.s-

.a l

VERMONT YANKEE NUCLEAR POWER STATION MONTliLY STATISTICAL REPORT 81-11 FOR TiiE MONTil 0F NOVEMBER,1981 8112170099 81120@

PDR ADOCK 05000271 R

PDR i:-

i f

~

[

OPERATING DATA REPORT 50-271-DOCKET NO, DATE 811209

' COMPLETED BY F.J.

Burger TELEPHONE'-(802)257-7711 Ext. 137 OPERATING STATUS' Notes il.' Unit)Name:

Vermont Yankee

2; Reporting ~ Period: November

!3. Licensed Thermal Power (MWt):

1593' i4. Nameplate Rating (Gross MWe):

540 l5. Design Electrical Rating (Net MWe):514(oc) 504(cc) l6. Maximum Dependable Capacity (Gross MWe):

535-l7. Maximum Dependable Capacity (Net MWe):

504 l8. If Changes Occur in Capacity Ratings (Items Number 3 Through 7)Since Last Report, Give Reasons:

9. Pow:r Level to Which Restricted.If Any(Net MWe):
0. Renons For Restrictions, If Any:

This Month Yr-to-Date

. Cumulative

1. Hours In Reporting Period 720.00 8016.00

)2.NumbsrOfHoursReactorWasCritical 0.00 6890.95 64,426.73

)3.R;actorReserveShutdownHours 0.00 0.00 0.00 14.HoursGeneratorOn-Line 0.00 6832.88 62.434.46

)S.UnitReserveShutdownHours 0.00 0.00 0.00

)6. Gro::n Thermal Energy Generated (MWH) 0.00 10.506.102.00 89.109.619.00 0.00 3,491,969.00 29,604,816.00

)7.GrossElectricalEnergyGenerated(MWH)

$8.NatE1cetrical-EnergyGenerated(MWH) 0.00 3,312,676.00 2R,50.255.00 f9.UnitServiceFactor 0.00 85.24 77.47

)0 Unit Availability Factor 0.00 85.24

77. 47 fl.UnitCapacityFactor(UsingMDCNet) 0.00 82.0D 60.0R

)2. Unit Capacity Factor (Using DER Net) 0.0n 80.40 67.74

)3.UnitForcedOutageRate 0.00 1 47 6.71

)4.ShutdownsScheduledOverNext6 Months (Typa,Date,andDurationofEach):

I5.-IfShutDownAtEndOfReportPeriod,EstimatedDateofStartup:

12/1/81

)6.UnitoInTestStatus(PriortoCommercialOperation):

Forecast Achieved INITIAL CRITICALITY INITIAL ELECTRICITY COMMERCIAL OPERATION

w,

- ;a:,..,

J AVERAGE DAILI UNIT: POWER LEVEL -

DOCEET:NO.- ~ 50--271 Vermont Yankee UNIT 811209 DATE COMPLETED BY-F.J. Burner:

' TELEPHONE ~

(802)257-7711 Ext. 137f

~

. MONTH'

. November

" DAY ~ AVERAGE DAILY' POWER LEVEL

, DAY _ AVERAGE DAILY POWER LEVEL

-(MWe-Net)

(MWe-Net) 1.

-0 17.

n 2.

0-18.

n 3.

0-19.

0~

i 4.

0.-

20.

~0 i

S.

0 21.

0

-l 6.

0 22.

0-l l

7.

0 23.

0 8.

0

24. -

o

9.

0 25.

o 10.

0 26.

n i

11.

0-27.

n i

L 12.

0 28.

n 13.

0 29s n-14.

0 30.

n L

15.

0 31.

16.

O INSTRUCTIONS:

On this format, list the average daily unit-power level in MWe-Net for each day in the reporting month. Con.pute to. the nearest whole megawatt.

l-s

UNIT SliUTDOWNS AND POWER REDUCTIONS DOCKET NO 50-271 UNIT NAME Vermont Yankee REPORT MONTil November COMPLETE Lurger-TELEP110NE (502)257-7711 Ext. 137

'89 Y$$

Cause & Corrective m

No.

Date y

gg g

gu pu go.

