05000311/LER-1981-087, Forwards LER 81-087/03L-0.Detailed Event Analysis Encl

From kanterella
(Redirected from ML20010G429)
Jump to navigation Jump to search
Forwards LER 81-087/03L-0.Detailed Event Analysis Encl
ML20010G429
Person / Time
Site: Salem 
Issue date: 09/09/1981
From: Midura H
Public Service Enterprise Group
To: Haynes R
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION I)
Shared Package
ML20010G430 List:
References
NUDOCS 8109210076
Download: ML20010G429 (3)


LER-1981-087, Forwards LER 81-087/03L-0.Detailed Event Analysis Encl
Event date:
Report date:
3111981087R00 - NRC Website

text

- ______-. _

O PSEG Pub ic Service Electric and Gas Company P.O. Box 168 Hancocks Bridge, New Jersey 08038 Salem Generating Station September 9, 1981 ik9'If97 [N

Mr.

R. C.

Haynes 8

Director of USNRC j

[8 SgN t. \\

Office of Inspection and Enforcement

-)j Region 1 gg

/O 631 Park Avenue y

/

~!

King of Prussia, Pennsylvania 19406

/

Dear Mr. Haynes:

/

LICENSE NO. DPR-75 DOCKET NO. 50-311 REPORTABLE OCCURRENCE 81-87/03L Pursuant to the requirements of Salem Generating Station Unit No. 2 Technical Specifications, Section 6.9.1.9.b, we are submitting Licensee Event Report for Reportable Occurrence 81-87/03L.

This report is required within thirty (30) days of the occurrence.

Sincerely yours,

/

<!lw J H.

J.

Midura Manager - Salem Generating Station CC:

R. A.

Uderitz General Manager - Nuclear Production Director, Office of Inspection and Enforcement (30 copies)

Director, Office of Management Information and Program Control (3 copies)

[

8109210076 810909 PDR ADOCK 05000311 S

PDR hl (

The Energy People 95 2189 (12 5M) 1180

/,

~

Report Number:

81-87/03L f

Report Date: 9-81 l

Occurrence Date:

8-12-81 Facility:-

Salem Generating-Station, Unit'2l Public. Service Electric & Gas. Company i

Hancocks Bridge, New Jersey 08038 l

IDENTIFICATION OF' OCCURRENCE:

28-Volt D.C. Battery Charger - Inoperable.

This re: port was-initiated by Incident Report 81-324.

CONDITIONS PRIOR TO OCCURRENCE:'

- Mode 1 - Rx Power 80% - Unit Load 840 MWe i'

a DESCRIPTION OF OCCURRENCE:

t i

1 j

On August 12,. 1981, during a routine surveillance, it was discovered.

1 l

that 2B1 battery. charger would not pick up the 28-volt d.c. electrical load. -At 0420 hours0.00486 days <br />0.117 hours <br />6.944444e-4 weeks <br />1.5981e-4 months <br />, 2B1 battery charger was declared inoperable, Land action statement 3.8.2.5 was entered.

This occurrence constituted operation in a degraded mode in accordance

[

with technical specification 6.9.1.9.b.

4 DESIGNATION OF APPARENT CAUSE OF OCCURRENCE:

2B1 battery charger-would not pick up the-electrical load-because the

}

high voltage cut-out had actuated.

4 I

ANALYSIS OF OCCURRENCE:

4 -

3 f

Technical specification 3.8.2.5 requires:

With one 28-volt d.c. battery charger inoperable, restore the inoperable charger tr operable status within 2 hours2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br />,

[

- or connect the backup charger'for no more than 7 days, or-be in at'least' hot standby within the next 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> and in cold shutdown within the following'30. hours.

1

CORRECTIVE ACTION

I

'TheLbackup battery charger was connected within.2 hours2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br /> as required by technical specification.

The high voltage cut-out had actuated and-i.

was reset.

The battery charger was tested ratisfactorily and-returned i

to service.

Action statement 3.8.2.5 was terminated at=1010 hours, August 12, 1981'.

t i

1 1

~.. ~,.. - -... _., ~,. _

~ _. -... - _ _.. _ -. _. _ - _ _ _. _,. _ _. _, _,. _.. - _. - _ _. -. _ - -, _. -.. -. -

LER:81-87/03L _

[

I FAILURE DATA:

Not Applicable 4

1 Prepared By F. Dickey

/*

Manager -: Sal'em Generating Station-

- SORC Pe(ting No.

81-88 4

'(

e 9

I i

i t

i l

4 I

l c

l l

l l

i

_,_n,

,.,-n

,.- e. -,,,,

n.-.,,,am,.v,.,,,m_,na.,,.,.,-,..m.

,n.,

en-

-+.

- n..