zi ,

Docket No. 50-336 813645

.a I

i Attachment 1 Millstone Nuclear Power _ Station, Unit No. 2 Proposed Revision to Technical Specifications 1

March 1991

),[g32gggg[((8$gg6 P

I '

INDEX m

~

y LLIMITING CONDITIONS FOR OPERATION AND SURVEILLANCE RE0VIREMENTS  ;

i

~SECTION- MQE l 3/4;7 -PLANT SYSTEMS ,

1 3/4.7.1; TURBINE: CYCLE .......................................... 3/4 7-1 1 S a fe ty V al ve s : . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3/4.7-l' l Auxiliary Feedwater Pumps ..................... ........ 3/4 7-4  !

Condensate Storage Tank ................................ 3/4 7-6 A ctivity................................................ - 3/4.7-7 Main Steam Line Isolation Valves ....................... 3/4 7-9 J3/4.7.2 STEAM GENERATOR PRESSURE / TEMPERATURE LIMITATION ......... 3/47.10 3/4.7=.3 _ REACTOR BUILDING CLOSED COOLING WATER SYSTEM ..,........ 3/4 7 11

- 3/4._7 ; 4^ SERVICE WATER SYSTEM ................................... 3/4 7-12

?3/4.7.5 FLOOD LEVEL ............................................ . 3/4 7-13 <

3/4.7.6- CONTROL ROOM EMERGENCY VENTILATION SYSTEM ............... 3/4 7-16 3/4.7.7- ' SEALED' SOURCE CONTAMINATION ............................ 3/4 7-19

' 3/4.7.8 SNUBBERS ........ .......................................- 3/4 7-21 3/4.7 9: FIRE-SUPPRESSION SYSTEMS ............................... 3/4 7-33

, Fire Suppression = Water System .......................... 3/4 7-33 Spray and/or Sprinkler Systems . . . . . . . . . . . . . . . . . . . . . . . . . 3/4-7-37 6

Fire Hose Stations ..................................... 3/47 -

1 Hal on Fi re Suppression Systems . . . . . . . . . . . . . . . . . . . . . 4 . . 3/4L7-41 l, ;3/4.7.10 PENETRATION FIRE-BARRIERS .............................. 3/4 7-42 L 3/4.7.11.' ULTIMATE HEAT SINK ..................................... 3/4 7-44

- -3/4.8 ELECTRICAL-POWER SYSTEMS 3/4.8.1- A,C. S00.RCES ........................................... 3/4 8-l' L _0perating ..........._................................... 3/48-1
'Shutdow. ...............................................- 3/4 8-5 i i 3/4.8.2 ONSITE. POWER DISTRIBUTION SYSTEMS ........;............. 3/4'8-6

).

!~ -A.C. Distribution - Operating ..........................e 3/48-6 p

i A.C.: Distribution - Shutdown .........................-.. 3/4 8-7 L

E

D.C.-Distribution _- Operating ................... ...... 3/4 8-8 D.C. Distribution - Shutdown ............................ - 3/4 8-10.

E MILLSTONE.- UNIT 2 VIII Amendment No. 77, JE, # , Jpf,

"" 1H g -- - - y T

^ ;b -l: -

TABLE 3'.3-10 ,

FIRE DETECTI0li INSTRUMENTS  :

^

kh! Heat Smoke

~ EE

-j Minimum Minimum

?R- Total No. Channels- -Total No. Channels

, Instrument Location (Zone) of Channels Operable of Channels Operable C

5 1. Containment' a

^'

. East' Penetration (37)--FLP 3-3 -- --

7 5 West Penetration (31)--FLP 3-7; -- --

7 5

2. . Control' Room Vent. Duct (42) Z -- --

1 1 Control 1 Room Vent Duct (2):Z-1 -- --

1 1

3. Cable" Vaults & Areas

- Aux. - Bldg Cable Vault (25') (10) 5 4 16 12 4" -Turbine Bldg. Cable Vault (25') (22) -- --

34 34 l Turbine Bldg Cable Vault Area (45') (21) -- --

8 6 t' Lunch Room Cable Chase Area (36'6") (24) -- --

4 3 l 2

4. 4.16 & 6.9 kV Switchgear Room (54'6") (40) -- --

4 3 4.16 kV Switchgear Room'(31'6") (18) -- --

4 3 480 V West Switchgear Room (36'6") (18) -- --

2 1 2, 480 V East Switchgear Room (36'6") (28) -- --

2 1 g East DC Equipment Room (43 Alarm) (FLP-5) -- --

6 6 ZL West DC Equipment' Room (45 Alarm) (FLP-6) -- --

6 6 2 East Cable Vault Ventilation Opening -- --

1 1 E' (44) (FLP 7)

