7 EAST SIDE DETAIL 9 WEST SIDE
- L-SHAPED WALL
n i
.' Attachment 1 to P-85069 Page 2 of 19 MASONRY BLOCK WALL. REINFORCING SCHEDULE
-WALL'#
CONSTRUCTION DETAIL SIDE OF WALL APPLIED 71 DETAIL 7 EAST SIDE DETAIL-8 WEST SIDE 173 ~
DETAIL 8 NORTH SIDE DETAIL 7:.
SOUTH SIDE' 85
' DETAIL 10 SOUTH SIDE DETAIL 7 NORTH SIDE 86 DETAIL 10 SOUTH SIDE DETAIL 7 NORTH SIDE 89 DETAIL 10 SOUTH SIDE DETAIL 7 NORTH SIDE 95 DETAIL 3 BOTH SIDES-98 DETAIL 3A.
EAST SIDE DETAIL 4 WEST SIDE 99 DETAIL 3A BOTH SIDES 100 DETAIL 7 NORTH SIDE DETAIL 10 SOUTH' SIDE 101 DETAIL 7 NORTH SIDE DETAIL 10-SOUTH SIDE 102 DETAIL 8 EAST SIDE DETAIL 7 WEST SIDE 104 DETAIL'3 EAST SIDE DETAIL IB WEST SIDE 105 DETAIL ^1A BOTH SIDES
=106 DETAIL 1A
.BOTH SIDES
ATTACHMfAM~ L.
PUBLICSERVICE COMPANY OF COLORADO pau 3 og jq FORT ST. VRAIN NUCLEAR GENERATING STATION l
CALCULATION WORKSHEET n
I po,neu n u sana CALCULATION NUMBER CALCULATION FOR PREPARED EY DATE REvtEW W3EY OATE CALC REV.
lPAGE OF DK7~A T L L.LA.
(pae sroa e nos n
)
Gn V
m WM s
s em W
M O
+
~
e a
,,g
"~
l l
l l
l rz2x3xYi I -
u --
W/ L th 40A/C. dXA i
g y
.8.-.
)
t l
l ANCNetS.
4y l
6k-3) suvA7TnM vrir W nfT~A TL 4 4-LA O f 7A TL BAR STRAP SZ2f i
2 "'y % "
LA 3" y %"
i l
s-l
AUAN#A# I PUBUC SERVIM COMPANY dF COLSRADO FORT ST. VRAIN NUCLEAR GENER ATING STATION PAf;g 4 op M
CALCULATION WORKSHEET n
i ro,mau.wmo8 CALCULATION NUMBER CALCULATION FOR PREPARED SY DATE REVIEWEO BY DATE CALC. REV.
lPAGE OF Df7~A T L 1R_
F45H kVFA2
- (7%f'hcoseu_rs, %i (p g h a g~ gt, % e
-~-
covuET of BL(Ck WML.
1(
)
GN l
O l-
+8 1
I I
I I
rz2x3x N g_,.
I -
W/ L 4A, CCAtC. EXA l
g y,m i
e e
e i
l ANe#NS.
%g Ok-3) lDXt/ATTnAl vrMW O FTA IL RAR STRAP SE2f iS 3" y %"
C r
ATTA C# MEN 7~.1 PUBUC SERVICE COMPANY OF COLORADO FORT ST. VRAIN NUCLEAR GENERATING STATION PA 6 7 f Of: M CALCULATION WORKSHEET Form 344 2M CALCULATION NUMBER CALCULATION FOR PREPARED BY DATE REVIEWGO SY DATE CALC.REV.
lPAGE OF nf 7A TL 242A e
muuBEmuu>
Wm l
um m en m
=m puu m eM C
h I
am me M
-M O
K
/
'~
r en srms@
t'L0"2 ELR1/A77/JM 1/rKV/
2_ e 2. A n
M rATL DFTA fL RAR STRAP STJ E 2.
