ML20044G666
| ML20044G666 | |
| Person / Time | |
|---|---|
| Site: | Oyster Creek |
| Issue date: | 01/31/1993 |
| From: | GENERAL PUBLIC UTILITIES CORP. |
| To: | |
| Shared Package | |
| ML20044G664 | List: |
| References | |
| NUDOCS 9306040073 | |
| Download: ML20044G666 (26) | |
Text
~
.. l 4
OYSTER CREEK NUCLEAR GENERATING STATION REACTOR CONTAINMENT BUILDING INTEGRATED LEAK RATE TEST
SUMMARY
TECHNICAL REPORT JANUARY,1993
$8861885!0888h9 P
TABLE OF CONTENTS SECTION PAGE A. INTRODUCTION.................................... 1 B. G ENER AL D ATA....................
........I C. TECHNICAL DATA
....................... 1 D. TYPE A TEST DATA
......................... 1 E. V E RI FI C ATI O N TEST.................................. 2 F. ACCEPTANCE CRITERIA............................... 2 G. TEST INSTR UM ENTATION.............................. 3 H. TEST PROCEDURE
- 1. GENERAL DISCUSSION..
............. 3
- 2. DETAILED DISCUSSION...
.........................4 1
I I. METHODS OF ANALYSIS
.................... 5 J. DISCUSSION OF RESULTS
- 1. AS-FOUND ILRT..
.............................. 5
- 2. AS-LEFT ILRT
.......................... 8
- 3. VERIFICATION TEST RESULTS.
......................9
- 4. LLRT RESULTS............
............. 9 K. SUMM ARY.....
....................10 L. R EFER EN C ES......................................
1 1 7
ATTACHMENTS 1.
Figure 1 Arrangement of Test Instrumentation 2.
Figure 2 Sensor Locations 3.
Figure 3 Plot of Leakrate Vs. Time 4.
Table 1 ILRT Calculated Values 5.
Table 2 13R LLRT Results 6.
Table 3 14R LLRT Results 7.
Table 4 Type B and C Tests - Cycle 12 and 13 1
8.
Report 1 Secondary Containment Test: 13R and 14R i
1 I
i 4
C321-93-2153 l -
Page 1 A. INTRODUCTION The Oyster Creek Primary Containment Integrated Leak Rate Test (PCILRT) was conducted on the dates of January 26,1993 through January 29,1993. The twenty-four ~
hour Type A Test was performed as required by 10CFR50, Appendix J; the applicable Oyster Creek Technical Specifications; and Station Procedure 666.5.007,." Primary Containment Integrated Leak Rate Test", Guidance in conducting the test was provided by ANSI N45.2-1972, ANSI /ANS 56.8-1981, and ANSI /ANS 56.8-1987.
Included herein, in accordance with 10CFR50, Appendix J, and Oyster Creek Technical I
Specifications, is a summary of pertinent data, Type B and Type C local leak rate test-l results, and an analysis and interpretation of test results. A description of the leak t
detection system, calculational methods, and supporting test data are provided as attachments. Additional test supporting data is available for review at the station site in accordance with ANSI /ANS 56.8-1987.
B.
GENERAL DATA
- 1. Oyster Creek Nuclear Generating Station, operated by GPU Nuclear.
- 2. Location: Forked River, New Jersey
- 3. Docket Number: 50-219
- 4. Containment Design: General Electric company, Mark I
- 5. Test Completion: January 29,1993 C. TECHNICAL DATA
- i
- 1. Containment Net Free Air Space 307,633 cubic feet
- 2. Design Pressure 62 psig (drywell) l 35 psig (torus)
- 3. Design Temperature 281 F (drywell) 150 F (torus)
- 4. Design Accident Peak Pressure 38 psig
- 5. Design Accident Peak Temperature 275 F l
D. TYPE A TEST DATA
- 1. Test Method Absolute
- 2. Data Analysis Mass Point
- 3. Test Pressure 23.5 psig
- 4. Maximum Allowable Leak Rate
.8194 wt%/ day 2
at Test Pressure 1
- 5. Measured Leakage Rate
.372 wt%/ day
- 6. Calculated UCL-95 Leakage Rate
.376 wt%/ day l
d y
v x
~$
[
4 C321-93-2153 i
Page 2 l
1 E.
VERIFICATION TEST
-i
- 1. Calibrated Superimposed Ixak 1.0421 wt%/ day
- 2. Measured UCL-95 Leak Rate
.376 wt%/ day -
from Type A test
- 3. Maximum Allowable Leak Rate
.8194 wt%/ day at Test Pressure
- 4. Composite Leak Rate calculated 1.412 wt%/ day i
from verification test I
F. ACCEPTANCE CRITERIA
- 1. The maximum allowable leakage rate (L,) shall not exceed 1.0 weight percent of the contained air per 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> at a test pressure adjusted to 35 psig (P,). The allowable leakage rate (I,), at the test pressure (PJ shall not exceed the following:
I,= 1.0 wt. % [P,/P,]"
I,= 1.0 [23.5/35]*
I,=.8194 The ratio of pressures is based on gauge pressure, not absolute pressure as stated in the technical specification. The use of gauge pressure is more conservative, as explained in Engineering Evaluation No 485-90.
1 2.
The maximum allowable operational leakage rate (1,m) Max, which shall be met prior to resumption of power operation following a PCILRT shall not exceed 0.751,:
1 I,, Max <.751, 4
Luo Max <.75 x.8194 L,, Max <.6146 3.
The difference between the verification test result and the sum of the induced leak plus the Type A test result shall be within 0.25 L.
{
t 4.
The maximum combined leakage rate of all potential leakage flow paths subject to l
Type 'B' and 'C' tests is:
i 0.60 L. (35 psig) = 0.6 (426.00 SCFH) = 255.6 SCFH (Ref: Procedure 665.5.020).
r
=
C321-93-2153 Page 3 G. TEST INSTRUMENTATION 1.
The measurement system installed inside containment prior to pressurization consists of two precision pressure gauges,30 resistance temperature detectors,10_ -
dewcells, and one multiplexer. These inputs are connected to a data acquisition system located outside containment which communicates with the Prime plant
'I computer. The arrangement of the Type A test instrumentation system is shown in Figure 1.
1 4
2.
The multiple inputs for each parameter (pressure,'drybulb temperature, and dewpoint temperature) are combined using a weighted average based on the represented volume.The sensor readings are processed at 15 minute intervals for a minimum period of 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />. The sensor locations are shown on Figure 2.
3.
All test sensors and flowmeters were calibrated prior to the ILRT in accordance with ANSI N56.8. In-situ checks were performed prior to the ILRT.
4.
All sensors, except for one dewcell, performed acceptably during the ILRT. The one dewcell was removed from the calculations, and the remaining sensors were re-weighted according to procedure 666.5.007.
5.
After completion of the Type A test, a known leak was superimposed on the containment through a calibrated flow sensor and measurements were continued.
The leakage rate calculated by the computer program during the verification test was compared to the leakage rate measured during the Type A test. Successful campletion of the verification test validated the test method and the instrumentation system.