West Cable Vault Ventilation Opening -- --

1 1

. (44).-(FLP 7) m

? 5. Battery Rooms un 2" West Battery Room (14'6") (39) -- --

1. I s, East Battery Room (14'6") (39) -- --

2 1 D

6. Electrical Penetration Rooms East.(14'6") (20) -- --

3 2 ,

West (14'6") (17) -- --

2 1

TABLE 3.3-10 (Continued) ,

FIRE DETECTION INSTRUMENTS a1 Heat Smoke r- '

- r-

$ Minimum Minimum EE Channels Total No. Channels )

n' . Total No. Operable-of Channels Operable of Channels Instrument Location (Zone)

E I

1 7. Diesel Generators m 8 8 -- --

Diesel 1221 (12) 8 8 -- --

Diesel'1321 (13)

8. Main Exhaust Equipment Room and B52 Enclosure

-- -- 3 3 Room (El 38'6") (5)

9. Auxiliary Building - 45 (FLP-1) w -- -- 3 2 1: General Area (48)

-- -- 2 1

$[ A. Safe Guards Room (48) -- -- 2 1

'" 8. Safe Guards Room (48) -- -- 1 1 l C. Safe Guards Room (48)

10. Auxiliary Building - 25 (FLP-2)

E -- -- 9 7 g General Area - 25 (52) -- -- 5 3 Et Charging Pump Rooms - 25 (52)

%r* 11. Containment Building FLP-3 (37) 5 RCP "A" - (FLP 3-1) 5 3 -- --

5 3 --

}g RCP "B" - (FLP 3-2) 5 3 --- --

RCP "C" - (FLP 3-5) 5 3 -- --

, la RCP "D" - (FLP 3-6) k 12.- Auxiliary Building (-5'/14'6") (FLP-4) 9 7 Auxiliary Building General Area 14'6" (41) to Auxiliary Building West Piping Penetration (41) -- -- 2 1 Room -5' 10 Auxiliary. Building -5' (41)

-- -- 13 l

~

TABIE 3.3-10-(Continued) .

[JRE DETECTION INSTRUMENTS

" Heat Smoke o --

IE Minimum Minimum' il Total No. Channels Total No. Channels EE

of Channels Operable of Channels Ooerable.

Instrument Location (Zone) 8 E 6 6 -- --

4 13. Hydrogen Seal Oil (31) m -- --

10 10

14. Intake Structure (6) 2 2
15. Motor Driven Aux. Feed Pump Rm (22) -- --

R a

a siF 8

n i.

[ , .. . ..

L PLANT SYSTEMS

~

SPRAY AN0/0R SPRINKLER SYSTEMS LIMITING CONDITION FOR OPERATION 3.7.9.2 The following spray and/or sprinkler systems shall be OPERABLE:

a. Diesel Generator Rooms
b. Diesei Generator Day Tank Rooms
c. Cable Vault (Aux. Building)
1. Sprinkler (in tray)
2. Sprinkler (ceiling level)
d. Cable Vault (Turbine Building)
1. Automatic Wet Pipe Sprinkler System (45'0")
2. Automatic Delugo System (vertical cable shaft and elevation 25'0" cable vault)
e. Hydrogen Seal Oil Unit f .' Turbine Building Northeast Corner
g. Turbine Building 31'6"/14'6" - North
h. Turbine Building 31'6"/14'6" - South
1. Lube Oil Room
j. Aux. Building (-45'6") General Area
k. Aux. Building (14'6") Truck Access
1. Turbine Bearing
m. Steam Generator Feed Pumps
n. Aux. Bldg. (14'6") at MCC B-61 o; Aux. Bldg. (-25'6") at Charging Pump Cubicle
p. Aux. Bldg. (14'6") General Area APPLICABILITY: Whenever equipment in the spray / sprinkler protected areas is required to be OPEhABLE.

ACTION:

a. With one or more of the above required spray and/nr sprinkler systems inoperable, establish a continuous fire watch with backup fire suppression equipment for the unprotected area (s) within I hour; restore the system to OPERABLE status within 14 days or, in lieu of any other report required by Specification 6.6.1, prepare and submit a Special Report to the Commission pursuant to Specification 6.9.2 within the next 30 days outlining the action taken, the cause of the inoperability and the plans and schedule for restoring the system to OPERABLE status,
b. The provisions of Specification 3.0.3 are not applicable.

