February 20, 1990
.Mr'.^A. Freund, Director Water Management Section.
J Department of Environmental Protection
+
s
'122 Washington ~ Street Hartford, CT 06106 -
Dear Mr.:
Freund -
i m
.Haddam Neck Station.
gi E
NPDES Permit No. CT0003123 1
Noncomoliance Report
- t 4
~ Northeast < Utilities :. Service - Company (NUSCO), - on behalf of Connecticut Yank'ee; a
- Atomic Power: Com)any (CYAPCO), herein submits = the :following written report of-noncompliance wit 1 the. NPDES Permit No. CT0003123'for CYAPC0's Haddam Neck Station-L
'in accordance. with of-Section 22a-430-3(j)(11)(D) 'of the DEP's regulations.
The:
w);:exceedance was reported by telephone to Mr. Robert Kaliszewski, DEP Water Compli-4 ance Unit, on February'7, 1990.
On January 3; 1990;' the value-for iron of 3.12:mg/l-for Discharge Serial Number j
- 001-E,sWaterxTreatment Waste - Liquid Tank ' Discharge, exceeded the. maximum permit'
- limit 1of 1.0'mg/1.w Also,- the value for total oil and grease of 16 mg/l. exceeded' "i
o L
- theimaximum' permit 11mit of.15 mg/1.
The iron exceedance is believed to have occurred ~ fromt corrosion -in the s system - duringJ an extended ' shutdown.
The grab Lsample was taken from the collection. sump located _ before the pump suction and final. filter. - Had the ' sample been taken at _. its1 normal? sample _ point afteri the a
filter, the total. iron would have been below the: permit limit.
It is believed a
that the cause of the total oil and grease exceedance-was due.to a dirty oil / water rseparator.
p In' order to: prevent a reoccurrence, the established sampling procedure for Dis-charge Serial No.: 001-E will be reviewed with appropriate personnel.-
The-3
. oil / water separatorLis presently being inspected and cleaned as required.
Should'you have any questions, please call Mr. Thomas J. Kenny, NUSCO - Production 10peration Services, at (203) 665-5137.
m Very truly yours NORTHEAST UTILITIES SERVICE COMPANY As Agent for Connecticut Yankee Atomic Power Company
.)