H. TEST PROCEDURE
- 1. General Discussion During the pressurization phase, weighted pressure is monitored until the desired pressure is reached. Conditions are then allowed to stabilize for a minimum of four hours before the test is begun. Stabilization is reached when the weighted temperature meets the relationship in paragraph 2b of this report. Data scans are recorded every 15 minutes. The measured leakrate is closely monitored to detect high leakage. If detected, an evaluation will be made to determine the course of action to take. In addition, sensor data is reviewed to detect any malfunctioning sensors. Window calculations are performed, wrich record the leakrate over the last hour. This data is reviewed periodically for trends which might affect the test results, a
C321-93-2153 Enclosure' 1 Page 4 The test is terminated when the measured leakrate and the UCL-95 leakrate are both within the allowable for the final 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br />, and the minimum time has elapsed. The final phase is the verification test, where a known leak is super-imposed on the containment and measured by the test equipment. A plot of the leakrate vs. time is printed.
- 2. Detailed Discussion a.
The pressurization phase took approximately 20 hours2.314815e-4 days <br />0.00556 hours <br />3.306878e-5 weeks <br />7.61e-6 months <br /> to reach 24 psig. The rate of pressurization was limited by the compressors ability to deliver flow,
- b. The stabilization phase took the minimum time of four hours. The slow pressurization rate allowed stabilization to occur quickly. The criteria for-temperature stabilization is when the test pressure is reached and the latest rate of ;
change of the weighted average contained air temperature averaged over the last.
j hour does not deviate by more than 0.5 F per hour from the average rate of :
change of the weighted average contained air temperature averaged over the last four hours.
73.164-72.698 =.1165 (four hour average) 4
.100 (last hour)
I 72.798-72.698
=
c.
During the first few hours of the test, a high leakrate was observed. As a result,-
l adjustments were made to reduce the leakage. Several valves were adjusted and -
the drywell sump was isolated. The test was then restarted, after about 26 hours3.009259e-4 days <br />0.00722 hours <br />4.298942e-5 weeks <br />9.893e-6 months <br />, on January 28 at 1015 hours0.0117 days <br />0.282 hours <br />0.00168 weeks <br />3.862075e-4 months <br />. Subsequent to the test completion, a review of the results was made. It was determined that the repairs made during the test and the j
induced leak were not detectable by the statistical model. For conservatism, the repairs were quantified and added to the UCL-95 value, along with the LLRT J
leakage savings, Isolated Penetrations, and Drywell Sump Level Correction to -
j
'~
determine the As-Found results. This evaluation is summarized in Engineering Evaluation No 314-93. The final ILRT test results are shown in Table 1 and.
Figure 3.
i
- d. After completion of the Type.A test, a known leak was superimposed on the L
containment through a calibrated flow sensor and measurements were continued.
The leakage rate measured during the verification test was compared to the sum of the induced leak plus the leakage rate measured during the Type A test.
Successful completion of the verification test validated the test method and the instrumentation system. The results are shown in Table 1.
1 u
^
C321-93-2153 Page 5 i
I.
METHODS OF ANALYSIS i
The containment integrated leakage rate is calculated using the Mass Point data analysis technique. This technique reduces the data to a contained air mass.by application of the ideal gas law. The test data consists of a sequence of independent values of contained air mass. The assumption is made that the leakage rate is constant with time and the data is 3
analyzed using the method oflinear least squares regression. The slope of this line represents the rate of change of air mass to time, which is the leakage rate. The data is also analyzed statistically to determine the upper 95 percent confidence interval. The final reported leakage rate is the upper 95 percent confidence leakage rate.
]
J.
DISCUSSION OF RESULTS
- 1. As-Found ILRT The following penetrations were isolated during the test and were, therefore, a.
added to the test results (Ref: procedure 665.5.020):
Penetration Leak Rate (SCFH)
@ 35 PSIG
.114 Cleanup System from Reactor V 1,2&l4
.075 Cleanup System to Reactor V-16-61 & 62 l
Feedwater Check Valves V-2-71 & 73
.031 V-2-72 & 74
.617 Liquid Poison Check Valves 1.12 V-19-16 & 20 RBCCW from Drywell
.848 j
V-5-166 & 167 RBCCW to Drywell 1.52 V-5147 & 165 Reactor Sample Line
.016 V-24-29 & 30 1
r:
C321-93-2153 Page 6 Penetration Leak Rate (SCFH) 6D 35 PSIG 3
Drywell Sump Discharge
.046 V-22-28 & 29 I
Drywell Equip Drain Tank Discharge IL4 V-22-1 & 2 i
Total Adjustment @ 35psig......... 4.611 Total Adjustment @ 23.5 psig..... 3.778 i
9 Convert to wt%/ day:
3.778 cu.ft.
X 1
X 14.70si
.X 24 hrs =
hr.
307,633 cu.ft.
(23.5+14.7) psi day.
- r
.00011 =.011 wtc/c/ day i
- b. Drvwell Sumo Level Correction
- l L=
2400 X (.1338 [F1-F0])
(V,+VJ AT l
l From ILRT Log:
First Integrator Reading-790738 1-27-93 0723 hrs.
Final Integrator Reading-791021 1-28-93 1038 hrs.
283 gal 27 hr 14 min
+15 gal
- 298 gal 27.25 hr
- 15 gal from A pump run j
L = 2400 (.1338) (298) =
.0114wt7c/ day (307633) (27.25) i I
m..
.6
.. ~. -
~
C321-93.-2153 Enclosure l' Page 7 i
i c.
To determine the as-found test results the following penalties will be added to the UCL-95 test results: LLRT Leakage Savings, Isolated Penetrations, Drywell
.i Sump Adjustment, and Repairs made during test.
l From Procedure 665.5.020 Total difference of all_ tests @35psig...... 35.484 l
Total difference of all tests @23.5psig.... 29.0759 t
Convert to wt%/ day:
L$
29.0759 cu.ft.
X 1
X 14.7esi.
X 24 hrs 2
=
hr.
307,633 (23.5+14.7) psi.
. day.
=.00087 =.087 wt%/ day i
I i
}
d.
Repairs made durine test An adjustment was made for the repairs made during the ILRT. This adjustment was.1345wt%/ day.
t q
e.
The sum of all the adiustments for the as-found test are:
UCL-95 Leakrate
.561 j
LLRT Leakage Savings
.087 Isolated Penetrations
.011-
'Drywell Sump Adjustment
.0114 Repairs Made During Test
,100 i
A s Found Results.............................. 7704 q
i
C321-93-2153 -
l
. Enclosure 1 1
Page 8 i
I
- 2. As-Left ILRT a.
Drywell Sump Adjustment Ref: Procedure 666.5.007 1
l L=
2400 X (.1338[F1-F0]).
(V,+V,) AT From ILRT Log:
First Integrator Reading-790952 1-28-93 1035 hrs.
Final Integrator Reading-791408 1-29-93 1915 hrs.
456 gal.
32.667 hrs.-
Vo+V,= 307,633 cu.ft.
dT= 32.667 hrs.
F1-F0= 456 gal.
L=
2400._
X (.1338) (456)
(307,633)(32.667) t L
'.0146
=
~.
b.
As Left Test Results Measured UCL-95 Leakage-L
.376 oo Isolated Penetrations
.010 DW Sumn Level Correction
.0146 j
~I Total Leakage...........
.4006
)
s y
+ s w-e
,,e,,,,
,a
~..
C321-93-2153 Page 9
+
- 3. Verification Test Results MEASURED UCL-95 Induced Leak-L 1.0421 o
Composite Leak-L 1.412 1.446 c
The following relationship must be satisfied, per ANSI 56.8:
1 L + L. - 0.251, i L, i L + Lo + 0.251, o
o l.0421 +.372 - 0.25[.8194] < l.412 < l.0421.+.372 + 0.25[.8194]
1.2093 < l.412 < l.6190 1
- 4. LLRT Results a.
