. _ _ _ _ _ _

IA3LE 3.4.3.2-1 REACTOR COOLANT SYSTEM PRESSURE ISOLATION VALVES l

i VALVE NUMBER VALVE DESCRIPTION 1.

RHR System Ell-F015A LPCI loop A Injection Isolation Valve Ell-F015B LPCI loop B Injection Isolation Valve E11-F050A LPCI loop A Injection Line Testable Check Valve E11-F050B t.PCI Loop B Injection Line Testable Check Valve i

Ell-F008 Shutdown Cooling RPV Suction Outboard Isolation Valve Ell-F009 Shutdown Cooling RPV Suction Inboard Isolation Valve E11-F608 shutdown Cooling Suction Isolation Valve 2.

Core Spray System E21-F005A Loop A Inboard Isolation Valve E21-F005B Loop B Inboard Isolation Valve E21-F006A Loop A Containment Check Valve E21-F006B Loop B Containment Check Valve 3.

High Pressure Coolant Injection System E41-F007 Pump Discharge Outboe d Isolation Valve E41-F006 Pump Discharge Inboard Isolation Valve 4.

Reactor Core Isolation Cooling System g-E51-F012 Pump Discharge Isolation Valve E51-F013 Pump Discharge to Feedwater Header Isolation Valve TABLE 3.4.3.2-2 REACTOR COOLANT SYSTEM INTERFACE VALVES LEAKAGE PRESSURE MONITORS ALARM SETPOINT VALVE NUMBER SYSTEM (osia)

Ell-F015A & B, E11-F050A & B RHR LPCI s 449 l

E11-F008, F009, F608 RHR Shutdown Cooling s 135 E21-F005A & B, E21-F006A & B Core Spray s 452 E41-F006, F007 HPCI s 71 E51-F012, F013 RCIC s 71 FERMI - UNIT 2 3/4 4-12 Amendment No. L4, P

DO O

O 41 P

PDR