-NMP-0135
=
NIAGARA MOHAWK POWER CORPORATION /300 ERIE BOULEVARD WEST. $YRACUSE N.Y. 32C2/ TELEPHONE (315) 47 March 13, 1978 Ah. Boyce H. Grier Ditect.or Udted States Nuclear Regulatory Commission Region 1 631 Park Avenue ICb19 of Prussia, PA.
19406 RE:.Doche.t No. 50-220-1.E.Bulletin 78-03
Dear Ah. Grier:
1.
In accordance with 1.E.Bulletin 78-03, Operations and Maintenance Procedures have been reviewed.to assure proper operation of be Of f-Gas Sys. ten in accordance with all design parme.ters.
Maintenance Procedwtes are being revised to include apptopria.te caution sta.tenents.
2.
Any Leaks in.the Off-Gas System in piphg or components up to and hcLuding the mixing jet will be into the Turbhe Building. These scilt be diluted by.the Turbine Bu. idling Ven.tilation Systen prior
.to behg released in the stack.
There ate no confhed spaces where
.the hydrogen can collec.c and reach explosive concenttalion.s.
Operating Procedures preciude bypassing the recombiners.
3.
No spaces or areas were iden.tified.
4.
From.the mixing jet 2.0 the vacuum pump,.the system is under a slight vacuum.
Titis condition atteviates any po.tential ptoblems from Leaks or Loop seats.
5.
Procedures for response.to Off-Gas Sys. ten explosions are adequate to insure ptoper operator action.
VeAy stuly youns, YF R.R. Schneider Vice Presiden.t Electtic Production I