During 13R, Local Leak Rate Tests were performed in accordance with Appendix J. The results by penetration are shown in Table 2. A summary is shown below.-
As-Found LLRT Total Several Valves failed the acceptance criteria, therefore, the Tech Spec Limit of l
426 SCFH was exceeded. LER 91-002 was issued to address these concerns.
AS-Left LLRT Total The as-left total was 165.6 SCFH; the acceptance criteria of 255.60 SCFH was met.
5 b.
During 14R, Local Leak Rate Tests were performed in accordance with Appendix-J. The results by penetration are shown in Table 3. A summary is given below.
l As-Found LLRT Total The total as-found LLRT's could not be calculated because the leakrate for MSIV i
NSO4B could not be quantified. Therefore the Tech Spec limit was exceeded.
l LER 92-013 was issued to address this failure.
As-Left LLRT Total The total max path as-left total was 127.5 SCFH, which is within the Tech Spec limit of 255.6 SCFH.
~.
C321-93-2153 '
Page 10-During Cycles 12 and 13, several valves and the drywell airlock were tested.
c.
Table 4 summarizes the tests. The valves were tested due to maintenance performed on the valves. The Airlock is tested _every 6 months, and whenever it is opened. There were no significant test results.
K.
SUMMARY
The calculated As-Found ILRT was.7704 wt%/ day vs the acceptance criteria of.8194 wt%/ day. The As-Found value was calculated conservatively because a _ leak was induced on the containment during the first test to try and find the source of the leakage.The affect of this induced leak was not removed from the calculation of As-Found results since it was below the acceptance criteria with this factor included.
The As-Left test results were.4006 wt%/ day compared to the acceptance criteria of
.6146 wt%/ day.
The verification test was performed in accordance with ANSI /ANS 56.8. Paragraph J3 of this report shows that the requirements of 56.8 were met, thus verifying the test -
instrumentation.
The As-Found LLRT results for both 13R and 14R exceeded the Tech Spec limit. LER's were issued as re. quired.
The As-Left LLRT results were below the acceptance criteria for both 13R and 14R.
1 Therefore, plant startup was allowed per Tech Spec requirements.
Periodic Local Leak Rate Tests were performed during Cycles 12 and 13 for Tech Spec Surveillances, forced outages, maintenance, or modifications. No significant results were found.
o I
l ii
'I i
P C321-93-2153 Page'l1 L.
REFERENCES 1.
Procedure 666.5.007, " Primary Containment Integrated Leak Rate Test" 2.
Procedure 665.5.006, " Local Leak Rate Tests" l
3.
Procedure 665.5.020, " Integrated' Local Leak Rate Test Results"-
l 4.
Title 10 Code of Federal Regulations Part 50, Appendix J, " Primary Reactor Containment Leakage Testing for Water Cooled. Power Reactors" 5.
ANSI N45.4 - 1972, " Leakage Rate Testing of Containment Structures for.;
Nuclear Reactors" 6.
ANSI /ANS 56.8 - 1981, " Containment System Leakage Testing Requirements" 7.
ANSI /ANS 56.8 - 1987, " Containment System Leakage Testing Requirements" 8.
Oyster Creek Nuclear Generating Station Technical Specifications,'Section 3.5,
" Containment", and Section 4.5, " Containment Systems" 9.
ILRT Computer Code j
10.
Engineering Evaluation No 485-90, "Use of Gage Pressure to Calculate Allowable Leakage at ILRT Pressure".
+
l 4
m" E
/
F n
N R
O
+
LE I
R G
AT T4 E
E O
TR A I E' MOT LOIE TST ISU ATGV AIS RTP e.
N I N DUY P
M A
DO QS O
C C
C A
.~
n
~.
n r
o n
0 S
0 S
0AN 0AI 1IA 1IR
- SR
- SP 0PT 0PT w'
R C
P O
A I KS r'
Vd LAi w'
l E
A E E' CLS
/
T
/
TN R
R EP T
E LE IM BE N
NO NU O
IS BE
/
MR y
Z-AP w
E J, MnD
.t OD
,s RT0 7uFR1
FIGURE 2 (RTD AND DEWCELL SENSOR IDCATION) b
.El 95'0" p%
.)
,,g GG 1r
\\
M G
I
-s y
. _ (:
El 53'0*
i; s - _. _. _.
.;i W
@s
'E El 48'0*
i g-
.l @ __ _ _ __ _\\
~'
\\
El 31'0*
O g
.I_ct__E'32__
s El 10'y' Iso ATIONS 6
NU!GERED 1-30 DEWCELL LOCATIONS NUIGERFD A - J
)
1 1
i
FIGURE 3 o
o
.o.
t 4
M.
.r 4
i g.
p 4
A
)O
)O 3
)
d 4
h i
6 I
',. 4,.
E C
I o
.o 4
4 5
mm T-WW We 4
.-.7.-
.j x
x
.;. -.;~
4 4
4 u
x,
.e%
1, 4
5
. '..,.....i..4
.o..
..o.O
.F
. p..
4 g..
O m
m I
i g,!.
!. M.. E..A.. 'S.U..R.
D... '
...-i.....~....i _
l
.~,.
i 4
t i
l l
i i
I l
l t'
d e
i 4
o m
.4
- 8. ~.J f
.}.
4. p 4
. ? --.
t s.
W.
.,p
- t. **:.'*+.+e m
,3
.p 4
i.
l i
c
.g.....p.6.=..._..
. i.. - e.
...a..{.....g.....4 4
=
4 5
y 6
i i
i 4
6 1
4 4
6 g
1, 4
4 4
6 1
4 g
g a
s e.
.i 5
4 5
s 4
hJ+A M
a
+
i 5
i 2
6 4
i 4
+. q..L
. p...j.. g..j..
q..
.. 4 d
4
.j....i..
a
...,6..
4 4
.d 4
4 6
a J
E 4
3 4
a 4
4 J
y 3
e a.
4 a
i s
i t
b I
4 4
4 8
4 4
3 8
8 M.j.
.-.D*
g.
t..
6
. j...y..~ q. _,. p.... 4...
4 4..
4
,. 6.
.J g.
4 5
6 4
a
.i w
g i
a i
4 4
4 4
4 Io f
. N s
s s
4
- b. 4.
8
. 4.
.s,-.
.e d*
s 4
s s
yQ
....C..
.s s
i N.
4 s
. s
.4,.,..4 0
e 1
4 J
4 QQ O
M 4
4 8
4 6
a s
a a
4 s
6 6
5 4
2 4
4 3
4
+
e y
i 4
i 4
--....a 6
.E 4...4...s.
b-4 eh-.
s
- -^
1.
6 6
5 4
4 4
4 4
0 4.-.+%
5
.-.a 4.
.b+-
ie.
y
. i 44 2
i 4
o.m o.
e i
i 6
i s
a s
wei 3
8 4
4 4
6 3
4 I
4 I
Q,,M,-
..DO
,i
.i...
.4 a.. _ 4
.a.,...a....
... a.
4 4
w a
a a
...-.a..
.4.