2." y '/v "
2A J * )( 'h" s.
l l
AT m m rA/r 9 PUBUC SERVICE COMPANY OF COLORADO FORT ST. VRAIN NUCLEAR GENERATING STATION pA gg g pp j9 CALCULATIONWORKSHEET
(
Form 344-24400 CALCULAIlON NUMBER CALCULATlON FOR PREPARED sy DATI REVIEWED BY DATE CALC.MEV.
lPAGE OF DMTAl* L 2.1A cmcrirs a _.
hi i
i_
_ =;
i_
_1 i-es I
O
/
T
/
4 a__'
i, '
- /
i-ibs,5 v i o.
ha s) mse o~e t
<xwi r-wen M'S' " CLrt/A77/n/ vrMV/
DETAZL
. B A L 9 W _.(TZ E 3
3 x X "
3A 2
- x yy
C
ATTAulMfMT 4 PUBLIC SERVICE COMPANY OF COLORADO pjgg 7 gg j9 FORT ST. VRAIN NUCLEAR GENERATING STATION CALCULATION WORKSHEET O
r-2mm CALCULAIlON NUM8LR CALCULAIlON FOR PREPAREDBY DATE REVIEWEO 8Y DATE CALC.REV.
lPAGE OF nmn 4, WA I
I contre watt critMN Cl BE&
l nr. wnvo sorrm i
n en srtAr.s e 7-r-o" cc :
g
=
-.am
- M C
~~
me w -
~~
WALL nt'$N W/\\
CCAttfrE
\\
\\s J
, v - - n c,,<s z
m en-rz FLFvhYTryJ i/fEW 11'f*A T L NP <TTAD _W?K ll 2" X VY VA j "y VV 'I G
ATTMMMEN7 i PUBLIC SE" NICE COMPANY OF COLCRADO FORT ST. VRAIN NUCl. EAR GENERATING STATION FA4A [ M# /9 CALCULATION WORKSHEET Form m2m s
CALCULAllON FOH CALCULATION NUMBkR PREPARED BY DATE REVIEWEO 8Y OATE CALC.REV.
lPAGE OF O f 7~A T L K%
BAR STRAM @ 9'-0"c-c :
.r x
\\
f l
C l
/--FME OF BLMk wa tt riu.sp w/
ccWcesta DPANtCON Y
A vuctS TYA 1
& M1*f
-Y i
FLE1/A M N VERV)
Of TA TL ttAt orny gg L
(,
f 3 " r %
5A 2
- x Vr
A TTA(H/Vf f A/ T &
- # # # #9 PUBUC SERVICE COMPANY OF COLCRADO FORT ST. VRAIN NUCLEAR GENER ATING STATION CALCULATION WORKSHEET L
Form *.W4-24 4309 CALCULATION FOR CALCULAIlON NUMBER PREPARED SY DATE
\\
REVIEWEO 8Y DATE CALC.REV.
lPAGE OF nRYA TL C "YbW (b5hk A
x 1
i i
i I
w srws
\\
1 ca,srs 6 foc.c :
cown" oe.ww \\
l l
g l
I O
\\
1
(
i i
-h g
_^ "
't t ak.3) m rvArren tirrw DCTAll RAf c1AP KTH 3"Yff m
A TTA fHMEAIT1 PU LIC SERVICE COMPAN CF CILCRADO PArypfg np /4 l
FORT ST. VRAIN NUCLEAR GENER ATING STATION y
CALCULATION WORKSHEET
{
Form su-2uaos
~
CALCULAT40N FOR CALCULATION NUM8ER PREPARED BY DATE REVIEWEO BY DATE CALC.REV.
lPAGE OF DWAT1. 7
+8 6#*-3) f
- 8 f.u-3) a a
l l
V'covcfETE W N 3
cL cewMN i
i i
i g
l I
O N,-_-
ye Srws 90, l
$ 0" C-C 2 i
j
___T
/~~
j::
A I
... P.