SVRVEILLANCE RE0VIREMENT 4.7.9.2 Each of the above required spray and/or sprinkler systems shall be demonstrated OPERABLE:

MILLSTONE - UNIT 2 3/4 7-37 Amendment No. JJi, f), JJE 0005

y _. . - _ - _ _ . _ . . .

e 4 ,

W 7

, 7 .. n, ,., , , .

iTABLE 3.7-2 -

4 g

g FIRE HOSE-STATIONS-

- Hose Station Number' Blda/ Elevation- Arg.g

}

201-207' LTurbine/14'6" Turbine Building 2_08 214 > Turbine /31'6" Turbine Building J

-1 215-221 Turbine /54'6" ~ Turbine Building ,

222L -Auxiliary /-45'6" - Center of Open Area-223 Auxiltary/-25'6" Near Elevator

, 224- . Auxiliary /-5'0" - Near Elevator-w

.225: _ Auxiliary /14'6"' Near Elevator 226' . Auxiliary /38'6" Spent Fuel PoolJ-LNorthwest j

-corner , j Wr '

~

I

227L Auxiliary /14'6": Boric? Acid-Batch Tank area-w e ?228' Auxiliary /14'6"- NearMCC;22-lE(B51) -

=t

, . !229: Auxiliary /14'0"- -Railway access l 9230 ' Auxiliary /38'6"- .< Spent Fuel _ Pool  ; South Wall;

}

f231 . Aux 111ary/14'6" -Outside Diesel Room'. 4 Auxil iary/38'6" -

1 J.234 - _ Southeast corner stairway I2'40 Auxiliary /5'0"-- _

Southeast' corner _ stairway-241! -Auxiliary /25'6"' ~

Cable Vault ESoutheast 1

['x Entrance g -

L242, Auxilfary/36'6"  : Control ' Room Ventilation

+-

.: Area. I

', 1243' :Turbiile/45'0" - - i North Entrance 1of Turbine - '

Bldg. Cable. Vaults p, 1250-251- Containment /38'6"- East- & West -Stairwells :

~-248-249' Containment /14'6" East &. West Stairwells ,

[ 244-245- Containment /-22'0" East & West Stai uells MILLSTONE - UNTI 2 3/4 7-40 Amendment No. AB, M , JJS

~

.- 0007..

l. ,

' - ,e .= r m-,. . , - + . -----%.--,-.,,e, , w 4< q m a s.--. > r. .r.,c.wa. . -- E, .c . ---- -..w.e,

PLANT SYSTF.MS

'HALON FIRE SUPPRESSION SYSTEM llMITING CONDITION FOR OPERATION 3.7.9.4 The following halon 1301 fire suppression systems shall be OPERABLE with: an intact gas boundary, an operable activation system, and a container having a net weight of not less than 95% of full charge weight at 325 psig minimum (corrected to 70*F).

a) West D.C. Switchgear Room b) East D.C. Switchgear Room APPLICABillTY: At all times.

ACTION:

a, With one or more of the above systems inoperable, establish a conttaucus fire watch with backup fire suppression equipment for the unprotected area (s) within I hour; restore the system to OPERABLE status within 14 days or, in lieu of any other report required by Specification 6.6.1, prepare and submit a Special Report to the Commission, pursuant to Specification 6.9.2, within the next 30 days cutlining the action taken, the cause of the inoperability and the plans and schedule for restoring the ystem to OPERABLE status,

b. The provisions of Specification 3.0.3 are not applicable.

SVRVEILLANCE RE0VIREMENTS 4.7.9.4 Each of the above halon fire suppression systems shall be demonstrated OPERABLE:

a. At least once per 6 months:
1. By performing a system functional test which includes simulated autcmatic operation of the system; and:
a. simulated manual actuation of the system.
b. verifying that the storage containers have a net weight of not less than 95% of full charge weight at 325 psig (corrected to 70*F).
c. verifying the associated room dampers close.
b. At least once per 18 months:
1. By performing a visual inspection of the discharge nozzles to assure no blockage.
2. By performing a visual inspection to assure the gas boundary is intact, l

MILLSTONE - UNIT 2 3/4 7-41 Amendment No.

0008

j

)

ELANT SYSTEMS

'3/4.7.10 PENETRATION FIRE BARRIERS LIMITING CONDITIONS FOR OPERATION 3.7.10 All fire rated assemblies (walls, floor / ceilings, cable tray enclosures, and other fire barriers) separating safety-related fire areas or separating portions of redundant systems important to safe shutdown within a fire area and all sealing devices in fire rated assembly penetrations (fire doors, fire windows, fire dampers, cable, piping, and ventilation duct penetration seals) shall be OPERABLE.

APPLICABILITY: At all times unless otherwise determined that the separation of safety-related fire areas or separating portions of redundant systems important to safe shutdown within a fire area is not required based on the MODE of operation.