-.4 g
e.
a 4..
a a
a a
4 i
s ZO 4.
i o
m 4
u a
i i
=
i 4
i 5
i 4
4 i
6 i
4
... _. 4...5....4......a......4..,...
E I
.... s
..._.3 8
,.L
.W..
4 t
l 2
4 wm
.n s
6 e
s a
a a
a 4
4 4
1g
..O.
i...
4..
.g
..g a
5 e
4 4
=
5
.=.a.=
4 6
4
=.'d
- -at-*
4 4
s 4
6 g
. 6 i
- +4
=N.-.*
,,e.
4 4
4
[3 e
s e
+
4 s
4 a
e a
+
4 4
4 3
+
8
'a 4
4.
.4..
4..
6.
M O
4 4
4 6
3 4
4 4
'a 1
.5 Q
,6 1
4 L
2
. 4 A
...8 1
4 4
4 a
e 4
4 4
4 4
4 4
5 4
4 e
2 4
4 4
4 6
4 s
s s
O 4
n s.
4 r
q,.
.+.i s.
<9, g
y,
y g
b n
n...f_.
og.
...g,..
s s
s
.s, 8
p q
L L
L 4
.h 4
4 a
1 6
8 1
I 4
d 4
8 4
4 F
3 1
t
. g 3
g 3
g y
~.
g.
.5...
.g w
J 6
(
e e
4 i
I e
(
B 1
3 O
O k
s 4
O O
a 4
e a
6 6
a s.
...e.
, O '0 2'.90 S.60 0.70 11.60 -
I 't. 50 17.90 20.30 23.20 r
e a
v i
i
- 0. C' O
O ELAPSED TIME HOURS i
l i
i
TABLE 1 MODE: PRESSURIZATION TIME: 026 0715 - 027 0330 PAGE 1/2 TREND OF ILRT CALCULATED VALUES 1993 AIR WGHTED WGHTED WGHTED VAPOR JDA HR MN MASS PRESSR RTTEMP DCTEMP PRESSR 26 7:15 23022.47 14.930 74.008 67.658 0.3348 26
,:30 23020.80 14.928 74.013 67.582 0.3340 l
26 7:45 23017.34 14.927 74.010 67.711 0.3354 1
26 8: 0 23037.68 14.939 74.009 67.699 0.3353 26 8:15 23036.16 14.938 73.998 67.668 0.3350 26 8:30 23016.18 ~14.938 74.209 68.284 0.3421 26 8:45 24161.20 15.677 74.356 68.956 0.3501 26 9: 0 24379.86 15.804 74.179 68.386 0.3433 26 9:15 24708.50 16.007 74.153 68.042 0.3393 i
26 9:30 25034.04 16.212 74.146 67.919 0.3379 26 9:45 25359.36 16.416 74.137 67.768 0.3361 26 102 0 25681.30 16.619 74.137 67.648 0.3347 26 10:15 26007.41 16.825 74.155 67.522 0.3333 26 10:30 26324.78 17.025 74.134 67.501 0.3330 26 10:45 26609.25 17.204 74.091-67.476 0.3328 26 11: 0 26888.90 17.379 74.054 67.441 0.3323 26 11:15 27357.98 17.680 74.168 67.441 0.3323 26 11:30 27868.81 18.005 74.212. 67.406 0.3319 26 11:45 28333.18 18.298 74.173 67.402 0.3319 26 12: 0 28661.91 18.502 74.038 67.381 0.3317 26 12:15 28659.93 18.487 73.772 66.999 0.3273 26 12:30 28656.54 18.482 73.660 67.034 0.3277 26 12:45 29011.36 18.717 73.904 67.203 0.3296 26 13: 0 29564.41 19.073 74.032 67.297 0.3307 26 13:15 30057.41 19.384 74.031 67.219 0.3298 26 13:30 30562.95 19.707 74.052 67.305 0.3308 26 13:45 31104.00 20.050 74.064 67.283 0.3305 26 14: 0 31631.45 20.384 74.073 67.277 0.3305 26 14:15 32160.60 20.718 74.070 67.166' O.3292 26 14:30 32680.75 21.047 74.055 67.162 0.3292 26 14:45 33205.73~ 21.379 74.048 67.082 0.3283 26 15: 0 33720.92 21.705 74.029 67.071 0.3281 26 15:15 34239.73 22.033 74.016 67.032 0.3277 26 15:30 34750.70 22.358 74.009 67.083 0.3283 26 15:45 35264.05 22.682 73.992 67.054 0.3279 26 16: 0 35771.88 23.003 73.965 67.102 0.3285 26 16:15 36242.12 23.300 73.930 67.104 0.3285 26 16:30 36758.46 23.628 73.951 67.125 0.3287 26 16:45 37274.04 23.958 73.956 67.351 0.3313
-j 26 17: 0 37785.96 24.279 73.954 67.099 0.3284 26 17:15 38293.31 24.603 73.950 67.334 0.3311 26 17:30 38801.67 24.924. 73.945 67.307 0.3308 26 17:45 39274.02 25.221 73.904 67.245 0.3301 26 18: 0 39790.08 25.547 73.917 67.098 0.3284 26 18:15 40262.54 25.846 73.881 67.226 0.3299 26 18:30 40732.59 26.141 73.874 66.971 0.3270' i
26 18:45 41187.38 26.430 73.839 67.141 0.3289 26 19: 0 41662.07 26.730 73.821 67.063 0.3280 26 19:15 42127.23 27.022 73.794 67.036 0.3277 26 19:30 42602.76 27.324 73.814 67.030 0.3277-26 19:45 43068.96 27.618 73.781 67.065 0.3281 26 20: 0 43543.32 27.919 73.766 67.217 0.3298 26 20:15 44009.98 28.213 73.751 66.992 0.3272 26 20:30 44484.16 28.513 73.741 66.979 0.3271
2
~
4 TABLE 1 MODE: PRESSURIZATION TIME: 026 0715 - 027 0330 t
PAGE 2/2 TREND OF ILRT CALCULATED VALUES 1993 AIR WGHTED WGHTED WGHTED VAPOR JDA HR MN MASS PRESSR RTTEMP DCTEMP PRESSR 26 20:45 44943.93 28.805 73.723. 66.976 0.3271 l
26 21: 0 45419.26 29.106 73.720 67.031 0.3277 26 21:15 45881.48 29.399 73.698 67.119 0.3287 26 21:30 46358.22 29.699 73.700 66.910 0.3263 26 21:45 46821.48 29.990 73.679 66.829 0.3254 26 22: 0 47291.37 30.290 73.683 67.028 0.3276 26 22:15 47753.48 30.581 73.654 67.023 0.3276 26 22:30 48449.91 31.033 73.803 67.251 0.3302 26 22:45 49232.39 31.529 73.872 66.996 0.3273 7
26 23: 0 50011.73 32.026 73.898 67.171 0.3293 26 23:15 50812.99 32.533 73.931 67.000 0.3273 26 23:30 51541.22 32.998 73.928 67.217 0.3298 26 23:45 52352.91 33.512 73.947 67.067 0.3281 27 0: 0 53084.32 33.975 73.936 67.082 0.3283 27 0:15 53882.16 34.482 73.959 67.104 0.3285 27 0:30 54613.92 34.944 73.930 67.089 0.3283 27 0:45 55405.76 35.448 73.932 67.150 0.3290 27 1: 0 56128.29 35.907 73.933-67.231 0.3299 l
27 1:15 56885.02 36.387 73.944 67.245 0.3301 27 1:30 57384.60 36.695 73.848 67.186 0.3294 27 1:45 57889.45 37.013 73.815 67.225 0.3299 27 2: 0 58391.31 37.331 73.822 67.202 0.3296 27 2:15 58891.96 37.650 73.819 67.263 0.3303 t
27 2:30 59399.51 37.969 73.793 67.027 0.3276 27 2:45 59900.26 38.287 73.750 67.309 0.3308 27 3: 0 60399.77 38.601 73.737 67.200 0.3296 L
t 27 3:15 60710.36 38.783 73.568 67.014 0.3275 27 3:30 60700.42 38.759 73.344 66.986 0.3272
'S s
6
k es s
.~
A r
