ML20056F028

From kanterella
Jump to navigation Jump to search
Rev 20 to Annunciator Response (AR) AR-403, PSA H Annunciator Response
ML20056F028
Person / Time
Site: Crystal River Duke Energy icon.png
Issue date: 08/06/1993
From: Gallion E
FLORIDA POWER CORP.
To:
References
AR-403, NUDOCS 9308250436
Download: ML20056F028 (198)


Text

.

Rev. 20 08/03/93 Effective Date 8988

_ == - - -

"' " ~~ '

' Document SectWA \

L

{ y.3 p o s g A T I O N O N L g' l r C. R. Nucisar =

i ANNUNCIATOR RESPONSE ,

AR-403 t.

FLORIDA POWER CORPORATION CRYSTAL RIVER UNIT 3 PSA H ANNUNCIATOR RESPONSE THIS PROCEDURE ADDRESSES SAFETY RELATED COMPONENTS 4

t APPROVED BY: Inter re /a (on ntact L

// .

DATE:

bd-N -

INTERPRETATION CONTACT: Manager Nuclear Plant Operations

[GGC h 9308250436 930806 *~- b t PDR ADOCK 05000302 U-

1 TABLE OF CONTENTS SECTION gagg 1.0 PURPOSE . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1

, 10 REFERENCES .......................... 1 2.1 INPLENENTING REFERENCES . . . . . . . . . . . . . . . 1 2.2 DEVELOPNENTAL REFERENCES .............. 1 3.0 PERSONNEL INDOCTRINATION ................... 2 4.0 INSTRUCTIONS ......................... 2 5.0 FOLLOW-UP ACTIONS . . . . . . . . . . . . . . . . . . . . . . . 2 I

ENCLOSURE 1 Annunciator Response ..................... 3 i

f O

AR-403 Rev. 20 Page 1

1.0 PURPOSE 1.1 Establish a reference document for each Annunciator Window on the PSA-Z Lampbox.

1.2 Establish operator actions for valid Annunciator alarms on the PSA-Z -

Lampbox.

1.3 Establish a reference to other procedures which address operator actions for valid Annunciator alarms on the PSA-Z Lampbox.

2.0 REFERENCES

2.1 IMPLEMENTING REFERENCES i

l 2.1.1 E0P, Emergency Operating Procedure 2.1.2 AP-250, Radiation Monitor Actuation 2.1.3 AP-1050, Flooding 2.1.4 CP-138, Secondary Water Chemistry Guidelines l 2.1.5 OP-103B, Heat-Up Cooldown Curves l 2.1.6 SP-146, EFIC Monthly Functional Test l 2.1.7 OP-302, RC Pump Operation l 2.1.8 OP-301, Operation Of The Reactor Coolant System l 2.1.9 OP-416, Domestic Water Supply System l 2.1.10 AP-470, Loss of Instrument Air '

e 2.2 DEVELOPMENTAL REFERENCES 2.2.1 INP0 90-021, Good Practice OP-217, Alarm Response Procedures 2.2.2 Annunciator Window Engraving Drawing E-224-048 O

AR-403 Rev. 20 Page 1

3.0 PERSONNEL INDOCTRINATION

%.),

3.1 The Annunciator System is powered from VBDP-5 Breaker 28.

4.0 INSTRUCTIONS 4.1 Respond to alarms on the PSA-Z Lampbor as indicated on Enclosure 1, Annunciator Response.

5.0 FOLLOW-UP A.CTJ_QNJ None.

O) c 6

i O

AR-403 Rev. 20- Page 2

ENCLOSURE 1 O (Page 1 of 194)

PSA-Z ANNUNCIATOR RESPONSE PSA-Z-01-01 H-01-01 GAMMA RADIATION HIGH EVENT POINT 1748 ,

INDICATED CONDITION:

o RM-G1 RADIATION LEVEL EXCEEDS HIGH SETPOINT.

REOUNDANT INDICATION WHICH WILL VERIFY ALARM:

o RM-G1 INDICATION AT RADIATION MONITORING PANEL.

o RM-G1 INDICATION AT DETECTOR.

o RM-G1 WARNING LIGHT.

o RM-G1 WARNING HORN.

o SPDS ALPHA PAGE.

OPERATOR ACTIONS FOR A VALID ALARM:

o INVESTIGATE CAUSE OF HIGH RADIATION.

o NOTIFY HEALTH PHYSICS TO MONITOR AFFECTED AREA (S). ,

o OBSERVE AREA MONITORS / RECORDERS FOR TREND INFORMATION.

DISCUSSION:

RM-G1 MONITORS THE CONTROL ROOM. THE DETECTOR IS ON THE BACK WALL NEXT TO THE ES RELAY ACTUATION CABINETS. THE REDAS SYSTEM MAY ALSO BE USED TO OBSERVE TREND INFORMATION.

REFERENCES:

DRAWING 208-049-RM-22 SENSING ELEMENT: RADIATION MONITORING PANEL AR-403 Rev. 20 Page 3

A ENCLOSURE 1

[ (Page 2 of 194)

PSA-Z ANNUNCIATOR RESPONSE PSA-Z-01-01 H-01-01 GAMMA RADIATION HIGH EVENT POINT 1750 ,

INDICATED CONDITION:

o RM-G2 RADIATION LEVEL EXCEEDS HIGH SETPOINT.

( REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o RM-G2 INDICATION AT RADIATION MONITORING PANEL.

o SPDS ALPHA PAGE.

OPERATOR ACTIONS FOR A VALID ALARM:

o INVESTIGATE CAUSE OF HIGH RADIATION.

o NOTIFY HEALTH PHYSICS TO MONITOR AFFECTED AREA (S). ,

o 0BSERVE AREA MONITORS / RECORDERS FOR TREND INFORMATION.

DISCUSSION:

RM-G2 MONITORS THE CHEMICAL LABORATORY. THE DETECTOR IS LOCATED ON THE EAST WALL INSIDE THE CHEMICAL LABORATORY. THE REDAS SYSTEM MAY ALSO BE USED TO OBSERVE TREND INFORMATION.

REFERENCES:

DRAWING 208-049-RM-23 SENSING ELEMENT: RADIATION MONITORING PANEL AR-403 Rev. 20 Page 4

1 ENCLOSURE 1

(

- (Page 3 of 194)

PSA-Z ANNUNCIATOR RESPONSE PSA-Z-01-01 H-01-01 l GAMMA I RADIATION I HIGH I

I I

EVENT POINT 1752 INDICATED CONDITION:

o RM-G3 RADIATION LEVEL EXCEEDS HIGH SElPOINT.

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o RM-G3 INDICATION AT RADIATION MONITORING PANEL.

o SPDS ALPHA PAGE.

OPERATOR ACTIONS FOR A VALID ALARM:

o INVESTIGATE CAUSE OF HIGH RADIATION.

o NOTIFY HEALTH PHYSICS TO MONITOR AFFECTED AREA (S).

o OBSERVE AREA MONITORS / RECORDERS FOR TREND INFORMATION.

DISCUSSION:

RM-G3 MONITORS THE PRIMARY SAMPLE ROOM. THE DETECTOR IS LOCATED ON THE SOUTH WALL INSIDE THE PRIMARY SAMPLE ROOM. THE REDAS SYSTEM MAY ALSO BE USED TO OBSERVE TREND INFORMATION.

REFERENCES:

DRAWING 208-049-RM-23 SENSING ELEMENT: RADIATION MONITORING PANEL AR-403 Rev. 20 Page 5

/ ENCLOSURE 1

( (Page 4 of 194)

PSA-Z ANNUNCIATOR RESPONSE PSA-Z-01-01 H-01-01 GAMMA RADIATION HIGH EVENT POINT 1754 ,

INDICATED CONDITION:

o RM-G4 RADIATION LEVEL EXCEEDS HIGH SETPOINT.

( REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o RM-G4 INDICATION AT RADIATION MONITORING PANEL.

o SPDS ALPHA PAGE.

OPERATOR ACTIONS FOR A VALID ALARM:

o INVESTIGATE CAUSE OF HIGH RADIATION.

o NOTIFY HEALTH PHYSICS TO MONITOR AFFECTED AREA (S). ,

o OBSERVE AREA MONITORS / RECORDERS FOR TREND INFORMATION.

DISCUSSION:

RM-G4 MONITORS THE AUXILIARY BUILDING ENTRANCE HALLWAY. THE DETECTOR IS LOCATED ON THE WALL OPPOSITE THE PAX PHONE NEAR THE ENTRANCE TO THE INTERMEDIATE BUILDING. THE REDAS SYSTEM MAY ALSO BE USED TO OBSERVE TREND INFORMATION.

c

REFERENCES:

DRAWING 208-049-RM-24

(,T

/ SENSING ELEMENT: RADIATION MONITORING PANEL AR-403 Rev. 20 Page 6

ENCLOSURE 1 (Page 5 of 194)

PSA-Z ANNUNCIATOR RESPONSE PSA-Z-01-01 H-01-01

GAMMA l RADIATION I HIGH l

l l

EVENT POINT 1756 ,

INDICATED CONDITION:

o RM-G5 RADIATION LEVEL EXCEEDS HIGH SETPOINT.

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o RM-G5 INDICATION AT RADIATION MONITORING PANEL.

o SPDS ALPHA PAGE.

OPERATOR ACTIONS FOR A VALID ALARM:

o INVESTIGATE CAUSE OF HIGH RADIATION.

o NOTIFY HEALTH PHYSICS TO MONITOR AFFECTED AREA (S).

o OBSERVE AREA MONITORS / RECORDERS FOR TREND INFORMATION.

DISCUSSION:

RM-G5 MONITORS THE WASTE GAS TANK VALVE ALLEY. THE DETECTOR IS LOCATED ON THE 95' AB, ON THE WALL IN THE WASTE GAS VALVE ALLEY, ADJACENT TO THE DETECTOR. THE REDAS SYSTEM MAY ALSO BE USED TO OBSERVE TREND INFORMATION.

REFERENCES:

DRAWING 208-049-RM-24 SENSING ELEMENT: RADIATION MONITORING PANEL AR-403 Rev. 20 Page 7

[ . .

7 i

ENCLOSURE 1 (Page 6 of 194)

PSA-Z ANNUNCIATOR RESPONSE PSA-Z-01-01 H-01-01 l

GAMMA RADIATION HIGH

, l l  :

EVENT POINT 1758 ,

l i

INDICATED CONDITION:

o RM-G6 RADIATION LEVEL EXCEEDS HIGH SETP0 INT.

l REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o RM-G6 INDICATION AT RADIATION MONITORING PANEL.

o SPDS ALPHA PAGE.

OPERATOR ACTIONS FOR A VALID ALARM:

o INVESTIGATE CAUSE OF HIGH RADIATION.

o NOTIFY HEALTH PHYSICS TO MONITOR AFFECTED AREA (S). ,'

o OBSERVE AREA MONITORS / RECORDERS FOR TREND INFORMATION.

DISCUSSION:

RM-G6 MONITORS THE MAKEUP TANK VALVE ALLEY. THE DETECTOR IS LOCATED ON THE WALL NEAR THE ENTRANCE LOCKED GATE. THE REDAS SYSTEM MAY ALSO BE.

USED TO OBSERVE TREND INFORMATION.

REFERENCES:

DRAWING 208-049-RM-25 SENSING ELEMENT: RADIATION MONITORING PANEL AR-403 Rev. 20 Page 8

ENCLOSURE 1 O (Page 7 of 194)

PSA-Z ANNUNCIATOR RESPONSE PSA-Z-01 H-01-01 5

GAMMA RADIATION HIGH EVENT POINT 1760 l

INDICATED CONDITION:

o RM-G7 RADIATION LEVEL EXCEEDS HIGH SETPOINT.

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o RM-G7 INDICATION AT RADIATION MONITORING PANEL.

o SPDS ALPHA PAGE.

OPERATOR ACTIONS FOR A VALID ALARM:

o INVESTIGATE CAUSE OF HIGH RADIATION. -

o NOTIFY HEALTH PHYSICS TO MONITOR AFFECTED AREA (S).  ;

o OBSERVE AREA MONITORS / RECORDERS FOR TREND INFORMATION.

DISCUSSION:

RM-G7 MONITORS THE RC BLEED TANK AREA. THE DETECTOR IS LOCATED ON THE WALL NEAR THE ENTRANCE INSIDE THE LOCKED GATE ON THE 95' ELEVATION. THE REDAS SYSTEM MAY ALSO BE USED TO OBSERVE TREND INFORMATION.

REFERENCES:

DRAWING 208-049-RM-25 SENSl;!G EL.9 INT: RADIATION MONITORING PANEL AR-403 Rev. 20 Page 9

l l

! l

! I ENCLOSURE 1

' (^)

V (Page 8 of 194) i PSA-Z ANNUNCIATOR RESPONSE PSA-Z-01-01 H-01-01 l l

l l l

GAMMA RADIATION HIGH EVENT POINT 1762

, lll l

INDICATED CONDITION:

o RM-G8 RADIATION LEVEL EXCEEDS HIGH SETPOINT.

(O L)

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

1 o RM-G8 INDICATION AT RADIATION MONITORING PANEL.

o SPDS ALPHA PAGE.

OPERATOR ACTIONS FOR A VALID ALARM:

o INVESTIGATE CAUSE OF HIGH RADIATION. '

o NOTIFY HEALTH PHYSICS TO MONITOR AFFECTED AREA (S). y o 0BSERVE AREA MONITORS / RECORDERS FOR TREND INFORMATION.

l DISCUSSION:

RM-G8 MONITORS THE RC BLEED TANK AREA. THE DETECTOR IS LOCATED ON THE WALL NEAR THE ENTRANCE INSIDE THE LOCKED GATE ON THE 119' ELEVATION, THE REDAS SYSTEM MAY ALSO BE USED TO OBSERVE TREND INFORMATION.

REFERENCES:

DRAWING 208-049-RM-26

( SENSING ELEMENT: RADIATION MONITORING PANEL AR-403 Rev. 20 Page 10

ENCLOSURE 1 (Page 9 of 194)

PSA-Z ANNUNCIATOR RESPONSE PSA-Z-01-01 H-01-01 I I GAMMA

, I l RADIATION-l l l HIGH I I I I l

l I EVENT POINT 1764

[

l INDICATED CONDITION:

o RM-G9 RADIATION LEVEL EXCEEDS HIGH SETPOINT.

l REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

l 0 RM-G9 INDICATION AT RADIATION MONITORING PANEL.

l 0 SPDS ALPHA PAGE.

OPERATOR ACTIONS FOR A VALID ALARM:

o INVESTIGATE CAUSE OF HIGH RADIATION.

o NOTIFY HEALTH PHYSICS TO MONITOR AFFECTED AREA (S). ,

! o OBSERVE AREA MONITORS / RECORDERS FOR TREND INFORMATION.

DISCUSSION:

RM-G9 MONITORS THE AREA OUTSIDE THE PERSONNEL HATCH. THE DETECTOR IS LOCATED ON THE WALL NEAR THE ENTRANCE INSIDE THE LOCKED GATE ON THE 119' ELEVATION. THE REDAS SYSTEM MAY ALSO BE USED TO OBSERVE TREND INFORMATION.

REFERENCES:

DRAWING 208-049-RM-26 SENSING ELEMENT: RADIATION MONITORING PANEL AR-403 Rev. 20 Page 11 l

. . _ . _ _ _ , _ _ . ._._..__ _._, , - . . . . , _ _ _ . _ ~ . - . - - . . . . . . - . - - . . _ . _ . - . - _ _ - -

4 i i

]tg q ENCLOSURE 1 (Page 10 of 194)

PSA-Z ANNUNCIATOR RESPONSE PSA-Z-01-01 H-01-01 ,

l 4 l GAMMA i l RADIATION I HIGH i I l

I i EVENT POINT 1766

?

1 1

l j INDICATED CONDITION:

o RM-G10 RADIATION LEVEL EXCEEDS HIGH SETPOINT.

i 4

i I

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

j o RM-G10 INDICATION AT RADIATION MONITORING PANEL. l i I o SPOS ALPHA PAGE.

j l

i j OPERATOR ACTIONS FOR A VALID ALARM:

l' o INVESTIGATE CAUSE OF HIGH RADIATION.

j o NOTIFY HEALTH PHYSICS TO MONITOR AFFECTED AREA (S). j i

o 0BSERVE AREA MONITORS / RECORDERS FOR TREND INFORMATION.  ;

! l i DISCUSSION:

j RM-G10 MONITORS THE MAKE-UP PUMP AREA. THE DETECTOR IS LOCATED ON THE WALL

NEAR THE ENTRANCE TO THE 'C' MAKE-UP PUMP (SOUTH ENTRANCE). THE REDAS SYSTEM MAY ALSO BE USED TO OBSERVE TREND INFORMATION.

REFERENCES:

DRAWING 208-049-RM-27 I SENSING ELEMENT: RADIATION MONITORING PANEL 4

i

AR-403 Rev. 20 Page 12

l l

! 4 ENCLOSURE 1

(Page 11 of 194)

PSA-Z ANNUNCIATOR RESPONSE- PSA-Z-01-01 H-01-01

i E

! GAMMA j RADIATION j HIGH i

1

! )

! EVENT POINT 1768'- I INDICATED CONDITION:

o RM-G11 RADIATION LEVEL EXCEEDS HIGH SETPOINT.

i REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

) o RM-Gli INDICATION AT RADIATION MONITORING PANEL.

j o SPDS ALPHA PAGE.

l

! l i OPERATOR ACTIONS FOR A VALID ALARM:

o INVESTIGATE CAUSE OF HIGH RADIATION.

?

o NOTIFY HEALTH PHYSICS TO MONITOR AFFECTED AREA (S).

o OBSERVE AREA MONITORS / RECORDERS FOR TREND INFORMATION.

I 1

i DISCUSSION:

1 RM-G11 MONITORS THE DEB 0 RATING DEMIN ROOM. THE DETECTOR IS LOCATED ON THE WALL INSIDE THE DEMIN ROOM ON THE 119' ELEVATION. THE REDAS SYSTEM MAY i ALSO BE USED TO OBSERVE TREND INFORMATION.

4

REFERENCES:

DRAWING 208-049-RM-27 SENSING ELEMENT: RADIATION MONITORING PANEL AR-403 Rev. 20 Page 13

._ . . - - . .-_ . . _ . . -- ---i

l-i i

ENCLOSURE 1 (Page 12 of 194) i PSA-Z ANNUNCIATOR RESPONSE PSA-Z-01-01 H-01-01 l GAMMA RADIATION HIGH EVENT POINT 1770 ,

INDICATED CONDITION:

o RM-G12 RADIATION LEVEL EXCEEDS HIGH SETP0 INT.

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o RM-G12 INDICATION AT RADIATION MONITORING PANEL.

o SPDS ALPHA PAGE.

OPERATOR ACTIONS FOR A VALID ALARM:

o INVESTIGATE CAUSE OF HIGH RADIATION. -

o NOTIFY HEALTH PHYSICS TO MONITOR AFFECTED AREA (S). ,

o OBSERVE AREA MONITORS / RECORDERS FOR TREND INFORMATION.

DISCUSSION:

RM-G12 MONITORS THE SPENT RESIN STORAGE TANK ROOM. THE DETECTOR IS LOCATED IN THE DECANT AND SLURRY PUMP ROOM JUST INSIDE THE LOCKED GATE ON THE WALL. THE REDAS SYSTEM MAY ALSO BE USED TO OBSERVE TREND INFORMATION.

l

REFERENCES:

DRAWING 208-049-RM-28 SENSING ELEMENT: RADIATION MONITORING' PANEL l

l AR-403 Rev. 20 Page 14

f '

i i

ENCLOSURE 1 ,

l (Page 13~of 194) 'l

[

l i

PSA-Z ANNUNCIATOR RESPONSE PSA-Z-01-01 H-01-01 ';

i 1

{ZZZZZZ i GAMMA  !

j I RADIATION l l HIGH )

I I

I i l l EVENT POINT 1772 '

l li l

i INDICATED CONDITION:  ;

i I o RM-G13 RADIATION LEVEL EXCEEDS HIGH SETPOINT. l l

[ REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o RM-G13 INDICATION AT RADIATION MONITORING PANEL.

o SPDS ALPHA ~PAGE.

OPERATOR ACTIONS FOR A VALID ALAR.: u o INVESTIGATE CAUSE OF HIGH RADIATION. '

o NOTIFY HEALTH PHYSICS TO MONITOR AFFECTED AREA (S). g o OBSERVE AREA MONITORS / RECORDERS FOR TREND INFORMATION.

DISCUSSION:

RM-G13 MONITORS THE DECONTAMINATION PIT AREA. THE DETECTOR IS LOCATED ON THE I43' ELEVATION, CLOSE TO THE STAIRWELL BY THE ECST'S. THE REDAS SYSTEM MAY ALSO BE USED TO OBSERVE TREND INFORMATION.

REFERENCES:

DRAWING 208-049-RM-28 SENSING ELEMENT: RADIATION MONITORING PANEL AR-403 Rev. 20 Page 15

1 ENCLOSURE 1 O (Page 14 of 194) l PSA-Z ANNUNCIATOR RESPONSE PSA-Z-01-01 H-01-01 ,

l l

GAMMA i RADIATION I HIGH I i

EVENT POINT 1774 t

1 INDICATED CONDITION:

o RM-G14 RADIATION LEVEL EXCEEDS HIGH SETPOINT.

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o RM-G14 INDICATION AT RADIATION MONITORING PANEL.

o SPDS ALPHA PAGE.

OPERATOR ACTIONS FOR A VALID ALARM:

o INVESTIGATE CAUSE OF HIGH RADIATION.

o NOTIFY HEALTH PHYSICS TO MONITOR AFFECTED AREA (S).

o OBSERVE AREA MONITORS / RECORDERS FOR TREND INFORMATION. g e

DISCUSSION:

RM-G14 MONITORS THE SPENT FUEL STORAGE AREA. THE DETECTOR IS LOCATED ON THE 143' AB, ON THE WALL OF THE REACTOR BUILDING IN THE PASSAGEWAY TO THE SPENT FUEL SYSTEM FILTERS. THIS DETECTOR IS THE ONLY S.T.S. AREA MONITOR AND IS COMMONLY REFERRED TO AS THE " SPENT FUEL CRITICALITY MONITOR". THE REDAS SYSTEM MAY ALSO BE USED TO OBSERVE TREND INFORMATION.

REFERENCES:

DRAWING 208-049-RM-29 SENSING ELEMENT: RADIATION MONITORING PANEL AR-403 Rev. 20 Page 16

ENCLOSURE I O (Page 15 of 194)  ;

PSA-Z ANNUNCIATOR RESPONSE PSA-Z-01-01 H-01-01 I

{ZZZZZZ l GAMMA I RADIATION I HIGH I

I I

EVENT POINT-1776

?

INDICATED CONDITION:

o RM-G15 RADIATION LEVEL EXCEEDS HIGH SETPOINT. l REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o RM-G15 INDICATION AT RADIATION MONITORING PANEL.

o SPDS ALPHA PAGE.

OPERATOR ACTIONS FOR A VALID ALARM:

l o INVESTIGATE CAUSE OF HIGH RADIATION.

o NOTIFY HEALTH PHYSICS TO MONITOR AFFECTED AREA (S). f o OBSERVE AREA MONITORS / RECORDERS FOR TREND INFORMATION.  :

o IF FUEL MOVEMENT IS IN PROGRESS, ENSURE FUEL IS PLACED IN A SAFE (

CONDITION PRIOR TO PERSONNEL EXIT.

DISCUSSION:

RM-GIS MONITORS THE SPENT FUEL AREA. THE DETECTOR IS LOCATED ON THE SPENT FUEL BRIDGE AND MOVES WITH THE BRIDGE. THE REDAS SYSTEM MAY ALSO BE USED TO OBSERVE TREND INFORMATION.

REFERENCES:

DRAWING 208-049-RM-29 SENSING ELEMENT: RADIATION MONITORING PANEL AR-403 Rev. 20 Page 17

I k

j ENCLOSURE 1 1 (Page 16 of 194)

[ PSA-Z ANNUNCIATOR RESPONSE PSA-Z-01-01 H-01-01 i  !

i l

GAMMA

! l RADIATION i '

l HIGH I

I I

EVENT POINT 1778 I

j INDICATED CONDITION:

l 0 RM-G16 RADIATION LEVEL EXCEEDS HIGH SETPOINT.

}

l REDUNDANT INDICATION WHICH WILL VERIFY ALARM: ,

l 0 RM-G16 INDICATION AT RADIATION MONITORING PANEL.

1 o SPDS ALPHA PAGE. ,

i i

l OPERATOR ACTIONS FOR A VALID ALARM:

. o INVESTIGATE CAUSE OF HIGH RADIATION. -

{; o NOTIFY HEALTH PHYSICS TO MONITOR AFFECTED AREA (S). 3 o OBSERVE AREA MONITORS / RECORDERS FOR TREND INFORMATION.

o IF FUEL MOVEMENT IS IN PROGRESS, ENSURE FUEL IS PLACED IN A SAFE i t

j CONDITION PRIOR TO PERSONNEL EXIT.

DISCUSSION:  !

RM-G16 MONITORS THE FUEL TRANSFER AREA. THE DETECTOR IS LOCATED ON THE l i MAIN FUEL BRIDGE AND MOVES WITH THE BRIDGE. THE REDAS SYSTEM MAY ALSO BE USED TO OBSERVE TREND INFORMATION.

)

REFERENCES:

DRAWING 208-049-RM-30 SENSING ELEMENT: RADIATION MONITORING PANEL l

AR-403 Rev. 20 Page 18 l l

l i

j ENCLOSURE 1

(Page 17 of 194) l!

1 PSA-Z ANNUNCIATOR RESPONSE PSA-2-01-01 H-01-01 1

i i l GAMMA 3 i RADIATION I HIGH I

l

. I i a

EVENT POINT 1780 i

j INDICATED CONDITION: ,

] o RM-G17 RADIATION LEVEL EXCEEDS HIGH SETPOINT.

3 REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

} o RM-G17 INDICATION AT RADIATION HONITORING PANEL.  !

O SPOS ALPHA PAGE.  ;

i 1

! OPERATOR ACTIONS FOR A VALID ALARM:

I o INVESTIGATE CAUSE OF HIGH RADIATION. A 1

o NOTIFY HEALTH PHYSICS TO MONITOR AFFECTED AREA (S). j i o OBSERVE AREA MONITORS / RECORDERS FOR TREND INFORMATION. J

}

i i

! DISCUSSION:

RM-G17 MONITORS THE 119' ELEVATION OF THE REACTOR BUILDING. THE DETECTOR l IS LOCATED ON THE STANCHION NEAR THE PERSONNEL HATCH. THE REDAS SYSTEM MAY

ALSO BE USED TO OBSERVE TREND INFORMATION.

4 j

REFERENCES:

DRAWING 208-049-RM-30 SENSING ELEMENT: RADIATION MONITORING PANEL I

_i

AR-403 Rev. 20 Page 19 4

i .- --, ., - . . . . . . - . _ . _ _. _ . . . - , . . - . . . . . . - . . . - ,_

ENCLOSURE 1 (Page 18 of 194)

PSA-Z ANNUNCIATOR RESPONSE PSA-Z-01-01 H-01-01 i

GAMMA l RADIATION I HIGH I

l I

l EVENT POINT 1782 ,

l INDICATED CONDITION:

l 0 RM-GI8 RADIATION LEVEL EXCEEDS HIGH SETPOINT.

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

l 0 RM-G18 INDICATION AT RADIATION MONITORING PANEL.

l o SPDS ALPHA PAGE.

OPERATOR ACTIONS FOR A VALID ALARM:

o INVESTIGATE CAUSE OF HIGH RADIATION.

o NOTIFY HEALTH PHYSICS TO MONITOR AFFECTED AREA (S). e l o OBSERVE AREA MONITORS / RECORDERS FOR TREND INFORMATION.

o VERIFY TRANSFER CANAL LEVEL AT DESIRED HEIGHT.

l DISCUSSION:

RM-G18 MONITORS THE INCORE PIT AREA. THE DETECTOR IS LOCATED IN THE PIT ON THE 164' ELEVATION NEAR THE TRANSFER CANAL. THE REDAS SYSTEM MAY ALSO BE USED TO OBSERVE TREND INFORMATION.

REFERENCES:

DRAWING 208-049-RM-31 SENSING ELEMENT: RADIATION MONITORING PANEL AR-403 Rev. 20 Page 20 L

ENCLOSURE I

(T (Page 19 of 194) i

\,_)

PSA-Z ANNUNCIATOR RESPONSE PSA-Z-01-01 H-01-01 1

GAMMA l RADIATION HIGH 1

l EVENT POINT 1784 )

i 4

INDICATED CONDITION: I o RM-G29/30 RADIATION LEVEL EXCEEDS HIGH SETPOINT.

REDUNDANT INDICATION WHICH WILL VERIFY ALARM-( })

, o RM-G29/30 INDICATION ON HVAC SECTION OF MAIN CONTROL BOARD. l o SPDS ALPHA PAGE.

l OPERATOR ACTIONS FOR A VALID ALARM:

o INVESTIGATE CAUSE OF HIGH RADIATION.

o NOTIFY HEALTH PHYSICS TO MONITOR AFFECTED AREA (S).

o OBSERVE AREA MONITORS / RECORDERS FOR TREND INFORMATION.

o VERIFY TRANSFER CANAL LEVEL AT DESIRED HEIGHT.

DISCUSSION:

RM-G29/30 ARE THE REACTOR BUILDING HIGH RANGE POST ACCIDENT MONITORS.

THE DETECTORS ARE LOCATED ON THE TOP 0F EACH 'D' RING AT THE 180' ELEVATION. THE REDAS SYSTEM MAY ALSO BE USED TO OBSERVE TREND INFORMATION.