Action to License H

p rt#

0 O

g g

u 8

81-19 811016 S

720 C

N/A N/A ZZ ZZ Refueling in progress (cont.)

PT F: Forced Reason:

Method:

Exhibit G. Instructions S: Scheduled A-Equipment Failure (Explain) 1-Manual for Preparation of Data B-Maintenance or Test 2-Manual Scram Entry Sheets for. Licensee C-Refueling 3-Automatic. Scram Event Report (LER) File D-Regulatory Restriction 4-Other (Explain)

(NUREG 0161)

E-Operator Training & License Examination-F-Administrative Exhibit I - - Same Source G-Operational Error (Explain)

II-Other (Explain) 7/80

uML&sf%ir. ;.,

e UNIT Varm nt.Yrnkca DATE.

811209 COMPLETED BY F.J. Burner TELEP110NE (802)257-771l' Ext.'137 SAFETY RELATED MAINTENANCE page 1 of 10 NATURE OF MALFUNCTION ER OR OWAGE EQUIPMENT MAINTENANCE NUMBER CAUSE RESULT CORRECTIVE-ACTION RWCU PCV'12-55 Corrective N/A Normal Wear Seat Leakage Cleaned and Lapped Seat MR 80-0221 MR 81-0550 RiiR Service Water Pump Preventive N/A N/A N/A Removed' Strainers.

Tcmporary Suction MR 80-0857 Strainers RllR Service Water Pumps Preventive N/A N/A N/A Disassembled, Cleaned, Suction and Discharge MR 80-1244

& Inspected Valves Valves "B" Diesel Generator Corrective N/A Vibration Leakage at.

Repaired As Necessary Standby Lube Oil lleater MR 80-1482 Threaded Joint Drain Service Water Instrument Corrective N/A Nermal Operation Leakage Cleaned & Flushed Valves

. Root Valves PI 70-104-MR 81-0042 34/55 Channel "B" IRM/APRM Corrective N/A Unknown Faulty Operation Replaced Parts'As Salect Switch MR 81-0178 Necessary Main' Steam Line Tunnel Corrective N/A Normal Wear Relay Noisey Rebuilt Relay Texperature Relay MR 81-0218 16 K2A j

A

lffQial'DA DTENB

]

UNIT VJrmont Y: kee DATE 811209 COMPLETED BY F.J. Burger TELEPHONE (802)257-7711 Ext. 137 SAFETY RELATED MAINTENANCE page 2 of 10 NATURE OF MALFUNCTION ER OR O WACE EQUIPMENT MAINTENANCE NUMBER CAUSE RESULT CORRECTIVE ACTION KWCU Valve V12-22A Corrective N/A Normal Wear Leakege Replaced Valve MR 81-0247 MR 81-0268 MR 81-0611 Rractor Recirc Pump Preventive N/A Normal Wear Decreasing Replaced Seal P18-1A Mechanical Seal MR 81-0454 2nd Stage Pres-sure Manifold Bypass and Corrective N/A Normal Operation Leakage Replaced Parte As Isolation Valves for MR 81-0499 Necessary Main Steam liigh Flow Switch / Indicator DPIS 2-118D RWCU Valve V12-24A Corrective N/A Normal Operation Leakage Replaced Valve MR 81-0632 RilR Valve V10-46A Preventive N/A N/A N/A Cleaned and Repacked MR 81-0659 Reactor Level Indicators Corrective N/A Unknown Out of Cali-Recalibrated 2-3-57 B and 72 B MR 81-0734 bration S'rvice Water Pump Co rrec.t ive N/A Normal Operation Shaft Needs Realigned Shaft P7-1B MR 81-0800 Alignment I

3

DOCKET NO, S Q-g lL,__

j

' l UNIT V rmont Y'nk'~

DATE 811209 COMPLETED BY F.J. Burger TELEPHONE (802)257-7711 Ext. 137 SAFETY RELATED MAINTENANCE oage 3 of 10 NATURE OF MAIJUNCTION EQUIPMENT MAINTENANCE NUMBER CAUSE RESULT CORRECTIVE ACTION IICU 34-23 Valve Corrective N/A Normal Wear I.eakage Replaced Valve 13-111 MR 81-0881 Shock Suppressors Corrective N/A Unknowr.