av.5xyv w/z EA. CCActBTS EXPAN.STON ANCIMLS ELE 1/A7TDA/ VIEW l
DFTA IL BAR STRAP SEZE
~7 3 Y7[
U l
1
A7TM NMf W &
. pgm gyyymy FORT ST.VRAIN NUCLEAR GENERATING STATION PA AE
//op /7 CALCULATIONWORKSHEET
.,; {
p sm.asmas CALCULATION FOR CALCULATION NUMBER PneAREDSY OATE REVIEWE3 5Y OATE CALC.REV.
lPAGE 0F nf7"ATL A cavaers(cacm, wssxe) n,q,M m
N l
I f
I I
I I
I I
I i*
l lansaw '
I
\\
ANCMAS I
~
71MGW N
1 O
_y'-o" c, ear f
c I
[
/
3 I
I I
T l
]
(
ELA1/ATTA / 1/T*FM/
DETAT/_
BAE K7 RAP ET7F V
3 XY9 l
l
ATTWHIMENT A PUZLIC CERVICE C2MPANY CF CSLSRADO FORT ST. VR AIN NUCLEAR GENERATING STATION CALCULATION WORKSHEET O
CALCULATION FOR CALCULATION NUMBER PREPARED BY DATE REVIEWE0 BY DATE CALC.REV.
lPAGE OF DATATL 9
EXfANS12MI Afh XS a+
ksws) 77R 8 co^'
- d. l l
I I
I i
l l
r I
i i
i i
i 1
l
,a 1
I l
l l
[
]
O e
.l
_Mk STRAPS
~
l l
l @ y to"c-c _t I
i l
i
.i j
i i
t i
.. '\\
l
[
x (e _ A -
L
\\
\\COVCLET8 flVSM W nut l4 w/t E Ccht;etTE
[ f R * *A-FACE OF Bla;t WALL, FIFVATTOA/ VIA W DEYATI RAF CTDP SIZE C1 3
- v' Ey "
/
^
PUBLIC SERVICE COMPANY dF COLORADO FORT ST.VRAIN NUCLEAR GENERATING STATION PA M /3 of I4 CALCULATION WORKSHEET f
1 emwame CALCULADON NUMBER f
CALCULADON FOR PREPARED BY DATE REVIEWEO 8Y DATE CALC. REV.
lPAGE OF DETATL In l$H Y
m N
i i
i i
i i
i_
I I
i f
I I
I I
d
l A$
Trn6conee i
o I
I I
I I
y r
ik i
N O
N -
f y'-o~ ce
.srxm c f[
/
I.
i i
i
, i i
I I
I i
i i
i i
1 i
ceWCRETE Ceouwn, wra, cm)
ELx1/A77DAl 1/rMV/
OfrAIL BAf STEAP <T7A l
JD 3 " x Yu" I
b
=
=
ATTA&MMB/r L PUZLIC SERVICE COMPANY CF CELCRADO FA 4 E N o p /4 FORT ST. VRAIN NUCLEAR GENERATING STATION CALCULATION WORKSHEET O
CALCULATION FOR CALCULATION NUMBER PREPARED BY DATE REVIEWEO BY DATE CALC.REV.
lPAGE OF DCTArL ll grw or enearre ewr. sue N
kstret v2;t A!.
V 1-t t _ a.;_ _._ _t-;_
_ _ 2
- L. _ _ t. r I
t L.
l l
l 1
I I
I l
I l
O l
l l
1 l
l l
I, conas,,
JQ a m szw s e n s ~
em e
3"xh EM.sTEArs& 6o'cc f ruv> m vrrw
.!kW $
twitLTE SYP41$12W N%H02$
gyn.gt
-A
- MEASE5, I
y a
c mwty s
(#
l
_a
/'
l
~
,,m,y(, g,g Q
gyl'
- - a
- i_- rwnws r
_s
=. - -
KfrTTON A-A l
l
^
PUZUC SERVICE COMPANY CF COLSRADO FORT ST. VRAIN NUCLEAR GENERATING STATION PAGE g Op fy _
CALCULATION WORKSHEET Form 344 24430s CALCULATION NUMBER CALCULATION FOR PREPARED 8Y DATE REVIEWED BY DATE CALC.REV.