REFERENCES:

DRAWING 208-049-RM-32 O

(_) SENSING ELEMENT: RADIATION MONITORING PANEL AR-403 Rev. 20 Page 21

l l

l ENCLOSURE I  :

("

+

(Page 20 of 194) j l

PSA-Z ANNUNCIATOR RESPONSE PSA-Z-01-02 H-01-02 i

l GAMMA MONITOR 1 WARNING u EVENT POINT 1749 ..

INDICATED CONDITION:

o RM-G1 RADIATION LEVEL EXCEEDS WARNING SETPOINT OR o RM-G1 RADIATION MONITOR FAILED LOW.

REDUNDANT INDICATION WHICH WILL VERIFY ALARM: l l 0 RM-G1 INDICATION AT RADIATION MONITORING PANEL.

o RM-G1 INDICATION AT DETECTOR.

o SPDS ALPHA PAGE.

OPERATOR ACTIONS FOR A VALID ALARM:

o INVESTIGATE CAUSE OF HIGH RADIATION OR, .

MONITOR LOW READING.

o NOTIFY HEALTH PHYSICS TO MONITOR AFFECTED AREA (S).

o OBSERVE AREA MONITORS / RECORDERS FOR TREND INFORMATION.

DISCUSSION:

RM-G1 MONITORS THE CONTROL ROOM. THE DETECTOR IS ON THE BACK WALL NEXT l TO THE ES RELAY ACTUATION CABINETS. EITHER WARNING SETPOINT EXCEEDED OR t

A DETECTOR FAILED LOW WILL GIVE THIS ALARM. THE REDAS SYSTEM MAY ALSO BE USED TO OBSERVE TREND INFORMATION.

REFERENCES:

DRAWING 208-049-RM-22 SENSING ELEMENT: RADIATION MONITORING' PANEL AR-403 Rev. 20 Page 22

ENCLOSURE 1 O (Page 21 of 194)

PSA-Z ANNUNCIATOR RESPONSE PSA-Z-01-02 H-01-02

, GAMMA i l MONITOR l WARNING l EVENT POINT 1751 ,

i INDICATED CONDITION: 1 o RM-G2 RADIATION LEVEL EXCEEDS WARNING SETPOINT OR, l RM-G2 RADIATION MONITOR FAILED LOW.

I I

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o RM-G2 INDICATION AT RADIATION MONITORING PANEL. ,

o SPDS ALPHA PAGE. l OPERATOR ACTIONS FOR A VALID ALARM:

l 0 INVESTIGATE CAUSE OF HIGH RADIATION OR, MONITOR LOW READING. '

o NOTIFY HEALTH PHYSICS TO MONITOR AFFECTED AREA (S).

o OBSERVE AREA MONITORS / RECORDERS FOR TREND INFORMATION.

DISCUSSION:

RM-G2 MONITORS THE CHEMICAL LABORATORY. THE DETECTOR IS LOCATED ON THE EAST WALL INSIDE THE CHEMICAL LABORATORY. EITHER WARNING SETPOINT EXCEEDED OR A DETECTOR FAILED LOW WILL GIVE THIS ALARM. THE REDAS SYSTEM .

MAY ALSO BE USED TO OBSERVE TREND INFORMATION. j

REFERENCES:

DPAWING 208-049-RM-23 SENSING ELEMENT: RADIATION MONITORING PANEL l

i AR-403 Rev. 20 Page 23 m., , ., ,, ,,4. w < - - - - ,

i l

l l

ENCLOSURE 1 lQ lg3 (Page 22 of 194)

PSA-Z ANNUNCIATOR RESPONSE PSA-Z-01-02 H-01-02 GAMMA

, MONITOR

! WARNING l

EVENT POINT 1753 1

! INDICATED CONDITION:

o RM-G3 RADIATION LEVEL EXCEEDS WARNING SETP0 INT OR, o RM-G3 RADIATION MONITOR FAILED LOW.

'(/)

~.

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

l 0 RM-G3 INDICATION AT RADIATION MONITORING PANEL.

o SPDS ALPHA PAGE.

OPERATOR ACTIONS FOR A VALID ALARM:

o INVESTIGATE CAUSE OF HIGH RADIATION OR, MONITOR LOW READING. -

o NOTIFY HEALTH PHYSICS TO MONITOR AFFECTED AREA (S).  ;

o OBSERVE AREA MONITORS / RECORDERS FOR TREND INFORMATION.

DISCUSSION:

RM-G3 MONITORS THE PRIMARY SAMPLE ROOM. THE DETECTOR IS LOCATED ON THE WALL INSIDE THE PRIMARY SAMPLE ROOM. EITHER WARNING SETPOINT EXCEEDED OR A DETECTOR FAILED LOW WILL GIVE THIS ALARM. THE REDAS SYSTEM MAY ALSO BE USED TO OBSERVE TREND INFORMATION.

REFERENCES:

DRAWING 208-049-RM-23

(]

'~'

SENSING ELEMENT: RADIATION MONITORING PANEL AR-403 Rev. 20 Page 24

l l

n ENCLOSURE I

( ) (Page 23 of 194)

PSA-Z ANNUNCIA10R RESPONSE PSA-Z-01-02 lH-01-02

! GAMMA MONITOR l WARNING EVENT POINT 1755 ,

l INDICATED CONDITION:

o RM-G4 RADIATION LEVEL EXCEEDS WARNING SETP0 INT OR, o RM-G4 RADIATION MONITOR FAILED LOW.

[ REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o RM-G4 INDICATION AT RADIATION MONITORING PANEL.

o SPDS ALPHA PAGE.

l OPERATOR ACTIONS FOR A VALID ALARM:

o INVESTIGATE CAUSE OF HIGH RADIATION OR, MONITOR LOW READING.

o o NOTIFY HEALTH PHYSICS TO MONITOR AFFECTED AREA (S). '

o OBSERVE AREA MONITORS / RECORDERS FOR TREND INFORMATION.

DISCUSSION:

RM-G4 MONITORS THE AUXILIARY BUILDING ENTRANCE HALLWAY. THE DETECTOR IS LOCATED ON THE WALL OPPOSITE THE PAX PHONE FEAR THE ENTRANCE TO THE INTERMEDIATE BUILDING. EITHER WARNING SETPOINT EXCEEDED OR A DETECTOR FAILED LOW WILL GIVE THIS ALARM. THE REDAS SYSTEM MAY ALSO BE USED TO OBSERVE TREND INFORMATION.

REFERENCES:

DRAWING 208-049-RM.-24 SENSING ELEMENT: RADIATION MONITORING PANEL AR-403 Rev. 20 Page 25

l l

! G 7

ENCLOSURE 1

() (Page 24 of 194)

PSA-Z ANNUNCIATOR RESPONSE PSA-Z-01-02 H-01-02 GAMMA MONITOR WARNING l

EVENT POINT 1757 '

l l INDICATED CONDITION:

o RM-G5 RADIATION LEVEL EXCEEDS WARNING SETPOINT OR, o RM-G5 RADIATION MONITOR FAILED LOW.

( REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o RM-G5 INDICATION AT RADIATION MONITORING PANEL.

o SPDS ALPHA PAGE.

OPERATOR ACTIONS FOR A VALID ALARM:

o INVESTIGATE CAUSE OF HIGH RADIATION OR, MONITOR LOW READING.

o o NOTIFY HEALTH PHYSICS TO MONITOR AFFECTED AREA (S).

o 0BSERVE AREA MONITORS / RECORDERS FOR TREND INFORMATION.

DISCUSSION:

RM-G5 MONITORS THE WASTE GAS TANK VALVE ALLEY. THE DETECTOR IS LOCATED ON THE WALL OPPOSITE THE WASTE GAS COMPRESSOR ROOM. EITHER WARNING SETPOINT EXCEEDED OR A DETECTOR FAILED LOW WILL GIVE THIS ALARM. THE REDAS SYSTEM MAY ALSO BE USED TO OBSERVE TREND INFORMATION.

-s

REFERENCES:

DRAWING 208-049-RM-24

(

(- SENSING ELEMENT: RADIATION MONITORING FANEL AR-403 Rev. 20 Page 26

ENCLOSURE 1 O

4 (Page 25 of 194)  !

PSA-Z ANNUNCIATOR RESPONSE PSA-Z-01-02 H-01-02 J

GAMMA MONITOR l

_ WARNING EVENT POINT 1759 ,1 INDICATED CONDITION:

o RM-G6 RADIATION LEVEL EXCEEDS WARNING SETPOINT OR o RM-G6 RADIATION MONITOR FAILED LOW.

j REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o RM-G6 INDICATION AT RADIATION MONITORING PANEL.

o SPDS ALPHA PAGE.

i OPERATOR ACTIONS FOR A VALID ALARM:

l~

0 INVESTIGATE CAUSE OF HIGH RADIATION OR, MONITOR LOW READING.

3 o NOTIFY HEALTH PHYSICS TO MONITOR AFFECTED AREA (S).

o OBSERVE AREA MONITORS / RECORDERS FOR TREND INFORMATION.

DISCUSSION:

RM-G6 MONITORS THE MAKEUP TANK VALVE ALLEY. THE DETECTOR IS LOCATED ON THE WALL NEAR THE ENTRANCE LOCKED GATE. EITHER WARNING SETPOINT EXCEEDED OR A DETECTOR FAILED LOW WILL GIVE THIS ALARM. THE REDAS SYSTEM MAY ALSO BE USED TO OBSERVE TREND INFORMATION.

REFERENCES:

DRAWING 208-049-RM-25 SENSING ELEMENT: RADIATION MONITORING PANEL l

l AR-403 Rev. 20 Page 27

l l

)

ERCLOSURE 1 .I i

(Page 26 of 194)

PSA-Z ANNUNCIATOR RESPONSE PSA-Z-01-02 H-01-02 l l l

l GAMMA l MONITOR .

WARNING I l

i l EVENT POINT 1761  :

i  :

! l INDICATED CONDITION:

l o RM-G7 RADIATION LEVEL EXCEEDS WARNING SETPOINT OR l 0 RM-G7 RADIATION MONITOR FAILED ~ LOW.

I REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o 7 IN CAT ON AT RADIATION MONITORING PANEL.

i OPERATOR ACTIONS FOR A VALID ALARM:

l 0 INVESTIGATE CAUSE OF HIGH RADIATION OR, 2 MONITOR LOW READING. j o NOTIFY HEALTH PHYSICS TO MONITOR AFFECTED AREA (S). '1 o OBSERVE AREA MONITORS / RECORDERS FOR TREND'INFORMATION.

l DISCUSSION:

RM-G7 MONITORS THE RC BLEED TANK AREA. THE DETECTOR IS LOCATED ON THE WALL l NEAR THE ENTRANCE INSIDE THE LOCKED GATE ON THE 95' ELEVATION. EITHER  :

WARNING SETPOINT EXCEEDED OR A DETECTOR FAILED LOW WILL GIVE THIS ALARM.  ;

THE REDAS SYSTEM MAY ALSO BE USED TO OBSERVE TREND INFORMATION. l

REFERENCES:

DRAWING 208-049-RM-25 SENSING ELEMENT: RADIATION MONITORING PANEL AR-403 Rev. 20 Page 28

-. - -, .-. -. -,. . . . . . -- . - .A

ENCLOSURE 1 O (Page 27 of 194)

PSA-Z ANNUNCIATOR RESPONSE PSA-Z-01-02 H-01-02 GAMMA MONITOR WARNING EVENT POINT 1763 INDICATED CONDITION:

o RM-G8 RADIATION LEVEL EXCEEDS WARNING SETPOINT OR o RM-G8 RADIATION MONITOR FAILED LOW.

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o RM-G8 INDICATION AT RADIATION MONITORING PANEL.

o SPDS ALPHA PAGE.

1 OPERATOR ACTIONS FOR A VALID ALARM:

t o INVESTIGATE CAUSE OF HIGH RADIATION OR, MONITOR LOW READING.

o NOTIFY HEALTH PHYSICS TO MONITOR AFFECTED AREA (S). i o OBSERVE AREA MONITORS / RECORDERS FOR TREND INFORMATION. i l

! DISCUSSION:

RM-G8 MONITORS THE RC BLEED TANK AREA. THE DETECTOR IS LOCATED ON THE WALL NEAR THE ENTRANCE INSIDE THE LOCKED GATE ON THE 119' ELEVATION. EITHER WARNING SETPOINT EXCEEDED OR A DETECTOR FAILED LOW WILL GIVE THIS ALARM.

THE REDAS SYSTEM MAY ALSO BE USED TO OBSERVE TREND INFORMATION.

REFERENCES:

DRAWING 208-049-RM-26 SENSING ELEMENT: RADIATION MONITORING PANEL AR-403 Rev. 20 Page 29

ENCLOSURE 1

{s (Page 28 of 194)

PSA-Z ANNUNCIATOR RESPONSE PSA-Z-01-02 H-01-02 l

GAMMA I MONITOR WARNING I

EVENT POINT 1765 t'

I INDICATED CONDITION:

l l o RM-G9 RADIATION LEVEL EXCEEDS WARNING SETPOINT OR

! o RM-G9 RADIATION MONITOR FAILED LOW. l REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o RM-G9 INDICATION AT RADIATION MONITORING PANEL.

l o SPDS ALPHA PAGE.

OPERATOR ACTIONS FOR A VALID ALARM:

o INVESTIGATE CAUSE OF HIGH RADIATION OR,

MONITOR LOW READING. p l

o NOTIFY HEALTH PHYSICS TO MONITOR AFFECTED AREA (S).

'i o 0BSERVE AREA MONITORS / RECORDERS FOR TREND INFORMATION.

i DISCUSSION:

RM-G9 MONITORS THE PERSONNEL HATCH. THE DETECTOR IS LOCATED ON THE WALL NEAR THE ENTRANCE INSIDE THE LOCKED GATE ON THE 119' ELEVATION. EITHER WARNING SETPOINT EXCEEDED OR A DETECTOR FAILED LOW WILL GIVE THIS ALARM.

THE REDAS SYSTEM MAY ALSO BE USED TO OBSERVE TREND INFORMATION.

REFERENCES:

DRAWING 208-049-RM-26 SENSING ELEMENT: RADIATION MONITORING PANEL I

l AR-403 Rev. 20 Page 30 l _ .__ _ ,_ .. . - . - . . .-

ENCLOSURE 1 (Page 29 of 194)

PSA-Z ANNUNCIATOR RESPONSE PSA-Z-01-02 H-01-02 GAMMA MONITOR

. WARNING EVENT POINT 1767 l

INDICATED CONDITION:

i o RM-G10 RADIATION LEVEL EXCEEDS WARNING SETo0 INT OR o RM-G10 RADIATION MONITOR FAILED LOW.

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

l 0 RM-G10 INDICATION AT RADIATION MONITORING PANEL.

o SPDS ALPHA PAGE. j I

OPERATOR ACTIONS FOR A VALID ALARM:

o INVESTIGATE CAUSE OF HIGH RADIATION OR, 1 l

MONITOR LOW READING. j l o NOTIFY HEALTH PHYSICS TO MONITOR AFFECTED AREA (S).

o OBSERVE AREA MONITORS / RECORDERS FOR TREND INFORMATION.  !

l DISCUSSION:

RM-G10 MONITORS THE MAKE-UP PUMP AREA. THE DETECTOR IS LOCATED ON THE WALL NEAR THE ENTRANCE TO THE 'C' MAKE-UP PUMP (SOUTH ENTRANCE). EITHER WARNING SETP0 INT EXCEEDED OR A. DETECTOR FAILED LOW WILL GIVE THIS ALARM. THE REDAS SYSTEM MAY ALSO BE USED TO OBSERVE TREND INFORMATION,

REFERENCES:

DRAWING 208-049-RM-27 SENSING ELEMENT: RADIATION MONITORING PANEL AR-403 Rev. 20 Page 31

J l

ENCLOSURE 1 (Page 30 of 194)

PSA-Z ANNUNCIATOR RESPONSE PSA-Z-01-02 H-01-02 .

l GAMMA i MONITOR I WARNING I l

I EVENT POINT 1769 INDICATED CONDITION:

o RM-G11 RADIATION LEVEL EXCEEDS WARNING SETPOINT OR o RM-G11 RADIATION MONITOR FAILED LOW.

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o RM-Gil INDICATION AT RADIATION MONITORING PANEL.

o SPDS ALPHA PAGE.

OPERATOR ACTIONS FOR A VALID ALARM:

o INVESTIGATE CAUSE OF HIGH RADIATION OR, MONITOR LOW READING. ,'

o NOTIFY HEALTH PHYSICS TO MONITOR AFFECTED AREA (S).

o OBSERVE AREA MONITORS / RECORDERS FOR TREND INFORMATION.

DISCUSSION: '

RM-G11 MONITORS THE DEB 0 RATING DEMIN ROOM. THE DETECTOR IS LOCATED ON THE WALL INSIDE THE DEMIN ROOM ON THE 119' ELEVATION. EITHER WARNING SETPOINT EXCEEDED OR A DETECTOR FAILED LOW WILL GIVE THIS ALARM. THE REDAS SYSTEM MAY ALSO BE USED TO OBSERVE TREND INFORMATION.

REFERENCES:

DRAWING 208-049-RM-27 '

SENSING ELEMENT: RADIATION MONITORING PANEL

'AR-403 Rev. 20 Page 32

. . _ _ . . . _ . . ~ . . ,_.___.2 .....a,.__.

I 1

l ENCLOSURE 1 (Page 31 of 194)

PSA-Z ANNUNCIATOR RESPONSE PSA-2-01-02 H-01-02 +

l l  !

1 GAMMA MONITOR l WARNING j EVENT POINT 1771

'\

INDICATED CONDITION: i o RM-G12 RADIATION LEVEL EXCEEDS WARNING SETPOINT OR o RM-G12 RADIATION MONITOR FAILED LOW. 1 REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o RM-G12 INDICATION AT RADIATION MONITORING PANEL.

o SPDS ALPHA PAGE.

i OPERATOR ACTIONS FOR A VALID ALARM:

4

! o INVESTIGATE CAUSE OF HIGH RADIATION OR, MONITOR LOW READING.

) o NOTIFY HEALTH PHYSICS TO MONITOR AFFECTED AREA (S). 9 l 0 OBSERVE AREA MONITORS / RECORDERS FOR TREND INFORMATION. 9 I

DISCUSSION:

. I RM-G12 MONITORS THE SPENT RESIN STORAGE TANK ROOM. THE DETECTOR IS LOCATED IN THE DECANT AND SLURRY PUMP ROOM JUST INSIDE THE LOCKED GATE. EITHER WARNING SETPOINT EXCEEDED OR A DETECTOR FAILED LOW WILL GIVE THIS ALARM.

3 THE REDAS SYSTEM MAY ALSO BE USED TO OBSERVE TREND INFORMATION.

REFERENCES:

DRAWING 208-049-RM-28 SENSING ELEMENT: RADIATION MONITORING PANEL l AR-403 Rev. 20 Page 33

i I

3 i ENCLOSURE 1 (Page 32 of 194)

I PSA-Z ANNUNCIATOR RESPONSE PSA-2-01-02 H-01-02 i i i

i l GAMMA )

MONITOR  ;

j WARNING l

! EVENT POINT 1773 i 1

)

I I

1 INDICATED CONDITION:

o RM-G13 RADIATION LEVEL EXCEEDS WARNING SETPOINT OR J

o RM-G13 RADIATION MONITOR FAILED LOW. I l

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o RM-G13 INDICATION AT RADIATION MONITORING PAliEL.

o SPDS ALPHA PAGE.

i l

OPERATOR ACTIONS FOR A VALID ALARM:

i i o INVESTIGATE CAUSE OF HIGH RADIATION OR, L MONITOR LOW READING.

['

o NOTIFY HEALTH PHYSICS TO MONITOR AFFECTED AREA (S).

i-

o 0BSERVE AREA MONITORS / RECORDERS FOR TREND INFORMATION.

i l DISCUSSION:

5 RM-G13 MONITORS THE DECONTAMINATION PIT AREA. THE DETECTOR IS LOCATED ON THE 143' ELEVATION, CLOSE TO THE STAIRWELL BY THE ECST'S. EITHER WARNING SETPOINT EXCEEDED OR A DETECTOR FAILED LOW WILL GIVE THIS ALARM. THE REDAS SYSTEM MAY ALSO BE USED TO OBSERVE TREND INFORMATION.

REFERENCES:

DRAWING 208-049-RM-28 SENSING ELEMENT: RADIATION MONITORING PANEL 2

} AR-403 Rev. 20 Page 34 i

e

~

i ENCLOSURE 1 (Page 33 of 194)

! PSA-Z ANNUNCIATOR RESPONSE PSA-Z-01-02 H-01-02

)

i 1 GAMMA 4 i MONITOR WARNING EVENT POINT 1775 INDICATED CONDITION:

o RM-G14 RADIATION LEVEL EXCEEDS WARNING SETPOINT OR 3 o RM GI4 RADIATION MONITOR FAILED LOW.

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

! o RM-G14 INDICATION AT RADIATION MONITORING PANEL.

I o SPDS ALPHA PAGE.

OPERATOR ACTIONS FOR A VALID ALARM:

, o INVESTIGATE CAUSE OF HIGH RADIATION OR,

, MONITOR LOW READING.

o NOTIFY HEALTH PHYSICS TO MONITOR AFFECTED AREA (S).  ;

j o OBSERVE AREA MONITORS / RECORDERS FOR TREND INFORMATION.

i,

DISCUSSION

l RM-G14 MONITORS THE SPENT FUEL STORAGE AREA. THE DETECTOR IS LOCATED ON i THE I43' AB, ON THE WALL OF THE REACTOR BUILDING IN THE PASSAGEWAY TO THE SPENT FUEL SYSTEM FILTERS. THIS DETECTOR IS THE ONLY S.T.S. AREA MONITOR AND IS COMMONLY REFERRED TO AS THE " SPENT FUEL CRITICALITY MONITOR". THE i REDAS SYSTEM MAY ALSO BE USED TO OBSERVE TREND INFORMATION.

4 i

REFERENCES:

DRAWING 208-049-RM-29 SENSING ELEMENT: RADIATION MONITORING PANEL 4 AR-403 Rev. 20 Page 3S i

] ENCLOSURE 1 (Page 34 of 194)

PSA-Z ANNUNCIATOR RESPONSE PSA-Z-01-02 H-01-02 GAMMA

MONITOR

! WARNING l EVENT POINT 1777 l INDICATED CONDITION:

, o RM-G15 RADIATION LEVEL EXCEEDS WARNING SETPOINT OR j o RM-GIS RADIATION MONITOR FAILED LOW.

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o RM-G15 INDICATION AT RADIATION MONITORING PANEL.

o SPDS ALPHA PAGE.

OPERATOR ACTIONS FOR A VALID ALARM:

l o INVESTIGATE CAUSE OF HIGH RADIATION OR, 1 MONITOR LOW READING.

o NOTIFY HEALTH PHYSICS TO MONITOR AFFECTED AREA (S).

o 0BSERVE AREA MONITORS / RECORDERS FOR TREND INFORMATION.

l DISCUSSION:

RM-GIS MONITORS THE SPENT FUEL AREA. THE DETECTOR IS LOCATED ON THE SPENT FUEL BRIDGE AND MOVES WITH THE BRIDGE. EITHER WARNING SETP0 INT l EXCEEDED OR A DETECTOR FAILED LOW WILL GIVE THIS ALARM. THE REDAS SYSTEM MAY ALSO BE USED TO OBSERVE TREND INFORMATION.

REFERENCES:

DRAWING 208-049-RM-29 SENSING ELEMENT: RADIATION MONITORING PANEL AR-403 Rev. 20 Page 36 l

f I

l i

ENCLOSURE 1 (Page 35 of 194)

PSA. JiNUNCIATOR RESPONSE PSA-Z-01-02 H-01-02 GAMMA MONITOR WARNING EVENT POINT 1779 ,

INDICATED CONDITION:

o RM-G16 RADIATION LEVEL EXCEEDS WARNING SETPOINT OR o RM-G16 RADIATION MONITOR FAILED LOW.

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o RM-G16 INDICATION AT RADIATION MONITORING PANEL.

o SPDS ALPHA PAGE.

OPERATOR ACTIONS FOR A VALID ALARM:

o INVESTIGATE CAUSE OF HIGH RADIATION OR,  ;

MONITOR LOW READING. j o NOTIFY HEALTH PHYSICS TO MONITOR AFFECTED AREA (S). l o OBSERVE AREA MONITORS / RECORDERS FOR TREND INFORMATION.

DISCUSSION:

RM-G16 MONITORS THE FUEL TRANSFER AREA. THE DETECTOR IS LOCATED ON THE MAIN FUEL BRIDGE AND MOVES WITH THE BRIDGE. EITHER WARNING SETPOINT EXCEEDED OR A DETECTOR FAILED LOW WILL GIVE THIS ALARM. THE REDAS SYSTEM MAY ALSO BE USED TO OBSERVE TREND INFORMATION.

REFERENCES:

DRAWING 208-049-RM-30 SENSING ELEMENT: RADIATION MONITORING PANEL AR-403 Rev. 20 Page 37

l

' ENCLOSURE 1 (Page 36 of 194) 1 l

PSA-Z ANNUNCIATOR RESPONSE PSA-Z-01-02 H-01-02 GAMMA MONITOR WARNING EVENT POINT 1781 ,

INDICATED CONDITION:

o RM-G17 RADIATION LEVEL EXCEEDS WARNING SETPOINT OR o RM-G17 RADIATION MONITOR FAILED LOW.

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o RM-G17 INDICATION AT RADIATION MONITORING PANEL.

o SPDS ALPHA PAGE.

OPERATOR ACTIONS FOR A VALID ALARM:

o INVESTIGATE CAUSE OF HIGH RADIATION OR, MONITOR LOW READING.

3 o NOTIFY HEALTH PHYSICS TO MONITOR AFFECTED AREA (S). '

o OBSERVE AREA MONITORS / RECORDERS FOR TREND INFORMATION.

DISCUSSION:

RM-G17 MONITORS THE 119' ELEVATION OF THE REACTOR BUILDING. THE DETECTOR IS LOCATED ON THE STANCHION NEAR THE PERSONNEL HATCH. EITHER WARNING SETPOINT EXCEEDED OR A DETECTOR FAILED LOW WILL GIVE THIS ALARM.THE-REDAS SYSTEM MAY ALSO BE USED TO OBSERVE TREND INFORMATION.

REFERENCES:

DRAWING 208-049-RM-30 SENSING ELEMENT: RADIATION MONITORING PANEL AR-403 Rev. 20 Page 38

ENCLOSURE 1 I

(Page 37 of 194) js i l PSA-Z ANNUNCIATOR RESPONSE PSA-Z-01-02 H-01-02

(

i 4

i 4

! GAMMA

MONITOR l i WARNING
1 i  !
1 i EVENT POINT 1783 l
9

) ^

i j INDICATED CONDITION:

i

, o RM-G18 RADIATION LEVEL EXCEEDS WARNING SETPOINT OR o RM-G18 RADIATION MONITOR FAILED LOW.

I REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

l

) o RM-G18 INDICATION AT RADIATION MONITORING PANEL.

o SPDS ALPHA PAGE.

1 4

i OPERATOR ACTIONS FOR A VALID ALARM:

}

l o INVESTIGATE CAUSE OF HIGH RADIATION OR, -

MONITOR LOW READING. j

! o NOTIFY HEALTH PHYSICS TO MONITOR AFFECTED AREA (S). 1 i o OBSERVE AREA MONITORS / RECORDERS FOR TREND INFORMATION.  !

o VERIFY TRANSFER CANAL LEVEL AT DESIRED HEIGHT.

4 j DISCUSSION:

1 RM-G18 MONITORS THE INCORE PIT AREA. THE DETECTOR IS LOCATED IN THE PIT l i

ON THE 164' ELEVATION NEAR THE TRANSFER CANAL. EITHER WARNING SETPOINT

. EXCEEDED OR A DETECTOR FAILED LOW WILL GIVE THIS ALARM. THE REDAS SYSTEM MAY ALSO BE USED TO OBSERVE TREND INFORMATION.

x I

REFERENCES:

DRAWING 208-049-RM-31 l SENSING ELEMENT: RADIATION MONITORING PANEL l

AR-403 Rev. 20 Page 39

\

-1

L

! ENCLOSURE 1 (Page 38 of 194)

PSA-Z ANNUNCIATOR RESPONSE PSA-2-01-02 H-01-02 l

GAMMA MONITOR WARNING EVENT POINT 1785 l-INDICATED CONDITION:

o RM-G29/30 RADIATION LEVEL EXCEEDS WARNING SETPOINT(S) OR o RM-G29/30 RADIATION MONITOR (S) FAILED LOW.

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:  ;

o RM-G29/30 INDICATION ON HVAC SECTION OF MAIN CONTROL BOARD.

o SPDS ALPHA PAGE.

i OPERATOR ACTIONS FOR A VALID ALARM:

I o INVESTIGATE CAUSE OF HIGH RADIATION OR MONITOR (S) LOW READING. -

o NOTIFY HEALTH PHYSICS TO MONITOR AFFECTED AREA (S).  ;

! o OBSERVE AREA MONITORS / RECORDERS FOR TREND INFORMATION.

0 VERIFY TRANSFER CANAL LEVEL AT DESIRED HEIGHT. '

l i

DISCUSSION:  ;

RM-G29/30 ARE THE REACTOR BUILDING HIGH RANGE POST ACCIDENT MONITORS.

THE DETECTORS ARE LOCATED ON THE TOP 0F EACH 'D' RING AT THE 180' ELEVATION. EITHER WARNING SETPOINT(S) EXCEEDED OR A DETECTOR FAILED LOW l WILL GIVE THIS ALARM. THE REDAS SYSTEM MAY ALSO BE USED TO OBSERVE TREND INFORMATION.

l-

REFERENCES:

DRAWING 208-049-RM-32 SENSING ELEMENT: RADIATION MONITORING PANEL r

AR-403 Rev. 20 Page 40 j

l ENCLOSURE 1 l (Page 39 of 194)

PSA-Z ANNUNCIATOR RESPONSE PSA-Z-01-05 H-01-05 l

l

, l MN STM LINE ,

A/B HIGH RAD )

MONITOR. FAIL j i

EVENT POINT 1977 N

l INDICATED CONDITION:

o RM-G25/26/27/28 RADIATION LEVEL EXCEEDS ALARM SETPOINT, OR o RM-G25/26/27/28 RADIATION MONITOR FAILED LOW.