Low Fluid Level Rebuilt Suopressor C5-11-86 A/B MR 81-0929 Service Water Valve Corrective N/A Normal Wear Leakage Repaired by Welding V70-22 C MR 81-0996 Rl!R Service Water Pump Corrective N/A Normal Wear Oil Leakage Repaireo As Necessary P8-1D MR 81-1014 Prnr::ure Transmitters Corrective N/A Unknown Out of Cali-Recalibrated 1

PT 2-3-56 A/B MR 81-1024 bration RWCU Valve V12-27B Corrective N/A Normal Wear Leakage Replaced Valve MR 81-1056 l

MSIV 80A Position Corrective N/A Normal Operation Out of Adjust-Reset Limit Switches i

Indication Limit Switched MR 81-1080 RWCU Piping In RWCU Pump Preventive N/A Possible IGSCC N/A Replaced Piping, and lleat Exchanger Rooms MR 81-1090 Main Steam Radiation

! Corrective N/A Normal Wear Scratchy Oper-Replaced Potentiometer Monitor 17-251 D Test

! MR 81-1097 ation Pot":ntiometer I

l

mm, wm

~.

UNIT V1rmont Yank:;

DATE 811209 COMPLETED BY F.J. Burger TELEPHONE (802)257-7711 Ext, 137 SAFETY RELATED MAINTENANCE page 4 of lu NATURE OF MALFUNCTION ER OR OUTAGE EQUIPMENT MAINTENANCE NUMBER CAUSE RESULT CORRECTIVE ACTION MSIV V2-80C Corrective LER Unkrown Valve Would Not Performed Scheduled MR 81-1140 81-27/3L Shut Preventive Maintenance On Valve Acutator "D"

IRM Corrective N/A Wora Parts Irratic Readings Replaced Parts As MR 81-1142 Necessary R'IR lleat Exchanger, Corrective N/A Dirt, Corrosion Valve Inoperable Cleaned and Lapped E-14-1A, Service Water MR 81-1149 Valve Seat Ralief Valve V70-80A RWCU Valve V12-15 Corrective LER Cracked Disc Seat Failed Leak Test Replaced Parts as MR 81-1153 81-32/3L Necessary St.ock Suppressor Corrective N/A Unknown Fluid Leakage Rebuilt Suppressor MS-35 MR 81-1159 Shock Suppressor Corrective N/A Unknown Fluid Leakage Rebuilt Suppressor RR-12 MR 81-1160 MSIV's V2-86A-D Preventive N/A N/A N/A Repacked Valves MR 81-1181 l

MR 81-0666 i

i e

hMLisf LJ1.

N V rmont - Y: :kc:2.

UNIT DATE 811209 COMPLETED BY F.J. Burger TELEP110NE (802)257-7711 Ext. 137 SAFETY RELATED MAINTENANCE page 5 of 10 NATURE OF MALFUNCTION ER OR OUTACE EQUIPMENT MAINTENANCE NUMBER CAUSE RESULT CORRECTIVE ACTION Core Spray, Service Corrective N/A Normal Operation Loose Nuts, Repaired As Necessary W ter, and CRD Piping MR 81-1192 ilangers Out of Hangers Alignment RWCU "B" Demineralizer Corrective N/A Dirt Leakage Cleaned and Lapped Seat Relief Valve V12-24B MR 81-1207 Service Water Pump Preventive N/A N/A N/A Overhauled Pump P7-1D MR 81-1210 R rctor Recire Pump Preventive N/A Normal Wear Decreasing 2nd Replaced Seal P18-1B Mechanical Seal MR 81-1212 Stage Pressure Various Feedwater Corrective N/A Normal Operation Loose Nuts Repaired as Necessary and CRD llangers MR 81-1213 RilR Valve V10-65B Corrective N/A Normal Wear Packing Leak Repacked Valve MR 81-1214 t

t

1;ut t.L t

..u ;

e.- g UNIT V:rmc-t Ycnke-DATE 811209 COMPLETED BY F.J. Burger TELEP110NE (802)257-7711 Ext. 137 SAFETY RELATED MAINTENANCE page 6 of 10 NATURE OF MALFUNCTION ER OR OUTAGE EQUIPMENT MAINTENANCE NUMBER CAUSE RESULT CORRECTIVE ACTION RWCU Valve V12-68 Corrective N/A Clutch Out Of Erratic Operation Adjusted Clutch Valve Operator MR 81-1222 Adjustment "A" Core Spray Safe End-

