k * #

~

4

..~

UNITED STATES t

NUCLEAR REGULATORY COMMISSION WASHINGTON, D. c. 20555

s. ~ /

JUL 0 61976 Karl R. Coller, Assistant Director for Operating Reactors, DDR BRUNSWICK UNIT 2 - COOLANT ACTIVITY LIMITS l

It has been brought to our attention that the present technical specifications for the Brunswick Unit 2 plant allow the equilibrium coolant activity to be as high as 6.2 pCi/ gram I-131 Equivalent and f

62.. pCi/ gram during 48-hour spike periods. We estimate that these limits may result in offsite doses in excess of 10 CFR Part 100 guidelines following a postulated main steam line failure outside containment (see Enclosure 1).

~

We recommend that the Brunswick Unit 2 coolant activity limits be changed to conform with the Standard Technical Specifications -(0.2 and 4.0 pCi/ gram of I-131 Equivalent, respectively) at the same time that Unit I reverts to the Standard Technical Specifications or at the next Unit 2 refueling outage, whichever comes first. These limits would result in appropriately low doses (5 rem and 100 rem) for a postulated steam line failure accident but should not represent a hardship to the facility since it has so far oper.ated below these limits (see Enclosure 2).

nA arrell G. Eisenhut, Assistant Director for Operational Technology

/

Division of Operating Reactors

Enclosures:

As stated i

cc:

V. Stello B. Grimes D. Bunch A. Schwencer C. Trammell E. Adensam W. Pasedag

/H.Fontecilla d 2--

8210200021 820917

' ~ ~

PDR FDIA MCINNIS82-389 PDR

,g.*

\\ s

\\

ENCLOSURE' 1 BRUNSWICK UNIT 2 - STEAM LINE FAILURE ACCIDENT Assumptions:

1.

140,000 lb of reactor coolant instantaneously released to the.

environment. (SRP 15.6.4)

~

8 X/Q = 7.4 x 10 sec/m at 914 meters for an eleva,ted release with fumigation (Regulatory Guide 1.5) and corrected for a wind speed of 0.5 m/sec.

Thyroid Doses:

1.

With Coolant Concentration

= 6.2 pCi/ gram I-131 Equivalent 150 rem 2.

With Coolant Conce,ntration

= 62, pCi/ gram I-131 Equivalent 1500 rem

~

e e

,1 9 -

ENCLOSURE 2 INFORMATION OBTAINED BY TELEPHONE CONVERSATION BE1VEEN C. TRAMMELL, ORPM, AND BRUNSWICK UNIT 2 PERSONNEL ON JULY 2,1976

~

Average operating I-131 Coolant Activity 10 pCi/cc June 22 Primary Coolant Activity measurement:

~0 I-131 2.17 x 10 pCi/cc I-133 1.79 x 10 ' pCi/cc June 24 Primary Coolant Activity measurement:

I-131 3.54 x 10 pCi/cc

-5 I-133 5.

x 10 pCi/cc O

4 e

e h

.