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o RM-G25/26/27/28 INDICATION ON HVAC SECTION OF MAIN CONTROL BOARD.

o AUDIBLE INDICATION ON RADIATION MONITOR (S) o SPDS ALPHA PAGE.

OPERATOR ACTIONS FOR A VALID ALARM:

o INVESTIGATE CAUSE OF HIGH RADIATION OR -

LOW MONITOR READING.  ;

l 0 NOTIFY HEALTH PHYSICS TO MONITOR AFFECTED AREA (S).

l l 0 REFER TO E0P-06, STEAM GENERATOR TUBE RUPTURE.  !

l DISCUSSION:

RM-G25/28 MONITOR THE ATMOSPHERIC DUMP LINES MSV-25/A1 AND MSV-26/B2.

RM-G26/27 MONITOR THE MAIN STEAM LINES B1 AND A2 RESPECTIVELY. THE' DETECTORS ARE ALL LOCATED ON THE 119' ELEVATION OF THE INTERMEDIATE BUILDING ON THEIR RESPECTIVE STEAM LINE. EITHER RADIATION SETPOINT EXCEEDED OR A DETECTOR FAILED LOW CAN GIVE THIS ALARM.

REFERENCES:

DRAWING 208-049-RM-47 O

g SENSING ELEMENT: RADIATION MONITORING PANEL AR-403 Rev. 20 Page 41

l I

l t

ENCLOSURE 1 l

O (Page 40 of 194)

PSA-Z ANNUNCIATOR RESPONSE PSA-Z-01-07 H-01-07 DO STOR TANK i

LEVEL HIGH/ LOW EVENT POINT 1512 l

INDICATED CONDITION:

1 o DO STORAGE TANK LEVEL >97" H2 O AS SENSED BY D0-4-LS u

l REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

i l

l

. l OPERATOR ACTIONS FOR A VALID ALARM:

l o INVESTIGATE CAUSE OF HIGH LEVEL. I o NOTIFY SECONDARY PLANT OPERATOR TO OBSERVE LOCAL LEVEL INDICATOR. l l

DISCUSSION:

THE DO STORAGE TANK HAS AN AUTO FILL FEATURE. IF THE LEVEL IS HIGH AND RISING THE FILL VALVE MAY BE STUCK OPEN.

REFERENCES:

DRAWING 208-022-00-07 SENSING ELEMENT: 00-4-LS I

AR-403 Rev. 20 Page 42

0 l 1

^

l 2

ENCLOSURE 1 (Page 41 of 194)

'}

PSA-Z ANNUNCIATOR RESPONSE PSA-Z-01-07 H-01-07 5

i i DO STOR TANK LEVEL

. HIGH/ LOW i

EVENT POINT 1520 j

i INDICATED CONDITION:

o 00 STORAGE TANK LEVEL <33" H2 0 AS SENSED BY D0-3-LS j

l

. REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

i l OPERATOR ACTIONS FOR A VALID ALARM:

i I o INVESTIGATE CAUSE OF LOW LEVEL.

l 0 NOTIFY SECONDARY PLANT OPERATOR.TO OBSERVE LOCAL LEVEL INDICATOR.

, DISCUSSION:

i THE DO STORAGE TANK HAS AN AUTO FILL FEATURE. IF THE LEVEL IS LOW AND

~

, NOT RISING THE FILL VALVE MAY BE STUCK CLOSED, OR D0 WATER FROM UNITS

' I/2 WATER TREATMENT BUILDING IS NOT AVAILABLE. CONTACT UNITS 1/2 TO INVESTIGATE.

1

REFERENCES:

DRAWING 208-022-D0-07 j SENSING ELEMENT: DO-3-LS AR-403 Rev. 20 Page 43

l ENCLOSURE 1 O (Page 42 of 194)

PSA-Z ANNUNCIATOR RESPONSE PSA-Z-02-01 H-02-01 E

l ATMOSPHERIC l RADIATION

! I HIGH l \

I l

l EVENT POINT 1712 INDICATED CONDITION:

o RM-Al RADIATION LEVEL EXCEEDS HIGH SETPOINT.

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o RM-Al INDICATION AT RADIATION MONITORING PANEL.

o SPDS ALPHA PAGE.

OPERATOR ACTIONS FOR A VALID ALARM:

l o REFER TO AP-250. .

o INVESTIGATE CAUSE OF HIGH RADIATION. g o OBSERVE AREA MONITORS / RECORDERS FOR TREND INFORMATION.

DISCUSSION:

RM-Al MONITORS THE REACTOR BUILDING PURGE EXHAUST DUCT. THREE DIFFERENT DETECTORS ARE USED, PARTICULATE, IODINE AND GAS. ANY ONE OF THESE CHANNELS CAN GIVE THIS ALARM. THE REDAS SYSTEM MAY ALSO BE USED TO OBSERVE TREND INFORMATION.

REFERENCES:

DRAWING 208-049-RM-16 SENSING ELEMENT: RADIATION MONITORING PANEL AR-403 Rev. 20 Page 44 l

i ENCLOSURE 1

( (Page 43 of 194)

PSA-Z ANNUNCIATOR RESPONSE PSA-2-02-01 H-02-01 l

EEEEE l

' 5 i ATMOSPHERIC l l RADIATION I I HIGH I I l l 1 l l EVENT POINT 1715 l

INDICATED CONDITION:

o RM-A2 RADIATION LEVEL EXCEEDS HIGH SETPOINT.

REDtJNDANT INDICATION WHICH WILL VERIFY ALARM:

o RM-A2 INDICATION AT RADIATION MONITORING PANEL.

o SPDS ALPHA PAGE.

OPERATOR ACTIONS FOR A VALID ALARM:

o REFER TO AP-250.

o INVESTIGATE CAUSE OF HIGH RADIATION.

o OBSERVE AREA MONITORS / RECORDERS FOR TREND INFORMATION DISCUSSION:

l RM-A2 MONITORS THE AUXILIARY BUILDING PURGE EXHAUST DUCT. THREE DIFFERENT DETECTORS ARE USED, PARTICULATE, I0 DINE AND GAS. ANY ONE OF THESE CHANNELS

! CAN GIVE THIS ALARM. THE REDAS SYSTEM MAY ALSO BE USED TO OBSERVE TREND INFORMATION.

REFERENCES:

DRAWING 208-049-RM-16 SENSING ELEMENT: RADIATION MONITORING PANEL AR-403 Rev. 20 Page 45 i

ENCLOSURE 1

("'s (Page 44 of 194)

V  ;

\

l PSA-Z ANNUNCIATOR RESPONSE PSA-2-02-01 H-02-01 1

ATMOSPHERIC RADIATION )

HIGH

! EVENT POINT 1718 l  !)

INDICATED CONDITION:

! i o RM-A3 RADIATION LEVEL EXCEEDS HIGH SETPOINT.  ;

REDUNDANT INDICATION WHICH WILL VERIFY' ALARM:

! o RM-A3 INDICATION AT RADIATION MONITORING PANEL. ,

I o SPDS ALPHA PAGE.  ;

l OPERATOR ACTIONS FOR A VALID ALARM:

o REFER TO AP-250. l o INVESTIGATE CAUSE OF HIGH RADIATION.

o OBSERVE AREA MONITORS / RECORDERS FOR TREND INFORMATION.

DISCUSSION:

1 RM-A3 MONITORS AUXILIARY BUILDING EXHAUST FROM SAMPLE AREAD', THE  !

WASTE GAS COMPRESSOR ROOM, THE WASTE GAS VALVE ALLEY, AND ADJ0INING AREAS.

THIS DETECTOR ONLY HAS A GAS CHANNEL. THE REDAS SYSTEM MAY ALSO BE USED TO OBSERVE TREND INFORMATION. ,

REFERENCES:

DRAWING 208-049-RM-17

'V SENSING ELEMENT: PADIATION MONITORING PANEL AR-403 Rev. 20 Page 46

)

i  % ENCLOSURE l' 4 1 (Page 45 of 194) l

! l j PSA-Z ANNUNCIATOR RESPONSE PSA-Z-02-01 H-02-01 1

2 4

l ATMOSPHERIC

, l RADIATION I HIGH

, I  !

1 l 3

I

! EVENT POINT 1721 '

INDICATED CONDITION:

o RM-A4 RADIATION LEVEL EXCEEDS HIGH SETPOINT.

i REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o RM-A4 INDICATION AT RADIATION MONITORING PANEL.

o SPDS ALPHA PAGE.

i I l

l OPERATOR ACTIONS FOR A VALID ALARM: )

o REFER TO AP-250. i

! o INVESTIGATE CAUSE OF HIGH RADIATION. i o 0BSERVE AREA MONITORS / RECORDERS FOR TREND INFORMATION. i l

DISCUSSION:

RM-A4 MONITORS THE SPENT FUEL AREA EXHAUST. THIS DETECTOR ONLY HAS A GAS CHANNEL. THE REDAS SYSTEM MAY ALSO BE USED TO OBSERVE TREND INFORMATION.

REFERENCES:

DRAWING 208-049-RM-17 SENSING ELEMENT: RADIATION MONITORING PANEL AR-403 Rev. 20 Page 47

l ENCLOSURE 1

, s (Page 46 of 194)

PSA-Z ANNUNCIATOR RESPONSE PSA-Z-02-01 H-02-01 7xrzzzr i ATMOSPHERIC l RADIATION l 1 HIGH i

I I

I l EVENT POINT 1724 - '

i I INDICATED CONDITION:

l l

o RM-A5 RADIATION LEVEL EXCEEDS HIGH SETPOINT.

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o RM-A5 INDICATION AT RADIATION MONITORING PANEL.

o SPDS ALPHA PAGE.

OPERATOR ACTIONS FOR A VALID ALARM:

! o REFER TO AP-250.

l 0 INVESTIGATE CAUSE OF HIGH RADIATION. ,

[ o 0BSERVE AREA MONITORS / RECORDERS FOR TREND INFORMATION.

l l

DISCUSSION:

l RM-A5 MONITORS THE CONTROL COMPLEX RETURN DUCT. THREE DIFFERENT DETECTORS '

ARE USED, PARTICULATE, IODINE AND GAS. ANY ONE OF THESE CHANNELS CAN GIVE THIS ALARM. THE REDAS SYSTEM MAY ALSO BE USED TO OBSERVE TREND INFORMATION.

REFERENCES:

DRAWING 208-049-RM-18 D

V SENSING ELEMENT: RADIATION MONITORING PANEL AR-403 Rev. 20 Page 48

1 ENCLOSURE 1 l (Page 47 of 194)

PSA-Z ANNUNCIATOR RESPONSE PSA-Z-02-01 H-02-01 l

ATMOSPHERIC RADIATION HIGH

! EVENT POINT 1727

! INDICATED CONDITION:

o RM-A6 RADIATION LEVEL EXCEEDS HIGH SETPOINT.

I REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

O o RM-A6 INDICATION AT RADIATION MONITORING PANEL.

o SPDS ALPHA PAGE.

OPERATOR ACTIONS FOR A VALID ALARM:

o INVESTIGATE CAUSE OF HIGH RADIATION.

o OBSERVE AREA MONITORS / RECORDERS FOR TREND INFORMATION.

DISCUSSION:

RM-A6 MONITORS THE REACTOR BUILDING ATMOSPHERE. SAMPLE POINTS ARE EITHER AHF-3B DUCT, OR THE RB ATMOSPHERE DIRECTLY. IT IS NORMALLY LINED UP TO THE DUCT OF AHF-38. IT CAN ALTERNATELY BE LINED UP TO SAMPLE THE RB ATMOSPHERE DIRECTLY PER OP-417.

TWO DIFFERENT DETECTORS ARE USED, PARTICULATE / IODINE AND GAS. ANY ONE OF THESE CHANNELS CAN GIVE THIS ALARM.

THE REDAS SYSTEM MAY ALSO BE USED TO OBSERVE TREND INFORMATION.

REFERENCES:

DRAWING 208-049-RM-18 SENSING ELEMENT: RADIATION MONITORING PANEL AR-403 Rev. 20 Page 49

ENCLOSURE 1 O (Page 48 of 194)

PSA-Z ANNUNCIATOR RESPONSE PSA-Z-02-01 H-02-01

}  ::::: l l

ATMOSPHERIC l RADIATION I HIGH I

I I

EVENT POINT 1730 INDICATED CONDITION:

o RM-A7 RADIATION LEVEL EXCEEDS HIGH SETPOINT.

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o RM-A7 INDICATION AT RADIATION MONITORING PANEL.

o SPDS ALPHA PAGE.

I OPERATOR ACTIONS FOR A VALID ALARM:

o INVESTIGATE CAUSE OF HIGH RADIATION.

o 0BSERVE AREA MONITORS / RECORDERS FOR TREND INFORMATION. g DISCUSSION:

RM-A7 MONITORS THE AHF-44A/B DISCHARGE AIR, THEREFORE THE ATMOSPHERES OF THE PRIMARY SAMPLE ROOM, PRIMARY SAMPLE ROOM SAMPLE HOOD, RADIO CHEMISTRY LAB SAMPLE HOODS, AND/0R PASS SYSTEM VALVE ALLEY MAY HAVE HIGH GASE0US ACTIVITY. THE REDAS SYSTEM MAY ALSO BE USED TO OBSERVE TREND INFORMATION.

REFERENCES:

DRAWING 208-049-RM-19 SENSING ELEMENT: RADIATION MONITORING PANEL AR-403 Rev. 20 Page 50'

ENCLOSURE 1 (Page 49 of 194)

PSA-Z ANNUNCIATOR RESPONSE PSA-Z-02-01 H-02-01 l l ATMOSPHERIC i l RADIATION I I HIGH I I I I I I EVENT POINT 1733 INDICATED CONDITION:

o RM-A8 RADIATION LEVEL EXCEEDS HIGH SETPOINT.

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

! o RM-A8 INDICATION AT RADIATION MONITORING PANEL. t l o SPDS ALPHA PAGE.

OPERATOR ACTIONS FOR A VALID ALARM:

o INVESTIGATE CAUSE OF HIGH RADIATION.

i o OBSERVE AREA MONITORS / RECORDERS FOR TREND INFORMATION.

DISCUSSION:

RM-A8 MONITORS THE AUXILIARY BUILDING EXHAUST UPSTREAM OF THE PENETRATION FOR THE FUEL HANDLING FLOOR EXHAUST. THE REDAS SYSTEM MAY ALSO BE USED T0 l OBSERVE TREND INFORMATION.

REFERENCES:

DRAWING 208-049-RM-19.

SENSING ELEMENT: RADIATION MONITORING PANEL AR-403 Rev. 20 Page 51

l l

lp lV ENCLOSURE 1 (Page 50 of 194) f PSA-Z ANNUNCIATOR RESPONSE PSA-Z-02-01 H-02-01 l  !

l l

l ATMOSPHERIC l RADIATION l l HIGH l l l l 1

EVENT POINT 1736 1-l INDICATED CONDITION: ,

, o RM-All RADIATION LEVEL EXCEEDS HIGH SETPOINT.

l l

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o RM-All INDICATION AT RADIATION MONITORING PANEL.

o SPDS ALPHA PAGE.

i OPERATOR ACTIONS FOR A VALID ALARM:

o INVESTIGATE CAUSE OF HIGH RADIATION. <

o IF WASTE GAS RELEASE IN PROGRESS, NOTIFY PRIMARY PLANT OPERATOR TO  ;

ENSURE WGDT RECYCLE VALVES AND RELEASE VALVE ARE CLOSED.

o OBSERVE AREA MONITORS / RECORDERS FOR TREND INFORMATION.

DISCUSSION:

l RM-All MONITORS THE AUXILIARY BUILDING EXHAUST PENETRATION FOR THE WASTE GAS RELEASE PATH. THE WGDT RECYCLE VALVES ARE WDV 393/394/395 AND THE RELEASE VALVE IS WDV-439. THE REDAS SYSTEM MAY ALSO BE USED TO OBSERVE TREND INFORMATION.

REFERENCES:

DRAWING 208-049-RM-20 SENSING ELEMENT: RADIATION MONITORING PANEL l

( AR-403 Rev. 20 Page 52

{ _ _ _ .. _.

' i i

l ENCLOSURE 1 y (Page 51 of 194) )

l PSA-Z ANNUNCIATOR RESPONSE PSA-Z-02-01 H-02-01 l l l l

______ l l

i ATMOSPHERIC i RADIATION l l l HIGH I

I l 1

l EVENT POINT 1738 l

INDICATED CONDITION
I l i o RM-Al2 RADIATION LEVEL EXCEEDS HIGH SETPOINT. l l

l l REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

I o RM-A12 INDICATION AT RADIATION MONITORING PANEL.

o SPDS ALPHA PAGE.

o MAIN STEAM LINE RAD MONITORS RMG-25, RMG-26, RMG-27, AND /0R RMG-28 READ HIGHER THAN NORMAL.

OPERATOR ACTIONS FOR A VALID ALARM:

l 0 REFER TO E0P-06, STEAM GENERATOR TUBE RUPTURE.

o INVESTIGATE CAUSE OF HIGH RADIATION.

o 0BSERVE AREA MONITORS / RECORDERS FOR TREND INFORMATION.

DISCUSSION:

RM-AI2 MONITORS THE AUXILIARY BUILDING EXHAUST PENETRATION FOR SECONDARY PLANT CONDENSER OFF GAS. THE REDAS SYSTEM MAY ALSO BE USED TO OBSERVE TREND INFORMATION.

REFERENCES:

DRAWING 208-049-RM-20 SENSING ELEMENT: RADIATION MONITORING PANEL AR-403 Rev. 20 Page 53

1 l

i 4

ENCLOSURE 1 3

(Page 52 of 194)

PSA-Z ANNUNCIATOR RESPONSE PSA-Z-02-01 H-02-01 i

I E E

, i l ATMOSPHERIC I I RADIATION  ;

j i i HIGH 2

I I i i I .

I I l

EVENT POINT 1740 l l t i

) INDICATED CONDITION:

o RM-A13 RADIATION LEVEL EXCEEDS HIGH SETPOINT.

i l j

l REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

1 o RM-A13 INDICATION AT RADIATION MONITORING PANEL. j l 0 SPDS ALPHA PAGE.  ;

I i OPERATOR ACTIONS FOR A VALID ALARM:

) o INVESTIGATE CAUSE OF HIGH RADIATION. ,

o OBSERVE AREA MONITORS / RECORDERS FOR TREND INFORMATION. j i

i '1 1

DISCUSSION:

RM-A13 MONITORS THE WASTE GAS SAMPLING STATION AREA (SAMPLE AREA 'D')

q THE REDAS SYSTEM MAY ALSO BE USED TO OBSERVE TREND INFORMATION, i

REFERENCES:

ORAWING 208-049-RM-21 r'%

V SENSING ELEMENT
RADIATION MONITORING PANEL i

i 1 AR-403 Rev. 20 Page 54 1

i i

1 l

J i

' ENCLOSURE l' l (Page 53 of 194)

]

l PSA-Z ANNUNCIATOR RESPONSE PSA-Z-02-01 H-02-01 I

K l l ZZZZZ ATMOSPHERIC

)

i

l l RADIATION l

. I I HIGH l l l I I I EVENT POINT 1742 ,

t INDICATED CONDITION:

o RM-A14 RADIATION LEVEL EXCEEDS HIGH SETPOINT.

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o RM-A14 INDICATION AT RADIATION MONITORING PANEL.

o SPDS ALPHA PAGE.

i OPERATOR ACTIONS FOR A VALID ALARM: l I

0 INVESTIGATE CAUSE OF HIGH RADIATION.

o OBSERVE AREA MONITORS / RECORDERS FOR TREND INFORMATION.

l l

DISCUSSION:

RM-A14 IS A PORTABLE MONITOR, NORMALLY LOCATED NEAR THE PRIMARY SAMPLE LABORATORY. THIS MONITOR IS NOT NORMALLY ENERGIZED. THE REDAS SYSTEM MAY ALSO BE USER,TO OBSERVE TREND INFORMATION.

I l

REFERENCES:

DRAWING 208-049-2-21 SENSING ELEMENT: RADIATION MONITORING PANEL l AR-403 Rev. 20 Page 55

l ENCLOSURE 1 (Page 54 of 194)

PSA-Z ANNUNCIATOR RESPONSE PSA-Z-02-01 H-02-01 )

EEEEE i l ATMOSPHERIC i l i RADIATION i I I HIGH l 1 i l l l l l EVENT POINT 1745 j i

INDICATED CONDITION: i 1

o RM-A15 RADIATION LEVEL EXCEEDS HIGH SETPOINT.  !

i REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

l o RM-A15 INDICATION AT RADIATION MONITORING PANEL.

o SPDS ALPHA PAGE.

i OPERATOR ACTIONS FOR A VALID ALARM:

o INVESTIGATE CAUSE OF HIGH RADIATION.

o 0BSERVE AREA MONITORS / RECORDERS FOR TREND INFORMATION. 3 l

DISCUSSION:

l RM-AIS IS A' PORTABLE MONITOR, NORMALLY LOCATED NEAR THE DECONTAMINATION PIT ON THE SPENT FUEL FLOOR. THIS MONITOR IS NOT NORMALLY ENERGIZED. THE REDAS SYSTEM MAY ALSO BE USED TO OBSERVE TREND INFORMATION.

REFERENCES:

DRAWING 208-049-RM-22 j SENSING ELEMENT: RADIATION MONITORING PANEL AR-403 Rev. 20 Page 56 l

ENCLOSURE I (Page 55 of 194) 1 PSA-Z ANNUNCIATOR RESPONSE PSA-2-02-02 H-02-02 ATMOSPHERIC MONITOR WARNING EVENT POINT 1713 0

INDICATED CONDITION:

o RM-Al RADIATION LEVEL EXCEEDS WARNING SETPOINT, OR o RM-Al RADIATION MONITOR FAILED LOW REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o RM-Al INDICATION AT RADIATION MONITORING PANEL.

o SPDS ALPHA PAGE. -

l OPERATOR ACTIONS FOR A VALID ALARM: l l

o INVESTIGATE CAUSE OF HIGH RADIATION, OR LOW MONITOR READING. j o 0BSERVE AREA MONITORS / RECORDERS FOR TREND INFORMATION. ,

1 l

DISCUSSION:

RM-Al MONITORS THE REACTOR BUILDING PURGE EXHAUST DUCT. THREE DIFFERENT DETECTORS ARE USED, PARTICULATE, IODINE AND GAS. ANY ONE OF THESE CHANNELS CAN GIVE THIS ALARM, EITHER WARNING SETPOINT EXCEEDED, OR DETECTOR FAILED "1.0W. THE REDAS SYSTEM MAY ALSO BE USED TO OBSERVE TREND INFORMATION.

REFERENCES:

DRAWING 208-049-RM-16 SENSING ELEMENT: RADIATION MONITORING PANEL AR-403 Rev. 20 Page 57

i l ENCLOSURE I (Page 56 of 194)

PSA-Z ANNUNCIATOR RESPONSE PSA-Z-02-02 H-02-02 ATMOSPHERIC MONITOR WARNING r

EVENT POINT 1714  :

INDICATED CONDITION:

l o RM-Al RADIATION MONITOR PUMP FLOW ABOVE NORMAL OR LESS THAN 5 SCFM.

l l

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o RM-Al FLOW INDICATION AT RADIATION MONITORING PANEL.

OPERATOR ACTIONS FOR A VALID ALARM:

o INVESTIGATE CAUSE OF RADIATION PUMP FLOW PROBLEM.

DISCUSSION:

RM-Al MONITORS THE REACTOR BUILDING PURGE EXHAUST DUCT. THREE DIFFERENT DETECTORS ARE USED, PARTICULATE, I0 DINE AND GAS. EITHER A HIGH OR LOW FLOW CAN GIVE THIS ALARM. -

REFERENCES:

DRAWING 208-049-RM-01 SENSING ELEMENT: RADIATION MONITORING PANEL AR-403 Rev. 20 Page 58

I

. _ - . . . . . - - - ------.e - - -

ENCLOSURE 1-(Page 57 of 194)

PSA-Z ANNUNCIATOR RESPONSE PSA-Z-02 H-02-02 ATMOSPHERIC

! MONITOR l

WARNING i

i  :

! EVENT POINT 1716

, INDICATED CONDITION:

o RM-A2 RADIATION LEVEL EXCEEDS WARNING SETPOINT, OR l o RM-A2 RADIATION MONITOR FAILED LOW l lO acou"oaa' taotcattoa w"tc" wt u vea1rv ^'aaa:

o RM-A2 INDICATION AT RADIATION MONITORING PANEL.

l I

l l OPERATOR ACTIONS FOR A VALID ALARM:

o INVESTIGATE CAUSE OF HIGH RADIATION, OR -

LOW MONITOR READING. <

o OBSERVE AREA MONITORS / RECORDERS FOR TREND INFORMATION. f l

DISCUSSION:

RN-A2 MONITORS THE AUXILIARY BUILDING PURGE EXHAUST DUCT. THREE DIFFERENT j DETECTORS ARE USED, PARTICULATE, IODINE AND GAS. ANY ONE OF THESE CHANNELS  :

CAN GIVE THIS ALARM, EITHER WARNING SETPOINT EXCEEDED, OR DETECTOR FAILED LOW. THE REDAS SYSTEM MAY ALSO BE USED TO OBSERVE TREND INFORMATION.

REFERENCES:

DRAWING 208-049-RM-16 SENSING ELEMENT: RADIATION MONITORING PANEL l

j AR-403 Rev. 20 Page 59

. - - ~ _ _ . _ - _ . . . . _ _ _ - -. . . . . _ . . _ - - . _ . - . _ . _ _ . . . . . _ _ . ~ _ . . . _ . - . _ _ - - - _ - _ _

i ENCLOSURE 1 O (Page 58 of 194)

PSA-Z ANNUNCIATOR RESPONSE PSA-Z-02-02 H-02-02 ,

8 ATMOSPHERIC MONITOR WARNING EVENT POINT 1717 INDICATED CONDITION:

o RM-A2 RADIATION MONITOR PUMP FLOW AB0VE NORMAL 03 LESS THAN 5 SCFM.

j

() REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o RM-A2 FLOW INDICATION AT RADIATION MONITORING PANEL.

l

JPERATOR ACTIONS FOR A VALID ALARM:

l o INVESTIGATE CAUSE OF RADIATION PUMP FLOW PROBLEM.

8 DISCUSSION:

RM-A2 MONITORS THE AUXILIARY BUILDING PURGE EXHAUST DUCT. THREE DIFFERENT DETECTORS ARE USED, PARTICULATE, IODINE AND GAS. EITHER A HIGH OR LOW FLOW CAN GIVE THIS ALAP.M. -

REFERENCES:

ORAWING 208-049-RM-02

()' SENSING ELEMENT: RADIATION MONITORING PANEL AR-403 Rev. 20 Page 60

ENCLOSURE 1 l

(] (Page 59 of 194)

() l PSA-Z ANNUNCIATOR RESPONSE PSA-Z-02-02 H-02-02 ATMOSPHERIC MONITOR WARNING EVENT POINT 1719 INDICATED CONDITION:

o RM-A3 RADIATION LEVEL EXCEEDS WARNING SETPOINT, OR o RM-A3 RADIATION MONITOR FAILED LOW

( REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o RM-A3 INDICATION AT RADIATION MONITORING PANEL.

OPERATOR ACTIONS FOR A VALID ALARM:

o INVESTIGATE CAUSE OF HIGH RADIATION, OR LOW MONITOR READING.

['

o OBSERVE AREA MONITORS / RECORDERS FOR TREND INFORMATION.

DISCUSSION:

RM-A3 MONITORS AUXILIARY BUILDING EXHAUST FROM SAMPLE AREA 'D', THE WASTE l GAS COMPRESSOR ROOM, THE WASTE GAS VALVE ALLEY, AND ADJ0INING AREAS. THIS

DETECTOR ONLY HAS A GAS CHANNEL AND EITHER WARNING SETPOINT EXCEEDED OR A l

DETECTOR FAILED LOW WILL GIVE THIS ALARM. THE REDAS SYSTEM MAY ALSO BE USED TO OBSERVE TREND INFORMATION.

7

REFERENCES:

DRAWING 208-049-RM-16 i b) SENSING ELEMENT: RADIATION MONITORING PANEL l

AR-403 Rev. 20 Page 61 l

l ENCLOSURE 1 O (Page 60 of 194)

PSA-Z ANNUNCIATOR RESPONSE PSA-Z-02-02 H-02-02 ATMOSPHERIC PtDNITOR WARNING EVENT POINT 1720 INDICATED CONDITION:

o RM-A3 RADIATION MONITOR PUMP FLOW ABOVE NORMAL OB LESS THAN 5 SCFM.

() REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

l o RM-A3 FLOW INDICATION AT RADIATION MONITORING PANEL.

OPERATOR ACTIONS FOR A VALID ALARM: .

o INVESTIGATE CAUSE OF RADIATION PUMP FLOW PROBLEM.

\

t DISCUSSION:

RM-A3 MONITORS AUXILIARY BUILDING EXHAUST FROM SAMPLE AREA 'D', THE WASTE GAS COMPRESSOR ROOM, THE WASTE GAS VALVE ALLEY, AND ADJOINING AREAS.

THIS DETECTOR ONLY HAS A GAS CHANNEL AND EITHER A HIGH OR LOW FLOW CAN GIVE THIS ALARM.

