UNITED STATES f
NUCLEAR REGULATORY COMMISSION 2
s, o
{
" ).:,E WASHINGTON, D. C. 20555 s'6.../
SAFETY EVALUATION BY THE OFFICE OF NUCLEAR REACTOR REGULATION SUPPORTING AMENDftENT NO. 51 TO FACILITY OPERATING LICENSE NO. DPR FLORIDA POWER CORPORATION, ET AL CRYSTAL RIVER UNIT NO. 3 NUCLEAR GENERATING PLANT DOCKET NO. 50-302 Introduction
'By application dated February 8,1982, Florida Power Corporation (FPC or the licensee) requested changes to the Technical Specifications (TSs) of Facility Operating License No. DPR-72 for operation of the Crystal River Unit No. 3 Nuclear Generating Plant (CR-3). These changes would allow a one time only operation at less than 40% power with the reactor coolant pump powe-monitor trip bypassed while conducting tests. The tests invol 1 the switchover between the startup and the unit auxiliary transformers while monitoring the reactor coolant flow and the 6900 volt bus current and voltage.
Discussion and Evaluation The pump power monitors are devices that monitor the electrical power to each of the four reactor coolant pumps at CR-3.
These monitors trip the reactor on a loss of power or a draw of too much power from two or more reactor coolant pumps. Therefore, the system detemines a loss or a reduction of the reactor coolant flow by monitoring the reactor coolant pump power and detecting an inoperable pump by abnormal power conditions.
The pump power monitors were installed to allow 3-3 reactor power to be increased from 2452 Mwt to 2544. The NRC authorized this power increase on July 21, 1981 The pump power monitors had not been required for the lower, 2452 Mwt, reactor power level because the response of other reactor protection systems was fast enough to detect pump failure at that power level.
FPC has recently experienced reactor trips from the pump power monitor system when starting reactor coolant pumps and when switching electrical power from the CR-3 auxiliary transformers to the startup transformer.
On three occasions (twice in Mode 3 during startup and once in Mode 1 during controlled shutdown), the pump power monitor trip has caused a reactor trip. Testing in Mode 3 indicated that the monitored parameter (bus powe;r in watts) did in fact go through a very short-lived (< 1 sec.)
transient when energizing an idle reactor coolant pump. It is thought that a similar transient occurred during the switchever from the unit auxiliary to the startup transformer and that it couW occur when deenergizing an active reactor coolant pump.
8203040590 B20212 PDR ADOCK 05000302 PDR lP -.
. The proposed tests will measure trip function parameters during unit operation and transfomer switchover. The results of these tests
)
will be used to detemine trip setpoints which will avoid spurious trips while maintaining the reactor coolant pump power monitor safety function. This TS change will allow the testing to be performed.
We have determined that operation at 40% or less reactor power with the pump power trip bypassed during the proposed testing is acceptable because: 1) the pump power trip is primarily needed at or near full power operations to compensate for slower reactor times of other reactor protection systems, and 2) the pump power monitor trip is backed up by the flux-flow trip and a high pressure trip for a loss of two or more reactor coolant pumps.
Environmental Consideration We have detemined that the amendment does not authorize a change in effluent types *or total amounts nor an increase in power level and will not result in any significant environmental impac Having made this determination, we have further concluded that th;t.
e amendment involves an action which is insignificant from the standpoint of environmental impact and, pursuant to 10 CFR 551.5(d)(4), that an environmental impact statement, or negative det'ipration and environ-mental impact appraisal need not be prepared in connection with the issuance of this amendment.
Conclusion We have concluded, based on the considerations discussed above, that:
(1) because the amendment does not involve a significant increase in the probability or consequences of accidents previously considered and does not involve a significant decrease in a safety margin, the amencment does not involve a significant hazards consideration, (2) there is reascnable assurance that the health and safety of the public will not be endangered by operation in the proposed manner, and (3) such activities will be conducted in compliance with the Commission's regulations and the issuance of this amendment will not be inimical to the common defense and security or to the health and safety of the public.
Dated: February 12, 1982 The following NRC personnel have contributed to +.his Safety Evalution:
Sydney Miner.