ML20084U548

From kanterella
Jump to navigation Jump to search
Telecopy Ao:Seven HPCI Turbine Area High Temp Switches Tripped at Temps Exceeding Tech Spec Limit.Switches Recalibr
ML20084U548
Person / Time
Site: Quad Cities 
Issue date: 01/10/1975
From: Kalivianakis N
COMMONWEALTH EDISON CO.
To: James Keppler
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION III)
Shared Package
ML20084U525 List:
References
NJK-75-24, NUDOCS 8306290112
Download: ML20084U548 (1)


Text

-

ym i s>h )

b3 N m

Comm acalth Edis:n ICDg/

C-Quad-C: tics Generating Stat.on

-d Post Office Box 216 Cordova,!!bnois 61242 Telephone 303/654-2241 7

s (<e NJK-75-24 fx

p.,,,
.f..

[7 TELECOPY: Region til, ATTENTION:

Mr. C. Feierabend O]U/)g 2

January 10, 1975 C;

.A, 5

f/ '. _

.-l 4:..

./

NL

~~

J. Keppler, Regional Director Directorate of Regulatory Operations Region til U. S. Atomic Energy Commission 799 Roosevelt Road Glen Ellyn, IL 60137 REF ERENCE: QUAD-CITIES NUCLEAR POWER STATION, Unit 2 Docket No.

0-2 DPR-30 Appendix A, ions 1.0.A.2, 3.2.A, 6.6.B.I.A, Table 3.2.1.

Dear Mr. Keppler:

The purpose of this letter is to provide you with notification of an Abnormal Occurrence as required by Technical Specification 6.6.S.I.a within 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> of tha occurrence.

While doing routine Refueling Outage surveillance calibration of the HPCI Tur-bine Area High Temperature switches, seven of the sixteen switches tripped at temperatures in excess of the 1imiting condition for operation of f 200 F.

The switches were recalibrated and functior. ally tested with a new setpoint established at 185 F.

This occurrence was discussed by telephone with Mr. Feierabend of your of fice

'on January 9,1975. Further information will be.provided by Abnormal Occur-rence Report A0 50-265/75-4 which will be submitted within 10 days of the date of this occurrence.