REFERENCES:

DRAWING 208-049-RM-03 O

\s ,/ SENSING ELEMENT: RADIATION MONITORING PANEL i

AR-403 Rev. 20 Page 62 j

- . . . - - l

ENCLOSURE 1 T

, (/

(Page 61 of 194) i PSA-Z ANNUNCIATOR RESPONSE PS4-Z-02-02 H-02-02 l

l l ATMOSPHERIC MONITOR WARNING t

EVENT P0 INT 1722 1

INDICATED CONDITION:

o RM-A4 RADIATION LEVEL EXCEEDS WARNING SETPOINT, OR o RM-A4 RADIATION MONITOR FAILED LOW (O,j REDUNDANT INDICATION WHICH WILL VERIFY A.LARM:

o RM-A4 INDICATION AT RADIATION MONITORING PANEL.

o SPDS ALPHA PAGE.

OPERATOR ACTIONS FOR A VALID ALARM:

o INVESTIGATE CAUSE OF HIGH RADIATION, OR LOW MONITOR READING. j o OBSERVE AREA MONITORS / RECORDERS FOR TREND INFORMATION.

DISCUSSION:

RM-A4 MONITORS THE SPENT FUEL AREA EXHAUST. THIS DETECTOR ONLY HAS A GAS CHANNEL AND EITHER WARNING SETPOINT EXCEEDED OR A DETECTOR FAILED LOW WILL GIVE THIS ALARM. THE REDAS SYSTEM MAY ALSO BE USED TO OBSERVE TREND INFORMATION.

REFERENCES:

DRAWING 208-049-RM-17 b)

(_ / SENSING ELEMENT: RADIATION MONITORING PANEL AR-403 Rev. 20 Page 63

3 i l 1

4 ENCLOSURE 1 j

(Page 62 of 194).

7 PSA-Z ANNUNCIATOR RESPONSE PSA-Z-02-02 H-02-02 i 1 i i 1 l i  !

1  :

ATMOSPHERIC j MONITOR j WARNING ,
l l

l l EVENT POINT 1723 l i

] INDICATED CONDITION: l l l o RM-A4 RADIATION MONITOR PUMP FLOW ABOVE NORMAL OR LESS THAN 5 SCFM. l 1

1 REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o RM-A4 FLOW INDICATION AT RADIATION MONITORING PANEL.

i OPERATOR ACTIONS FOR A VALID ALARM: l i '

o INVESTIGATE CAUSE OF RADIATION PUMP FLOW PROBLEM. l DISCUSSION

RM-A4 MONITORS THE SPENT FUEL AREA EXHAUST. THIS DETECTOR ONLY HAS A GAS CHANNEL AND EITHER A HIGH OR LOW FLOW CAN GIVE THIS ALARM.

i i

REFERENCES:

ORAWING 208-049-RM-04 SENSING ELEMENT: RADIATION MONITORING PANEL AR-403 Rev. 20 Page 64

I l

l ENCLOSURE 1 (Page 63 of 194)

PSA-Z ANNUNCIATOR RESPONSE- PSA-Z-02-02 H-02-02 ATMOSPHERIC MONITOR WARNING EVENT POINT 1725 ,

1 i

INDICATED CONDITION:

l o RM-A5 RADIATION LEVEL EXCEEDS WARNING SETPOINT, OR l o RM-A5 RADIATION MONITOR FAILED LOW l

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o RM-A5 INDICATION AT RADIATION MONITORING PANEL.

o SPDS ALPHA PAGE.

l OPERATOR ACTIONS FOR A VALID ALARM: 1 l 0 INVESTIGATE CAUSE OF HIGH RADIATION, OR LOW MONITOR READING. ,

o OBSERVE AREA MONITORS / RECORDERS FOR TREND INFORMATION.

DISCUSSION:

RM-A5 MONITORS THE CONTROL COMPLEX RETURN DUCT. THREE DIFFERENT DETECTORS ARE USED, PARTICULATE, IODINE AND GAS. ANY ONE OF THESE CHANNELS CAN GIVE THIS ALARM, EITHER WARNING SETPOINT EXCEEDED, OR DETECTOR FAILED LOW. THE REDAS SYSTEM MAY ALSO BE USED TO OBSERVE TREND INFORMATION.

REFERENCES:

DRAWING 20f-049-RM-18 SENSING ELEMENT: RADI/. TION MONITORING PANEL AR-403 Rev. 20 Page 65

1 l

1 ENCLOSURE 1 (Page 64 of 194) l PSA-Z ANNUNCIATOR RESPONSE PSA-Z-02-02 -

H-02-02 l ATMOSPHERIC ,

MONITOR l WARNING l

( l l

EVENT POINT 1726 INDICATED CONDITION:

o RM-A5 RADIATION MONITOR PUMP FLOW ABOVE NORMAL 03 LESS THAN 5 SCFM.

l REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o RM-A5 FLOW INDICATION AT RADIATION MONITORING PANEL.

l l

OPERATOR ACTIONS FOR A VALID ALARM: l 0 INVESTIGATE CAUSE OF RADIATION PUMP FLOW PROBLEM.

I DISCUSSION:

RM-A5 MONITORS THE CONTROL COMPLEX RETURN DUCT. THREE DIFFERENT DETECTORS ARE USED, PARTICULATE, IODINE AND GAS. EITHER A HIGH OR LOW FLOW CAN GIVE THIS ALARM.

REFERENCES:

DRAWING 208-049-RM-05 SENSING ELEMENT: RADIATION MONITORING PANEL AR-403 Rev. 20 Page 66

j 1 l

l ...

q ENCLOSURE _1 (Page 65 of 194) g l

PSA-Z ANNUNCIATOR RESPONSE PSA-Z-02-02 H-02-02 l l

l ATMOSPHERIC MONITOR l WARNING l EVENT POINT 1728 i

l 5

INDICATED CONDITION:

! o RM-A6 RADIATION LEVEL EXCEEDS WARNING SETPOINT, OR l 0 RM-A6 RADIATION MONITOR FAILED LOW l

1 REDUNDANT INDICATION WHICH WILL VERIFY ALARM

o RM-A6 INDICATION AT RADIATION MONITORING PANEL.

o SPDS ALPHA PAGE.

I OPERATOR ACTIONS FOR A VALID ALARM:

o INVESTIGATE CAUSE OF HIGH RADIATION, OR l LOW MONITOR READING.

o OBSERVE AREA MONITORS / RECORDERS FOR TREND INFORMATION. -

l l

4

DISCUSSION:

l RM-A6 MONITORS THE REACTOR BUILDING ATMOSPHERE. SAMPLE POINTS ARE EITHER AHF-3B DUCT, OR THE RB ATMOSPHERE DIRECTLY. IT IS NORMALLY LINED UP TO THE DUCT OF AHF-3B. IT CAN ALTERNATELY BE LINED UP TO SAMPLE THE RB ATMOSPHERE DIRECTLY PER OP-417.

TWO DIFFERENT DETECTORS ARE USED, PARTICULATE / IODINE AND GAS. ANY ONE OF THESE CHANNELS CAN GIVE THIS ALARM.

THE REDAS SYSTEM MAY ALSO BE USED TO OBSERVE TREND INFORMATION.

[

REFERENCES:

DRAWING 208-049-RM-18 SENSING ELEMENT: RADIATION MONITORING PANEL i

AR-403 Rev. 20 Page 67

ENCLOSURE 1 (Page 66 of 194)

(G PSA-Z ANNUNCIATOR RE5PONSE PSA-Z-02-02 H-02-02 l

l ATMOSPHERIC MONITOR WARNING ,

I l

EVENT POINT 1729 l l

INDICATED CONDITION: l 0 RM-A6 RADIATION MONITOR PUMP FLOW ABOVE NORMAL, LESS THAN 5 SCFM, 03 RMA-6 BACKUP SAMPLE PUMP IS RUNNING.

[v ') REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

i o RM-A6 FLOW INDICATION AT RADIATION MONITORING PANEL. l l

l OPERATOR ACTIONS FOR A VALID ALARM:

)

o INVESTIGATE CAUSE OF RADIATION PUMP FLOW PROBLEM.

DISCUSSION:

EITHER A HIGH OR LOW FLOW CAN GIVE THIS ALARM.

RM-A6 MONITORS THE REACTOR BUILDING ATMOSPHERE. SAMPLE POINTS AR EITHER AHF-3B DUCT, OR THE RB ATMOSPHERE DIRECTLY. IT IS NORMALLY LINED UP TO THE DUCT OF AHF-3B. IT CAN ALTERNATELY BE LINED UP TO SAMPLE THE RB ATMOSPHERE DIRECTLY PER OP-417.

TWO DIFFERENT DETECTORS ARE USED, PARTICULATE / IODINE AND GAS. ANY ONE OF THESE CHANNELS CAN GIVE THIS ALARM.

THE REDAS SYSTEM MAY ALSO BE USED TO OBSERVE TREND INFORMATION.

(~}

REFERENCES:

DRAWING 208-049-RM-06 SENSING ELEMENT: RADIATION MONITORING PANEL AR-403 Rev. 20 Page 68

1 ENCLOSURE 1 (Page 67 of 194)

PSA-Z ANNUNCIATOR RESPONSE PSA-Z-02-02 H-02-02 ATMOSPHERIC MONITOR WARNING ,

EVENT POINT 1731 INDICATED CONDITION:

o RM-A7 RADIATION LEVEL EXCEEDS WARNING SETPOINT, OR o RM-A7 RADIATION MONITOR FAILED LOW REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o RM-A7 INDICATION AT RADIATION MONITORING PANEL. ]

l l

l l OPERATOR ACTIONS FOR A VALID A! ARM:

l l o INVESTIGATE CAUSE OF HIGH RADIATION, OR l LOW MONITOR READING.

l o OBSERVE AREA MONITORS / RECORDERS FOR TREND INFORMATION.

DISCUSSION:

RM-A7 MONITORS THE AHF-44A/B DISCHARGE AIR, THEREFORE THE ATMOSPHERES OF 1

! THE PRIMARY SAMPLE ROOM, PRIMARY SAMPLE ROOM SAMPLE HOOD, RADIO CHEMISTRY l LAB SAMPLE HOODS, AND/0R PASS SYSTEM VALVE ALLEY MAY HAVE HIGH l GASE0US ACTIVITY. THE REDAS SYSTEM MAY ALSO BE USED TO OBSERVE TREND l INFORMATION.

REFERENCES:

DRAWING 208-049-RM-19 SENSING ELEMENT: RADIATION MONITORING PANEL l

l AR-403 Rev. 20 Page 69

\ - -. . - _ - . . - - . - ,,

l ENCLOSURE 1

] (Page 68 of 194) 1 PSA-Z ANNUNCIATOR RESPONSE PSA-Z-02-02 H-02-02 l l

l l

ATMOSPHERIC i l

MONITOR l WARNING l

i EVENT POINT 1732 j INDICATED CONDITION:

l o RM-A7 RADIATION MONITOR PUMP FLOW AB0VE NORMAL M LESS THAN 5 SCFM. j i

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

l 0 RM-A7 FLOW INDICATION AT RADIATION MONITORING PANEL.

l l

OPERATOR ACTIONS FOR A VALID ALARM:

l o INVESTIGATE CAUSE OF RADIATION PUMP FLOW PROBLEM. -

l DISCUSSION:

EITHER A HIGH OR LOW FLOW CAN GIVE THIS ALARM. RM-A7 MONITORS THE AHF-44A/B DISCHARGE AIR, THEREFORE THE ATMOSPHERES OF THE PRIMARY SAMPLE ROOM, PRIMARY SAMPLE ROOM SAMPLE HOOD, RADIO CHEMISTRY LAB SAMPLE HOODS, AND/0R PASS SYSTEM VALVE ALLEY MAY HAVE HIGH GASEOUS ACTIVITY. THE REDAS SYSTEM MAY ALSO BE USED TO OBSERVE TREND INFORMATION.

I

REFERENCES:

DRAWING 208-049-RM-07 SENSING ELEMENT: RADIATION MONITORING PANEL l

AR-403 Rev. 20 Page 70 1

ENCLOSURE I

.O, l (Page 69 of 194)

PSA-Z ANNUNCIATOR RESPONSE PSA-Z-02-02 H-02-02 i

ATMOSPHERIC' MONITOR WARNING J

! EVENT POINT 1734 ,

INDICATED CONDITION: ,

! o RM-A8 RADIATION LEVEL EXCEEDS WARNING SETPOINT, OR

o RM-A8 RADIATION MONITOR FAILED LOW.

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

I.

1 o RM-A8 INDICATION AT RADIATION MONITORING PANEL.

o SPDS ALPHA PAGE.

)

OPERATOR ACTIONS FOR A VALID ALARM:

i

< o INVESTIGATE CAUSE OF HIGH RADIATION, OR -

i LOW MONITOR READING.

3 i o 0BSERVE AREA MONITORS / RECORDERS FOR TREND INFORMATION.

.l .

d l DISCUSSION:

I RM-A8 MONITORS THE AUXILIARY BUILDING EXHAUST UPSTREAM 0F THE PENETRATION FOR THE FUEL HANDLING FLOOR EXHAUST. THIS DETECTOR ONLY HAS A GAS CHANNEL AND, EITHER WARNING SETPOINT EXCEEDED, OR DETECTOR FAILED LOW WILL GIVE THIS ALARM. THE REDAS SYSTEM MAY ALSO BE USED TO OBSERVE TREND INFORMATION.

REFERENCES:

DRAWING 208-049-RM-16

, O lV SENSING ELEMENT: RADIATION MONITORING PANEL 4

AR-403 Rev. 20 Page 71 4

3 -, ,. .- .- . , - -

- .- . ,. - , _ . . - . ~ . . .- - _. . . . . .

t i

ENCLOSURE 1 l

(Page 70 of 194) l I

PSA-Z ANNUNCIATOR RESPONSE PSA-Z-02-02 H-02-02 j l

ATMOSPHERIC MONITOR.  !

WARNING l l

l EVENT POINT 1735 i l

i l

INDICATED CONDITION: i o RM-A8 RADIATION MONITOR PUMP FLOW AB0VE NORMAL 03 LESS THAN 5 SCFM.

REDUNDANT INDICATION WHICH WILL VERIFY ALARM: l o RM-A8 FLOW INDICATION AT RADIATION MONITORING PANEL.

i i

OPERATOR ACTIONS FOR A VALID ALARM:

l o INVESTIGATE CAUSE OF RADIATION PUMP FLOW PROBLEM.

]

DISCUSSION:

RM-A8 MONITORS THE AUXILIARY BUILDING EXHAUST UPSTREAM 0F THE PENETRATION FOR THE FUEL HANDLING FLOOR EXHAUST. THIS DETECTORS ONLY HAS A GAS CHANNEL AND, EITHER A HIGH OR LOW FLOW CAN GIVE THIS ALARM.

REFERENCES:

DRAWING 208-049-RM-08 O

V SENSING ELEMENT: RADIATION MONITORING PANEL I

AR-403 Rev. 20 Page 72

j i

1 ENCLOSURE 1 ,

]q (Page 71 of 194) .

i

- PSA-Z ANNUNCIATOR RESPONSE PSA-Z-02-02 H-02-02 1

i I

i ATMOSPHERIC

MONITOR WARNING '

I I EVENT POINT 1737 i 1 I

! INDICATED CONDITION:

o RM-All RADIATION LEVEL EXCEEDS WARNING SETPOINT, OR o RM-All RADIATION MONITOR FAILED LOW-REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

j o RM-All INDICATION AT RADIATION MONITORING PANEL.

OPERATOR ACTIONS FOR A VALID ALARM:

o INVESTIGATE CAUSE OF HIGH RADIATION, OR i i LOW MONITOR READING.

  • 0

, o OBSERVE AREA MONITORS / RECORDERS FOR TREND INFORMATION.

e DISCUSSION: l RM-All MONITORS THE AUXILIARY BUILDING EXHAUST PENETRATION FOR THE WASTE GAS RELEASE PATH. THIS DETECTOR ONLY HAS A GAS CHANNEL AND, EITHER WARNING SETPOINT EXCEEDED, OR DETECTOR FAILED LOW CAN GIVE THIS ALARM. THE REDAS SYSTEM MAY ALSO BE USED TO OBSERVE TREND INFORMATION.

REFERENCES:

DRAWING 208-049-RM-20 SENSING ELEMENT: RADIATION MONITORING PANEL AR-403 Rev. 20 Page 73

ENCLOSURE 1 (Page 72 of 194)

PSA-Z ANNUNCIATOR RESPONSE PSA-Z-02-02 H-02-02 k

ATMOSPHERIC MONITOR WARNING EVENT POINT 1739 .

INDICATED CONDITION:

o RM-A12 RADIATION LEVEL EXCEEDS WARNING SETPOINT, OR o RM-AI2 RADIATION MONITOR FAILED LOW REDUNDANT INDICATION WHICH WILL VERIFY ALARM:  !

o RM-AI2 FLOW INDICATION AT RADIATION MONITORING PANEL.  ;

o MAIN STEAM LINE RAD MONITORS RMG-25, RMG-26, RMG-27, AND/0R RMG-28 READ l HIGHER THAN NORMAL.

i l

OPERATOR ACTIONS FOR A VALID ALARM:

o INVESTIGATE CAUSE OF RADIATION PUMP FLOW PROBLEM.

I DISCUSSION:

RM-AI2 MONITORS THE AUXILIARY BUILDING EXHAUST PENETRATION FOR SECONDARY  !

PLANT CONDENSER OFF GAS. THIS DETECTOR ONLY HAS A GAS CHANNEL AND,EITHER i WARNING SETPOINT EXCEEDED OR DETECTOR FAILED LOW CAN GIVE THIS ALARM.

REFERENCES:

DRAWING 208-049-RM-20 SENSING ELEMENT: RADIATION MONITORING PANEL AR-403 Rev. 20 Page 74

ENCLOSURE 1

(~~} (Page 73 of 194) q ,/

PSA-Z ANNUNCIATOR RESPONSE PSA-Z-02-02 H-02-02 ATMOSPHERIC MONITOR WARNING EVENT POINT 1741 INDICATED CONDITION:

o RM-A13 RADIATION LEVEL EXCEEDS WARNING SETPOINT, OR o RM-A13 RADIATION MONITOR FAILED LOW I ) REDUNDANT INDICATION WHICH WILL VERIFY ALARH:

L.-

o RM-A13 INDICATION AT RADIATION MONITORING PANEL.

OPERATOR ACTIONS FOR A VALID ALARM:

o INVESTIGATE CAUSE OF HIGH RADIATION, OR LOW MONITOR READING.

3 o OBSERVE AREA MONITORS / RECORDERS FOR TREND INFORMATION.

DISCUSSION:

RM-A13 MONITORS THE WASTE GAS SAMPLING STATION AREA. (SAMPLE AREA 'D')

THIS DETECTOR ONLY HAS A GAS CHANNEL AND, EITHER WARNING SETPOINT EXCEEDED OR A DETECTOR FAILED LOW CAN GIVE THIS ALARM. THE REDAS SYSTEM MAY ALSO BE USED TO OBSERVE TREND INFORMATION.

REFERENCES:

DRAWING 208-049-RM-21

) SENSING ELEMENT: RADIATION MONITORING PANEL AR-403 Rev. 20 Page 75

i L .

l ENCLOSURE 1

) (Page 74 of 194) l PSA-Z ANNUNCIATOR RESPONSE PSA-Z-02-04 H-02-04 l

EDAS l l SYSTEM TROUBLE EVENT POINT 2045' 1

, INDICATED CONDITION:

l i o LOSS OF MULTIPLEXER POWER. ]

o PRIMARY METEOROLOGICAL TOWER ON BACKUP POWER. i o PRIMARY METEOROLOGICAL TOWER BACKUP POWER OUT OF SYNCHRONIZATION.

o PRIMARY METEOROLOGICAL TOWER SIGNAL FAILURE.

o PRIMARY METEOROLOGICAL TOWER BUILDING TEMPERATURE HIGH/ LOW.

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o PRIMARY METEOROLOGICAL ALARM PANEL.

OPERATOR ACTIONS FOR A VALID ALARM:

o INVESTIGATE CAUSE OF ALARM CONDITION.

DISCUSSION:

l

REFERENCES:

SENSING ELEMENT: MMP-3 METEOROLOGICAL ALARM PANEL AR-403 Rev. 20 Page 76

l l

I l

FNCLOSURE 1  !

(Page 75 of 194)

! l PSA-Z ANNUNCIATOR RESPONSE PSA-Z-02-05 H-02-05  ;

i I

l l COND PUMP PIT l l SUMP LEVEL i l HIGH j l

l EVENT POINT 1329 i I

I l

INDICATED CONDITION:

o CONDENSATE PUMP PIT SUMP A LEVEL >88.6' ELEVATION AS SENSED BY SD-31-LS.

l l l

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

l l

l l

OPERATOR ACTIONS FOR A VALID ALARM:

o REFER TO AP-1050. -

o NOTIFY SECONDARY PLANT OPERATOR TO INVESTIGATE CAUSE OF ALARM CONDITION.

f a

DISCUSSION:

4 l

l

REFERENCES:

DRAWING 208-072-SD-07 SENSING ELEMENT: SD-31-LS l

l- AR-403 Rev. 20 Page 77 l

i i ENCLOSURE 1 (Page 76 of 194)

PSA-Z ANNUNCIATOR RESPONSE PSA-Z-02-05 H-02-05 i

i I

l j COND PUMP PIT

! SUMP LEVEL

] l HIGH i

i

! EVENT POINT 1317

! l 4 i j INDICATED CONDITION:

i o CONDENSATE PUMP PIT SUMP B LEVEL >88.6' ELEVATION AS SENSED BY SD-32-LS.

1 i

REDUNDANT INDICATION WHICH WILL VERIFY ALARM

i i OPERATOR ACTIONS FOR A VALID ALARM:

o REFER TO AP-1050.

j o NOTIFY SECONDARY PLANT OPERATOR TO INVESTIGATE CAUSE OF ALARM CONDITION.

l i l DISCUSSION:

i

REFERENCES:

DRAWING 208-072-SD-08 SENSING ELEMENT: SD-32-LS 4

AR-403 Rev. 20 Page 78 y . , - . ~ . -- .-.,-.-u - ~ - - . - - - - , , , - - . - , , - - , - - , - -

i ENCLOSURE 1 l (Page 77 of 194)

PSA-Z ANNUNCIATOR RESPONSE PSA-Z-02-06 H-02-06 i

AUX BLDG SUMP LEVEL-HIGH EVENT POINT 1292 ,

INDICATED CONDITION:

j o DECAY HEAT PIT SUMP A LEVEL >74' ELEVATION AS SENSED BY WD-133-LS.

. O i i V REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

l l

OPERATOR ACTIONS FOR A VALID ALARM: 1 i

l o NOTIFY PRIMARY PLANT OPERATOR TO INVESTIGATE CAUSE OF ALARM CONDITION.

i, f-1 DISCUSSION:

l l

REFERENCES:

DRAWING 208-060-WD-09 SENSING ELEMENT: WD-133-LS O

AR-403 Rev. 20 Page 79

ENCLOSURE 1 O (Page 78 of 194)

PSA-Z ANNUNCIATOR RESPONSE PSA-Z-02-06 H-02-06 4

AUX BLDG j SUMP LEVEL l HIGH l

l EVENT POINT 1305

?

INDICATED CONDITION:

o DECAY HEAT PIT SUMP B LEVEL >74' ELEVATION AS SENSED BY WD-134-LS.

O REDUNDANT INDICATION WHICH WILL VERIFY ALARM: '

OPERATOR ACTIONS FOR A VALID ALARM:

o NOTIFY PRIMARY PLANT OPERATOR TO INVESTIGATE CAUSE OF ALARM CONDITION.

j DISCUSSION:

REFERENCES:

DRAWING 208-060-WD-10 SENSING ELEMENT: WD-134-LS O

AR-403 Rev. 20 Page 80

l ENCLOSURE 1 O (Page 79 of 194)

PSA-Z ANNUNCIATOR RESPONSE PSA-Z-02-06 H-02-06 AUX BLDG SUMP LEVEL HIGH EVENT POINT 1300 l

INDICATED CONDITION:

o AUXILIARY BUILDING SUMP LEVEL >92.5' ELEVATION AS SENSED BY WD-132-LS.

O REDUNDANT INDICATION WHICH WILL VERIFY ALARH:

OPERATOR ACTIONS FOR A VALID ALARM:

o NOTIFY PRIMARY PLANT OPERATOR TO INVESTIGATE CAUSE OF ALARM CONDITION. -

i t

l DISCUSSION:

REFERENCES:

DRAWING 208-060-WD-12 l SENSING ELEMENT: WD-132-LS 1

O l

l AR-403 Rev. 20 Page 81

i l

l e ENCLOSURE 1

( )s (Page 80 of 194) l PSA-Z ANNUNCIATOR RESPONSE lPSA-Z-02-06 H-02-06 l

l

! AUX BLDG SUMP LEVEL HIGH EVENT POINT 1809 l

l l

l INDICATED CONDITION:

o NUCLEAR SERVICE COOLER AREA SUMP >93.5' ELEVATION AS SENSED BY SD-5-LS3.

fm U

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

OPERATOR ACTIONS FOR A VALID ALARM:

o NOTIFY PRIMARY PLANT OPERATOR TO INVESTIGATE CAUSE OF ALARM CONDITION.

DISCUSSION:

l

REFERENCES:

DRAWING 208-072-SD-03 SENSING ELEMENT: SD-5-LS3

, -~3

'% r AR-403 Rev. 20 Page 82

a ENCLOSURE 1 O (Page 81 of 194)

PSA-Z ANNUNCIATO,R RE5PONSE PSA-2-02-06 H-02-06 AUX BLDG SUMP LEVEL EVENT POINT 1810 ,.

~

INDICATED CONDITION:

o TENDON ACCESS GALLERY SUMP >72.5' ELEVATION AS SENSED BY SD-6-LS3.

l O

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

OPERATOR ACTIONS FOR A VALID ALARM:

o NOTIFY PRIMARY PLANT OPERATOR TO INVESTIGATE CAUSE OF ALARM CONDITION.

i.

DISCUSSION:

REFERENCES:

DRAWING 208-072-SD-05 SENSING ELEMENT:_yD-6-LS3 AR-403 Rev. 20 Page 83

l ENCLOSURE 1 t (Page 82 of 194)

PSA-Z ANNUNCIATOR RESPONSE PSA-Z-02-07 H-02-07 l

BLDG SUMPS SUMP PUMP TROUBLE

)

EVENT POINT 1198 i

INDICATED CONDITION:

l o DIESEL GENERATOR SUMP A/B LEVEL HIGH AS SENSED BY EG-027-LS. l O

l REDUNDANT INDICATION \'HICH WILL VERIFY ALARM:

OPERATOR ACTIONS FOR A VALID ALARM:

o NOTIFY PRIMARY PLANT OPERATOR TO INVESTIGATE CAUSE OF ALARM CONDITION.

DISCUSSION:

REFERENCES:

DRAWING 208-027-EG-17 SENSING ELEMENT: EG-027-LS.

O AR-403 Rev. 20 Page 84

ENCLOSURE 1 O (Page 83 of 194)

PSA-Z ANNUNCIATOR RESPONSE PSA-Z-02-07 H-02-07 i

BLDG SUMPS SUMP PUMP l

! TROUBLE l I

i EVENT POINT 1586

? '

l INDICATED CONDITION: )

i o DECAY HEAT PIT SUMP PUMP AUTO START.

j o DECAY HEAT PIT SUMP PUMP TRIP.

! bl l REDUNDANT INDICATION WHICH WILL VERIFY ALARM: i i

OPERATOR ACTIONS FOR A VALID ALARM:

o NOTIFY PRIMARY PLANT OPERATOR TO INVESTIGATE CAUSE OF ALARM CONDITION. ,

d i

l i

DISCUSSION:

THIS ALARM MAY INDICATE AN AUTO SHUT DOWN IF THE PRIMARY PLANT OPERATOR ,

MANUALLY STARTED THE DECAY HEAT PIT SUMP PUMP. THE ALARM IS BASED ON THE ,

PUMP CONTROL SWITCH CONTACTS (NORMAL AFTER START OR NORMAL AFTER STOP)

IN SERIES WITH THE SUMP LEVEL SWITCH.

REFERENCES:

DRAWING 208-060-WD-09, WD-10, WD-134 SENSING ELEMENT: WD-133-LS, WD-134-LS, WDP-3A/3B CONTROL SWITCH CONTACTS.

l AR-403 Rev. 20 Page 85

~%, ENCLOSURE 1 (V (Page 84 of 194)

PSA-Z ANNUNCIATOR RESPONSE PSA-Z-02-07 H-02-07 BLDG SUMPS SUMP PUMP TROUBLE EVENT POINT 1587 ,

INDICATED CONDITION:

o AUXILIARY BUILDING SUMP PUMP AUTO START.

o AUXILIARY BUILDING SUMP PUMP TRIP.

o WASTE GAS COMPRESSOR SEAL LEAKAGE DRAIN TANK LOW LEVEL.

l REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

OPERATOR ACTIONS FOR A VALID ALARM:

l 0 NOTIFY PRIMARY PLANT OPERATOR TO INVESTIGATE CAUSE OF ALARM CONDITION.

i DISCUSSION: j THIS ALARM MAY INDICATE AN AUTO SHUT DOWN IF THE PRIMARY PLANT OPERATOR MANUALLY STARTED THE AUXILIARY BUILDING SUMP PUMP (S). THE ALARM IS BASED ON THE PUMP CONTROL SWITCH CONTACTS (NORMAL AFTER STAPT/STOP) IN SERIES WITH THE SUMP LEVEL SWITCH. THE WASTE GAS COMPRESSOR 3EAL LEAKAGE DRAIN TANK CAN GIVE THIS ALARM BY OPERATING WDV-1030-SV TO LOWER THE DRAIN TANK LEVEL UNTIL THE LOW LEVEL SWITCH CONTACT OPENS. (SEE DRAWING WD-175)

REFERENCES:

DRAWING 208-060-WD-II, WD-12, WD-135, WD-175 O

V SENSING ELEMENT: WD-132-LS, WDP-4A/4B CONTROL SWITCH CONTACTS.

l l

AR-403 Rev. 20 Page 86

4 4

i

ENCLOSURE 1 (Page 85 of 194) i

PSA-Z ANNUNCIATOR RESPONSE PSA-2-02-07 H-02-07 i

l 1'

BLDG SUMPS j SUMP PUMP 4 TROUBLE

I EVENT POINT 1589 ,

1 I INDICATED CONDITION:

4 o LAUNDRY AND SHOWER SUMP PUMP AUTO START.

o LAUNDRY AND SHOWER SUMP PUMP TRIP. l

REDUNDANT INDICATION WHICH WILL VERIFY ALARM

i 1

1

OPERATOR ACTIONS FOR A VALID ALARM
I 5

DISCUSSION: 1 i

REFERENCES:

SENSING ELEMENT:

O

-AR-403 Rev. 20 Page 87

l 4

a i ENCLOSURE 1 3 (Page 86 of 194) i PSA-Z ANNUNCIATOR RESPONSE PSA-Z-02-07 H-02-07 l l

BLDG SUMPS SUMP PUMP TROUBLE t

l EVENT POINT 1806 ,i INDICATED CONDITION:

o DIESEL GENERATOR ROOM 'A' SUMP LEVEL HIGH AS SENSED BY SD-19-LS.

O REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

OPERATOR ACTIONS FOR A VALID ALARM:

o NOTIFY PRIMARY PLANT OPERATOR TO INVESTIGATE CAUSE OF HIGH LEVEL. -

4 DISCUSSION: *

REFERENCES:

DRAWING 208-072-SD-IS.

SENSING ELEMENT: SD-19-LS O

AR-403 Rev. 20 Page 88

l i '

l I l

(

(y s ENCLOSURE 1 (Page 87 of 194) j PSA-Z ANNUNCIATOR RESPONSE PSA-Z-02-07 H-02-07 l

l BLDG SUMPS SUMP PUMP l TROUBLE l EVENT POINT 1807 INDICATED CONDITION:

! o DIESEL GENERATOR ROOM 'B' SUMP LEVEL HIGH AS SENSED BY SD-20-LS. l O l REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

OPERATOR ACTIONS FOR A VALID ALARM: i l

o NOTIFY PRIMARY PLANT OPERATOR TO INVESTIGATE CAUSE OF HfGH LEVEL.

6 l

DISCUSSION:

i l

REFERENCES:

DRAWING 208-072-SD-16.  !

SENSING ELEMENT: SD-19-LS AR-403 Rev. 20 Page 89

ENCLOSURE 1 (Page 88 of 194)

PSA-Z' ANNUNCIATOR RESPONSE PSA-Z-02-07 H-02-07 BLDG SUMPS SUMP PUMP TROUBLE.

l EVENT POINT 1811 INDICATED CONDITION:

o INTAKE ELECTRIC VAULT SUMP LEVEL HIGH AS SENSED BY SD-14-LS.

Ii REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

l

OPERATOR ACTIONS FOR A VALID ALARM

l o NOTIFY SECONDARY PLANT OPERATOR TO INVESTIGATE CAUSE OF HIGH LEVEL. 1 b

DISCUSSION: 4 l

REFERENCES:

DRAWING 208-072-SD-09.

SENSING ELEMENT: SD-14-LS l

l AR-403 Rev. 20 Page 90

l ENCLOSURE 1

~

O, (Page 89 of 194) '

PSA-Z ANNUNCIATOR RESPONSE PSA-Z-02-07 H-02-07 l l

BLDG SUMPS SUMP PUMP TROUBLE I EVENT POINT 1880 l I

l l INDICATED CONDITION: l l

o TURBINE ROOM SUMP LEVEL HIGH AS SENSED BY SD-24-LS i

OE  ;

! o OILY WATER SEPARATOR TROUBLE O  :

REDUNDANT INDICATION WHICH WILL VERIFY ALARM ,

OPERATOR ACTIONS FOR A VALID ALARM:

o NOTIFY SECONDARY PLANT OPERATOR TO INVESTIGATE CAUSE OF HIGH LEVEL AND/0R OILY WATER 5EPARATOR PROBLEM ,

DISCUSSION:

OILY WATER SEPARATOR TROUBLE MAY BE CAUSED BY ANY OF THE FOLLOWING:  !

HIGH/ LOW VACUUM PREFILTER HIGH AP OIL DISCHARGE l EMERGENCY STOP WHEN IN AUTO -

THE ALARM WINDOW DOES NOT TYPE "0ILY WATER SEPARATOR TROUBLE" BUT IN FACT IS LABELED " TURBINE BUILDING SUMP LEVEL HIGH".

REFERENCES:

DRAWING 208-072 SD-01, SD-17.

SENSING ELEMENT: SD-24-LS, SD-24-DPIS, SD-26-PIS AR-403 Rev. 20 Page 91

ENCLOSURE 1 O (Page 90 of 194)

PSA-Z ANNUNCIATOR RESPONSE PSA-Z-02-07 H-02-07 BLDG SUMPS l SUMP PUMP TROUBLE l

i EVENT POINT 1913 '

l INDICATED CONDITION:

l 0 SEWAGE PUMP SUMP LEVEL HIGH AS SENSED BY LOCAL CIRCUIT.

l l

l

!O REDUNDANT INDICATION WHICH WILL VERIFY ALARM: i o SEP-1A AND/0R SEP-1B RUNNING. I I

OPERATOR ACTIONS FOR A VALID ALARM:

o NOTIFY TURBINE BUILDING OPERATOR TO ENSURE LEVEL DOES NOT OVERFLOW ONTO l TURBINE BUILDING FLOOR AND THAT SEP-1A AND OR SEP-1B ARE RUNNING TO [

LOWER LEVEL.

l ,

i DISCUSSION:

i l

REFERENCES:

DRAWING 208-064 ME-10

.' SENSING ELEMENT: R1.

AR-403 Rev. 20 Page 92 l

r' ENCLOSURE 1

( (Page 91 of 194) 1 PSA-Z ANNUNCIATOR RESPONSE PSA-Z-02-08 H-02-08 I I l l SEC SAMPLE  !

I I SYSTEM )

I I ALARM I J

I I Z

l EVENT POINT 0798 t l

i INDICATED CONDITION:

)

o HOTWELL/ CONDENSATE CONDUCTIVITY HIGH.

O REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o SS-141-CIR, CONDUCTIVITY RECORDER ON HVAC SECTION OF MCB.

o COMPUTER POINTS A-100 TO A-104.

OPERATOR ACTIONS FOR A VALID ALARM:

o NOTIFY SECONDARY CHEMISTRY TO INVESTIGATE CAUSE OF HIGH CONDUCTIVITY.

o REFER TO CP-138 j DISCUSSION:

l l

l

REFERENCES:

DRAWING 208-054-SS-10 SENSING ELEMENT: SS-141-CIR l

1 AR-403 Rev. 20 Page 93 i

a-J m, I

A ENCLOSURE 1 (Page 92 of 194)

V PSA-Z ANNUNCIATOR RESPONSE PSA-Z-02-08 H-02-08 i

1 I I l l l SEC SAMPLE l I i SYSTEM l 1 l ALARM i i l i

EVENT POINT 0887 i INDICATED CONDITION:

o SECONDARY CYCLE SAMPLE ANALYSIS ALARM.

I l l REDUNDANT INDICATION WHICH WILL VERIFY ALARM OPERATOR ACTIONS FOR A VALID ALARM:

o NOTIFY SECONDARY CHEMISTRY TO INVESTIGATE CAUSE OF SAMPLE ALARM. j d

DISCUSSION:

THIS ALARM INDICATES AN ALARM HAS NOT BEEN ACKNOWLEDGED IN THE SECONDARY l CHEMISTRY LABORATORY WITHIN AN ADJUSTABLE TIMER SETTING.

REFERENCES:

DRAWING 208-054-SS-11 SENSING ELEMENT: SSCP-1 (SECONDARY CYCLE SAMPLE ANALYZER PANEL) l l

AR-403 Rev. 20 - Page 94

, 1 l

l ENCLOSURE 1 l

(Page 93 of 194)

PSA-Z ANNUNCIATOR RESPONSE PSA-Z-03-01 H-03-01 LIQUID RADIATION HIGH l

. EVENT POINT 1786 1

INDICATED CONDITION: ,

1 o RM-L1 RADIATION LEVEL EXCEEDS HIGH SETPOINT. l l

1 REDUNDANT INDICATION WHICH WILL VERIFY ALARM: l 0 RM-L1 INDICATION AT RADIATION MONITORING PANEL.

o SPDS ALPHA PAGE OPERATOR ACTIONS FOR A VALID ALARM.

b o INVESTIGATE CAUSE OF HIGH RADIATION.

o REFER TO OP-301, OPERATION OF THE REACTOR COOLANT SYSTEM.

  • DISCUSSION:

REFERENCES:

DRAWING 208-049-RM-32

() SENSING ELEMENT: RADIATION MONITORING PANEL AR-403 Rev. 20 Page 95

E l

ENCLOSURE 1 (Page 94 of 194)

PSA-Z ANNUNCIATOR RESPONSE PSA-2-03-01 H-03-01 i l LIQUID l l RADIATION I I HIGH I I I I I i

, EVENT POINT 1788 l 1 INDICATED CONDITION:

o RM-L2 RADIATION LEVEL EXCEEDS HIGH SETPOINT.

l l

1 REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o RM-L2 INDICATION AT RADIATION MONITORING PANEL.

o SPDS ALPHA PAGE OPERATOR ACTIONS FOR A VALID ALARM:

o INVESTIGATE CAUSE OF HIGH RADIATION.

o NOTIFY PRIMARY PLANT OPERATOR TO ENSURE WDV-891 AND WDV-892 CLOSED.

DISCUSSION:

WDV-891 AND WDV-892 ARE PRIMARY LIQUID RELEASE VALVES.

REFERENCES:

DRAWING 208-049-RM-31 0

Q SENSING ELEMENT: RADIATION MONITORING PANEL AR-403 Rev. 20 Page 96

l ENCLOSURE 1 1

(Page 95 of 194)

PSA-Z ANNUNCIATOR RESPONSE PSA-Z-03-01 H-03-01 LIQUID RADIATION

HIGH l EVENT POINT 1792 -

l l

INDICATED CONDITION:

o RM-L3 RADIATION LEVEL EXCEEDS HIGH SETPOINT.

l l

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o RM-L3 INDICATION AT RADIATION MONITORING PANEL.

OPERATOR ACTIONS FOR A VALID ALARM:

l 0 INVESTIGATE CAUSE OF HIGH RADIATION.

l o REFER TO OP-301, OPERATION OF THE REACTOR COOLANT SYSTEM.

l l

l DISCUSSION:

1

REFERENCES:

DRAWING 208-049-RM-32 SENSING ELEMENT: RADIATION MONITORING PANEL I AR-403 Rev. 20 Page 97 l

'-- . . - , ~ - . . . _ - . - . . _ -. - ~

1 ENCLOSURE 1 (Page 96 of 194)

PSA-Z ANNUNCIATOR RESPONSE PSA-Z-03-01 H-03-01 l

Z K i i ZZZZ LIQUID l l l RADIATION I I HIGH I I I I I I <

EVENT POINT 1794  !

INDICATED CONDITION:  !

o RM-L5 RADIATION LEVEL EXCEEDS HIGH SETPOINT.

O l

REDUNDANT INDICATION WHICH WILL VERIFY ALARM: '

I l

o RM-L5 INDICATION AT RADIATION MONITORING PANEL.

OPERATOR ACTIONS FOR A VALID ALARM: -

o INVESTIGATE CAUSE OF HIGH RADIATION.

o REFER TO OP-301, OPERATION OF THE REACTOR COOLANT SYSTEM.

DISCUSSION:

1

REFERENCES:

DRAWING 208-049-RM-32 SENSING ELEMENT: RADIATION MONITORING PANEL 1

i

[

i AR-403 Rev. 20 Page 98

,,.e

, ..,,,-.~w,,,-- , . . , , , . - , . , - , , , , . , , , - e ..n, . , ,,n~ , . , _ , , , ,,,w,,,, ,<n-, ,,ar- ew....,.,.. ,- .

i i

I ENCLOSURE 1 l

(Page 97 of 194)

PSA-Z ANNUNCIATOR RESPONSE PSA-Z-03-01 H-03-01 l

LIQUID I RADIATION I HIGH j l I

I EVENT POINT 1796 1:

INDICATED CONDITION:

i o RM-L6 RADIATION LEVEL EXCEEDS HIGH SETPOINT.

(  :

lO i

REDUNDANT INDICATION WHICH WILL VERIFY ALARM-  !

1 o RM-L6 INDICATION AT RADIATION MONITORING PANEL.

1 OPERATOR ACTIONS FOR A VALID ALARM: -

i o INVESTIGATE CAUSE OF HIGH RADIATION. I' l 0 REFER TO OP-301, OPERATION OF THE REACTOR COOLANT SYSTEM.

DISCUSSION:

l l

REFERENCES:

DRAWING 208-049-RM-32 SENSING ELEMENT: RADIATION MONITORING PANEL AR-403 Rev. 20 Page 99

l 1

ENCLOSURE 1

/ (Page 93 of 194) l PSA-Z ANNUNCIATOR RESPONSE PSA-Z-03-01 H-03-01 i

i LIQUID l RADIATION I HIGH I

I I

EVENT POINT 1798 ,l i

I INDICATED CONDITION:

o RM-L7 RADIATION LEVEL EXCEEDS HIGH SETPOINT.

O l REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o RM-L7 INDICATION AT RADIATION MONITORING PANEL. )

o SPDS ALPHA PAGE. j OPERATOR ACTIONS FOR A VALID ALARM:

o INVESTIGATE CAUSE OF HIGH RADIATION.

o NOTIFY PRIMARY PLANT OPERATOR TO ENSURE SDV-90 CLOSED.

l i

I I

DISCUSSION:

SDV-90 IS THE SECONDARY LIQUID RELEASE VALVE.

l l

REFERENCES:

DRAWING 208-049-RM-31 SENSING ELEMENT: RADIATION MONITORING PANEL AR-403 Rev. 20 Page 100

l l ENCLOSURE 1 (Page 99 of 194) l l PSA-Z ANNUNCIATOR RESPONSE PSA-Z-03-02 H-03-02 LIQUID MONITOR WARNING t

EVENT POINT 1787 INDICATED CONDITION:

o RM-L1 RADIATION LEVEL EXCEEDS WARNING SETPOINT.

i o

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o RM-LI INDICATION AT RADIATION MONITORING PANEL.

o SPDS ALPHA PAGE OPERATOR ACTIONS FOR A VALID ALARM:

o INVESTIGATE CAUSE OF HIGH RADIATION.

o REFER TO OP-301, OPERATION OF THE REACTOR COOLANT SYSTEM.

DISCUSSION:

REFERENCES:

DRAWING 208-049-RM-32 SENSING ELEMENT: RADIATION MONITORING PANEL i

l AR-403 Rev. 20 Page 101

l l

l A ENCLOSURE 1 V (Page 100 of 194)

PSA-Z ANNUNCIATOR RESPONSE PSA-2-03-02 H-03-02 LIQUID MONITOR WARNING 7

i EVENT POINT 1789 i  !

INDICATED CONDITION: ,

o RM-L2 RADIATION LEVEL EXCEEDS WARNING SETPOINT.

l l

l0/

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o RM-L2 INDICATION AT RADIATION MONITORING PANEL.

o SPDS ALPHA PAGE l

l OPERATOR ACTIONS FOR A VALID ALARM: i o INVESTIGATE CAUSE OF HIGH RADIATION.

]  !

l l DISCUSSION:

REFERENCES:

DRAWING 208-049-RM-31

( SENSING ELEMENT: RADIATION MONITORING PANEL i

l AR-403 Rev. 20 Page 102

l

^ -

l \

ENCLOSURE 1 1 (Page 101 of 194) l PSA-Z ANNUNCIATOR RESPONSE PSA-Z-03-02 H-03-02 ,

LIQUID MONITOR WARNING l

EVENT POINT 1791 k

I INDICATED CONDITION: l o RM-L3 RADIATION LEVEL EXCEEDS WARNING SETPOINT.

IA lV l

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o RM-L3 INDICATION AT RADIATION MONITORING PANEL.

OPERATOR ACTIONS FOR A VALID ALARM:  ;

i o INVESTIGATE CAUSE OF HIGH RADIATION.

o REFER TO OP-301, OPERATION OF THE REACTOR COOLANT SYSTEM. i DISCUSSION:

l I

REFERENCES:

DRAWING 208-049-RM-32 SENSING ELEMENT: RADIATION MONITORING PANEL AR-403 Rev. 20 Page 103

, ~ . - - - e, 4 - , ,- r - ,w w -e,ms

1 ENCLOSURE 1 O (Page 102 of 194)

PSA-Z ANNUNCIATOR RESPONSE PSA-Z-03-02 H-03-02 LIQUID MONITOR WARNING EVENT POINT 1795 ,

INDICATED CONDITION:

o RM-L5 RADIATION LEVEL EXCEEDS WARNING SETPOINT.

'O REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o RM-L5 INDICATION AT RADIATION MONITORING PANEL.

I OPERATOR ACTIONS FOR A VALID ALARM: -

o INVESTIGATE CAUSE OF HIGH RADIATION.

o REFER TO OP-301, OPERATION OF THE REACTOR COOLANT SYSTEM. '

DISCUSSION:

l

REFERENCES:

DRAWING 208-049-RM-32 l SENSING ELEMENT: RADIATION MONITORING PANEL l AR-403 Rev. 20 Page 104

I I

l ENCLOSURE 1 (Page 103 of 194)

PSA-Z ANNUNCIATOR RESPONSE PSA-Z-03-02 H-03-02 LIQUID I l MONITOR WARNING l

EVENT POINT 1797 j INDICATED CONDITION:

o RM-L6 RADIATION LEVEL EXCEEDS WARNING SETPOINT.

~

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o RM-L6 INDICATION AT RADIATION MONITORING PANEL.

OPERATOR ACTIONS FOR A VALID ALARM:

o INVESTIGATE CAUSE OF HIGH RADIATION.

o REFER TO OP-301, OPERATION OF THE REACTOR COOLANT SYSTEM.

DISCUSSION:

REFERENCES:

DRAWING 208-049-RM-32 SENSING ELEMENT: RADIATION MONITORING PANEL AR-403 Rev. 20 Page 105

l l

l r,

ENCLOSURE I (Page 104 of 194)

()

PSA-Z ANNUNCIATOR RESPONSE ,

PSA-Z-03-02 H-03-02 l l

l LIQUID MONITOR WARNING

, L

1 EVENT POINT 1799 l 1

l l INDICATED CONDITION:

l 0 RM-L7 RADIATION LEVEL EXCEEDS WARNING SETPOINT.

l l

l

,O, U

l REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o RM-L7 INDICATION AT RADIATION MONITORING PANEL.

o SPDS ALPHA PAGE.

OPERATOR ACTIONS FOR A VALID ALARM: ,

o INVESTIGATE CAUSE OF HIGH RADIATION.

o DISCUSSION:

REFERENCES:

DRAWING 208-049-RM-31

,~.,

!d SENSING ELEMENT: RADIATION MONITORING PANEL AR-403 Rev. 20 Page 106

i l

1 1

ENCLOSURE 1 l O ce 9e ios er 194) l PSA-Z ANNUNCIATOR RESPONSE PSA-2-03-03 H-03-03 J RM-L2/7 INTERLOCK l BYPASSED EVENT POINT 2044 l

INDICATED CONDITION:

o INTERLOCK BETWEEN SDV-90 AND RWP-3A/38 DEFEATED.

o INTERLOCK BETWEEN WDV-892 AND RWP-2A/2B DEFEATED.

O  :

l REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o RM-L2/7 BYPASS KEY INSTALLED AT RADIATION MONITORING PANEL. 1 OPERATOR ACTIONS FOR A VALID ALARM:

1 DISCUSSION:

BYPASSING THE RM-L2/7 INTERLOCK ALLOWS OPENING OF SDV-90 WITH EITHER RWP-2A OR RWP-2B RUNNING INSTEAD OF RWP-3A OR RWP-3B. ALSO WDV-892 MAY BE OPENED WITH RWP-3A OR RWP-3B RUNNING INSTEAD OF RWP-2A OR RWP-28.

l

REFERENCES:

DRAWING 208-060-WD-60 SENSING ELEMENT: RADIATION MONITORING PANEL BYPASS INTERLOCK KEY SWITCH l

l AR-403 Rev. 20 Page 107

.__ _ _ _ _ _ ____. _ _ _ _ .. ~ , .. . . .-

t ENCLOSURE 1 (Page 106 of 194)

PSA-Z ANNUNCIATOR RESPONSE PSA-Z-03-05 H-03-05 FLUSH WATER SYSTEM PRESS LOW EVENT POINT 1517 INDICATED CONDITION:

o FLUSH WATER SYSTEM PRESSURE <75 PSIG AS SENSED BY D0-2-PS.

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

OPERATOR ACTIONS FOR A VALID ALARM:

o REFER TO OP-416 FOR ALTERNATE RWP FLUSH WATER SUPPLIES DISCUSSION:

THE RWP'S ARE CURRENTLY SUPPLIED WITH DOMESTIC WATER VIA 1 0F 2 FILTERS AND PUMPS. OP-416 LISTS TWO ALTERNATIVE SUPPLIES, DEMIN WATER VIA 00V-128 OR NUCLEAR SERVICES WATER VIA D0V-210 OR D0V-238. IF THE FLUSH WATER PRESSURE DROPS BELOW RWP DISCHARGE PRESSURE, THEN THE RUNNING RWP'S WILL SUPPLY THEIR OWN FLUSH WATER FOR THE RUNNING RWP'S.

REFERENCES:

DRAWING 208-022-D0-13 SENSING ELEMENT: D0-2-PS AR-403 Rev. 20 Page 108

ENCLOSURE 1 (Page 107 of 194)

PSA-Z ANNUNCIATOR RESPONSE PSA-Z-03-06 H-03-06 FLUSH WATER PUMP TRIP l

EVENT POINT 1513 e INDICATED CONDITION:

i o 00P-2A MOTOR NOT ENERGIZED WITH CONTROL SWITCH IN NORMAL AFTER START POSITION.

O REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

, o GREEN LIGHT ON WITH A RED FLAG ON 00P-2A CONTROL STATION.

1 OPERATOR ACTIONS FOR A VALID ALARM:

l o REFER TO OP-416 ' DOMESTIC WATER SUPPLY SYSTEM' FOR ALTERNATE RWP FLUSH e WATER SUPPLIES.

o INVESTIGATE CAUSE OF PUMP TRIP.

DISCUSSION:

REFERENCES:

DRAWING 208-022-00-02 SENSING ELEMENT: D0P-2A CONTROL SWITCH CONTACTS CS/SC, CS/0 AR-403 Rev. 20 Page 109 l

I l

l

~ ENCLOSURE 1 (Page 108 of 194) l (V}

l PSA-Z ANNUNCIATOR RESPONSE PSA-Z-03-06 H-03-06 FLUSH WATER l PUMP l TRIP l EVENT POINT 1515 ,

INDICATED CONDITION:

o DOP-2B MOTOR NOT ENERGIZED WITH CONTROL SWITCH IN NORMAL AFTER START POSITION.

I

! REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o GREEN LIGHT ON WITH A RED FLAG ON DOP-28 CONTROL STATION.

I l

OPERATOR ACTIONS FOR A VALID ALARM:

o REFER TO OP-416 ' DOMESTIC WATER SUPPLY SYSTEM' FOR ALTERNATE RWP FLUSH o T bSEOFPUMPTRIP.

f DISCUSSION:

)

i

REFERENCES:

DRAWING 208-022-00-03

(

O) SENSING ELEMENT: D0P-2B CONTROL SWITCH CONTACTS CS/SC, CS/0 4

AR-403 Rev. 20 Page 110

i ENCLOSURE 1 (Page 109 of 194)

Os PSA-Z ANNUNCIATOR RESPONSE PSA-Z-03-07 H-03-07 i

FLUSH WATER PUMP AUTO START EVENT POINT 1514 j INDICATED CONDITION:  !

o D0P-2A MOTOR ENERGIZED WITH CONTROL SWITCH IN NORMAL AFTER STOP ,

POSITION.  !

O REDUNDANT INDICATION WHICH WILL VERIFY ALARM- l o RED LIGHT ON WITH A GREEN FLAG ON DOP-2A CONTROL STATION.

OPERATOR ACTIONS FOR A VALID ALARM:

o TNVESTIGATE CAUSE OF PUMP AUTO START. i o REFER TO 00-416 '0OMESTIC WATER SUPPLY SYSTEM' FOR ALTERNATE RWP FLUSH UATER SUPPLIES.

l l

DISCUSSION:

l

REFERENCES:

DRAWING 208-022-00-02 l SENSING ELEMENT: D0P-2A CONTROL SWITCH CONTACTS CS/SC, CS/0 l l

AR-403 Rev. 20 Page III l

i 1

r~'s ENCLOSURE 1  !

( ,) (Page 110 of 194)

PSA-Z ANNUNCIATOR RESPONSE PSA-Z-03-07 H-03-07 FLUSH WATER PUMP AUTO START EVENT POINT 1516 .

INDICATED CONDITION:

o D0P-2B MOTOR ENERGIZED WITH CONTROL SWITCH IN NORMAL AFTER STOP POSITION.

[ ~')

V REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o RED LIGHT ON WITH A GREEN FLAG ON DOP-28 CONTROL STATION.

OPERATOR ACTIONS FOR A VALID ALARM:

o INVESTIGATE CAUSE OF PUMP AUTO START.

o REFER TO OP-416 ' DOMESTIC WATER SUPPLY SYSTEM' FOR ALTERNATE RWP FLUSH WATER SUPPLIES.

DISCUSSION:

1 1

1 1 1 i

l fs

REFERENCES:

DRAWING 208-022-D0-03 N _- SENSING ELEMENT: D0P-2B CONTROL SWITCH CONTACTS CS/SC, CS/0 l

i AR-403 Rev. 20 Page 112 i

ENCLOSURE I j's (Page 111 of 194)

PSA-Z ANNUNCIATOR RESPONSE PSA-Z-03-08 H-03-08 l

l l l SW SYSTEM I I SUPPLYING I I FLUSH WATER I l EVENT POINT 1511 ,

INDICATED CONDITION:

o D0V-210 OR D0V-238 OPEN.

lO REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o VALVE POSITION INDICATION FOR D0V-210 AND/0R D0V-238.

OPERATOR ACTIONS FOR A VALID ALARM:

o REFER TO OP-416 DISCUSSION:

THIS ALARM INDICATES THAT THE SW SYSTEM IS SUPPLYING RW PUMP FLUSH WATER FROM THE SW PUMP DISCHARGE HEADER. INCREASED USE OF DW TO THE SW SURGE TANK CAN BE EXPECTED.

REFERENCES:

DRAWING 208-022-D0-14 SENSING ELEMENT: D0V-210 AND D0V-238 OPEN LIMIT SWITCHES AR-403 Rev. 20 Page 113

ENCLOSURE 1 O (Page 112 of 194)

PSA-Z ANNUNCIATOR RESPONSE PSA-Z-04-01 H-04-01 MAKEUP TANK LEVEL LOW LOW EVENT POINT 0792 ,

i i INDICATED CONDITION:  ;

1 o MAKEUP TANL LEVEL <18" AS SENSED BY MU14-LYI-4, MU14-LY2-4.

i REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o MU-014-LIR1, MUT LEVEL / PRESSURE RECORDER.

o MU-14-LII, MUT LEVEL INDICATION (REDUNDANT INSTRUMENT PANEL).

o MU-14-LI2, HUT LEVEL INDICATION (REDUNDANT INSTRUMENT PANEL).

OPERATOR ACTIONS FOR A VALID ALARM:

o ENSURE MUV-58, AND MUV-73 OPEN. I o RESTORE MAKEUP TANK LEVEL TO NORMAL BAND.

t i

DISCUSSION:

l

REFERENCES:

DRAWING 208-041-MU-17,MU-18 SENSING ELEMENT: MU14-LY1-4,MU14-LY2-4.

AR-403 Rev. 20 Page 114

ENCLOSURE 1 j

(Page 113 of 194)

PSA-Z ANNUNCIATOR RESPONSE PSA-Z-04-02 H-04-02 ,

MAKEUP TANK LEVEL HIGH/ LOW l

EVENT POINT 1064 1

INDICATED CONDITION:

o MAKEUP TANK LEVEL >86" AS SENSED BY MU-14-LSI.

l l

lO REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o MU-014-LIR1, MUT LEVEL / PRESSURE RECORDER. I o MU-14-LII, MUT LEVEL INDICATION (REDUNDANT INSTRUMENT PANEL).

o MU-14-LI2, MUT LEVEL INDICATION (REDUNDANT INSTRUMENT PANEL).

l OPERATOR ACTIONS FOR A VALID ALARM:

{

l o RESTORE MAKEUP TANK LEVEL TO NORMAL BAND.

i l

l DISCUSSION:

REFERENCES:

DRAWING 208-041-MU-47.

SENSING ELEMENT: MU-14-LSI.

l t

l AR-403 Rev. 20 Page 115

i ENCLOSURE I es (Page 114 of 194)

(j PSA-Z ANNUNCIATOR RESPONSE PSA-Z-04-02 H-04-02 MAKEUP TANK LEVEL HIGH/ LOW EVENT POINT 1065 INDICATED CONDITION: I o MAKEUP TANK LEVEL <55" AS SENSED BY MU-14-LS1.