. Corrective N/A Construction NDT Surface Removed by Grinding to-R ducer Weld MR 81-1225 Indications RWCU PCV12-55 Operator Corrective N/A Failed Parts Not Operating Replaced Solenoid MR 81-1235 RilR Piping llanger Corrective-N/A Normal Operation Inadequate Thread Installed Longer Bolts 11D-188D MR 81-1238 Engagement R11R Service Water Pump Corrective N/A Normal Wear Seal Leak?ge Replaced Seal P8-1B MR 81-J 245 Main Steam Piping licngers Corrective N/A Normal Operation Loose Bolts Tightened Bolting MS-2,13,30 l

MR 81-1250 Reactor Vessel Stabilizer Corrective N/A Normal Operation Loose Screws Reset Gap and Tig*itened Brackets MR 81-1253 Screws Toru / Reactor Building Corrective N/A Failed Solenoid Actuator Failed Replaced Solenoid Vacuum Breaker V16-19-11A;i MR 81-1254 Shut MSIV V2-86B Actuator Preventive N/A N/A N/A Rebuilt Actuator MR 81-1258 I

.m.

UNIT V rmoat_Jankee DATE 611209 COMPLETED BY F.J. Burcer TELEP110NE (802)257-7711 Ext. 137 SAF}gY RELATED MAINTENANCE page 7 of 10 NATURE OF MALFUNCTION ER OR OUTAGE EQUIPMENT MAINTENANCE NUMBER CAUSE RESULT CORRECTIVE ACTION UPSA/B Batteries Preventive N/A N/A N/A Replaced Batteries MR 81-1259 Prinary Containment Corrective Dirt Failed Leak Cleaned and Lapped Attosphere Control Valves MR 81-1264 N/A Test Seats V16-19-51/52 Core Spray Piping llanger Corrective N/A Construction llanger Out of Realigned CS-IID-54B MR 81-1265 Alignment RPS Analog Trip System Preventive N/A N/A N/A Repisced With 6 Amp 10 Amp Power Supplies MR 81-1266 Power Supplies (EDCR 79-02, ECN-7)

CRP 9-15, PCIS and RPS Preventive N/A N/A N/A Replaced Relay Coils Channal A-1 Relays MR 81-1269 "B" Main Steam Line Corrective N/A Failed Parts Failed Down Replaced Parts As Radiation Monitor l MR 81-1274 Scale Necessary i

Shock Suppressor l Corrective N/A Unknown Low Fluid Rebuilt Suppressor CU-2 MR 81-1275 Level Shock Suppresser Corrective N/A Unknown Low Fluid Rebuilt Suppressor FW-3 i MR 81-1276 Level i

Liquid Radwaste Carrective N/A Normal Wear Packing Leaks Repacked Valves i

Valves V20-94/95 MR 81-1282

UNIT V rmont Y a k:

DATE 811209 COMPLETED BY F.J. Burger TELEP110NE (802)257-7711 Ext. 137 SAFETY RELATED MAINTENANCE page 8 of 10 NATUPE OF MALFUNCTION ER OR OUTACE EQUIPMENT MAINTENANCE NUMBER CAUSE RESULT CORRECTIVE ACTION RilR Piping llangers11-191, Corrective N/A Normal Operation Set Point Drift Reset flangers llD87, IID87D MR 81-1292 Liquid Radwaste talves Corrective N/A Normal Wear Packing Leaks V20-82/83 MR 81-1293 Repacked Valves RilR Service Water Valve Corrective N/A Normal Wear Back Leakage Replaced Parts As V70-40B MR 81-1295 Necessary PCIS Relay 16A-K6C Corrective N/A Normal Wear Coil Burned Out Replaced Parts As MR 81-1302 Necessary S rvice Water Piping Corrective N/A Construction Inadequate Thread Installed Longer Bolts llanger 11-188 MR 81-1303 Engagement RWCU Valve V12-68 Corrective LER Worn Parts Seat Leakage Replaced Parts As l

