05000368/LER-1983-001-03, /03L-0:on 830106,during Mode 1,control Room Emergency Air Conditioner 2VE-1B Failed Surveillance Test Due to Excessive Compressor Cycling.Caused by Low Freon Due to Leak on Discharge Relief Valves.Valve Will Be Replaced

From kanterella
(Redirected from ML20028G609)
Jump to navigation Jump to search
/03L-0:on 830106,during Mode 1,control Room Emergency Air Conditioner 2VE-1B Failed Surveillance Test Due to Excessive Compressor Cycling.Caused by Low Freon Due to Leak on Discharge Relief Valves.Valve Will Be Replaced
ML20028G609
Person / Time
Site: Arkansas Nuclear 
Issue date: 02/01/1983
From: Rogers P
ARKANSAS POWER & LIGHT CO.
To:
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION IV)
Shared Package
ML20028G607 List:
References
LER-83-001-03L-01, LER-83-1-3L-1, NUDOCS 8302170136
Download: ML20028G609 (2)


LER-1983-001, /03L-0:on 830106,during Mode 1,control Room Emergency Air Conditioner 2VE-1B Failed Surveillance Test Due to Excessive Compressor Cycling.Caused by Low Freon Due to Leak on Discharge Relief Valves.Valve Will Be Replaced
Event date:
Report date:
3681983001R03 - NRC Website

text

,

NRC FORM 366 b

U.S. NUCLEAR REGULATORY CCMMISSION (7-77)

LICENSEE EVENT REPORT EXHIBIT A CONTROL BLOCK: l_l_l_i_l_l_11 (PLEASE PRINT OR TYPE ALL REQUIRED INFORMATION) 1 6

7 ~ I ~T l IT lA R I A l N I O I 2 12 9

l ITCEsSEE C05E- ~ 14 l010 1F --~1 - 1 0 1 0 1 0 1 0 l 0 l - l 0 1 0 13 l 4 l 1 1 1 1 1 1 1 14 l l

l5 8

LICENSE T MBER -"

-~ 75 2 I ITCEs5I T W E--30 57 CA H 8 7~-~1 ~1 1 SOURCE 6D-l6 l0 REPORT l L l0 - 0l0l013 6 1183 3 19 6I~1 5 1~66CIET EuT4BTl--l 8 17 l 0 i 1 1 0 l 6 I 8 !~~3 18 10l210l 8

68 69 7 VENT DXTE ~ 74 7F REPORT DAT I ~ 50 EVENT DESCRIPTION AND PROBABLE CONSEQUENCES 10 l111l lOn 1/6/83 while in Mode 1 at 100% full power, control room emeroency air conditioner 2VE-1B failed its l

l_T__ill (surveillance test because the compressor was cycling excessively. Redundant air conditioner 2VE-1A was t

l1111 lavailab;e and operable. 2VE-1B was returned to operable status within the time requirements of Technical l

l_Till ISpecification 3.7.6.1.

This occurrence is reportable per Technical Specification 6.9.1.9.b.

Other failures l

l1111 f relating to the control room emergency air c.onditioners were reported in LER's82-050, 81-040,81-007, 80-092, [

l1111 180-070,80-054, 80-026,79-026, 79-053 and 79-050.

I l7_.0._ i _8._ l l

1 8 9 80 SYSTEM

CAUSE

CAUSE COMP VALVE CODE CODE SUBCODE COMPONENT CODE SUBCODE SUBCODE ITill l_S_I G 111 l E 112 l B_l13 l_H_l T l E l1l C l H l14 l C l15 l Z l16 7

8 9

10 11 12 13 18 19 20 SEQUENTIAL OCCURRENCE REPORT REVISION LER/R0 l EVENT YEAR REPORT NO.

CODE TYPE NO 17 REPORT Ii813I l---l 1 0 l ~0 l 1 l l/l l0l 3l lLl l---l l 01 NUMBER l_21 22 23 24

--26 2F 28 29 3D-~

31~

32~

ACTION FUTURE EFFECT SHUTDOWN ATTACHMENT NPRD-4 PRIME COMP.

COMPONENT TMEN ACTION ON PLANT METHOD HOURS SUBMITTED FORM SUB SUPPLIER MANUFACTURER l X_l18 l 1 119 I Z l20 I Z 121 l_0_f 0 1 0 1 0 122 l Y_l23 1 1 124 l A l25 l C_l_7_I l l l l26 34 35 36 37 40 41_

42 43 44 47 33 CAUSE DESCRIPTION AND CORRECTIVE ACTIONS 27 lllT)

]The cause of the occurrence was low freon which resulted from a leak on the discharqe relief valves. It could l 1111l jnot be determined which relief valve was leaking because of the design of the discharge piping. A modificationt l1111 ito facilitate relief valve leakage identification is being considered. Spare relief valves were not available.1 11l11 IThe air conditioning unit '2VE-18) was recharged, tested and returned to service. The leaking relief valve l

11l_Tl lwill be replaced when spare valves are received. In the interim 2VE-1B will be checked weekly to (continued) l 7

8 9 80 FACILITY METHOD OF STATUS

% POWER OTHER STATUS DISCOVERY DISCOVERY DESCRIPTION l_1_lil

! E l29 l 1 1 0 1 1 129 i NA 130 l B_131 i Routine Surveillance 132 7

8 9 10 12 13 44 45 46 80 ACTIVITY CONTENT RELEASED OF RELEASE AMOUNT OF ACTIVITY LOCATION OF RELEASE l_1._l i l l_Z_l33 l 1 134 i NA 135 l NA 136 7

8 9 10 11 44 45 80 PERSONNEL EXPOSURES NUMdER TYPE

DESCRIPTION

l _1_ i _1,l l 0 1 0 1 0 137 l Z_l38 i NA (39 7

8 9 11 12_

13 80 PERSONNEL INJURIES NUMBER

DESCRIPTION

l _1._ l _8_ l l_0._[ 1 1 1 140 i NA l41 7

8 9 11 12 e0 LOSS OF OR DAMAGE TO FACILITY TYPE

DESCRIPTION

l_1_Ill 11142i NA

~ ']4J - 6 PUBLICITY ISSUED DESCRIPTION NRC USE ONLY l 2,_l,,ill l N,_l44 l NA 145 l_l_I,l_l_f_!_!_I_l_i_l_I IU 7

8 9

, ud 69 60 NAME OF PREPARER Patrick Rnners PHCNE: (501) 964-3100 8302170136 830201 PDR ADOCK 05000368 S

PDR

o

\\

l Page 1 of 1 LER No. 50-368/83-001/03L-0 Cause Description and Corrective Actions (Continued):

verify proper charge until repairs can be made.

I