.=M5-AA TABLE l' MODE: STABILIZATION TIME: 027 0345 - 027 0800 PAGE 1/1 TREND OF ILRT CALCULATED VALUES 1993 AIR WGHTED WGHTED WGliTED VAPOR JDA HR MN MASS PRESSR RTTEMP DCTEMP PRESSR t
27 3:45 60698.37 38.749 73.246 66.861 0.3258 27 4: 0 60698.55 38.741 73.164 66.711 0.3241 l
27 4:15 60691.90 38.733 73.100 66.790 0.'3250 27 4:30 60689.88 38.728 73.063 66.691 0.3239 27 4:45 60682.55 38.722 73.038 66.800 0.3251 27 5: 0 60677.11 38.717 73.001 66.810 0.3252 27 5:15 60670.52 38.713 72.974 66.898 0.3262 27 5:30 60674.58 38.707 72.936 66.391 0.3205 27 5:45 60667.76 38.703 72.905 66.644 0.3233 27 6: 0 60658.94 38.698 72.889 66.779 0.3248 27 6:15 60657.80 38.693 72.864 66.526 0.3220 27 6:30 60653.05 38.689 72.852 66.536 0.3221 27 6:45 60650.90 38.684 72.817 66.432 0.3210 27 7: 0 60644.56 38.680 72.798 66.576 0.3226 27 7:15 60644.45 38.676 72.761 66.456 0.3212 27 7:30 60638.35 38.670 72.743 66.400 0.3206 27 7:45 60630.17 38.666 72.709 66.669 0.3236 27 8: 0 60628.20 38.662 72.698 66.540 0.3222 l
1 i
- i 1
t i
1 i
TABLE 1 MODE: TYPE A TEST (FINAL)
TIME: 028 1015 - 029 1015 PAGE 1/2 TREND OF ILRT CALCULATED VALUES 1993 MEAS UCL95 WINDO WINDO AIR WGHTED WGHTED WCHTED VAPOR JDA HR MN LR LR LR UCL MASS PRESSR RTTEMP DCTEMP PRESSR 28 10:15 0.000 0.000 0.000 0.000 60249.04 38.385 72.202 66.222 0.3186 28 10:30 0.000 0.000 0.000 0.000 60240.97 38.384 72.216 66.533 0.3221 28 10:45 0.000 0.000 0.000 0.000 60233.27 38.379 72.234 66.498 0.3217 28 11: 0 0.000 0.000 0.000 0.000 60235.17 38.379 72.246 66.339 0.3199 28 11:15 0.631 1.056 0.000 0.000 60232.13 38.379 72.256 66.423 0.3209 28 11:30 0.622 0.874 0.000 0.000 60226.64 38.378 72.267 66.522.0.3220 28 11:45 0.614 0.783 0.000 0.000 60222.98 38.378 72.287 66.525 0.3220' 28 12: 0 0.580 0.708 0.000 0.000 60221.45 38.377 72.296 66.485 0.3216 28 12:15 0.618 0.722 0.000 0.000 60212.81 38.377 72.313 66.769 0.3247 28 12:30 0.583 0.673 0.000 0.000 60215.06 38.376 72.323 66.482 0.3215 28 12:45 0.574 0.647 0.000 0.000 60210.12 38.376 72.336 66.685 0.3238 28 13: 0 0.552 0.616 0.000 0.000 60209.16 38.375 72.352 66.614 0.3230 28 13:15 0.530 0.589 0.000 0.000 60207.38 38.375 72.363 66.694 0.3239 28 13:30 0.506 0.562 0.000 0.000 60206.27 38.373 72.370 66.560 0.3224 l
28 13:45 0.485 0.537 0.000 0.000 60204.66 38.373 72.391 66.543 0.3222 28 14: 0 0.473 0.520 0.000 0.000 60200.80 38.373 72.406 66.672 0.3236 L
28 14:15 0.464 0.506 0.000 0.000 60198.23 38.372 72.422 66.642 0.3233 28 14:30 0.456 0.495 0.000 0.000 60195.70 38.371 72.419 66.658 0.3235 28 14:45 0.456 0.490 0.000 0.000 60190.91 38.370 72.423 66.720 0.3242 28 15: 0 0.463 0.495 0.000 0.000 60184.48 38.367 72.423 66.850 0.3256 28 15:15 0.465 0.493 0.000 0.000 60183.73 38.365 72.418 66.714 0.3241 28 15:30 0.465 0.491 0.000 0.000 60181.02 38.364 72.420 66.748 0.3245 28 15:45 0.463 0.487 0.000 0.000 60179.34 38.362 72.417 66.723 0.3242 28 16: 0 0.463 0.485 0.000 0.000 60175.73 38.360 72.411 66.713 0.3241 1
28 16:15 0.464 0.484 0.000 0.000 60171.94 38.358 72.404 66.815 0.3252 28 16:30 0.466 0.484 0.000 0.000 60168.79 38.356 72.402 66.769 0.3247 28 16:45 0.468 0.485 0.000 0.000 60164.54 38.354 72.393 66.914 0.3264 28 17: 0 0.464 0.481 0.000 0.000 60166.82 38.353 72.389 66.754 0.3246 28 17: 15 0.461 0.476 0.000 0.000 60164.20 38.351 72.391 66.803 0.3251 28 17:30 0.459 0.474 0.000 0.000 60160.20 38.349 72.387 66.948 0.3267 28 17:45 0.453 0.468 0.000 0.000 60161.50 38.347 72.388 66.767 0.3247 28 18: 0 0.444 0.460 0.000 0.000 60164.18 38.345 72.388 66.483 0.3215 28 18:15 0.439 0.456 0.000 0.000 60157.52 38.343 72.384 66.735 0.3243 28 18:30 0.436 0.452 0.000 0.000 60153.84 38.342 72.385 66.794 0.3250 28 18:45 0.437 0.451 0.000 0.000 60147.02 38.341 72.386 66.954 0.3268 28 19: 0 0.434 0.448 0.000 0.000 60148.89 38.339 72.396 66.626 0.3231 28 19:15 0.430 0.444 0.000 0.000 60148.79 38.339 72.401 66.657 0.3235 28 19:30 0.428 0.442 0.000 0.000 60142.63 38.337 72.411 66.854 0.3257 28 19:45 0.427 0.439 0.000 0.000 60140.85 38.336 72.404 66.861 0.3258 28 20: O 0.422 0.435 0.000 0.000 60143.93 38.334 72.411 66.488 0.3216 28 20:15 0.418 0.431 0.000 0.000 60140.05 38.332 72.399 66.620 0.3231 28 20:30 0.419 0.431 0.000 0.000 60131.29 38.329 72.398 66.898 0.3262 28 20:45 0.417 0.428 0.000 0.000 60132.88 38.327 72.388 66.694 0.3239 28 21: 0 0.415 0.427 0.000 0.000 60129.33 38.325 72.386 66.695 0.3239 28 21:15 0.415 0.426 0.000 0.000 60125.58 38.323 72.381 66.714 0.3241 28 21:30 0.413 0.424 0.000 0.000 60125.17 38.320 72.366 66.561 0.3224 28 21:45 0.412 0.422 0.000 0.000 60123.41 38.319 72.372 66.531 0.3221 28 22: 0 0.410 0.420 0.000 0.000 60122.72 38.320 72.397 66.545 0.3222 28 22:15 0.408 0.418 0.000 0.000 60119.80 38.320 72.422 66.549 0.3223 28 22:30 0.408 0.417 0.000 0.000 60112.19 38.320 72.422 66.934 0.3266 28 22:45 0.407 0.416 0.000 0.000 60114.35 38.318 72.414 66.731 0.3243 28 23: 0 0.406 0.415 0.000 0.000 60110.73 38.319 72.431 66.873 0.3259 28 23:15 0.406 0.414 0.000 0.000 60105.92 38.319 72.447 67.087 0.3283 28 23:30 0.406 0.414 0.000 0.000 60104.15 38.317 72.436 67.026 0.3276
~
TABLE 1
?