lPAGE OF DETArL T2-cwucerre mar. stas k
s n-
=
q
~
I i
'l i
t-1 i
I l
l^+
l l
l
~-
j
. O l
k l
l I
CONCRETS
\\
)~
m 2 *tN "
HAR STEAfS$ y 0' cc !.
ruvarma vrrw e
(CONC 2E7~6 E*PsWSION ANtMots COVCEETE St.AS
}
O/ANNEL g
S*W "rFSres
/l EMsTENCr STEfA s
/
FRAtw(,.
4
,s'l /.
t'Q.
sMAsrNEy' Blot.k N
m) y C
BAE srepp W TTON A-A
~
v 19
ATTACHMFNf L PU.~ LIC SERVICE COMPANY CF CELCRADO FORT ST. VR AIN NUCLEAR GENERATING STATION CALCULATION WORKSHEET O
CALCULATION FOR GALCULATION NUMBER PREPARED 8Y DATE REVIEWE0 BY DATE CALC.REV.
lPAGE OF DF7~ATL /3 J /3A Ae p-TOP OFC.t'AC/ZT2 SLAB.
I l
I I
i i
1 I
A l
e_
+
O
"" Ny
\\
\\
/
FfrvATTOA/ VZfW r> 4TA T/
RA 2 ff2A9 SF"7 f
/T 7_ ' x W' l
JTA 3*yYY virrn cwcurE CMF SLAB a-
'e MAT'l LESY
}
g
l
@ AN6/ES
, ASTM A-M
- ~
4
@ srfa wrE, WM A ~36 l
/
@ a wt M TE~ EWANsttW AArb0' 2 1
' ursrrue srea.
@ SM STW vMgf srgg MATE, 1
(',
/
Asr/1 A-%
i f'i v
e 6At SrtAP SFCl~ ION A-A
ATTACJ/AGENY 4 PUZLIC SERVICE COMPANY CF COL /l!RADO pgg g g jq FORT ST. VRAIN NUCLEAR GENER ATING STATION CALCULATION WORKSHEET Form 344-24-4309 CALCULATION NUMBER CALCULATION FOR PREPARED BY DATE REVIEWED E Y DATE CALC.REV.
lPAGE OF TYPYrA L RETNFORCENG OETATL AffvAfD DPfMENSS BAC STEAf Tff? BOfNM/S (THKV ECL( W
)
N l
a I
(
- I I\\
)
)l
/f
/
\\
\\
\\
)
\\
~
~wwr"s-C
/
\\
- l
\\
li I
l l [M
[
reem/4. v? O" + /*" rw J
l
'l NrTFS!
j Q SPLECE BARS MrM, CF TWO (,z.) SLXk WEDTMS 2)shrCE ECYN Szoss 0F LAr6r creprNSS {TWO d2.) Ct. Mces SLM'c LENGTH 3 h
&SA2 MACEN& V'-O" C-C VNL/S3 NOTEO. TELEEANC8 * $ lZ O BAE STCAEG CN FR'Nf'N/D WCk SCES Of WALL.
S) riotf srzs = W9, Et%8tE NW L
Sk
.O 4
s
' J U J-~
~-
ip e,
~
?
?+,
, -~
~
PAGE 19 or 19 SK-2
.. m:..
. c..
. : : L,;c.u;::: s,7 :,p;..
.r.',. "; iIi.i:
. f.'ui<>~*:
~
.. giu dp
'.n
~.i c
~ ~ ^
. > :-. e.
,,, : :w
, ~.
- .._~.. *@;-;4 jgip&;w ~f;Ci'%35 &@;*it:
. c..- ;; w 0,42 %7':'-?'
= ?
A?a+'G 9M SW(i
- ; ~,.
, te '.
st G
\\$h.
