ML20024F567

From kanterella
Jump to navigation Jump to search
Notice of Violation from Insp on 830426-0525
ML20024F567
Person / Time
Site: Catawba 
Issue date: 07/11/1983
From:
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II)
To:
Shared Package
ML20024F526 List:
References
50-413-83-12, NUDOCS 8309090477
Download: ML20024F567 (1)


Text

.,.

g 48 APPENDIX A NOTICE OF VIOLATION Duke Power Company Docket No. 50-413 Catawba 1.

License No. CPPR-116 As a result of the inspection conducted on April 26.- May 25, 1983, and in accordance with the NRC Enforcement Policy, 47 FR9987 (March 9, 1982), the following violation was identified.

10 CFR 50, Appendix B, Criterion V, as implemented by Topical Report Duke 1A, Section 17, paragraph 17.1.5 requires that activities affecting quality r

be accomplished in accordance with established drawings.

Duke Power. Company Drawing No. ICS-A-20.3, Rev. 6 requires that functionally redundant safety class instrument lines for nuclear safety related instruments meet the physical separation criterion of 18-inches minimum.

Contrary to the,above, an activity affecting quality was not accomplished in accordance with! established drawings on April 13, 1983 in that the installed

' safety class instrument lines for nuclear safety related instrument Loop Nos. ISM 511 and ISM 514 were found to be separated by several inches rather than by the minimum required 18-inches.

This is a Severity Level-IV Violation (Supplement II).

Pursuant to the provisions of 10 CFR 2.201, youJare hereby required to submit to this office within thirty days of the date of this Notice, a wrJtten statement or explanation in reply, includirig:

(1) admission or denial of the alleged viola-tion; (2) the reasons for the violation if admitted; (3) the corrective steps which have been taken and the results achieved; (4) corrective steps which will

be taken to avoid further violations; and (5) the date when full compliance will be achieved. Consideration may be given to extending your response time for good

~cause shown.

Date.JUL 1 1 1983 1.

i 1

/

4.

8309090477 830831 PDR ADOCK 05000413 0

PDR s

.