MODE: TYPE A TEST (FINAL)
TIME: 028 1015 - 019 1015 PAGE 2/2 TREND OF ILRT CALCULATED VALUES 1993 MEAS UCL95 WINDO WINDO AIR WGHTED WGHTED WGHTED VAPOR JDA HR MN LR LR LR UCL MASS PRESSR RTTEMP DCTEMP PRESSR 28 23:45 0.404 0.412 0.000 0.000 60105.24 38.312 72.401 66.786 0.3249 29 0 0 0.403 0.410 0.000 0.000 60103.48 38.309 72.381 66.692 0.3239 29 0:15 0.402 0.410 0.000 0.000 60098.34 38.307 72.372 66.861 0.3258 29 0:30 0.401 0.409 0.000 0.000 60096.34 38.304 '72.365 66.791 0.3250 29 0:45 0.401 0.408 0.000 0.000 60091.89 38.302 72.370 66.830 0.3254 29 1: 0 0.400 0.407 0.000 0.000 60093.83 38.301 72.361 66.690 0.3238 29 1:15 0.399 0.406 0.000 0.000 60090.21 38.299 72.358 66.729 0.3243 29 1:30 0.398 0.405 0.000 0.000 60088.24 38.298 72.360 66.739 0.3244 29 1:45 0.398 0.405 0.000 0.000 60082.77 38.296 72.363 66.843 0.3256 29 2: 0 0.397 0.403 0.000 0.000 60086.73 38.295 72.363 66.534 0.3221 29 2:15 0.396 0.402 0.000 0.000 60082.93 38.293 72.363 66.633 0.3232 29 2:30 0.395 0.401 0.000 0.000 60079.62 38.292 72.368 66.699 0.3239 29 2:45 0.393 0.399 0.000 0.000 60080.02 38.291 72.368 66.609 0.3229 29 3: 0 0.392 0.398 0.000 0.000 60076.34 38.290 72.358 66.797 0.3250 29 3:15 0.390 0.396 0.178 0.394 60079.00 38.289 72.352 66.569 0.3225 29 3:30 0.390 0.396 0.300 0.498 60070.88 38.288 72.367 66.788 0.3249 29 3:45 0.339 0.395 0.343 0.484 60069.05 38.287 72.375 66.698 0.3239 29 4: 0 0.387 0.393 0.285 0.406 60072.62 38.286 72.365 66.470 0.3214 29 4:15 0.386 0.392 0.307 0.401 60066.22 38.285 72.373 66.740 0.3244 29 4:30 0.385 0.391 0.321 0.396 60063.95 38.284 72.377 66.776 0.3248 29 4:45 0.384 0.390 0.308 0.370 60064.80 38.283 72.384 66.621 0.3231 29 5: 0 0.384 0.389 0.348 0.414 60055.20 38.282 72.385 66.991 0.3272 29 5:15 0.384 0.389 0.367 0.425 60053.95 38.281 72.392 66.878 0.3260 29 5:30 0.383 0.389 0.377 0.428 60052.03 38.280 72.392 66.923 0.3265 29 5:45 0.382 0.387 0.366 0.411 60054.05 38.279 72.397 66.686 0.3238 i
29 6: 0 0.382 0.387 0.366 0.405 60049.72 38.278 72.405 66.813. O.3252 29 6:15 0.381 0.386 0.363 0.398 60048.37 38.276 72.395 66.769 0.3247 29 6:30 0.380 0.385 0.357 0.388 60047.54 38.275 72.395 66.680 0.3237 29 6:45 0.379 0.384 0.350 0.379 60046.35 38.273 72.396 66.680 0.3237 29 7: 0 0.379 0.383 0.352 0.378 60041.10 38.272 72.400 66.789 0.3250 29 7:15 0.378 0.383 0.353 0.376 60039.20 38.270 72.407 66.670 0.3236 29 7:30 0.377 0.382 0.348 0.370 60039.52 38.269 72.397 66.602 0.3229 L
29 7:45 0.377 0.381 0.349 0.369 60034.99 38.267 72.398 66.643 0.3233 29 8: 0 0.376 0.381 0.352 0.370 60031.74 38.265 72.395 66.709 0.3241 i
29 8:15 0.376 0.380 0.352 0.369 60030.30 38.264 72.373 66.718 0.3242 29 8:30 0.376 0.380 0.360 0.378 60022.57 38.262 72.379 66.887 0.3261 29 8:45 0.375 0.380 0.361 0.377 60024.92 38.261 72.367 66.788 0.3249 29 9: 0 0.375 0.379 0.359 0.374 60024.50 38.259 72.3631 66.754 0.3246 l
29 9:15 0.374 0.378 0.355 0.369 60025.33 38.258 72.367 66.598 0.3228 29 9:30 0.373 0.377 0.350 0.365 60023.48 38.256 72.365 66.627 0.3231 29 9:45 0.373 0.377 0.348 0.362 60019.80 38.255 72.370 66.639 0.3233 29 10: 0 0.372 0.376 0.348 0.360 60016.60 38.252 72.360 66.554 0.3223 29 10:15 0.372 0.376 0.350 0.362 60011.39 38.249 72.346 66.518 0.3219 i
t l
=.
~.. -
~
TABLE 1 i
MODE: VERIFICATION TIME: 029 1130 - 029 1530 PAGE 1/1 TREND OF ILRT CALCULATED VALUES 1993 MEAS UCL95 AIR WGHTED WGHTED WGHTED VAPOR.