ACTION:

a. With one or more of the above required fire rated assemblies and/or penetration sealing devices inoperable, within 1 hour:
1. Determine that the fire areas / zones on both sides of the affected fire rated assembly and/or penetration sealing device are monitored by either an OPERABLE fire detection or automatic suppression system at the fire barrier and establish a fire watch patrol that inspects both areas at least once per hour, 2I
2. Establish a continuous fire watch on at least one side of the affected fire rated assembly and/or penetration seal, er
3. Temporarily repair the inoperable fire rated assembly and/or sealing device and classify it as temporary.

All teinporary or inoperable fire rated assemblies and/or sealing devices shall be permanently repaired within 30 days, or implement ACTION 1 or 2 above,

b. The provisions of Specification 3.0.3 are not applicable.

SVRVEI1 LANCE RE0VIREMENTS l

4.7.10 The above required fire rated assemblies and penetration sealing devices shall be verified to be OPERABLE by a visual inspection:

a. At least once per 18 months for fire doors and fire dampers.

MILLSTONE - UNIT 2 3/4 7-42 Amendment No. JE, JJE 0010 l

l

Te ; 4; SURVElllANCE RE0VIREMENTS (Continued)'

, , s '.

b.- Atlleast onceiper-18 montiisL for fire barrier penetration seals, on--

.at. least 10% of the total' number of; penetration seals. If any of; .

m the penetration Lseals ' in the' inspection _ sample are found toibe - -

inoperable, then an additional -10% sample' of. the total' number of penetration .. seals shall. be visually inspected. Sampling and-inspection shallicontinue- until all' of the seals in a . sample are found OPERABLE or 100% of- the seals are inspected.=

s_ c.- .Pr.ior .to returning a-- fire rated assembly and/or- penetration sealing device to OPERABLE- status following repairs or

. maintenance, a

m s

d ,

-)

h.E s

' MILLSTONE - UNIT 2 3/4 7-43 Amendment No. # , JJE

-0010 l $

L. ,.a.- - - . .,_._._

s ,

q v.: ,  ; ,

PLANTISYSTEMS ".. j

( ,

P: M 3/4?7-11 ULTIMATE HEAT SINK

LIMITING CONDITION FOR OPERATION' L.

a 3.7.111 . The ultimate heatisink'shall be10PERABLE with an- average water l stemperature of less than:or equal to 75'F at the Unit 2 intake structure. ]

APPLICABILITY: :. MODES 1, 2, 3, AND.4 ACTION:..

With the : requirements- of .the above specificationi nots satisfied, be ' in at .

Lleast HOT STANDBY ~ within 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> -and<in COLD SHUTDOWN within the following l

.30 hours3.472222e-4 days <br />0.00833 hours <br />4.960317e-5 weeks <br />1.1415e-5 months <br />; '

. SURVEILLANCE RE0VIREMENTS-I

4.7.11' .The ultimate heat sin'k shall b'e determined OPERABLE:
1. .. At :least once per .24 ~ hours . by- verifying tha . average . water

, temperature at - the. Unit 2 intake struuure to :be' within  ;

" limits.

b. At least once per 6 ' hours by verifying . the average water-temperature rat the s Unit 2o intake' structure to be ~.within limits when the average water temperature exceeds-70*F.

4

(

+

i
'

i 7

L 1.

h;. 4 t

l

MILLSTONE - UNIT 2 3/4 7-44 Amendment No. J #

0011-l

?4

g. .

m .

p h:l ,

i

' 'i

. n ,

ms .

~~

. m FADMINISTRATIVE CONTROLS  !

. c .S Safety Class:IcInservice Inspection Program-Review,_-Sp'ecification

4.4.10.1.

ECCS Actuation,' Specifications 3.5.2-and 3.5.3.

~

3., < L d '. .

, ei- Fire Detection ~ Instrumentation,' Specification 3.3.3,7. q

" a

f. Fire Suppression Systems, Specifications 3.7.9.1, 3.7.9.2 : and l 3.7.9.4.

1 -

j

.g.- RCS Overpressure Mitigation, Specification 3.4.9.3.

R i

- h. Radiological Effluent Reports required Lby - Speci fications 3~.11=1.2,.3.11.2.2, 3.11.2.3 and 3.'11.4.

t

i. Degradation of -containment structure, Specification 4~.6.1.6.4.

c j.- Steam GeneratorLTube Inspection, Specification _4.4.S.1.5.  ;

ki Accident Monitoring: Instrumentation, Specification 3.3.3.8.

, 1. uRadiation Monitoring: Instrumentation, Specification 3.3.3.1.-

m . .. Reactor Coolant _-System Vents, Specification 3.4.11.- <j s

y ,

^

t

4;

-, j J

'I

. j

-MILLSTONE - UNIT 2 6-19(b) Amendment No. JfE