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o MU-014-LIR1, MUT LEVEL / PRESSURE RECORDER.

O MU-14-LII, MUT LEVEL INDICATION (REDUNDANT INSTRUMENT PANEL).

o MU-14-LI2, MUT LEVEL INDICATION (REDUNDANT INSTRUMENT PANEL).

OPERATOR ACTIONS FOR A VALID ALARM:

(

o RESTORE MAKEUP TANK LEVEL TO NORMAL BAND.

7 DISCUSSION:

1 l

REFERENCES:

DRAWING 208-041-MU-47.

d,. SENSING ELEMENT: MU-14-LSI.

l AR-403 Rev. 20 Page 116 I

~ ~ ~ -

ENCLOSURE 1 O (Page 115 of 194)

PSA-Z ANNUNCIATOR RESPONSE PSA-Z-04-03 H-04-03 MAKEUP  ;

FLOW .,

HIGH EVENT POINT 1066 f

INDICATED CONDITION:

o MAKEUP FLOW >160 GPM THROUGH MUV-31 AS. SENSED BY MU-24-FS.

( -

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o MU-24-FI i

OPERATOR ACTIONS FOR A VALID ALARM:

0 REFER TO OP-301 .

l ,

! d DISCUSSION:

- l l

l

REFERENCES:

DRAWING 208-041-MU-47.

) SENSING ELEMENT: MU-24-FS.

l t

I; AR-403 Rev. 20 Page 117 l

L l

l t

( ENCLOSURE 1 (Page 116 of 194)

PSA-Z ANNUNCIATOR RESPONSE PSA-Z-04-04 H-04-04 LETDOWN i

TEMP HIGH EVENT POINT 1027 i INDICATED CONDITION:

o LETDOWN TEMPERATURE TO PREFILTERS >130*F AS SENSED BY MU-5-TS.

l O

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o MU-5-TI OPERATOR ACTIONS FOR A VALID ALARM:  ;

o REDUCE LETDOWN FLOW WITH MUV-51 FLOW CONTROL VALVE.

o NOTIFY PRIMARY PLANT OPERATOR TO VERIFY SW THROTTLE VALVES TO LETDOWN .

COOLERS ' SEALED'. 'j i

DISCUSSION:

IF LETDOWN HAS ISOLATED VIA MUV-49 REFER TO OP-402 FOR LETDOWN REC 0VERY.

l IF HIGH LETDOWN FLOW IS DESIRED THEN CONSIDER STARTING SWP-1A OR SWP-1B TO PROVIDE ADDITIONAL COOLING WATER TO THE LETDOWN COOLERS.

REFERENCES:

DRAWING 208-041-MU-33.

SENSING ELEMENT: MU-5-TS. 1 4

AR-403 Rev. 20 Page 118

ENCLOSURE 1 O (Page 117 of 194)

PSA-Z ANNUNCIATOR RESPONSE PSA-Z-04-05 H-04-05 RC PUMP

SEAL BLEED OFF HIGH EVENT POINT 1075 '

l l INDICATED CONDITION:  ;

l l 0 RC PUMP 1A CONTROL BLEED 0FF >1.75 GPM AS SENSED BY MU-31-FSI.

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

i o COMPUTER POINT P-221.

l I

OPERATOR ACTIONS FOR A VALID ALARM:

l 0 REFER TO OP-502 'RC PUMP OPERATION'.

l DISCUSSION:

REFER TO STS FOR ADMINISTRATIVE REQUIREMENTS.

COMPUTER GROUP 78 CONTAINS ADDITIONAL DATA FOR RCP-1A.

l

REFERENCES:

DRAWING 208-041-MU-47.

SENSING ELEMENT: MU-31-FSI.

AR-403 Rev. 20 Page 119

_. - . , , - - , . - - - . - , - + - ,

\

ENCLOSURE 1

'N (Page 118 of 194)

(V PSA-Z ANNUNCIATOR RESPONSE ,

PSA-Z-04-05 H-04-05 l l

l RC PUMP SEAL BLEED OFF 1 HIGH EVENT POINT 1076 INDICATED CONDITION:

o RC PUMP IB CONTROL BLEED 0FF >1.75 GPM AS SENSED BY MU-31-FS2.

O

( REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

, o COMPUTER POINT P-222.

OPERATOR ACTIONS FOR A VALID ALARM:

o REFER TO OP-302 'RC PUMP OPERATION'.

DISCUSSION:

REFER TO STS FOR ADMINISTRATIVE REQUIREMENTS.

COMPUTER GROUP 79 CONTAINS ADDITIONAL DATA FOR RCP-18. .

REFERENCES:

DRAWING 208-041-MU-47.

SENSING ELEMENT: MU-31-FS2.

AR-403 Rev. 20 Page 120

i l

ENCLOSURE 1 l (Page 119 of 194) j I

PSA-Z ANNUNCIATOR RESPONSE PSA-Z-04-05 H-04-05 RC PUMP SEAL BLEED OFF HIGH i

EVENT POINT 1077 >

l INDICATED CONDITION: {

l l

o RC PUMP IC CONTROL BLEED 0FF >1.75 GPM AS SENSED BY MU-31-FS3.

l l REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o COMPUTER POINT P-223.

OPERATOR ACTIONS FOR A VALID ALARM:

o REFER TO OP-302 'RC PUMP OPERATION'.  ;

l i

DISCUSSION:

REFER TO STS FOR ADMINISTRATIVE REQUIREMENTS.

COMPUTER GROUP 80 CONTAINS ADDITIONAL DATA FOR RCP-lC.

REFERENCES:

DRAWING 208-041-MU-47.

SENSING ELEMENT: MU-31-FS3.

AR-403 Rev. 20 Page 121 i

ENCLOSURE 1 O (Page 120 of 194)

PSA-Z ANNUNCIATOR RESPONSE PSA-2-04-05 H-04-05 RC PUMP

~

SEAL BLEED OFF HIGH i

EVENT POINT 1078 ,

INDICATED CONDITION:

o RC PUMP ID CONTROL BLEED 0FF >1.75 GPM AS SENSED BY MU-31-FS4.

O l REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o COMPUTER POINT P-253.

OPERATOR ACTIONS FOR A VALID ALARt':

l 0 REFER TO OP-302 'RC PUMP OPERATION'. .

i DISCUSSION: ,

i REFER TO STS FOR ADMINISTRATIVE REQUIREMENTS.

COMPUTER GROUP 81 CONTAINS ADDITIONAL DATA FOR RCP-10.

1

REFERENCES:

DRAWING 208-041-MU-47.

l SENSING ELEMENT: MU-31-FS4.

l AR-403 Rev. 20 Page 122 l

i 1

ENCLOSURE 1 (Page 121 of 194)

PSA-Z ANNUNCIATOR RESPONSE PSA-Z-04-06 H-04-06 MAKEUP TANK l PRESS l HIGH/ LOW l l

l EVENT POINT 1062 l INDICATED CONDITION:

o MAKEUP TANK PRESSURE > THE OVERPRESSURE VALUE CALCULATED BY THE PLANT COMPUTER.

A V

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o MU-014-LIR1, MUT LEVEL / PRESSURE RECORDER.

l 0 COMPUTER POINTS X359 AND X401.

OPERATOR ACTIONS FOR A VALID ALARM:

o ENSURE MUV-141, MUV-143 CLOSED o REDUCE PRESSURE WITHIN LIMITS OF MAKEUP TANK PRESSURE / LEVEL CURVE ,

OF OP-1038. j l

i DISCUSSION:

THE VALUES OF THE COMPUTER POINTS ARE INPUT TO A CALCULATION WHICH ACTUATES THIS EVENT POINT WHEN MUT LEVEL / PRESSURE COMBINATION ARE BEING OPERATED IN THE UNACCEPTABLE REGION OF CURVE 8 OP-103B.

l

REFERENCES:

DRAWING 208-041-MU-47. l l SENSING ELEMENT: -COMPUTER POINT X359 AND X401 i

l AR-403 Rev. 20 Page 123 i l - . - .. - . - .- - . . - . . _ , . . . ..

ENCLOSURE 1 (Page 122 of 194)

PSA-Z ANNUNCIATOR RESPONSE PSA-Z-04-06 H-04-06 i MAKEUP TANK PRESS j __

HIGH/ LOW t EVENT POINT 1063 INDICATED CONDITION:

o MAKEUP TANK PRESSURE <3 PSIG AS SENSED BY MU-17-PS.

l 1O REDUNDANT INDICATION WHICH WILL VERIFY ALARM: ,

o MU-014-LIR1, MUT LEVEL / PRESSURE RECORDER.

OPERATOR ACTIONS FOR A VALID ALARM:

o ENSURE MUV-134 CLOSED o INCREASE PRESSURE WITHIN LIMITS OF MAKEUP TANK PRESSURE / LEVEL CURVE OF OP-103B. $

DISCUSSION:

REFERENCES:

DRAWING 208-041-MU-47.

SENSING ELEMENT: MU-17-PS. j AR-403 Rev. 20 Page 124 ,

_ _ . . . . .~. , _ _ _

-s ENCLOSURE 1

( ) (Page 123 of 194)

PSA-Z ANNUNCIATOR RESPONSE PSA-Z-04-07 H-04-07 1

i RC PUMP SEAL RTN (MUV-253)

NOT FULL OPEN EVENT POINT 1036 2

INDICATED CONDITION:

o MUV-253 NOT FULL OPEN.

,r-(,,

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o MUV-253 VALVE INDICATION ON PSA SECTION AND E.S. LIGHT MATRIX.

o COMPUTER POINT P064.

OPERATOR ACTIONS FOR A VALID ALARM:

o RE0 PEN MUV-253.

o MONITOR RCP SEALS TEMPERATURE / PRESSURE DISCUSSION:

IF MUV-253 CANNOT BE REOPENED THEN REFER TO OP-302.

RCP DATA CAN BE OBSERVED ON COMPUTER GROUPS 78,79,80 AND 81.

REFERENCES:

DRAWING 208-041-MU-44.

( / SENSING ELEMENT: RELAY 3MVV-2530.

AR-403 Rev. 20 Page 125

f ENCLOSURE 1 (Page 124 of 194) s PSA-Z ANNUNCIATOR RESPONSE PSA-Z-04-08 H-04-08 l l l l MAKEUP VALVES I l AIR I I FAILURE l- l 22 222 EVENT POINT 1094 <

INDICATED CONDITION:

o LETDOWN FLOW CONTROL VALVE MUV-51 LOCKED.

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o MUV-51 AIR FAILURE PUSHBUTTON ILLUMINATED.

l OPERATOR ACTIONS FOR A VALID ALARM:

l 0 REFER TO AP-470 o INVESTIGATE LOSS OF INSTRUMENT AIR PRESSURE TO MUV-51.

o DISCUSSION:

l TWO PRESSURE SWITCHES SUPPLY PRESSURE INFORMATION TO THE CONTROL CIRCUITS FOR MUV-51. MU-3-PSI SET FOR 32 PSIG AND MU-3-PS2 SET FOR 28'PSIG. IF EITHER MU-3-PSI OR MU-3-PS2 IS ACTUATED, THE VALVE POSITION WILL BE LOCKED "AS IS" BY THE ISOLATION OF THE AIR LINE FROM THE POSITIONER TO THE VALVE DIAPHRAGM. OPERATION OF THE VALVE BY DEPRESSING THE AIR FAILURE RESET PUSHBUTTON IS NOT CERTAIN AT THIS LOW AIR PRESSURE.

I

REFERENCES:

DRAWING 208-041-MU-54.

SENSING ELEMENT: MU-3-PSI, MU-3-PS2.

i l

l l

l AR-403 Rev. 20 Page 126

i l

l /~' ENCLOSURE 1 (Page 125 of 194) l (_))

PSA-Z ANNUNCIATOR RESPONSE PSA-Z-04-08 H-04-08 l

MAKEUP VALVES l AIR FAILURE EVENT P0 INT 1095 l INDICATED CONDITION

o MAKEUP CONTROL VALVE MUV-31 LOCKED.

,r~%

i. ) REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

( o MVV-31 AIR FAILURE PUSHBUTTON ILLUMINATED.

o MUV-31 CONTROL STATION IN ' HAND'.

OPERATOR ACTIONS FOR A VALID ALARM:

o REFER TO AP-470 o INVESTIGATE LOSS OF INSTRUMENT AIR PRESSURE TO MUV-31.

DISCUSSION:

TWO PRESSURE SWITCHES SUPPLY PRESSURE INFORMATION TO THE CONTROL CIRCUITS FOR MUV-31. MU-25-PS1 SET FOR 32 PSIG AND MU-25-PS2 SET FOR 28 PSIG. IF EITHER MU-25-PS1'OR MU-25-PS2 IS ACTUATED, THE VALVE POSITION WILL BE LOCKED "AS IS" BY THE ISOLATION OF THE AIR LINE FROM THE POSITIONER TO THE l VALVE DIAPHRAGM. OPERATION OF THE VALVE BY DEPRESSING THE AIR FAILURE RESET PUSHBUTTON IS NOT CERTAIN AT THIS LOW AIR PRESSURE.

REFERENCES:

DRAWING 208-041-MU-54.

(_) SENSING ELEMENT: MU-25-PSI, MU-25-PS2.

l AR-403 Rev. 20 Page 127

ENCLOSURE 1 (Page 126 of 194)

PSA-Z ANNUNCIATOR RESPONSE PSA-Z-04-08 H-04-08 I I l l MAKEUP VALVES I i AIR I I FAILURE I I 22 222 EVENT POINT 1096 '

i INDICATED CONDITION:

o MAKEUP CONTROL VALVE MUV-16 LOCKED.

, REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o MUV-16 AIR FAILURE PUSHBUTTON ILLUMINATED.

o MUV-16 CONTROL STATION IN ' HAND'.

OPERATOR ACTIONS FOR A VALID ALARM:

o REFER TO AP-470 o INVESTIGATE LOSS OF INSTRUMENT AIR PRESSURE TO MUV-16.

i i

DISCUSSION:

TWO PRESSURE SWITCHES SUPPLY PRESSURE INFORMATION TO THE CONTROL CIRCUITS l

FOR MUV-16. MU-15-PS1 SET FOR 32 PSIG AND MU-15-PS2 SET FOR 28 PSIG. IF EITHER MU-15-PSI OR MU-15-PS2 IS ACTUATED, THE VALVE POSITION WILL BE LOCKED "AS IS" BY THE ISOLATION OF THE AIR LINE FROM THE POSITIONER TO THE VALVE DIAPHRAGM. OPERATION OF THE VALVE BY DEPRESSING THE AIR FAILURE RESET PUSHBUTTON IS NOT CERTAIN AT THIS LOW AIR PRESSURE.

l

REFERENCES:

DRAWING 208-041-MU-54.

SENSING ELEMENT: MU-15-PS1, MU-15-PS2.

AR-403 Rev. 20 Page 128

l l

ENCLOSURE 1 g (Page 127 of 194) l PSA-Z ANNUNCIATOR RESPONSE- PSA-Z-04-08 H-04-08 l

l l l I I l l MAKEUP VALVES l l AIR I I FAILURE I I i

EVENT POINT 1102 INDICATED CONDITION:

o RC PUMP SEAL BLEED 0FF VALVE MUV-253 AIR SUPPLY PRESSURE <80 PSIG AS SENSED BY MU-253-PS.

O' REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

l OPERATOR ACTIONS FOR A VALID ALARM:

l 0 REFER TO AP-470 l 0 INVESTIGATE LOSS OF INSTRUMENT AIR PRESSURE TO MUV-253.

l l

l l

DISCUSSION: l OPERATION OF THE VALVE IS NOT CERTAIN AT THIS LOW AIR PRESSURE. MUV-253 i FAILS CLOSED IF THE AIR PRESSURE IS INSUFFICIENT AGAINST THE CLOSURE i

SPRING OF THE VALVE OPERATOR.

1

REFERENCES:

DRAWING 208-041-MU-54. -

SENSING ELEMENT: MU-15-PS1, MU-15-PS2.

1 AR-403 Rev. 20 Page 129 l

l l

ENCLOSURE 1 A

(,) (Pr.ge 128 of 194)

PSA-Z ANNUNCIATOR RESPONSE PSA-2-05-01 H-05-01 1

I STM GEN A l MAIN STEAM ISO l ACTUATED i l

EVENT POINT 2007 l 1

INDICATED CONDITION:

o EFIC CHANNEL "A", STEAM GENERATOR "A" MAIN STEAM LINE ISOLATION BUS 1 OR l BUS 2 TRIPPED.

l O

\  :

l

'd REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

i o HALF OR FULL TRIP ON EFIC CHANNEL "A" MAIN STEAM LINE ISOLATION.

o MS-106-PI, CHANNEL "A", 0TSG A PRESSURE INDICATION.

O MS-106-PIR, CHANNEL "A", OTSG A/B PRESSURE RECORDER.

l OPERATOR ACTIONS FOR A VALID ALARM:

l l 0 REFER TO E0P-05, EXCESSIVE HEAT TRANSFER. i o INVESTIGATE CAUSE OF TRIP CONDITION.

DISCUSSION:

MSLI ACTUATION SETPOINT IS OTSG PRESSURE <600 PSIG. WITH THIS EVENT POINT  ;

IN ALARM, A HALF TRIP OR FULL TRIP CONDITION EXISTS. THE OPERATOR MUST l OBSERVE THE EFIC PUSHBUTTONS TO DETERMINE EFIC ACTUATION STATUS.

NO ADDITIONAL ALARMS DIFFERENTIATE BETWEEN FULL AND HALF TRIPS.

(~]

REFERENCES:

VITRO DRAWING 3801-3005 SHEET 1 SENSING ELEMENT:

AR-403 Rev. 20 Page 130

i l

,/~T ENCLOSURE 1 (Page 129 of 194)

!()

PSA-Z ANNUNCIATOR RESPONSE PSA-Z-05-01 H-05-01 i

l l STM GEN A l MAIN STEAM ISO ACTUATED l

EVENT POINT 2015 INDICATED CONDITION:

o EFIC CHANNEL "B", STEAM GENERATOR "A" MAIN STEAM LINE ISOLATION BUS 1 OR BUS 2 TRIPPED.

w REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o HALF OR FULL TRIP ON EFIC CHANNEL "B" MAIN STEAM LINE ISOLATION.

o MS-107-PI, CHANNEL "B", OTSG A PRESSURE INDICATION.

o MS-107-PIR, CHANNEL "B", OTSG A/B PRESSURE RECORDER.

OPERATOR ACTIONS FOR A VALID ALARM:

l 0 REFER TO E0P-05, EXCESSIVE HEAT TRANSFER.

o INVESTIGATE CAUSE OF TRIP CONDITION. r DISCUSSION:

MSLI ACTUATION SETPOINT IS OTSG PRESSURE <600 PSIG. WITH THIS EVENT POINT l

IN ALARM, A HALF TRIP OR FULL TRIP CONDITION EXISTS. THE OPERATOR MUST OBSERVE THE EFIC PUSHBUTTONS TO DETERMINE EFIC ACTUATION STATUS.

NO ADDITIONAL ALARMS DIFFERENTIATE BETWEEN FULL AND HALF TRIPS.

REFERENCES:

VITRO DRAWING 3801-3005 SHEET 2 f]

SENSING ELEMENT:

AR-403 Rev. 20 Page 131

^ ENCLOSURE 1 (Page 130 of 194)

PSA-Z ANNUNCIATOR RESPONSE PSA-Z-05-02 H-05-02 i

l STM GEN A l

FEEDWATER ISO ACTUATED EVENT POINT 2009 ,

l l

INDICATED CONDITION:

o EFIC CHANNEL "A", STEAM GENERATOR "A" MAIN FEEDWATER ISOLATION BUS 1 OR BUS 2 TRIPPED.

l

! REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o HALF OR FULL TRIP ON EFIC CHANNEL "A" MAIN FEEDWATER ISOLATION.

l 0 MS-106-PI, CHANNEL "A", OTSG A PRESSURE INDICATION.

l o MS-106-PIR, CHANNEL "A", OTSG A/B PRESSURE RECORDER.

OPERATOR ACTIONS FOR A VALID ALARM:

l l 0 REFER TO E0P-05, EXCESSIVE HEAT TRANSFER.

o INVESTIGATE CAUSE OF TRIP CONDITION.

l DISCUSSION:

MFWI ACTUATION SETPOINT IS OTSG PRESSURE <600 PSIG. WITH THIS EVENT POINT IN ALARM, A HALF TRIP OR FULL TRIP' CONDITION EXISTS. THE OPERATOR MUST-OBSERVE THE EFIC PUSHBUTTONS TO DETERMINE EFIC ACTUATION STATUS.

NO ADDITIONAL ALARMS DIFFERENTIATE BETWEEN FULL AND HALF TRIPS.

REFERENCES:

VITRO DRAWING 3801-3005 SHEET I SENSING ELEMENT:

AR-403 Rev. 20 Page 132

l f ENCLOSURE 1 (Page 131 of 194)

, PSA-Z ANNUNCIATOR RESPONSE PSA-Z-05-02 H-05-02 ,

STM GEN A FEEDWATER ISO ACTUATED l

EVENT POINT 2017 1:

INDICATED CONDITION: ,

o EFIC CHANNEL "B", STEAM GENERATOR 'A' MAIN FEEDWATER ISOLATION BUS 1 OR BUS 2 TRIPPED.

lO REDUNDANT INDICATION WHICH WILL VERIFY ALARM: ,

i l

o HALF OR FULL TRIP ON EFIC CHANNEL "B" MAIN FEEDWATER ISOLATION.

o MS-107-PI, CHANNEL "B", OTSG A PRESSURE INDICATION.

o MS-107-PIR, CHANNEL "B", OTSG A/B PRESSURE RECORDER.

I OPERATOR ACTIONS FOR A VALID ALARM:

l o REFER TO E0P-05, EXCESSIVE HEAT TRANSFER.

o INVESTIGATE CAUSE OF TRIP CONDITION. ,

'I DISCUSSION:

I MFWI ACTUATION SETPOINT IS OTSG PRESSURE <600 PSIG. WITH THIS EVENT POINT IN ALARM, A HALF TRIP OR FULL TRIP CONDITION EXISTS. THE OPERATOR MUST OBSERVE THE EFIC PUSHBUTTONS TO DETERMINE EFIC ACTUATION STATUS.

NO ADDITIONAL ALARMS DIFFERENTIATE BETWEEN FULL AND HALF TRIPS.

O

REFERENCES:

VITRO DRAWING 3801-3005 SHEET 2 V SENSING ELEMENT:

AR-403 Rev. 20 Page 133

l' ENCLOSURE 1 O (Page 132 of 194)

PSA-Z ANNUNCIATOR RESPONSE PSA-Z-05-03 H-05-03 1

MAIN STEAM ISO VALVE AIR FAILURE EVENT POINT 0956 g INDICATED CONDITION:

o MSV-413 AND MSV-414 AIR SUPPLY PRESSURE <80 PSIG AS SENSED BY MS-99-PS.

O REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

OPERATOR ACTIONS FOR A VALID ALARM:

o REFER TO AP-470 o INVESTIGATE LOSS OF INSTRUMENT AIR PRESSURE TO MSIV's.

t b

DISCUSSION:

ON A LOSS OF INSTRUMENT AIR, THE ACCUMULATORS SHOULD MAINTAIN THE MSIV'S

, OPEN FOR AT LEAST 1 HOUR DEPENDENT O!: ACTUATOR LEAKAGE. DEGRADATION OF l THE ACCUMULATOR PRESSURE WILL BE INDICATED BY THE ILLUMINATION OF THE SV-1/SV-2 WHITE LIGHT ON THE PSA PANEL.

REFERENCES:

DRAWING 208-039 MS-14

( SENSING ELEMENT: MS-99-PS l

AR-403 Rev. 20 Page 134

. _ . . . , _ , , . . . . . _ . _ . . . ,_ .. . . . ~

l \

l l

t g LNCLOSURE 1 (Page 133 of 194)

.g PSA-Z ANNUNCIATOR RESPONSE PSA-Z-05-03 H-05-03  !

I i

1 l

l MAIN STEAM ISO VALVE l AIR FAILURE l

EVENT POINT 0959 ,

INDICATED CONDITION: ,

l o MSV-411 AND MSV-412 AIR SUPPLY PRESSURE <80 PSIG AS SENSED BY MS-98-PS.

l l i i l REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

I l

i OPERATOR ACTIONS FOR A VALID ALARM:

o REFER TO AP-470 o INVESTIGATE LOSS OF INSTRUMENT AIR PRESSURE TO MSIV'S.

e i

DISCUSSION:

1 l

ON A LOSS OF INSTRUMENT AIR, THE ACCUMULATORS SHOULD MAINTAIN THE MSIV'S OPEN FOR AT LEAST 1 HOUR DEPENDENT ON ACTUATOR LEAKAGE. DEGRADATION OF THE ACCUMULATOR PRESSURE WILL BE INDICATED BY THE ILLUMINATION OF THE SV-1/SV-2 WHITE LIGHT ON THE PSA PANEL.

REFERENCES:

DRAWING 208-039 MS-14 SENSING ELEMENT: MS-98-PS l

j AR-403 Rev. 20 Page 135 i

ENCLOSURE 1 (Page 134 of 194)

PSA-Z ANNUNCIATOR RESPONSE PSA-Z-05-04 H-05-04 l LETDOWN l PRESSURE l HIGH

=

EVENT POINT 1060 5

INDICATED CONDITION:

o LETDOWN PRESSURE AFTER BLOCK ORIFICE >145 PSIG AS SENSED BY MU-6-PS.

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o COMPUTER POINT X002.

OPERATOR ACTIONS FOR A VALID ALARM:

o INVESTIGATE CAUSE OF HIGH PRES 9URE CnNDITION.

o REDUCE LETDOWN FLOW.

i DISCUSSION:

A POSSIBLE CAUSE OF HIGH PRESSURE AT THIS POINT IN THE SYSTEM IS ISOLATION OF D0WNSTREAM COMPONENTS OR ANY FLOW RESTRICTIONS IN THE PREFILTERS, POSTFILTERS OR MAKEUP DEMINS. IF THE HIGH PRESSURE CONDITION EXISTS AND ITS CAUSE CANNOT BE DETERMINED THEN CLOSURE OF MUV-49 MAY BE REQUIRED TO PREVENT POSSIBLE RELIEF VALVE OPERATION TO THE A.B. SUMP.

REFERENCES:

DRAWING 208-041 MS-47 SENSING ELEMENT: MS-6-PS AR-403 Rev. 20 Page 136

1 l ENCLOSURE 1 l i (Page 135 of 194) i 4 1 l

1 PSA-Z ANNUNCIATOR RESPONSE PSA-Z-05-05 H-05-05 i  !

l

MAKEUP FILTERS

, A PRESS  ;

HIGH j l  !

i EVENT POINT 1061 I j

l INDICATED. CONDITION:

I o MAKEUP POSTFILTER DIFFERENTIAL PRESSURE >25 PSIG AS SENSED BY MU-18-DPS.

i

( REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

1 4

o MAKEUP POSTFILTER DIFFERENTIAL PRESSURE MU-18-DPI.

} OPERATOR ACTIONS FOR A VALID ALARM:  :

i o PLACE "A" AND "B" POSTFILTERS IN SERVICE.

4 o REDUCE LETDOWN FLOW.

1 1

DISCUSSION:

REFERENCES:

DRAWING 208-041 MU-47 SENSING ELEMENT: MU-18-DPS AR-403 Rev. 20 Page 137

ENCLOSURE 1 (Page 136 of 194)

PSA-Z ANNUNCIATOR RESPONSE PSA-Z-05-05 H-05-05 MAKEUP FILTERS A PRESS HIGH EVENT POINT 1082 i INDICATED CONDITION:

o MAKEUP PREFILTER DIFFERENTIAL PRESSURE >12 PSIG AS SENSED BY MU-81-DPS.

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o MAKEUP PREFILTER DIFFERENTIAL PRESSURE INDICATION MU-81-DPI.

OPERATOR ACTIONS FOR A VALID ALARM:

o PLACE "A" AND "B" PREFILTERS IN SERVICE.

o REDUCE LETDOWN FLOW.

6 I

DISCUSSION:

REFERENCES:

DRAWING 208-041 MU-47 SENSING ELEMENT: MU-81-DPS AR-403 Rev. 20 Page 138

}

. 1 l

ENCLOSURE 1

( (Page 137 of 194) 1 PSA-Z ANNUNCIATOR RESPONSE PSA-Z-05-06 H-05-06 MAKEUP DEMIN APRESS

, HIGH 4 l

1 EVENT POINT 1083 INDICATED CONDITION:

o MAKEUP DEMIN DIFFERENTIAL PRESSURE >14 PSIG AS SENSED BY MU-75-DPS.

O-RED @ DANT INDICATION WHICH WILL VERIFY ALARM: 1 o MAKEUF DEMIN DIFFERENTIAL PRESSURE INDICATION MU-75-DPI.

OPERATOR ACTIONS FOR A VALID ALARM:

o REFER TO OP-402 o BYPASS DEMINERALIZERS OR PLACE ALTERNATE DEMIN IN SERVICE o REDUCE LETDOWN FLOW  ;

DISCUSSION:

CONSIDERATION SHOULD BE GIVEN TO THE AFFECT ON THE RCS OF PLACING THE '

ALTERNATE DEMIN IN SERVICE. IF IT IS NOT SATURATED AT THE SAME LEVEL AS THE RCS IS AT THE TIME THE ALTERNATE DEMIN IS PLACED IN SERVICE.THERE WILL BE A SIGNIFICANT CHANGE IN CORE REACTIVITY THAT MAY CAUSE A SIGNIFICANT OPERATIONAL EXCURSION OR REDUCTION OF THE SHUTDOWN MARGIN.