JDA HR MN LR LR MASS PRESSR RTTEMP DCTEMP PRESSR 29 11:30 0.000 0.000 59983.16 38.231 72.362 66.533 0.3221 29 11:45 0.000 0.000 59972.66 38.226 72.366-66.667 0.3236 29 12: 0 0.000 0.000 59958.02 38.222 72.383 66.952 0.3268 29 12:15'O.000 0.000 59949.23 38.212 72.366 66.694 0.3239-29 12:30 1.697 1.976 59941.85 38.210 72.379 66.849 0.3256 f
29 12:45 1.576 1.799 59934.48 38.202 72.350 66.726 0.3242 l
29 13: 0 1.543 1.697 59924.01 38.199 72.368 66.904 0.3262 29 13:13 1.513 1.628 59915.63 38.194 72.381 66.843 0.3256 29 13:30 1.475 1.571 59908.43 38.190 72.380 66.893 0.3751 29 13:45 1.484 1.561 59895.87 38.177 72.346 66.761 0.3246 29 14: 0 1.488 1.549 59886.84 38.168 72~.288 66.775 0.3248 29 14:15 1.471 1.525 59880.60 38.160 72.266 66.587 0.3227 29 14:30 1.448 1.499 59873.86 38.155 72.262 66.495 0.3217 29 14:45 1.428 1.476 59866.05 38.149 72.252 66.500 0.3217 29 15: 0 1.423 1.465 59855.09 38.141 72.239 66.525 0.3220 29 15:15 1.424 1.460 59845.09 38.136 72.241 66.579 0.3226 29 15:30 1.412 1.446 59840.09 38.129 72.221 66.425 0.3209 i
s I
l 1
1 i
4 I
~
TABLE 2 - 13R LLRTRESULTS TYPE AS-FOUND AS-LEFT AS-FOUND AS-LEFT TEST A OR B MAX., PATH. MAX. PATH MIN. PATH M:N. PATH SCFH SCFH ACFH SCFH BIO. SHIELD STAB. MANWAYS (8)
B 1.1569 1.1569 1.1569 1.1569 DEMINERALIZED WATER SYST.
B 0.0147 0.0147 -
0.0147 0.0147 DRYWELL AIRLOCK B
1.91 10.53 1.91 10.53 DW AIRLOCK ELECTRICAL PENET.
B O.0088 0.0096 0.0088 0.0096 DRYWELL AIRLOCK SEAL B
0013 0.0088 0.013 0.0088 DRYWELL HEAD MANHOLE COVER B
0.012 0.0117 0.012.
0.0117 DRYWELL HEAD SEAL B
0.0857 0.0274 0.0857 0.0274 ELECTRICAL PENETRATIONS (40)
B 2.3034 2.3034 2.3034 -
2.3034 MSIV DRAIN LINE FLANGE B
0.0095 0,0095 0.0095 0.0095 Y 15 B
0.018 0.0129 0.018 0.0129 Y-26-15 WELD D
0.011 0.011 RWCU PENETRATION X-9 B
0.038 0.038 RWCU PENETRATION X-10 B
0.008 0.008 ISO CONDENSER PENETRATION X-3A B
0.0297 0.0297 0.0191 0.0191 ISO CONDENSER PENETRATION X-3E B
0.051 0.051 ISO CONDENSER PENETRATION X-SA B
ISO CONDENSER PENETRATION X-5E B
0.021-0.021-STEAM DRYER PENETRATION B
0.0219 0.0219 0.0219 0.0219 STEAM DRYER TAPS (16)
B 1.66 1.66 1.66 1.66 TIP PENETRATIONS (4)
B 0.1169 0.1169 0.1169 0.1169 TORUS MANHOLE COVER - NORTH B
0.011 0.0114 0.011 0.0114 TORUS MANHOLE COVER - SOUTH B
0.000 0.0107 0.009 0.0107 RB TO TORUS VAC BRKRS,GASK&ORif B
0.1737 0.1823
.0.1737 0.1823 1ORUS TO CW VAC. BRKRS. (14)
B 4.9495 2.9917 4.9495 2.9917 V 1.2,&14 C
91.8 5.1913 5.43 1.621 V 30 C
0.0791 0.0791 0.0791 0.0791 V 61 & G2 C
41.15 13.91 13.91 0.0175 V 27 & 28 C
0.356 0.356 0.0362 0.0362 V 1 & 2 C
1.043 0.0158 0.5215 0.0079 i
V 17 & 18 C
1.025 0.7931 0.5125 0.3966 V 13 & 14 C
0.0287 0.0287 0.0144 0.0144 V 9 & t o C
0.116 0.116 0.1133 0.1133 V 3 & 4 C
9.399 0.5916 4.7 0.2958 V 28 & 29 C
2.8526 0.554 1.4263 0.277 V 1 & 2 C
0.02 0.0727 0.01 0.0364 V 21 & 22 C
0,014 0.0355 0.007 0.0178 V 71 & 73 C
1.557 1.557 0.0826 0.0826 V 72 & 74 C
26.4 26.66 5.93 5.93 1.388 0.421 0.421 V 37 & 38 C
V 39 & 40 C
0.526 0.526 0.048 0.048 V 41 & 43 C
0.1002 0.1002 0.0901 0.0901 i
V 44 & 46 C
0.6 0.6 0.066 0.066 V 93 & 94 C
0.0162 0.0162 0.012 0.012 V 393 & 395 C
11.19 11.19 0.1653 0.1653 V 1 & 19 C
1.61 0.0432 0.6 0.0322 V 5 & 20 C
3.13 0.0565 0.6 0.0561 i
V 16 & 20 C
19.3679 4.5133 1.8798 1.7308 V-40-6 & V-24-30 C
1.01 1.01 0.0212 0.0212 MSIV's NSO3A & 4A C
6.251 1.1781 3.126 MSIV $ NSO3B & 4D C
3.07 14.726 -
. 1.46 2.14' V 12 C
3.155 1.293 3.155 1.293 V 24 C
0.1886 0.1886 0.1886 0.1686 V 166 & 167 C
9.641 9.641 0.0267 0.0267 1
V 147 & 165 C
3.189 0.1528 0.1528 V 15 & 16 C
38.23 16.78 19.115 3.484 -
V 17 & 18 C
7.011 3 484 l
V 2 & 5 C
44.08 1.788 0.0142 0.0142 V 29 & 30 C
0.1644 0.1644 0.0212 0.0212 V 8 C
0.9991 0.9991 0.9991 0.9991 TIP BALL VALVES (4)
C 2.0353 2.0353 2.0353 2.0353 V 70 C
0.0114 0.0129 -
0.0114 0.0129 V 19 & 20 C
0.0489 3.484 0.0245
'O.2888 V 15 & 16 C
6.0689 6.0689 3.0345 3.484 V 22 & 23 C
0.0096 0.0096 0.0096 0.009 V 16 & 17 C
0.0911 0.0911 0.0872 0.0872 l
V 17,18, & 47 C
3.2032 0.7204 1.6016 V 92 C
0.0138 0.0138 0,0138 0.0138 TOTAL B & C TESTS
>426 165.6117
> 322 53.2881
- - 13R MODIFICATION
- - EXCEEDED LIMITS 9
P I
TABLE 3 - 14R LLRTRESULTS TYPE AS-FOUND AS-LEFT AS-FOUND AS-LEFT i
TEST A OR B MAX. PATH MAX. PATH MIN. PATH MIN. PATH SCFH SCFH SCFH SCFH BIO. SHIELD STAB. MANWAYS (8)
B 1.024 1.024 1.024 1.024 DEMINERAUZED WATER SYST.
B 0.054 0.054 0.054 0.054 r
DRYWELL AIRLOCK B
2.479 14.32 2.479 14.32 DW AIRLOCK ELECTRICAL PENET.
