Provides Alternative Acceptance Criteria for Determining Workability of Concrete During Period in Which 1-1/2 H Time Requirement Deleted from Bldg 10 Concrete Spec
ML20079H542
Person / Time
Site: Fort Saint Vrain 
Issue date: 01/06/1984
From: Brey H
PUBLIC SERVICE CO. OF COLORADO
To: Jay Collins
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION IV)
References
P-84004, TAC-42925, NUDOCS 8401230479
Download: ML20079H542 (2)


Text

.

p public Service Company @ OcBomdle I

tG '

2420 W. 26th Avenue, Suite 1000, Denver, CO 80211 0

January 6, 1984 Fort St. Vrain Unit No. 1 P.-84004

$ h f{ h

]

J m

Mr. John T. Collins jgggg g Regional Administrator l

U.S. Nuclear Regulatory Commission

-]

Region IV 611 Ryan Plaza Drive, Suite 1000 Arlington, Texas 76011

SUBJECT:

Fort St. Vrain Building 10 Concrete for Floor & Walls

REFERENCE:

NRC Letter dated December 7, 1983 from Mr. E. H. Johnson to Mr. O. R. Lee (G-83423)

Dear Mr. Collins:

This letter is in response to your request to state our alternative acceptance criteria for determining the workability of concrete during the period in which the 1-1/2 hour time requirement was deleted.

PSC RESPONSE When the 1-1/2 hour time limit was deleted from the Building 10 concrete specification, alternate acceptance criteria was specified.

That alternate was that no water could be added to increase the workability of the concrete.

The acceptance criteria for the concrete prior to the deletion of the 1-1/2 hour time limit was specified in the Building 10 Specification 75-J-02 as follows:

1)

The concrete slump shall be between 3 to 5 inches (ACI 309 defines this slump as plastic).

2)

The concrete air entrainment shall be between 3-1/2 to 6-1/2%.

/

$$0*$$oE0 ph

,'i!O 4 e

P-84004 Page 2

,,o 3)L The concrete temperature shall not be less than 40 degrees F nor exceed 90 degrees F.

4)

Discharge of concrete from trucks shall be completed within 90 minutes or before the truck drum has revolved 300 revolutions, whichever comes first.

This same acceptance criteria for the Building 10 concrete, with the exception of item number 4, was u:ed during the period in which the 1-1/2 ~ hour time requirement was deleted.

Therefore it is PSC's position that the workability of the concrete was not affected and sufficient acceptance criteria was used during the time period of the deletion of the 1-1/2 hour time requirement.

If you have any questions on.this item please contact Mr. J. R. Reesy (303) 571-8406.

Very truly yours,

$4Wt4%

H. L. Brey, Manager Nuclear Engineering Division HLB / RAG:pa w.m.

"