I J

REFERENCES:

DRAWING 208-041 MU-Al l SENSING ELEMENT: MU-76-DPS l

l l AR-403 Rev. 20 Page 139 l

l ENCLOSURE 1

,,g) (Page 138 of 194)

! v l

! PSA-Z ANNUNCIATOR RESPONSE PSA-Z-05-07 H-05-07 l

w RC PUMP SEAL FLOWS l HIGH/ LOW EVENT POINT 1079 ,

INDICATED CONDITION:

o REACTOR COOLANT PUMP TOTAL SEAL FLOW >42 GPM AS SENSED BY MU-27-FS.

1

'/ REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o REACTOR COOLANT PUMP TOTAL SEAL FLOW INDICATION MU-27-FI.

OPERATOR ACTIONS FOR A VALID ALARM:

o REFER TO OP-302.

o REESTABLISH NORMAL SEAL FLOW.

61 DISCUSSION:

REFERENCES:

DRAWING 208-041 MU-47

/m

() SENSING ELEMENT: MU-27-FS AR-403 Rev. 20 Page 140

g EtL(LOSURE I (Page 139 of 194)

PSA-Z ANNUNCIATOR RESPONSE PSA-Z-05-07 H-05-07 RC PUMP SEAL FLOWS HIGH/ LOW  :

EVENT POINT 1080  ;

INDICATED CONDITION:

o REACTOR COOLANT PUMP TOTAL SEAL FLOW <22 GPM AS SENSED BY MU-27-FS.

b REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

l- o REACTOR COOLANT PUMP TOTAL SEAL FLOW INDICATION MU-27-FI.

OPERATOR ACTIONS FOR A VALIO ALARM:

o REFER TO OP-302.

o REESTABLISH NORMAL SEAL FLOW.

DISCUSSION:

REFERENCES:

DRAWING 208-041 MU-47 SENSING ELEMENT: MU-27-FS

! AR-403 Rev. 20 Page 141

I l

i ENCLOSURE 1 i (Page 140 of 194)

PSA-lANNUNCIATORRESPONSE PSA-Z-05-07 H-05-07 r

RC PUMP SEAL FLOWS HIGH/ LOW EVENT POINT 1084 ,

j INDICATED CONDITION:

o REACTOR COOLANT PUMP 1A SEAL FLOW <3 GPM AS SENSED BY MU-7-FSI.

lO I

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o REACTOR COOLANT PUMP 1A SEAL FLOW INDICATION MU-7-FII. ,

OPERATOR ACTIONS FOR A VALID ALARM:

o REFER TO OP-302.

o REESTABLISH NORMAL SEAL FLOW.

1 l

l DISCUSSION:

i I

4

REFERENCES:

DRAWING 208-041 MU-47 SENSING ELEMENT: MU-7-FS1 AR-403 Rev. 20 Page 142

i i

ENCLOSURE 1

, (Page 141 of 194)

PSA-Z ANNUNCIATOR RESPONSE PSA-Z-05-07 H-05-07

)

e RC PUMP SEAL FLOWS HIGH/ LOW

EVENT POINT 1085

! 1 4

~

INDICATED CONDITION:

o REACTOR COOLANT PUMP 18 SEAL FLOW <3 GPM AS SENSED BY MU-7-FS2.

3 i REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

] o REACTOR COOLANT PUMP IB SEAL FLOW INDICATION MU-7-FI2.

1 OPERATORACTIONSFORAVgDALARM:

o REFER TO OP-302.

o REESTABLISH NORMAL SEAL FLOW.

l )

I j DISCUSSION:

i

REFERENCES:

DRAWING 208-041 MU-47 .

i fm  !'

}\j SENSING ELEMENT: MU-7-FS2 e

h AR-403 Rev. 20 Page 143

- . , . . _. -.. .. - .=- .

ENCLOSURE I (Page 142 of 194)

PSA-Z ANNUNCIATOR RESPONSE PSA-Z-05-07 H-05-07 t

i I

RC PUMP l SEAL FLOWS l HIGH/ LOW-l EVENT POINT 1086 l INDICATED CONDITION:

o REACTOR COOLANT PUMP 1C SEAL FLOW <3 GPM AS SENSED BY MU-7-FS3.

l REDUNDANT INDICATION WHICH WILL VERIFY ALARM: ,

o REACTOR COOLANT PUMP IC SEAL FLOW INDICATION MU-7-FI3.

OPERATOR ACTIONS FOR A VALID ALARM:

1 o REFER TO OP-302. .

o REESTABLISH NORMAL SEAL FLOW. l DISCUSSION:

1 i

REFERENCES:

DRAWING 208-041 MU-47 SENSING ELEMENT: MU-7-FS3 l '

l.

AR-403 Rev. 20- Page 144 l

4 ENCLOSURE 1

/~

(Page 143 of 194)

't PSA-Z ANNUNCIATOR RESPONSE PSA-Z-05-07 H-05-07 a l RC PUAP SEAL FLOWS  :

HIGH/ LOW EVENT POINT 1087 f

1 I

INDICATED CONDITION:

l 0 REACTOR COOLANT PUMP 10 SEAL FLOW <3 GPM AS SENSED BY MU-7-FS4.

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o REACTOR COOLANT PUMP 10 SEAL FLOW INDICATION MU-7-FI4.

l OPERATOR ACTIONS FOR A VALID ALARM:

o REFER TO OP-302.

o REESTABLISH NORMAL SEAL FLOW.

c DISCUSSION:

REFERENCES:

DRAWING 208-041 MU-47

() SENSING ELEMENT: MU-7-FS4 AR-403 Rev. 20 Page 145

ENCLOSURE 1 l (Page 144 of 194) l PSA-Z ANNUNCIATOR RESPONSE PSA-Z-05-08 H-05-08 l l l l l l l BWST VLV I I INTERLOCK i l i BYPASSED 1 I I 1 L EVENT POINT 2048 i

1:

l INDICATED CONDITION:

l 0 MAKEUP TANK LOW-LOW LEVEL INTERLOCK DEFEATED. l

[

'DO  !

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

l l

OPERATOR ACTIONS FOR A VALID ALARM: l

! DISCUSSION:

I l THE SWITCH FOR THE BWST VALVE INTERLOCK IS LOCATED IN THE "B" REMOTE SHUTDOWN AUXILIARY CABINET IN THE "B" ES 4160V SWITCHGEAR ROOM. USE SS00 KEY 47 TO ACCESS THE AUXILIARY CABINET. l I

i

REFERENCES:

DRAWING 208-041 MU-17 n

(d SENSING ELEMENT: MU-14-LY2-4 AR-403 Rev. 20 Page 146 l

\

1 I

J J

ENCLOSURE 1 (Page 145 of 194)
]

l PSA-Z ANNUNCIATOR RESPONSE PSA-Z-06-01 H-06-01 1

l

_____ U--- __

STM GEN B l

2 MAIN STEAM ISO

! ACTUATED l'

l EVENT POINT 2008 l i

2 4

INDICATED CONDITION:

o EFIC CHANNEL "A", STEAM GENERATOR "B" MAIN STEAM LINE ISOLATION BUS 1 OR BUS 2 TRIPPED.

i i i REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o HALF OR FULL TRIP ON EFIC CHANNEL "A" MAIN STEAM LINE ISOLATION. l

. o MS-110-PI, CHANNEL "A", OTSG B PRESSURE INDICATION. l o MS-106-PIR, CHANNEL "A", OTSG A/B PRESSURE RECORDER. )

OPERATOR ACTIONS FOR A VALID ALARM: I I

l 0 REFER TO E0P-05, EXCESSIVE HEAT TRANSFER.  !

l l o INVESTIGATE CAUSE OF TRIP CONDITION.

)

i j

DISCUSSION:

MSLI ACTUATION SETPOINT IS OTSG PRESSURE <600 PSIG. WITH THIS EVENT POINT IN ALARM, A HALF TRIP OR FULL TRIP CONDITION EXISTS. THE OPERATOR MUST OBSERVE THE EFIC PUSHBUTTONS TO DETERMINE EFIC ACTUATION STATUS.

NO ADDITIONAL ALARMS DIFFERENTIATE BETWEEN FULL AND HALF TRIPS.

i

REFERENCES:

VITRO DRAWING 3801-3005 SHEET 1 SENSING ELEMENT:

I AR-403 Rev. 20 Page 147 i

ENCLOSURE 1

(~)N ts ,

(Page 146 of 194)

PSA-Z ANNUNCIATOR RESPONSE PSA-Z-06-01 H-06-01 STM GEN B MAIN STEAM ISO ACTUATED EVENT POINT 2016 l INDICATED CONDITION:

o EFIC CHANNEL "B", STEAM GENERATOR "B" MAIN STEAM LINE ISOLATION BUS 1 OR BUS 2 TRIPPED.

4 4

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o HALF OR FULL TRIP ON EFIC CHANNEL "B" MAIN STEAM LINE ISOLATION. I o MS-111-PI, CHANNEL "B", OTSG A PRESSURE INDICATION.

o MS-107-PIR, CHANNEL "B", OTSG A/B PRESSURE RECORDER.

l OPERATOR ACTIONS FOR A VALID ALARM:

l o REFER TO E0P-05, EXCESSIVE HEAT TRANSFER.

o INVESTIGATE CAUSE OF TRIP CONDITION.

q l

DISCUSSION:

MSLI ACTUATION SETPOINT IS OTSG PRESSURE <600 PSIG. WITH THIS EVENT POINT IN ALARM, A HALF TRIP OR FULL TRIP CONDITION EXISTS. THE OPERATOR HUST OBSERVE THE EFIC PUSHBUTTONS TO DETERMINE EFIC ACTUATION STATUS.

NO ADDITIONAL ALARMS DIFFERENTIATE BETWEEN FULL AND HALF TRIPS.

[)

%J

REFERENCES:

VITRO DRAWING 3801-3005 SHEET 2 SENSING ELEMENT:

AR-403 Rev. 20 Page 148

- m _

ENCLOSURE 1 (Page 147 of 194)

PSA-Z ANNUNCIATOR RESPONSE PSA-Z-06-02 H-06-02 STM GEN B FEEDWATER ISO ACTUATED EVENT POINT 2010 ,

i INDICATED CONDITION:

o EFIC CHANNEL "A", STEAM GENERATOR "B" MAIN FEEDWATER ISOLATION BUS 1 OR BUS 2 TRIPPED. l O REDUNDANT INDICATION WHICH WILL VERIFY ALARM: i o HALF OR FULL TRIP ON EFIC CHANNEL "A" MAIN FEEDWATER ISOLATION.

o MS-110-PI, CHANNEL "A", OTSG B PRESSURE INDICATION. j o MS-106-PIR, CHANNEL "A", OTSG A/B PRESSURE RECORDER.

OPERATOR ACTIONS FOR A VALID ALARM:

l 0 REFER TO E0P-05, EXCESSIVE HEAT TRANSFER. ,

o INVESTIGATE CAUSE OF TRIP CONDITION. j k

DISCUSSION:

1 MFWI ACTUATION SETPOINT IS OTSG PRESSURE <600 PSIG. WITH THIS EVENT POINT IN ALARM, A HALF TRIP OR FULL TRIP CONDITION EXISTS. THE OPERATOR HUST

' OBSERVE THE EFIC PUSHBUTTONS TO DETERMINE EFIC ACTUATION STATUS.

NO ADDITIONAL ALARMS DIFFERENTIATE BETWEEN FULL AND HALF TRIPS.

I

REFERENCES:

VITRO DRAWING 3801-3005 SHEET 1 SENSING ELEMENT:

, AR-403 Rev. 20 Page 149 w 7 y rw- ,--.<r * -,- e~y.in- gw+m --e .v.4e--+t< r- w- r+ k-m+--- -

1 l

ENCLOSURE 1 (Page 148 of 194)  !

l PSA-Z ANNUNCIATOR RESPONSE PSA-Z-06-02 H-06-02 l l

l STM GEN B l FEEDWATER ISO I ACTUATED l EVENT POINT 2018 i i l l

INDICATED CONDITION: j 1

o EFIC CHANNEL "B", STEAM GENERATOR "B" MAIN FEEDWATER ISOLATION BUS 1 ';R l BUS 2 TRIPPED. )

e REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o HALF OR FULL TRIP ON EFIC CHANNEL "B" MAIN FEEDWATER ISOLATION.

o MS-111-PI, CHANNEL "B", OTSG B PRESSURE INDICATION.

o MS-107-PIR, CHANNEL "B", OTSC A/B PRESSURE RECORDER.

OPERATOR ACTIONS FOR A VALID ALARM:

l 0 REFER TO E0P-05, EXCESSIVE HEAT TRANSFER.

o INVESTIGATE CAUSE OF TRIP CONDITION.

DISCUSSION:

MFWI ACTUATION SETPOINT IS OTSG PRESSURE <600 PSIG. WITH THIS EVENT POINT IN ALARM, A HALF TRIP OR FULL TRIP CONDITION EXISTS. THE OPERATOR MUST OBSERVE THE EFIC PUSHBUTTONS TO DETERMINE EFIC ACTUATION STATUS.

l NO ADDITIONAL ALARMS DIFFERENTIATE BETWEEN FULL AND HALF TRIPS.

l

/7

REFERENCES:

VITRO DRAWING 3801-3005 SHEET 2

\) SENSING ELEMENT:

I l AR-403 Rev. 20 Page 150

() ENCLOSURE 1 (Page 149 of 194)

PSA-Z ANNUNCIATOR RESPONSE- PSA-Z-06-03 H-06-03 84 ERG FW ACTUATION EVENT POINT 2006 ,;

9 i

INDICATED CONDITION: l 1

o EFIC CHANNEL "A", EMERGENCY FEEDWATER BUS I OR BUS 2 TRIPPED.

1 REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o HALF OR FULL TRIP ON EFIC CHANNEL "A" EMERGENCY FEEDWATER ACTUATION.

OPERATOR ACTIONS FOR A VALID ALARM:

l o REFER TO E0P.

o INVESTIGATE CAUSE OF TRIP CONDITION. 4 i.

DISCUSSION: )

l

! WITH THIS EVENT POINT IN ALARM, A HALF TRIP OR FULL TRIP CONDITION EXISTS.

l' THE OPERATOR MUST OBSERVE THE EFIC PUSHBUTTONS TO DETERMINE EFIC ACTUATION STATUS. EFIC ACTUATES BY ANY OF THE FOLLOWING CONDITIONS:

i EITHER OTSG <600 PSIG EITHER OTSG <6 INCHES MANUAL ACTUATION LOSS OF ALL RCP'S NI POWER >25% W/FW <I7% HPI A AND B ACTUATION LOSS OF BOTH MFP'S W/RPS NOT IN S/D BYPASS

REFERENCES:

VITRO DRAWING 3801-3005 SHEET I

(}

SENSING ELEMENT:

AR-403 Rev. 20 Page 151

l I

1

! ENCLOSURE 1 jI (Page 150 of 194) i 1 PSA-Z ANNUNCIATOR RESPONSE PSA-2-06-03 H-06-03 i

i l

1 EMERG FW j ACTUATION i

4

! EVENT POINT 2014

] INDICATED CONDITION:

1 j o EFIC CHANNEL "B", EMERGENCY FEEDWATER BUS 1 OR BUS 2 TRIPPED.

l REDUNDANT IND'. CATION WHICH WILL VERIFY ALARM:

{

j o HALF OR t'ULL TRIP ON EFIC CHANNEL "B" EMERGENCY FEEDWATER ACTUATION, i

OrcRATOR ACTIONS FOR A VALID ALARM:

l i l 0 REFER TO E0P. -

j o INVESTIGATE CAUSE OF TRIP CONDITION. ,

i

e i DISCUSSION:

WITH THIS EVENT POINT IN ALARM, A HALF TRIP OR FULL TRIP CONDITION EXISTS.

i THE OPERATOR MUST OBSERVE THE EFIC PUSHBUTTONS TO DETERMINE EFIC ACTUATION STATUS. EFIC ACTUATES BY ANY OF THE FOLLOWING CONDITIONS:

i EITHER OTSG <600 PSIG EITHER OTSG <6 INCHES MANUAL ACTUATION

] LOSS OF ALL RCP'S NI POWER >25% W/FW <17% HPI A AND B ACTUATION

] LOSS OF BOTH MFP'S W/RPS NOT IN S/D BYPASS

REFERENCES:

VITRO DRAWING 3801-3005 SHEET 1 SENSING ELEMENT:

2 AR-403 Rev. 20 Page 152

l l

l

, s ENCLOSURE I (Page 151 of 194)

PSA-Z ANNUNCIATOR RESPONSE PSA-Z-06-06 H-06-06 l

l l

l EFIC BYPASS l

l EVENT POINT 2012 1

INDICATED CONDITION:

o EFIC CHANNEL A IN MAINTENANCE BYPASS.

l o ANY EFIC CHANNEL A TEST SWITCH NOT IN NORMAL.

o ANY EFIC CHANNEL A CIRCUIT BREAKER OPEN.

o ANY EFIC CHANNEL A MODULE WITHDRAWN.

j o EFIC CHANNEL A CABINET POWER SUPPLY FAILURE.

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

1.

OPERATOR ACTIONS FOR A VALID ALARM:

l o INVESTIGATE CAUSE OF ALARM CONDITION. .

b r

DISCUSSION:

/~

REFERENCES:

VITRO DRAWING 3801-3005 SHEET I SENSING ELEMENT:

l l

! AR-403 Rev. 20 Page 153

l l

l

,7s ENCLOSURE 1 l(v) 1 (Page 152 of 194) l I

l PSA-Z ANNUNCIATOR RESPONSE PSA-Z-06-06 H-06-06 l

l i

EFIC l l BYPASS l EVENT POINT 2020 '

INDICATED CONDITION:

o EFIC CHANNEL B IN MAINTENANCE BYPASS.

o ANY EFIC CHANNEL B TEST SWITCH NOT IN NORMAL.

o ANY EFIC CHANNEL B CIRCUIT BREAKER OPEN.

O' o ANY EFIC CHANNEL B MODULE WITHDRAWN.

o EFIC CHANNEL B CABINET POWER SUPPLY FAILURE.

( )I s.

REDUNDANT INDICATION WHICH WILL VERIFY ALARM: i n ,

OPERATOR ACTIONS FOR A VALID ALARM:

o INVESTIGATE CAUSE OF ALARM CONDITION.

  • 1

'l l

DISCUSSION:

I l

(] '

REFERENCES:

VITRO DRAWING 3801-3005 SHEET 2 SENSING ELEMENT:

AR-403 Rev. 20 Page 154

i l

ENCLOSURE I (Page 153 of 194)

PSA-Z ANNUNCIATOR RESPONSE PSA-Z-06-06 H-06-06 EFIC.

BYPASS EVENT POINT 2025 '

l I

INDICATED CONDITION:

l o EFIC CHANNEL C IN MAINTENANCE BYPASS.

l o ANY EFIC CHANNEL C TEST SWITCH NOT IN NORMAL.

o ANY EFIC CHANNEL C CIRCUIT BREAKER OPEN.

o ANY EFIC CHANNEL C MODULE WITHDRAWN.

o EFIC CHANNEL C CABINET POWER SUPPLY FAILURE.

l REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

OPERATOR ACTIONS FOR A VALID ALARM:

o INVESTIGATE CAUSE OF ALARM CONDITION.

DISCUSSION:

(~

REFERENCES:

VITRO DRAWING 3801-3005 SHEET 3 SENSING ELEMENT:

AR-403 Rev. 20 Page 155 e.w--g y- --i me-r w- -w-p., ,-"Oe Mte WN'N* 'TWW4' 'W & T 9- BrT-*^*#rr*W V

~

ENCLOSURE 1

(\--^/ (Page 154 of 194) l PSA-Z ANNUNCIATOR RESPONSE PSA-Z-06-06 H-06-06 l

l EFIC BYPASS EVENT POINT 2029 INDICATED CONDITION:

o EFIC CHANNEL D IN MAINTENANCE BYPASS.

o ANY EFIC CHANNEL D TEST SWITCH NOT IN NORMAL.

o ANY EFIC CHANNEL D CIRCUIT BREAKER OPEN.

o ANY EFIC CHANNEL D MODULE WITHDRAWN.

o EFIC CHANNEL D CABINET POWER SUPPLY FAILURE.

I)T L

REDUNDANT INDICATION WHICH WILL VERIFY ALARM: ,

1 OPERATOR ACTIONS FOR A VALID ALARM:

o INVESTIGATE CAUSE OF ALARM CONDITION.

i DISCUSSION:

REFERENCES:

VITRO DRAWING 3801-3005 SHEET 4 V SENSING ELEMENT:

AR-403 Rev. 20 Page 156

ENCLOSURE 1 lq (Page 155 of 194) l g PSA-Z ANNUNCIATOR RESPONSE PSA-Z-06-06 H-06-06 EFIC l

l BYPASS EVENT POINT 2030 INDICATED CONDITION:

o EFIC CHANNEL A IN MAINTENANCE BYPASS.

l l REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

i i OPERATOR ACTIONS FOR A VALID ALARM:

l 0 INVESTIGATE CAUSE OF ALARM CONDITION.

4 i

l l DISCUSSION:

1 l

REFERENCES:

DRAWING 208-032-FW-47, 208-026-EF-15 SENSING ELEMENT:

AR-403 Rev. 20 Page 157

,e'g ENCLOSURE 1 t

v/ (Page 156 of 194)

PSA-Z ANNUNCIATOR RESPONSE PSA-Z-06-06 H-06-06 EFIC BYPASS EVENT POINT 2031 ,

INDICATED CONDITION:

o EFIC CHANNEL B IN MAINTENANCE BYPASS.

(~N.,

()

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

OPERATOR ACTIONS FOR A VALID ALARM:

o INVESTIGATE CAUSE OF ALARM CONDITION.

o 9

DISCUSSION:

l l

REFERENCES:

ORAWING 208-032-FW-48, 208-026-EF-16 SENSING ELEMENT:

l i AR-403 Rev. 20 Page 158 l

4 1

i p ENCLOSURE 1 (Page 157 of 194)

)

V l

l PSA-Z ANNUNCIATOR RESPONSE PSA-2-06-06 H-06-06 1

1 I

EFIC BYPASS l EVENT POINT 2032 t i

INDICATED CONDITION:

o EFIC AUXILIARY RELAY B0X IC TEST SWITCH IN TEST.

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

OPERATOR ACTIONS FOR A VALID ALARM:

o INVESTIGATE CAUSE OF ALARM CONDITION. -

d DISCUSSION:

REFERENCES:

ORAWING 208-026-EF-21 SENSING ELEMENT:

Rev. 20 I AR-403 Page 159

ENCLOSURE 1 (Page 158 of 194)

PSA-Z ANNUNCIATOR RESPONSE PSA-Z-06-06 H-06-06 l EFIC l BYPASS EVENT POINT 2033 l

INDICATED CONDITION:

i

o EFIC AUXILIARY RELAY B0X ID TEST SWITCH IN TEST.

l REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

i OPERATOR ACTIONS FOR A VALID ALARM:

o INVESTIGATE CAUSE OF ALARM CONDITION. j b

T DISCUSSION:

REFERENCES:

DRAWING 208-026-EF-22 SENSING ELEMENT:

AR-403 Rev. 20 Page 160 l __ _ _ . __ . . _ _ . _. - _ - . . - - _ .. _ _ _ - - - _ . - . -

1 ENCLOSURE 1 I

l pd (Page 159 of 194)

PSA-Z ANNUNCIATOR RESPONSE PSA-Z-06-06 H-06-06 l

1 l

! l l

EFIC  :

i BYPASS I

i EVENT POINT 2034 l INDICATED CONDITION:

I o EFIC ES-A BYPASS / TESTING.

lO l l

l REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

OPERATOR ACTIONS FOR A VALID ALARM:

o INVESTIGATE CAUSE OF ALARM CONDITION. ,

b t  ;

1  ;

DISCUSSION: I THIS EVENT POINT IS RECEIVED DURING EFIC TESTING BY PLACING THE SPRING RETURN TO NORMAL SWITCH TO EITHER TEST I OR TEST 2 POSITION IN THE ES-A MANUAL ACTUATION CABINET 40. THESE TEST POSITIONS SIMULATE AN ES "A" l SIGNAL TO EFIC CHANNELS "A" OR "B". THIS SWITCH DOES NOT BYPASS ANY ACTUATION SIGNAL FROM ENGINEERED SAFEGUARDS.

REFERENCES:

DRAWING 208-028-ES-A65 SENSING ELEMENT:

l AR-403 Rev. 20 Page 161 i

i i ENCLOSURE 1 i

(Page 160 of 194)

PSA-Z ANNUNCIATOR RESPONSE PSA-Z-06-06 H-06-06 4

4 j EFIC j BYPASS i

j EVENT POINT 2035 t

i i

INDICATED CONDITION

o EFIC ES-B BYPASS / TESTING.

i

!O i.

l REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

i

]

j. OPERATOR ACTIONS FOR A VALID ALARM:

o INVESTICATE CAUSE OF ALARM CONDITION.

b j j j

j DISCUSSION:

2 i

! THIS EVENT POINT IS RECEIVED DURING EFIC TESTING BY PLACING THE SPRING I RETURN TO NORMAL SWITCH TO EITHER TEST 1 OR TEST 2 POSITION IN THE ES-B i MANUAL ACTUATION CABINET SD. THESE TEST POSITIONS SIMULATE AN ES "B" ,

4 SIGNAL TO EFIC CHANNELS "A" OR "B". THIS SWITCH DOES NOT BYPASS ANY ACTUATION SIGNAL FROM ENGINEERED SAFEGUARDS.

l i

REFERENCES:

DRAWING 208-028-ES-865

) SENSING ELEMENT:

Rev. 20 AR-403 Page 162

ENCL 0SURE 1 7 (Page 161 of 194)

PSA-Z ANNUNCIATOR RESPONSE PSA-Z-06-07 H-06-07 I

EFIC SHUTDOWN BYPASS l EVENT POINT 2013 ,

INDICATED CONDITION:

! o EFIC CHANNEL "A" MAIN STEAM ISOLATION ACTUATION BYPASSED.

l f.

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o CHANNEL "A" <725 PSI STM GEN PRESS EFIC ACT BYPASS' PUSHBUTTON '

ILLUMINATED.

OPERATOR ACTIONS FOR A VALID ALARM:

i DISCUSSION:

l THIS EVENT POINT IS RECEIVED WHEN PLANT CONDITIONS ALLOW THE BYPASSING OF l MSLI/MWFI ACTUATION, AND THE BYPASS PUSHBUTTON HAS BEEN DEPRESSED. THE ACTUATION SETPOINT IS <600 PSIG AND THE BYPASS IS ALLOWED WHEN OTSG PRESSURES ARE APPR0XIMATELY <725 PSIG.

I f

REFERENCES:

VITRO DRAWING 3801-3005 SHEET I i SENSING ELEMENT:

l AR-403 Rev. 20 Page 163 1

i

l ENCLOSURE 1 (Page 162 of 194)

[

PSA-Z ANNUNCIATOR RESPONSE PSA-Z-06-07 H-06-07 l

l EFIC SHUTDOWN BYPASS EVENT POINT 2021 2

l INDICATED CONDITION:

o EFIC CHANNEL "B" MAIN STEAM ISOLATION ACTUATION BYPASSED.

I lO REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o CHANNEL "B" <725 PSI STM GEN PRESS EFIC ACT BYPASS' PUSHBUTTON ILLUMINATED.

OPERATOR ACTIONS FOR A VALID ALARM:

DISCUSSION:

THIS EVENT POINT IS RECEIVED WHEN PLANT CONDITIONS ALLOW THE BYPASSING 0F MSLI/MWFI ACTUATION, AND THE BYPASS PUSHBUTTON HAS BEEN DEPRESSED.-THE ACTUATION SETPOINT IS <600 PSIG AND THE BYPASS IS ALLOWED WHEN OTSG PRESSURES ARE APPR0XIMATELY <725 PSIG. -

REFERENCES:

VITRO ORAWING 3801-3005 SHEET 2 SENSING ELEMENT:

l AR-403 Rev. 20 Page 164 i

ENCLOSURE 1 O (Page 163 of 194)

PSA-Z ANNUNCIATOR RESPONSE PSA-Z-06-07 H-06-07 EFIC SHUTDOWN BYPASS EVENT POINT 2024 INDICATED CONDITION:

l 0 EFIC CHANNEL "C" MAIN STEAM ISOLATION ACTUATION BYPASSED.

O  :

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o CHANNEL "C" <725 PSI STM GEN PRESS EFIC ACT BYPASS' PUSHBUTTON ILLUMINATED. ,

i OPERATOR ACTIONS FOR A VALID ALARM:

4 L

DISCUSSION:

l THIS EVENT POINT IS. RECEIVED WHEN PLANT CONDITIONS ALLOW THE BYPASSING OF MSLI/MWFI ACTUATION, AND THE BYPASS PUSHBUTTON HAS BEEN DEPRESSED. THE l ,

1 ACTUATION SETPOINT IS <600 PSIG AND THE BYPASS IS ALLOWED WHEN OTSG  ;

PRESSURES ARE APPR0XIMATELY <725 PSIG.

(

i

(

REFERENCES:

VITRO DRAWING 3801-3005 SHEET 3 SENSING ELEMENT:

l AR-403 Rev. 20 Page 165 l 1 i . . . _ , _ _ _ - . , _ _ _ . . . . . , - . _

ENCLOSURE 1 (Page 164 of 194)

PSA-Z ANNUNCIATOR RESPONSE PSA-Z-06-07 H-06-07 EFIC SHUTDOWN BYPASS i

EVENT POINT 2028 1

INDICATED CONDITION:

o EFIC CHANNEL "D" MAIN STEAM ISOLATION ACTUATION BYPASSED.

O REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

l o CHANNEL "D" <725 PSI STM GEN PRESS EFIC ACT BYPASS' PUSHBUTTON ILLUMINATED.

