ML20030B167

From kanterella
Jump to navigation Jump to search
Application for Amend to Source Matl Licenses SNM-1879 & SNM-1852 Clarifying That Fire Detection Devices Are Not Provided Inside Fuel Handling Bldg
ML20030B167
Person / Time
Site: San Onofre, 07002901, 07002882  
Issue date: 07/17/1981
From: Cotton G, Dietch R
SAN DIEGO GAS & ELECTRIC CO., SOUTHERN CALIFORNIA EDISON CO.
To:
Shared Package
ML20030B164 List:
References
19401, NUDOCS 8108060178
Download: ML20030B167 (4)


Text

-

BEFORE THE UNITED STATES NUCLEAR REGULATORY COMMISSION In the matter of SOUTHERN CALIFORNIA

)

DOCKET NO. 50-361 UNIT 2 EDIS0N COMPANY and SAN DIEGO GAS &

)

ELECTRIC COMPANY San Onofre Nuclear DOCKET NO. 50-362 UNIT 2 Generating Station, Units 2 and 3 Application for Amendment No.1 to NRC Materials License Nos. SNM-1879 and SNM-1852 SOUTHERN CALIFORNIA EDISON COMPANY and SAN DIEGO GAS &

ELECTRIC COMPANY hereby apply for amendment to the special nuclear materials license by submitting herewith Application for Amendment No.1 to NRC Materials License Nos. SNM-1879 and SNM-1852 issued on May 21, 1981.

This application for amendment consists of information to clarify that fire detection devices are not provided inside the fuel handling building.

l In the event of a conflict, the information in this i

application for Amendment No. I to the NRC Materials License Nos. SNM-1879 and SNM-1852 supersedes the information previously l

submitted.

8108060178 810717 PDR ADOCK 05000361 PDR

.A

. Subscribed on this /7d day of

/P//

pr Respectfully submitted, SOUTHERN CALIFORNIA EDISON COMPANY By Charles R. Kocher James A. Beoletto Attorneys for Southern California Edison Company By W

xi. 4%

q

\\

Subscribg and swor to before me this /7 day of _ //, /9//.

d,

@;;;AGNESCRABTREE 1I

enkkistac

\\

//

v v

Noraavrueue.caumma i i

PR1NDPAL OmM IN g l LOS ANGELES COUNTY My Commisson Em Aug.27.1982

[

l OccceAr-:-r-r-x ::: ;; 6l r l

Not9p} Public in and for the Couh'ty of Los Angeles, State of California

. SAN DIEGO GAS & ELECTRIC COMPANY By gm b

s 9 --

v David R. Pigott Frank S. Bayley, III Samuel B. Casey Orrick, Herrington & Sutcliffe Attorneys for San Diego Gas & Electric Company By 4F

(/

l Subscribed jnd sworn to7 efpre me b

this / M 4 day of (f(( & A f

/

i l

$$db lbJMbh i

Notary Public in 'and for the City' and County of San'Diego, California 9 Pr!ncipsloffice in San Die orric1AL stAL CAROL L. MOODY NOTARY PUBUC CAUTORNIA l

My Commission Exp. Jan. 24.1984 i

l l.

l'

APPLICATION FOR AMENDMENT NO. 1 TO NRC MATERIALS LICENSE NOS. SNM-1879 AND SNM 1852 ISSUED MAY 21, 1981 SAN ON0FRE NUCLEAR GENERATING STATION UNITS 2 AND 3 PROPOSED AMENDMENT Delete references to fire detection equipment in the fuel handling building (FHB) by revising the October 27, 1980 Amendment No. 2 to the License Application, Subsection 1.2 Storage Conditions, first complete paragraph on page 5 as follows:

1.

delete:

" detection devices, alarms, and" 2.

delete:

"The detection devices, smoke, and fire-temperature-rate-of-rise heat detectors will activate alarms locally and in the control room in case of fire."

Basis for not providing fire detection in the FHB Fire detection devices are not needed in the FHB because 1.

The FHB is a controlled access area - the access door is locked and alarmed.

2.

Once/nour security patrols outside the entry door.

3.

There is a very low fire loading with essentially no combustibles in FHB. The only combustibles that have been identified in the F'iB are the following:

a.

Approximately 60 wood blocks (12" x 12" x 2") to support tubing which prevent use of spent fuel storage locations to assure quarter loading of new fuel in the dry spent fuel pool.

b.

Approximately 2 quarts of lube oil in the spent fuel cask crane gear box.

c.

Excore detector wooden crates.

4.

Fire suppression systems are CO2 extinguishers, standpipes with hose cabinets, and a fire truck.

LE)(1(12.

__-____