B 0.009 0.009 0.009 0.009 DRYWELL A!RLOCK SEAL B
0.036 0.016 0.036 0.016 DRYWELL HEAD MANHOLE COVER B
0.009 0.0103 0.009 0.0103 DRYWELL HEAD SEAL B
O.096 0.0313 0.096 0.0313 ELECTRICAL PENETRATIONS (40)
B 2.775
' 2.775 2.775 2.775
0.03 0.03 0.03 0.03 Y 15 B
0.018 0 015 0.018 0.015 Y 1 B
0.427 0.427 Y-27 -2 B
0.014 0.014 Y-28-26 B
0.03 0.03 Y-27-1 WELD B
0.009 0.009 t
Y-27-2 WELD B
0.012 0.012 Y-28-26 WELD B
0.014 0.014 STEAM DRYER PENETRATION B
0.016 0.016 0.016 0.016 STEAM DRYER TAPS (16)
B 0.158 0.158 0.158 0.158 TIP PENETRATIONS (4)
B 0.197 0.197 0.197 0.197 TCRUS MANHOLE COVER - NORTH B
0.0103 0.011 0.0103 0.011 TORUS MANHOLE COVER - SOUTH B
0.0105 0.013 0.0105 0.013 TORUS TO DW VAC. BRKRS. (14)
B 4.107 1.639 4.107 1.639 -
V 1.2 &14 C
10.98 2.2 0.269 0.114 V 30 C
0.041 0.012 0.041 0.012 V 61 & 62 C
24.092 0.734 0.035 0.075 V 27 & 28 C
0.614 0.614 0.036 0.036 V 1 & 2 C
4.283 3.63 2.02 0224 i
V 17 & 18 C
0.559 0.559 0.28 0.269 V 13 & 14 C
0.018 0269' O.009 0.018 V 9 & 10 C
0.348 0.348 0.345 0.345 V 3 & 4 C
36.46 1,4 0.41 0.269 V 28 & 29 C
18.47 0.428 0.997 0.046 V 1 & 2 C
0.635 1.51 0.318 0.635 V 21 & 22 C
0.038 1.51 0.019 0.038 V 71 & 73 C
0031 0.854 0.03 0.031 V 72 & 74 C
4.25 4.25 0.617 0.617 V 37 & 38 C
1.33 0.074 0.848 0.056 V 39 & 40 C
0.763 0.044 0.034 0.022 V 41 & 43 C
0.259 0.896 0205 0.883 V 44 & 46 C
0,574 0.701 0.059 0.029 V 393 & 395 C
2.65 2.65 1.46 1,46 V 1 & 19 C
1.5616 1.5616 1.5489 1.5489 V 5 & 20 C
0.469 0.469 0.196 0.196 V 16 & 20 C
5.763 5.763 1.122 1.122 V 6&V 30 C
0.354 0.354 0.074 0.074 MSfV's NSO3A & 4 A C
7.66 3.934 5.66 3.623.
MSfV's NSO3B & 4B C
11.61 22.78 4.882 V 12 C
0.012 0.012 0.012 0.012 V 24 C
0.617 0.617 0.617 0.617 V 166 & 167 C
3.79 7.86 0.848
. 0.848 V 147 & 165 C
47.37 1.53 9.87 1.52 V 15 & 16 C
15 534 15.534 4.22 8 84 V 17 & 18 C
6.923 8 84 422 6.923 V 2 & 5 C
1.68 1.68 0.408 0.408 V 29 & 30 C
2.644 0.074 0.074 0.016 V 8 C
0.033 0.033 0.033 0.033 TIP BALL VALVES (4)
C 2.001 2.001 2.001 2.001 V 70 C
0.011 0.011 0.011 0.011 V 19 & 20 C
4 22 8.84
. 0.133 0.133 V 15 & 16 C
5.434 8.84 422 3.59 V 22 & 23 C
0.008 0.008 0.008 0.008
[
V 16 & 17 C
0.302 0.302 0.302 0 302 V 17,18. & 47 C
5.236 4.16 0.203 0203 V 92 C
0.042 0 013 0.042 0.013 V 93 & 94 C
0.022 0.009 l
a TO7AL B & C TESTS
>426 127.5542 77.6727 62.9275
- - 14R MODIFICATIONS
- - EXCEEDED UMITS i
1
TABLE 4 '
TYPE B AND C TESTS CYCLES 12 AND 13 COMPONENT DATE OUTAGE LEAKRAT_E COMMENTS DW Airlock 4-19-89 12R-1 DW Airlock seal 4-16-89 12R-1 DW Airlock 5-08-89 12R-2 11.25 DW Airlock 6-30-89 12U-2 1.49 V-38-37 6-29-89 12U-2 13.03 V-38-38 6-29-89 12U-2 12.61 V-38-39 6-29-89 12U-2 2.43-V-38-40 6-29-89 12U-2 2.4 DW Airlock 7-01-89 12U-2 8.01 DW Airlock 9-15-89 12U-5 1.47 V-2-72 9-14-89 12U-5
.0119 DW Airlock 9-18-89 12U-5
.964 V-38-93 11-14-89
.0116 Added Valve V-38-94 11-14-89
.0096 Added Valve DW Airlock 2-14-90 12U-8 1.333 Torus MW-S 2-10-90 12U-8
.045 T-DW Vac Brkr.
2-09-90 12U-8 5.993 DW Airlock 2-16-90 12U-8 1.570 DW Airlock 4-03-90 12UJ 16.30 V-14-5 4-02-90 12UJ
.321 V-24-29 3-28-90 12UJ
.126 DW Airlock 4-04-90 12UJ 7.29 V-14-1 5-02-90 12UK 2.101 V-14-15 9-02-90 12UK 2.158 DW Airlock 5-02-90 12UK 12.58 DW Airlock 5-12-90 12UK 1.602 DW Airlock 6-27-91 13R 11.17 DW Airlock 11-04-91 13U4 18.94 V-26-18 11-04-91 13U4 5.67 Rebuilt Valve Y-26-15 11-04-91 13U4
.0196 DW Airlock 5-02-92 6Mo 2.246 DW Airlock 6-06-92 13U6 16.93 V-26-18 5-30-92 1306 7.10
_ Replaced Actuator T-DW Vac Brkr 6-06-92 13U6 2.9942 Indication Problem.
DW Airlock 6-08-92 13U6 10.11
a REPORT 1 SECONDARY CONTAINMENT LEAK RATE TEST RESULTS Secondary Containment Leak Rate Tests were performed in accordance with 10CFR50 and Oyster Creek Technical Specifications prior to the start of refueling outages 13R and 14R. The acceptance criteria of the test is satisfied if the Reactor Building is capable of maintaining a vacuum equal to or greater than.25" H O with a Standby 2
Gas Treatment System flowrate of 2600 CFM i 260 CFM.
The results of the initial test prior to 14R did not meet the acceptance criteria for the Reactor Building vacuum. Minor repairs were made to door seals on the Reactor Building and the test was reperformed. The results met the acceptance criteria for both flow and vacuum.
l The results of the tests are summarized below:
l TEMPERATURE (70 F)
VACUUM j
DATE CORRECTED FLOW (INCHES H O) 2 12/21/90 2733 CFM
.320 11/14/92 2544 CFM
.211*
11/15/92 2421 CFM
.274
- Initial value found out of specification.
. - _ _ _ _ _ - _ - - - _ - - _ _ _ _ _ _ - - _ _ _ _ - _ _ - _ _ _ _ _ _ - - _ _ - -