MR 81-1304 81-32/3L Necessary and Changed Operating Conditions MS1V V2-80C Preventive N/A N/A N/A Overhauled Valve MR 81-1308 Operator MS1V's V-80A-D Preventive N/A N/A N/A Repacked Valves MR 81-1309 i

i Corrective N/A Worn Packing Leakage Adjusted Packing Srrvice Water Pump P7-1A MR 81-1314 i

uuth t.1 I.u,

su

A liNIT V rmont Y nkee DATE 811209 COMPLETED BY F.J.

Burger TELEP110NE (802)257-7711 Ext. 137 SAFETY RELATED MAINTENANCE pane 9 of 10 NATURE OF MALFUNCTION R OR OUTACE EQUIPMENT MAINTENANCE NIIMBER CAUSE RESULT CORRECTIVE ACTION "B" Diesel Generator Corrective N/A Normal Operation liigh AP Changed Filter Fual Oil Filter MR 81-1315 Control Rod Drive Corrective N/A Corrosion Corroded U Bolt Replaced U Bolt llanger 11-9 MR 81-1325 R: actor Valve V2-54A Corrective N/A Normal Wear Failed Limitorqu(

Replaced Heater Motor Operator MR 81-1326 Heater Spara Clapper for RilR Corrective N/A Normal Operation Seating Surface Repaired by Welding Valvrs V10-46 A/B MR 81-1323 Worn Control Rod 34-27 Corrective N/A Misaligned Fuel Stuck Rod Realigned Casting, MR 81-1330 Support Casting Replaced Control Rod and Drive RllR Piping llanger j

Corrective N/A Resetting of Hanger ilD194C Reset ilD194C llD194C MR 81-1337 Ilanger llD-87 Out of Adjust-3 ment i

RCIC Valve V13-22 l

Corrective N/A

'*orn Packing Leakage Repacked Valve j

MR 81-1353 F :dwater Valves I

Corrective i

N/A Worn Packing Leakage Repacked Valves V2-29 A/B MR 81-1360

DOCKEf NO, 3u-isi UNIT VeregnLYankee DATE 811209 COMPLETED BY F.J. Burger (802)257-7711 Ext. 137 TELEP110NE SAFETY RELATED MAINTENANCE page 10 of 10 NATURE OF MALFUNCTION ER OR OUTAGF EQUIPMENT MAINTENANCE NUMBER CAUSE RESULT CORRECTIVE ACTION PCIC Relay 16A-K24 Corrective N/A Worn Parts Will Not Stay Rebuilt Relay MR 81-1371 Closed Shock Suppressor MS-3 Corrective N/A Unknown Gummy Substance Rebuilt Suppressor MR 81-1394 on Piston Rod llPCI Turbine Lube 011 Corrective N/A Normal Operation Oil Leaks at Repaired as Necessary Syrtem MR 81-1397 Tubing Connect-ion MSIV V2-86A Actuator Corrective N/A Unknown Air Leak At Replaced "0" Ring Pilot Valve MR 81-1398 Tubing Connection Srrvice Water Pump P7-1A Corrective N/A Worn Packing Leakage Repacked Pump MR 81-1401 S rvice Water Pump P7-1B j Corrective N/A Worn Packing Leakage Adjusted Packing l

MR 81-1402 I

I i

i

~~

r _..,

, ; y;,;,-;;

s; c.;-.

t

<.g, DOCKET NO. _50-271

~' '

UNIT Vermont Yankee

'DATEL 811209

~ COMPLETED BY-F.J.' Burger-

- TELEPHONE:

(802)257-7711 Ext. 137; REPORT MONTH November'

SUMMARY

OF OPERATING EXPERIENCES During.the' reporting period the' plant was shut down-

'for refueling and maintenance.

z.

[

u-.

~.:

.,