LER 83-003/01T-0:on 821222,w/RCS in Mode 6,during Test on Diesel Generator Load Shedding,Five Relay Timers Found Exceeding Tech Spec Tolerance.Caused by Instrument Drift. Timers Recalibr on 830118 During Mode 3
ML20028F014
Person / Time
Site: Cook American Electric Power icon.png
Issue date: 01/19/1983
From: Palmer R
INDIANA MICHIGAN POWER CO. (FORMERLY INDIANA & MICHIG
To:
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION III)
Shared Package
ML20028F007 List:
References
LER-83-003-01T, LER-83-3-1T, NUDOCS 8301280354
Download: ML20028F014 (2)


Text

.. -_ _. .

LICENSEE EVENT REPORT CdNTROL BLOCK: I l l l l lh IPLEASE PIINT CR TYPE ALL REtulRED INFOIMATl!N)

o lile l9 MI !!LaCEN5tE 8

01 CCQOg l C 12 t@l 010 !- 1010101010 14 16 LsGEN54 NUMukd4 l- 10 l023 l@l a6 41LaGENbt il il 11 1l@lDJ 4l I $dIg TYPE JJ CON'T olil e

sEis LLJ@lOI 6J 68 5 l QQCKgTNuuggR 01010131116bdl@l11212121812 td tytNT DATE l@l J4 011111918 it REPORT DATE l 3tal@

EVENT DESCPIPTION AND PROBABLE CONSEQUENCES hio g l WITH THE RCS IN MODE 6. DURING A SURVEILLANCE TEST ON THE DIESEL GENERATOR LOAD SHED ,

,o,,,i DING, FIVE RELAY TIMERS WERE FOUND TO HAVE EXCEEDED THE TOLERANC8E ALLOWED BY TECHNICAL,

,o ,,,,; SPECIFICATION 4.8.1.1.2.c.2. THESE RELAY TILLERS WERE NOT RECALIBRATED UNTIL 1-18-83  ;

,o,s, , WHEN THE UNIT WAS IN MODE 3. THIS CONSTITUTED AN IN0PERABLE A.C. ELECTRICAL POWER ,

,O 9,,; SOURCE AS REQUIRED BY TECHNICAL SPECIFICATION 3.8.1.1.b. THE PUBLIC HEALTH AND ,

lo ! rl i SAFETY WERE NOT AFFECTED.  ;

ionii I Yoo'E ##

Co $E susC$5E COYPONENT CODE suBC Of s E l o l <> 1 lE I Gl@ l Al@ l C l@ IR IE IL lA l Yl Xl@ lM l@ lZ l@

Lin EVENTY AR REPORT O CODE Y N ,

O ,ag.;AO at

.;l I 813 I J2 l-l 23 I 01 01 31 24 26 y77 1011i 23 LTJ I-I LO_1 23 30 31 22 AKEN ACT ON O PLANT MET HOURS s a IT E F OR 49 S. SUPPL 1 MAN ACTURER lEl@lXl@

J3 J4 l2l@

h

[Zj@

J6 l 0101010 l 31 (Y l@ l42Y l@ Lgj@ lA l i l 0191{

40 43 43 44 47 CAUSE DESCRIPTION AND CORRECTIVE ACTIONS h

, , , o i l THE OUT OF SPECIFICATION VALUES OF THESE FIVE RELAY TIMERS (MANUFACTURED BY AGASTAT, i

i.,,,i fl0 DEL 7012) IS ATTRIBUTED TO INSTRUMENT DRIFT. ON 1-18-83 THE TIMERS WERE INDIVIDUAL ,

,,,,ji LY RETESTED WITH THREE OF THE FIVE RE1.AYS FOUND TO BE WITHIN THE ALLOWABLE LIMITS. ,

,,,3, l THE REMAINING TWO RELAYS WERE READJUSTED AND VERIFIED TO OPERATE WITHIN THE ALLOWABLE ,

,, ,.,i l LIf1ITS. (SEE ATTACHED SUPPLEMENT) l

'sTAN.Y .cowsR orscRsTATus @ o?sEC?vid i oiscovERv oEsCRiefioN @

^

is *l 'I Hl@ l '0 l 0 l 0i2l@ln NA l lB l@lSURVEILLANCE l u 4s 4 so Activity CO2reNr af LE ASED OF RELE ASE i is'l *l Zl @ ' l Z lg[ AMOUNT NA OF Activityl @ NA l LOCATION OF RELEASE @

l

, Rsewel exposers " " "

Nuveia rves orsemarioN @

i I 711010 l0 l@lZ l@l NA l etasowe'tiNau'les Nuvu R

' I ' I l 0 l 0 10 l@lcesCnierioN@ NA 4 9 11 12 SO l

' 5,'e ' "Es'C%A'd"'"@

t '

' i o l l Z j@l NA

~

l i

  • S 'u 8301280354 830119 '

' a0 es PDR ADOCK 05000 Nac usE cNLY S

2 l01 8 9 dsur @ l cesCniatios im i lI11!!!!!lIi11 10 68 69 80 5 mAuE or ,nePAnen R.A. N H ,goyg, 616-465-5901 4{ l

ATTACHMENT TO LER# 83-D03 -

SUPPLEMENT TO CAUSE DESCRIPTION THE OUT OF SPECIFICATION VALUSS OF THESE FIVE RELAY TIMERS (MANUFACTURED BY AGASTAT, MODEL 7012) IS ATTRIBUTED TO INSTRUMENT DRIFT. ON JANUARY 18, 1983, '-

THE TIMERS WERE INDIVIDUALLY RETESTED WITH THREE OF THE FIVE RELAYS FOUND TO BE WITHIN THE ALLOWABLE LIMITS. THE REMAINING TWO TIMERS: ESW PUMP 2E EXCEEDED THE MINIMUM ALLOWABLE TIME BY 0.37 SECONDS AND SI PUMP 2N EXCEEDED THE MINIMUM ALLOWABLE TIME BY 0.14 SECONDS DURING THE RETEST. THE TWO RELAY TIMERS WERE

! READJUSTED AND VERIFIED TO OPERATE WITHIN THE ALLOWABLE LIMITS.

l THE RELAY TIMERS HAD BEEN CALIBRATED PRIOR TO THE SURVEILLANCE TEST ON DECEMBER 22, 1982, AND LEFT WITHIN SPECIFICATION. PAST HISTORY ON THESE AGASTAT RELAY TIMERS IS THAT THE TIMERS DO NOT REPEAT THEIR SET TIME CONSIS-TANTLY. A CONSCIOUS DECISION WAS MADE BY THE SUPERVISOR IN CHARGE NOT TO RECALIBRATE THE RELAYS SINCE THEY HAD JUST BEEN CALIBRATED PRIOR 10 THE SURVEILLANCE TEST AND THE RECALIBRATION WOULD NOT ASSURE CONTINUED PERFORMANCE WITHIN REQUIRED TOLERANCES.

FRESENTLY AN ENGINEERING REVIEW IS BEING CONDUCTED ON A NEW TYPE OF SOLID l

STATE RELAY. DEPENDING ON THE RESULTS OF THIS REVIEW, THE EXISTING RELAY TIMERS MAY BE REPLACED.

l l