OPERATOR ACTIONS FOR A VALID ALARM:

)

i l

DISCUSSION:

THIS EVENT POINT IS RECEIVED WHEN PLANT CONDITIONS ALLOW THE BYPASSING 0F MSLI/MWFI ACTUATION, AND THE BYPASS PUSHBUTTON HAS BEEN DEPRESSED. THE ACTUATION SETPOINT IS <600 PSIG AND THE BYPASS IS ALLOWED WHEN OTSG PRESSURES ARE APPROXIMATELY <725 PSIG.

REFERENCES:

VITRO DRAWING 3801-3005 SHEET 4 i

SENSING ELEMENT:

l l AR-403 Rev. 20 Page 166

i l l

ENCLOSURE 1  !

(Page 165 of 194)

PSA-Z ANNUNCIATOR RESPONSE PSA-Z-06-08 H-06-08 l

l l  :

l l EFIC AH I l SYSTEM I I TROUBLE I l 2222 2 EVENT POINT 0767 ,

INDICATED CONDITION:

o AHF-54A/AHF-54B DUCT, SM0KE DETECTED, OR TROUBLf. AS SENSED BY PYROTRONIC l SM0KE DETECTION MODULES AH-934-CE1 OR AH-934-CE2.

O REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

OPERATOR ACTIONS FOR A VALID ALARM:

o INVESTIGATE CAUSE OF SM0KE DETECTED OR TROUBLE ALARM.

(

DISCUSSION:

REFERENCES:

DRAWING 208-005-AH-185 SENSING ELEMENT: AH-934-CE1, AH-934-CE2 AR-403 Rev. 20 Page 167 I

m ENCLOSURE 1 (Page 166 of 194)

() .

PSA-Z ANNUNCIATOR RESPONSE PSA-Z-06-08 !H-06-08 l l l l EFIC AH I I SYSTEM i i TROUBLE I I EVENT POINT 0768  ;

t INDICATED CONDITION:

o AHF-54A/AHF-548 DUCT, TEMPERATURE >85* AS SENSED.BY AH-932-TS1/TS2.

O  ;

REDUNDANT INDICATION WHICH WILL VERIFY ALARM: l l

OPERATOR ACTIONS FOR A VALID ALARM:

o INVESTIGATE CAUSE OF DUCT HIGH TEMPERATURE ALARM. j l

DISCUSSION:

REFERENCES:

DRAWING 208-005-AH-185 SENSING ELEMENT: AH-932-TSI, AH-932-TS2 AR-403 Rev. 20 Page 168

ENCLOSURE 1

,O (Page 167 of 194) i I

PSA-Z ANNUNCIATOR RESPONSE PSA-Z-06-08 H-06-08 l l l 1 i

1 I l l EFIC AH J l l SYSTEM I I TROUBLE- .

I l E22 -

EVENT POINT 0774 1 L

INDICATED CONDITION: j o AHF-54A/AHF-548 D' JCT, FLOW LOW AS SENSED BY AH-933-FSI/FS2.

O .

REDUNDANT INDICATION WHICH WILL VERIFY ALARM-l

-)

l OPERATOR ACTIONS FOR A VALID ALARM:

o INVESTIGATE CAUSE OF LOW AIRFLOW ALARM. t 1

9 DISCUSSION:

THIS ALARM POINT IS ACTUATED WHEN EFIC DUCT AIRFLOW IS LESS THAN 70%

OF DESIGN AIRFLOW.

l i

-i

REFERENCES:

DRAWING 208-005-AH-185 SENSING ELEMENT: AH-933-FSI, AH-933-FS2 '

AR-403 Rev. 20 Page 169

, (') ENCLOSURE 1

( ,/ (Page 168 of 194) l l ,

PSA-Z ANNUNCIATOR RESPONSE PSA-Z-06-08 H-06-08 l

EFIC AH SYSTEM l TROUBLE l

l EVENT POINT 0775 i

INDICATED CONDITION:

o EFIC ROOM (S) TEMPERATURE HIGH/ LOW AS SENSED BY AH-944-TS1/TS2/TS3/TS4.

l (m.

L.]

I REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

OPERATOR ACTIONS FOR A VALID ALARM:

o INVESTIGATE CAUSE OF EFIC ROOM TEMPERATURE ALARM.

+

DISCUSSION:

THIS ALARM POINT IS ACTUATED WHEN ANY EFIC R00H TEMPERATURE IS LESS THAN 60*F OR GREATER THAN 85'F. ONE DETECTOR IS LOCATED IN EACH EFIC ROOM MOUNTED ON THE WALL APPR0XIMATELY 4' FROM THE FLOOR. IF ALARM IS l IN FOR NO APPARENT REASON ENGINEERIllG CAN ADJUST DAMPER AND/0R DUCT REGISTER POSITIONS TO BETTER DISTRIBUTE AIR FLOW THROUGHOUT THE ROOMS.

REFERENCES:

DRAWING 208-005-AH-185

(]

U SENSING ELEMENT: AH-944-TS1, AH-944-TS2, AH-944-TS3, AH-944-TS4 AR-403 Rev. 20 Page 170

3 fw ENCLOSURE 1

( I (Page 169 of 194)

PSA-Z ANNUNCIATOR RESPONSE PSA-2-07-01 H-07-01 EF TANK LEVEL LOW-LOW EVENT POINT 0815 .

i INDICATED CONDITION:

o EFT-2 LEVEL <8'0" AS SENSED BY EF-98-LT.

. (~)

\J REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o EF-98-LII, EMERGENCY FEED TANK LEVEL INDICATION.

o EF-99-LII, EMERGENCY FEED TANK LEVEL INDICATION.

OPERATOR ACTIONS FOR A VALID ALARM:

l o REFER TO E0P.

c i

DISCUSSION:

THE LOW-LOW LEVEL ALARM SETPOINT IS EQUIVALENT TO 30,600 GALLONS.

REFER TO STS FOR ADMINISTRATIVE REQUIREMENTS.

f')

REFERENCES:

DRAWING 205-026-EF-05 SENSING ELEMENT: EF-98-LT AR-403 Rev. 20 Page 171

g ENCLOSURE 1 (Page 170 of 194)

PSA-Z ANNUNCIATOR RESPONSE PSA-Z-07-02 H-07-02 EF PUMP 1 AUTO START EVENT POINT 1681 s

INDICATED CONDITION:

l 0 EFP-1 MOTOR ENERGIZED WITH CONTROL SWITCH IN NORMAL AFTER STOP POSITION.

O l REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

i o RED LIGHT ON WITH A GREEN FLAG ON EFP-1 CONTROL STATION.

OPERATOR ACTIONS FOR A VALID ALARM:

l 0 REFER TO E0P.

l l

i l

DISCUSSION:

l l

Q

- \_/

REFERENCES:

DRAWING 208-026-EF-OlB SENSING ELEMENT: EFP-1 CONTROL SWITCH CONTACTS CS/ST, CS/0 l

l-AR-403 Rev. 20 Page 172

l ENCLOSURE 1 (Page 171 of 194) l PSA-Z ANNUNCIATOR RESPONSE PSA-Z-07-03 H-07-03 EF PUMP 1 '

i START l FAILURE i

l EVENT POINT 1680 l

INDICATED CONDITION:

l o EFP-1 MOTOR NOT ENERGIZED WITH CONTROL SWITCH IN NORMAL AFTER STOP POSITION, AND 50 SECONDS HAVE ELAPSED WITH AN ACTUATION SIGNAL PRESENT.

t O

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

OPERATOR ACTIONS FOR A VALID ALARM:

l 0 REFER TO E0P.

o MANUALLY START EFP-1 ,

DISCUSSION:

IF EFP-1 FAILED TO START FROM A VALID ACTUATION SIGNAL, BUT WAS MANUALLY STARTED THEN THIS ALARM WILL NOT ACTUATE DUE TO THE 50 SECOND TIME DELAY RELAY CIRCUIT. THE CONTROL SWITCH MUST BE IN THE NORMAL AFTER STOP POSITION TO ACTUATE THIS ALARM.

REFERENCES:

DRAWING 208-026-EF-01B SENSING ELEMENT: EFP-1 CONTROL. SWITCH CONTACTS CS/ST, CS/0 AR-403 Rev. 20 Page 173

. _ . _ . . . _ = _ . . . _ . . ._ _ _ _ _ _

f. .-. _

1 ENCLOSURE 1 (Page 172 of 194)

PSA-Z ANNUNCIATOR RESPONSE PSA-Z-07-03 H-07-03 i EF PUMP 1 START FAILURE EVENT POINT 1682  ;

t f

INDICATED CONDITION: ,

o EFP-1 DISCHARGE PRESSURE <1100 PSIG AS SENSED BY EF-17-PS WITH CONTROL SWITCH IN NORMAL AFTER START POSITION.

l O  ;

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

l l

OPERATOR ACTIONS FOR A VALID ALARM: j l o REFER TO E0P. i o INVESTIGATE CAUSE OF LOW DISCHARGE PRESSURE.  !

I l DISCUSSION:

i THE CONTROL SWITCH MUST BE IN THE NORMAL AFTER START POSITION TO ACTUATE THIS EVENT POINT. i

l.  :

l l

REFERENCES:

DRAWING 208-026-EF-01B  :

C SENSING ELEMENT: EFP-1 CONTROL SWITCH CONTACTS CS/SC, CS/0, EF-17-PS l

r i

AR-403 Rev. 20 Page 174

_ ___ . . - . - _ . _ . ~ . . . . _ . . . _ . . . - _ _ . . . . . . _ . . _ . . _ . . . . . . . _ _ . - . _ . _ . . - . , _ ,

.h.

ENCLOSURE 1 (Page 173 of 194)

PSA-Z ANNUNCIATOR RESPONSE PSA-Z-07-04 H-07-04 i

EF PUMP 1 TRIP EVENT POINT 1261  :

l INDICATED CONDITION:

l o EFP-1 MOTOR NOT ENERGIZED WITH CONTROL SWITCH IN NORMAL AFTER START POSITION.

j REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o GREEN LIGHT ON WITH A RED FLAG ON EFP-1 CONTROL STATION.

OPERATOR ACTIONS FOR A VALID ALARM:

l l 0 REFER TO E0P. t l 0 INVESTIGATE CAUSE OF BREAKER TRIP. g

a

! DISCUSSION:

THE CONTROL SWITCH MUST BE IN THE NORMAL AFTER START POSITION TO ACTUATE THIS EVENT POINT.

REFERENCES:

DRAWING 208-026-EF-01 SENSING ELEMENT: EFP-1 CONTROL SWITCH CONTACTS CS/SC, CS/0 AR-403 Rev. 20 Page 175

f --

r- ENCLOSURE 1 (Page 174 of 194)

(

PSA-Z ANNUNCIATOR RESPONSE PSA-Z-07-05 H-07-05 EF PUMP 1 OUT OF SERVICE EVENT POINT 1191 t' INDICATED CONDITION:

o EFP-I CONTROL SWITCH IN PULL TO LOCK POSITION L)

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

1 o GREEN AND RED LIGHTS EXTINGUISHED ON CONTROL STATION.

l

OPERATOR ACTIONS FOR A VALID ALARM

4 l u.

DISCUSSION:

(]

REFERENCES:

DRAWING 208-026-EF-01

, SENSING ELEMENT: EFP-1 CONTROL SWITCH CONTACTS CS/PTL

, AR-403 Rev. 20 Page 176 l

l '

l ENCLOSURE 1 (Page 175 of 194)

PSA-Z ANNUNCIATOR RESPONSE PSA-Z-07-05 H-07-05 I

l 1

EF PUMP 1  ;

OUT OF SERVICE i

EVENT POINT 1257 l i

INDICATED CONDITION:

o EFP-1 CIRCUIT BREAKER NOT RACKED IN.

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o GREEN AND RED LIGHTS EXTINGUISHED ON CONTROL STATION.

OPERATOR ACTIONS FOR A VALID ALARM:

l <

DISCUSSION:

REFERENCES:

DRAWING 208-026-EF-01 l

SENSING ELEMENT: EFP-1 BREAKER 52H/B CONTACTS AR-403 Rev. 20 Page 177

ENCLOSURE 1 (Page 176 of 194)

PSA-Z ANNUNCIATOR RESPONSE PSA-2-07-05 H-07-05

-EF PUMP 1 OUT OF SERVICE ,

EVENT POINT 1259 INDICATED CONDITION:

i o EFP-1 CIRCUIT BREAKER LOSS OF DC CONTROL POWER.

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o GREEN AND RED LIGHTS EXTINGUISHED ON CONTROL STATION.

1 OPERATOR ACTIONS FOR A VALID ALARM:

C d

i i

DISCUSSION:

REFERENCES:

DRAWING 208-026-EF-01 SENSING ELEMENT: EFP-1 BREAKER CONTROL CIRCUIT 27 RELAY AR-403 Rev. 20 Page 178

-ENCLOSURE 1 p)s

( (Page 177 of 194)

PSA-Z ANNUNCIATOR RESPONSE PSA-Z-07-06 H-07-06 EF PUMP 1 MOTOR OVERLOAD l EVENT POINT 1260 ,

l INDICATED CONDITION:

o EFP-1 MOTOR AMPS >115% RATED LOAD.

l lO i

l REDUNDANT INDICATION WHICH WILL VERirY ALARM:

l o HIGH MOTOR AMPS.

o EFP-1 BREAKER TRIP.

OPERATOR ACTIONS FOR A VALID ALARM:

l 0 REFER TO E0P.

o START EFP-2. '

o REDUCE EMERGENCY FEEDWATER FLOW FROM EFP-1 IF STILL RUNNING.

l DISCUSSION:

THIS ALARM INDICATES THAT EITHER THE TIMED OVERCURRENT OR INSTANTANEOUS OVERCURRENT PROTECTIVE DEVICES HAVE ACTUATED. INSTANTANE0US OVERCURRENT PROTECTIVE RELAY ACTUATION WILL TRIP THE BREAKER.

IT IS POSSIBLE TO HAVE THIS ALARM PRIOR TO THE BREAKER TRIP.

REFERENCES:

DRAWING 208-026-EF-01 SENSING ELEMENT: EFP-1 BREAKER 51 RELAY (INSIDE 4160 BREAKER CUBICLE)

AR-403 Rev. 20 Page 179

l ENCLOSURE-1 (Page 178 of 194)

PSA-Z ANNUNCIATOR RESPONSE PSA-Z-07-07 H-07-07

(

c FWP-7 l TRIP l EVENT POINT 0819 ,

! i INDICATED CONDITION:

l o FWP-7 MOTOR NOT ENERGIZED WITH CONTROL STATION IN NORMAL AFTER START l POSITION.

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

i o GREEN LIGHT ON WITH A RED FLAG ON FWP-7 CONTROL STATION.

OPERATOR ACTIONS FOR A VALID ALARM:

l o INVESTIGATE CAUSE OF BREAKER TRIP.

I DISCUSSION:

REFERENCES:

DRAWING 208-032 FW-55 SENSING ELEMENT: CS/SC, CS/0 AR-403 Rev. 20 Page 180

. . . . . _ _ _ _ _ . . . -~ - - -. _ . _ _ . . _ . .-

I ENCLOSURE 1 (Page 179 of 194)

PSA-Z ANNUNCIATOR RESPONSE PSA-Z-07-08 H-07-08 l l l l l l l l FWP-7 I I OVERCURRENT I I l 222

! EVENT POINT 0780 l C l

INDICATED CONDITION:

o FWP-7 MOTOR AMPS >115% RATED LOAD l l

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o HIGH MOTOR AMPS o FWP-7 BREAKER TRIP OPERATOR ACTIONS FOR A VALID ALARM: l l

o REDUCE FEEDWATER FLOW FROM FWP-7 IF STILL RUNNING ,l 9

DISCUSSION:

THIS ALARM INDICATES THAT EITHER THE TIMED OVERCURRENT OR INSTANTANEOUS OVERCURRENT PROTECTIVE DEVICES HAVE ACTUATED. INSTANTANE0US OVERCURRENT PROTECTIVE RELAY ACTUATION WILL TRIP THE BREAKER. l IT IS POSSIBLE TO HAVE THIS ALARM PRIOR TO THE BREAKER TRIP.

REFERENCES:

DRAWING 208-032 FW-55 SENSING ELEMENT: FWP-7 BREAKER 51 RELAY (INSIDE 4160 BREAKER CUBICLE)

O AR-403 Rev. 20 Page 181~

ENCLOSURE 1 (Page 180 of 194)

PSA-Z ANNUNCIATOR RESPONSE PSA-Z-08-01 H-08-01 l l EF TANK l l LEVEL-1 I HIGH/ LOW l l I I I I EVENT POINT 0816 1

INDICATED CONDITION:

o EFT-2 LEVEL >37'0" AS SENSED BY EF-98-LT.

iO REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o EF-98-LII EMERGENCY FEED TANK LEVEL INDICATION.

o EF-99-LII EMERGENCY FEED TANK LEVEL It'DICATION.

OPERATOR ACTIONS FOR A VALID ALARM:

l 0 RESTORE TANK LEVEL TO NORMAL OPERATING BAND. ,

b e

DISCUSSION:

THE HIGH LEVEL ALARM SETPOINT IS EQUIVALENT TO 163,900 GALLONS.

i

REFERENCES:

DRAWING 205-026 EF-05 SENSING ELEMENT: EF-98-LT l

AR-403 Rev. 20 Page 182 l

l

ENCLOSURE 1 4

(Page 181 of 194) l PSA-Z ANNUNCIATOR RESPONSE PSA-Z-08-01 H-08-01 l

l

_______ )

I EF TANK LEVEL HIGH/ LOW l

EVENT POINT 0817 INDICATED CONDITION:

o EFT-2 LEVEL <34'6" AS SENSED BY EF-99-LT.

O l REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o EF-98-LIl EMERGENCY FEED TANK LEVEL INDICATION.

o EF-99-LII EMERGENCY FEED TANK LEVEL INDICATION.

I OPERATOR ACTIONS FOR A VALID ALARM: l 1

o RESTORE TANK LEVEL TO NORMAL OPERATING BAND.  !

DISCUSSION:

THE LOW LEVEL ALARM SETPOINT IS EQUIVALENT TO 152,500 GALLONS.

REFER TO STS FOR ADMINISTRATIVE REQUIREMENTS.

I

REFERENCES:

DRAWING 205-026 EF-05 SENSING ELEMENT: EF-99-LT AR-403 Rev. 20 Page 183 l 1

- . _ ._. _ _ . - , , _ - . -- I

, ENCLOSURE 1 (Page 182 of 194) l PSA-Z ANNUNCIATOR RESPONSE PSA-Z-08-02 H-08-02 I

l EF PUMP 2 AUTO START l

l EVENT POINT 1707 l

INDICATED CONDITION:

1 o EFP-2 DISCHARGE PRESSURE >1100 PSIG AS SENSED BY EF-18-PS, AND 50 )

SECONDS HAVE ELAPSED WITH AN ACTUATION SIGNAL PRESENT. j l

O l REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

OPERATOR ACTIONS FOR A VALID ALARM:

l l 0 REFER TO E0P.

DISCUSSION: l I i l

REFERENCES:

DRAWING 205-008 AS-01 SENSING ELEMENT: EF-18-PS l j AR-403 Rev. 20 Page 184

i ENCLOSURE-1 l

O (Page 183 of 194)

PSA-Z ANNUNCIATOR RESPONSE PSA-Z-08-03 H-08-03 i

EF PUMP 2 .

START FAILURE I

EVENT POINT 1706 i

INDICATED CONDITION:

o EFP-2 DISCHARGE PRESSURE <1100 PSIG AS SENSED BY EF-18-PS, AND 50 SECONDS HAVE ELAPSED WITH AN ACTUATION' SIGNAL PRESENT.

O 1 REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

I l

0PERATOR ACTIONS FOR A VALID ALARM:

l o REFER TO E0P. .

i!

f:

j DISCUSSION:  ;

REFERENCES:

DRAWING 205-008 AS-01 SENSING ELEMENT: EF-18-PS l

AR-403 Rev. 20 Page 185 I

. . . - . - . - ~ -, , . . -

l l

l ENCLOSURE 1 (Page 184 of 194) l*

PSA-Z ANNUNCIATOR RESPONSE PSA-Z-08-04 H-08-04 EF PUMP 2 TRIP l

EVENT POINT 0326 l

INDICATED CONDITION:

l 0 TURBINE DRIVEN EMERGENCY FEEDWATER PUMP STEAM SUPPLY VALVE ASV-50 NOT OPEN.

1O l REDUNDANT INDICATION WHICH WILL VERIFY ALARM: l t

OPERATOR ACTIONS FOR A VALID ALARM:

o NOTIFY PRIMARY PLANT OPERATOR TO RESET ASV-50 5

l i l DISCUSSION:

4

REFERENCES:

DRAWING 205-008 AS-01 SENSING ELEMENT: 33C/ASV-50 AR-403 Rev. 20 Page 18C

1 i

ENCLOSURE 1 j[ (Page 185 of 194)

PSA-Z ANNUNCIATOR RESPONSE PSA-Z-08-05 H-08-05 i

I i

l EF PUMP 2 j OUT OF SERVICE l

! EVENT POINT 0100 1 l-i i

j INDICATED CONDITION:

o ASV-5 CLOSED, WITH DC CONTROL POWER NOT AVAILABLE FOR >5 SECON05.

1 o MSV-55 CLOSED.

o MSV-56 CLOSED.

1 4

! REDUNDANT INDICATION WHICH WILL VERIFY ALARM: i j o ASV-5 POSITION INDICATION.

  • i o MSV-55 POSITION INDICATION.

l o MSV-56 POSITION INDICATION.

i j OPERATOR ACTIONS FOR A VALID ALARM:

o INVESTIGATE LOSS OF CONTROL POWER TO ASV-5. -

) o INVESTIGATE CLOSURE OF MSV-55 OR MSV-56. j i

DISCUSSION:

IF THIS ALARM IS DUE TO THE ASV-5 CIRCUITRY THEN IT MEANS ASV-5 IS CLOSED j

WITH NO CONTROL POWER AVAILABLE TO ALLOW AN AUTO OPEN DURING AN EFW i ACTUATION. -

! THE MSV-55 AND MSV-56 ALARMS ARE DUE TO FULLY CLOSED LIMIT SWITCHES.

] ,

CONTROL POWER FOR ASV-5 IS SUPPLIED FROM DPDP-8B FUSE #6.

s

REFERENCES:

DRAWING 205-008 AS-01 SENSING ELEMENT: ASV-5 LS(13), 2ASV-5 RELAY, MSV-55 LS(5), MSV-56 LS(14) 4 3

AR-403 Rev. 20 Page 187

I I

(~~ ENCLOSURE 1 (Page 186 of 194)

PSA-Z ANNUNCIATOR RESPONSE PSA-Z-08-05 H-08-05 i

EF PUMP 2 OUT OF SERVICE l

l EVENT POINT 1521 l

INDICATED CONDITION:

o ASV-204 CLOSED, WITH DC CONTROL POWER NOT AVAILABLE.

l O

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o ASV-204 POSITION INDICATION.

OPERATOR ACTIONS FOR A VALID ALARM:

o INVESTIGATE LOSS OF CONTROL POWER TO ASV-204.

DISCUSSION:

THIS ALARM MEANS ASV-204 IS CLOSED WITH NO CONTROL POWER AVAILABLE TO ALLOW AN AUTO OPEN DURING AN ACTUATION. CONTROL POWER FOR ASV-204 IS SUPPLIED FROM DPDP-8A FUSE #15.

REFERENCES:

DRAWING 208-008 AS-07 SENSING ELEMENT: ASV-204 LS(13), 27ASV-204 RELAY AR-403 Rev. 20 Page 188

i

!(g ENCLOSURE 1

' (j (Page 187 of 194)

PSA-Z ANNUNCIATOR RESPONSE PSA-Z-08-06 H-08-06 l

EMERG FW VALVE NOT FULL OPEN i

EVENT POINT 1192 INDICATED CONDITION:

o EFV-32 NOT FULL OPEN.

rm

'v REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o EFV-32 POSITION INDICATION.

l OPERATOR ACTIONS FOR A VALID ALARM:

o INVESTIGATE CLOSURE OF EFV-32.

DISCUSSION:

(

)

REFERENCES:

DRAWING 205-026 EF-11 SENSING ELEMENT: EFV-32 FULL OPEN LIMIT SWITCH AR-403 Rev. 20 Page 189

1 i

ENCLOSURE 1 (Page 188 of 194) l

. PSA-Z ANNUNCIATOR RESPONSE PSA-Z-08-06 H-08-06 l

I EMERG FW

, VALVE  :

1 NOT FULL OPEN i ,

EVENT POINT 1193 .

. INDICATED CONDITION:

, o EFV-11 NOT FULL OPEN.

O .

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

, \

o EFV-11 POSITION INDICATION.

OPERATOR ACTIONS FOR A VALID ALARM:

o INVESTIGATE CLOSURE OF EFV-11.

o i

DISCUSSION: )

REFERENCES:

DRAWING 205-026 EF-09 SENSING ELEMENT: EFV-11 FULL OPEN LIMIT SWITCH AR-403 Rev. 20 Page 190

ENCLOSURE 1 O (Page 189 of 194)

PSA-Z ANNUNCIATOR RESPONSE PSA-Z-08-06 H-08-06 l

1 D4 ERG FW VALVE NOT FULL OPEN 1

l EVENT POINT 1194 i  ;

INDICATED CONDITION:

o EFV-14 NOT FULL OPEN.

!O REDUNDANT INDICATION WHICH WILL VERIFY ALARM: I

\

o EFV-14 POSITION INDICATION.

l l OPERATOR ACTIONS FOR A VALID ALARM:  !

l 0 INVESTIGATE CLOSURE OF EFV-14.

e i

DISCUSSION:

REFERENCES:

DRAWING 205-026 EF-10

(}

SENSING ELEMENT: EFV-14 FULL OPEN LIMIT SWITCH AR-403 Rev. 20 Page 191

l -

i ENCLOSURE 1 O (Page 190 of 194) )

PSA-Z ANNUNCIATOR RESPONSE PSA-Z-08-06 H-08-06 l l

EMERG FW VALVE NOT FULL OPEN  !

I EVENT POINT 1196

! l INDICATED CONDITION: l l

o EFV-33 NOT FULL OPEN. l l

O REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o EFV-33 POSITION INDICATION.

OPERATOR ACTIONS FOR A VALID ALARM:

i o INVESTIGATE CLOSURE OF EFV-33.

h i

DISCUSSION:

REFERENCES:

DRAWING 205-026 EF-11 SENSING ELEMENT: EFV-33 FULL OPEN LIMIT SWITCH l

AR-403 Rev. 20 Page 192

i i

ENCLOSURE 1 (Page 191 of 194) l i

4 PSA-Z ANNUNCIATOR RESPONSE PSA-Z-08-06 H-08-06 i

i i EMERG F)i j VALVE NOT FULL OPEN i

a i

I EVENT POINT 1255 f

a l

! l i INDICATED CONDITION: l 1 \

! o EFV-3 NOT FULL OPEN. )

+

l ()

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

4 o EFV-3 POSITION INDICATION.

t

i i OPERATOR ACTIONS FOR A VALID ALARM:

j o INVESTIGATE CLOSURE OF EFV-3.

1

~

DISCUSSION:

i i

4 i

1

- /T

REFERENCES:

DRAWING 205-026 EF-02 D

SENSING ELEMENT: EFV-3 FULL OPEN LIMIT SWITCH AR-403 Rev. 20 Page 193

i i

ENCLOSURE I g (Page 192 of 194) i PSA-Z ANNUNCIATOR RESPONSE PSA-Z-08-06 H-08-06 EMERG FW l VALVE l NOT FULL OPEN l l l EVENT POINT 1256 l ill l

INDICATED CONDITION:

o EFV-4 NOT FULL OPEN.

l l

O i l REDUNDANT INDICATION WHICH WILL VERIFY ALARM: j i

o EFV-4 POSITION INDICATION. i l

l OPERATOR ACTIONS FOR A VALID ALARM:

l 0 INVESTIGATE CLOSURE OF EFV-4. -J l

DISCUSSION:

l l

REFERENCES:

DRAWING 205-026 EF-03 SENSING ELEMENT: EFV-4 FULL OPEN LIMIT SWITCH 4

AR-403 Rev. 20 Page 194

_ _ , . - - - ~ . _ _ . . . _ . _ . ~ - . - . . _ _ _ _ _ . _ . _ . . _ _ _ _ . _ .

ENCLOSURE 1 j

] (Page 193 of 194) l

, PSA-Z ANNUNCIATOR RESPONSE PSA-Z-08-06 H-08-06 l

! EMERG FW

VALVE
NOT FULL OPEN ,

i 1

l EVENT POINT 1262 l

INDICATED CONDITION:

o EFV-7 NOT FULL OPEN. I 4

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

, o EFV-7 POSITION INDICATION. ,

4

! OPERATOR ACTIONS FOR A VALID ALARM:

1 o INVESTIGATE CLOSURE OF EFV-7.

1 .

O l

DISCUSSION:

l 4

REFERENCES:

DRAWING 205-026 EF-04 s

SENSING ELEMENT: EFV-7 FULL OPEN LIMIT SWITCH AR-403 Rev. 20 Page 195 w

ENCLOSURE 1 (Page 194 of 194)  !

. PSA-Z ANNUNCIATOR RESPONSE PSA-Z-08-06 H-08-06 r

l 1

EMERG FW j VALVE NOT FULL OPEN EVENT POINT 1263 i

j INDICATED CONDITION:

l 0 EFV-8 NOT FULL OPEN.

l O

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

o EFV-8 POSITION INDICATION.

OPERATOR ACTIONS FOR A VALID ALARM:

o INVESTIGATE CLOSURE OF EFV-8.

DISCUSSION:

i l

l

(

REFERENCES:

DRAWING 205-026 EF-05 SENSING ELEMENT: EFV-8 FULL OPEN LIMIT SWITCH AR-403 Rev. 20 Page 196 (LAST PAGE)

. . >