Forwards Info Re Fire Protec Prog Review.Details Review of Cables Passing Thru Component Cooling Water Pump Room.Due to Congestion of Cables,Licensee Plans to Remove B Train Auxiliary Feedwater Pump Room Cooler Cable
ML20064H815
Person / Time
Site: Farley  
Issue date: 12/13/1978
From: Clayton F
ALABAMA POWER CO.
To: Schwencer A
Office of Nuclear Reactor Regulation
References
TAC-8671, NUDOCS 7812270169
Download: ML20064H815 (1)


Text

_

A.aosma Nwer Corecary SCC Nortn 18m S:teet Rst Ceca Box 2641 Birmrgnam. Alacama 35291 Tetecnone 205 323 5341 F. L CLAYTON, JR.

S******

AlabamaPower me scurrem eiecircsystem December 13, 1978 Docket Mos. 50-34 5 -364 Director of Nuclear Reactor Regulation U. S. Nuclear Regulatory Commission f

Washington, D.C.

20555 Attn:

Mr. Albert Schwencer

Dear Mr. Schwencer:

RE: JOSEPH M. FARLEY NUCLEAR PIANT Fire Protection Program Review Alabama Power Company has conducted a detailed review of cables passing through the component cooling water pump room.

Et was determined that only one exists (power cable for auxiliary feedwater pump room cooler) where redun-dant cables for hot shutdown equipment run through the area with less than twenty foot separation that do not terminate in the room. While the subject cables do not carry power to the auxiliary feedwater pumps they are required for long term cooling of the pump rooms.

Due to the congestion of cables in this area, Alabama Power Company plans to remove the "B" train auxiliary feedwater pump room cooler cable from the room as discussed with Mr. Ed Reeves by phone on December 12, 1978.

It is our understanding that no other outstanding items exist in review of our fire protection program at Farley Nuclear Plant Units 1 and 2.

1 If you have questions, please advise.

Yours very truly, F. L. Clayton, Jr.