ML20028C454

From kanterella
Jump to navigation Jump to search
Comments on Div of Operating Reactors Proposed Action on Prevention of Offgas Explosions Per IE Bulletin 78-03,in Response to 790130 Request.Concern Re Location of Instrument Readouts at Facility Expressed
ML20028C454
Person / Time
Site: 05000000, Cooper
Issue date: 02/07/1979
From: Madsen G
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION IV)
To: Jordan E
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE)
Shared Package
ML20027A594 List: ... further results
References
FOIA-82-545 IEB-78-03, IEB-78-3, NUDOCS 8301100204
Download: ML20028C454 (1)


Text

w.

~~

y;?

i a'

4 n ateo UNITED STATES

/

/ja o

NUCLEAR REGULATORY COMMISSION h

2.p' o

REGION IV

=*

a

"'" f E

611 RYAN PLAZA DRIVE, SUITE 1000

,f' b'

/ f )/FY

\\,

/

February 7, 1979 w -z17 MEMORANDUM FOR:

E. L. Jordan A/D for Technical Programs, IE.

FROM:

G. L. Madsen, Chief, RO&NS Branch, RIV

SUBJECT:

INFORMATION REGARDING PROPOSED 00R ACTION ON PREVENTION OF 0FFGAS EXPLOSIONS

~

In response to your request of January 30, 1979, same subject, the follow-ing comments are provided for your consideration.

Region IV has completed the followup inspections for Bulletin 78-03. We have only one concern with the offgas system instrumentation at Cooper Station and that relates to the location of the instrument readouts. The offgas system is well instrumented for. flows, terrperatures, pressures, and gas concentrations; however, the readouts are located in the Augmented Offgas Control Room (A0CR) in the radwaste building. An annunciator alarm from one of these parameters would give a master alarm in the main control room but as the A0CR is not continuously manned, there would be a reaction time delay.

.'j.$ h b c l.a. < -

G. L. Madsen, Chief, Reactor Operations and Nuclear Support Branch (7001100204 821207 PDR FOIA HIATT02-545 PDR l