SAR STRAP SAR STRAP MEONRY SLOCK 1
s wr'U #
Nd a
1
.i 1
~
.wp x(^i f N SPuCE.
NT, N EEO'O '
1-f I
I 9
l THRu BOLT l
EI II
.s SECTION A-A l3A R STRA P SPL 'CC R DETAT L enum..
9
^
ATTA&HMEN1~A PAC-E M of M SK-3
_v-SOLT g THRU 3
CoueLE nut d
SOTM SOES cut BOLT frLC5H W/Nur + E" Salt STRAP %
MA5ONEY 4
SLOCK WALL TYP)
,,y A
5X 3X$ X l'-l/ AN4sLE CTYP) l s
(
\\
f l
l CONCRETE Floce, watt, og, COLUMN l
1 I
i 1
1 I i i I
I I
TWO (Z) CON (.
l l
l 1
EXPANSLON ANCH l
PER. At%LE l-J I_.
, if ANdi4cir. DETAIL
Attachm:nt 2 to P-85069 Page 1 of 2 NRC QUESTION 1-Provide details of modifications which will be made to the tops of turbine room walls #4, #6, #7, #8, and #9 in order to qualify these boundries as pinned joints.
~
PSC RESPONSE 1 Lateral restraints will be added to the tops of these walls as shown in Attachment 1, Pages 14 through 16. This work will be completed by August 2, 1985.
NRC QUESTION 2 Provide information on the number of unmortared-stacked block walls at FSV and their proximity to safety-related components.
PSC RESPONSE 2 PSC performed a field audit of all stacked block walls at FSV and identified a total of 13.
It was determined that 6 of the 13 could potentially impact safety related components if failure were to occur during a seismic event.. The largest of these 6 walls, #97, is to be removed completely since it is no longer required for j
shielding as orignially intended. The remaining.5 walls will be mortared in place, as _ required, to withstand the seismic forces.
This work will be completed by August 2,1985.
NRC QUESTION 3 Describe the acceptance criteria used in examining reactor building walls with cracked mortar joints between the masonry and concrete walls.
PSC RESPONSE 3 PSC believes that the full scale test performed. on wall #87 adequately demonstrates that the boundry between masonry and concrete is capable of resisting design seismic loads. At the time of testing, the boundries of wall #87 contained cracks similar to those currently found in other reactor building walls. However, to eliminate further discussion on this subject, PSC will extend all bar straps past the masonry-concrete boundry and anchor the straps to the concrete or install clip angles as shown in Attachment 1,
Pages 3 through 16. All strap extensions, clip angles and anchors will be designed to resist seismic loads.
l i
s
I to P-85069 Page 2 of 2 These modifications will affect walls number 3, 3a, 4, 6, 7, 8, 9, 11, 12, 27, 49, 62, 65, 85, 86, 89, 95, 98, 99, 100, 101, 104 and will be completed by August 2, 1985.
NRC QUESTION 4 Does a change notice deviation request exist which allows the deletion.of one bar strap on one side of a rectangular penetration through wall #12.
PSC RESPONSE 4 No deviation request exists which allows for the deletion of a bar
~
strap on one side of the penetration through wall #12.
A field audit was performed to examine all walls which have been reinforced to insure that all penetrations were properly framed out with bar straps.
No other walls were found to have discrepancies.
Therefore, PSC considers the missing strap on wall
- 12 to be an isolated incidence.
.The missing strap on the penetration in question will be installed as originally specified by August 2, 1985.
NRC QUESTION 5 Is bar strap design adequate to transfer shear load from masonry to bolts and prevent damage to masonry blocks from bolt bearing.
PSC RESPONSE 5 Calculations were performed te analyze the shear stress transferred from the masonry to the bolts and to analyze the compression stress in the masonry resulting fr?m ooit bearing. The results of these calculations demonstrate that actual masonry and steel stresses are within the allowables dictated by IEB-80-11 and that the strap design is adequate as installed. These calculations are available for review in our office.
I i-i k