Text
-
i
)
BEFORE THE UNITED STATES NUCLEAR REGULATORY COMMISSION 1
l In the Matter of Docket No. 50-388 i
PENNSYLVANIA POWER &
LIGHT COMPANY
)
i PROPOSED AMENDMENT No.117 FACILITY OPERATING LICENSE NO. NPF-22 l
SUSQUEHANNA STEAM ELECTRIC STATION UNIT NO. 2 l
Licensee, Pennsylvania Power & Light Company, hereby files proposed Amendment No.117 i
to its Facility Operating License No. NPF-22 dated March 23, 1984.
]
This amendment contains a revision to the Susquehanna SES Unit 2 Technical Specifications.
j PENNSYLVANIA POWER & LIGHT COMPANY BY:
\\
l r\\'
t&
G. T. Jone's Vice Pre ent - Nuclear Engineering j
Sworn to and spbscribed before me this // of '/) wr4u 1993.
i
~
7
,4
/ /,<
,, f / /N Ye tk -
I otary p NOTARAL SEAL i'
"o M ucN!. N:::an Pubbe u m e. Lemg, cc e s
' ;;; n on Ee -s s..no n ms
~
9312090005 933124 3
PDR ADOCK 05000388 9
P PDR
l ATTACHMENT 1 TO PLA-4055 i
i TABLE 1 TEST CONDITIONS AND TEST PLATEAUS TEST CONDITION UPRAlf POWER LfVEL CORE FLOW TEST PLAllAU A
< 90%
3 A
B 89 - 90 %
3 A
f C'
95 - 96 %
3 B
i D
97 - 98 %
3 C
E 99-100%
3 D
l N - This test is not required to be performed for power uprate NOTES:
1 - The old 100% power level (3293 MWt) is in this test condition at = 95.7%
power.
2-100% power level - 3441 MWt.
3-Any flow within the safe operating region of the Power / Flow Map that will produce the required power level.
r i
P i
t i
?
t I
i t
3
i ATTACHMENT 1 TO PLA-4055 i
TABLE 2 FSAR CHAPTER 14 TESTS I
IIST CONDlilONS' TEST CAltGORIES A
B C
D E
N l
1 Chemical and Radiochemical X
X 2 Radiation Measurements X
X 3 Fuel Loading X
i 4 Full Core Shutdown Margin X
5 Control Rod Drive X
6 SRM/ Cont Rod Seq O
X 7 Reactor Water Cleanup X
j t
t 9 Water level Measurements X
1 10 SR.WIRM/ Cont Rod Seq O
X i
11 LPRM Calibration X
X X
i I
12 APRM Calibration X
X X
X X
I 13 Process Computer X
14 RCIC X.
X f
15 HPCI X
X 16 Selected Process Temperatures X-17 System Expansion X
18 TIP Uncertainty X
j
{
19 Core Performance X
X X
X 20 Steam Production X
21 Core Power-Void Mode Response X
1 22 Pressure Regulator X
X X
X
~.-
.. _. _ _ ~.
ATTACHMENT 1 TO PLA-4055 l
l
)
TEST CONDillONS' TEST CATEGORifS l'
A B
C D
[
N 23 Feedwater X
X X
X X
24 Turbine Valve Surveillance.
X X
X X-25 Main Steam isolation Valves X
26' Relief Valves X-27 TSV Trip & Gen load Rejection X
1 i
i 28 Shutdown From Outside CR X-l 29 Recirculation Flow Control X
- 30. Recirculation System X l-31 Loss of T-G & Offsite Power X
32 Cont Atm & Steam Tunnel Cooling X
~X 33 Piping Steady State Vibration X
34 Rod Sequence Exchange X
l 35 Recirc System flow Calibratior X
j i
36 Cooling' Water Systems
-X J
37 Gaseous Radwaste X
39 Piping Vib During Dynamic Trans X
NOTI 5:
Tests 38 and 40 were merged into Tests 17 and 33 in the original startup test program.
Refer to Table 1 for definition of Test Conditions.
X Indicates test is to be performed in indicated test condition with the exception that an X on column N indicates this test is not a required test for power uprate.
O Indicates that test is performed during each startup following a refueling outage.
1 l
n
. ~.
ATTACHMENT 1 TO PLA-4055 TABLE 3 ADDITIONAL TESTING REQUIRED BY LICENSE AMENDMENT 1E51 CONDITION 5' TEST CATEGORIES A
B C
D E
N 2
42 I&C Surveillances X
i 43 Steady State Data Collection X
X X
X i
TABLE 4 1
TECHNICAL SPECiflCATION SETPOINT CHANGE l
1EST CONDlilON5' d
IEST CATEGORIES A
B C
D E
N 45 Main Steam Line High flow X
46 Main Steam Line High Tunnel Temp
.X 47 Recirc Single loop Operation X
TABLE 5 FULL POWER SETPOINT ADJUSTMENTS TEST CONDillON5' TEST CATEGORif5 A
B C
D E
N 48 Loose Parts Monitor X
X 49 Main Steam Line Rad Monitor X
X 50 Core Spray Leak Detection X
X TABLE 6 POWER UPRATE PERFORMANCE TESTS I
TEST CONDITION 5' 115i CATEGORIE5 A
B C
D E
N 60 Performance Test X
. _ _ _ =
1 i
l ATTACHMENT 1 TO PLA-4055 j
i NOMS:
Test Numbers do not correspond to any Chapter 14 Tests and are not sequential.
t Refer to Table 1 for definition of Test Conditions.
2 Prior to the plant condition for which they are required to be operable.
i t
i L
)
i i
I i
T f
-. j e
t i
i n
F 5
k I
h i
i I
[
I
i ATTACHMENT 1 TO PLA-4055 u
l t
TABLE 7
SUMMARY
OF SUSQUEHANNA POWER-UPRATE ATWS RESULTS r
PIAK RPV PRES 5URE P[AK SUPPRESSION PEAK CLADDING 1RAN51[ NT (PSIG)
POOL TEMP, ( f)
TEMPERATURE (*f)
MSIV Closure 1317 178.9 1463 Pressure Regulator 1283 178.4 1458
'l Failure - Maximum Demand I
Inadvertent Open 1069*
147.4 Relief Valve Loss of Feedwater 1069*
90.0*
l 1
feedwater Controller 1232 98.1 1299 failure-Maximum Demand Turbine Trip 1217 114.1 loss of Normal AC 1234 161.7 Power
- No increase.
l l
1 1
l
'I l
l i