Lc2 GD-RW9/8 l-09 puhuc service company e conoude 16805 ROAD 19%

PLATTEVILLE, COLORADO 80651 t

July 2, 1981 Fort St. Vrain Unit No. 1 P-81180 h- (fb ' 2 u

Mr. Karl V. Seyfrit, Director ges- ~

]B" g ?., T \\

Nuclear Regulatory Commission

~

p# p

})

Region IV a

8' Office of Inspection and Enforcement [7

611 Ryan Plaza Drive p

Suite 1000 Arlington, Texas 76012 W

Re fe rence : Facility Operating License No. DP R-34 Docket No. 50-267

Dear Mr. Seyf rit:

Enclosed please find a copy of Reportable Occurrence Report No. 50-26,.81-040, Final, submitted per the re<;virements of Technical Specificatio.

AC 7.5.2(b)2.

Also, please find enclosed one copy of the Licensee Event Report for Reportable Occurrence Report No. 50-267/81-040.

Very truly yours,

]Wu Don Warembourg Manager, Nuclear Production DW/cls Enclosure cc: Director, IEPC S

///

8107280292 810702 PDR ADOCK 05000267 S

PDR l

e

~. ~.... - -

e OCCURRENCE REPORT DISTRIBUTION Number of Copies De pa r t men t o f E ne r gy - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -

1 (P Letter)

San Francisco Operations Of fice Attn: California Pater: Group 1333 Broadway Oakland, California 94612 1

(P Letter)

Department of EnergI Mr. Glen A. Newby, Chief liTR Brar.ch Division of Nuclear Power Developnent Mail Station B-107 Washington, D.C.

20545 De pa r tme nt o f Ene r gy - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -

1 (P Letter)

Attn: Project Manager 113 West A Street, Suite 460 San Diego, California 92101 (Original of P Letter Mr. Karl V. Seyfrit. Director Region IV and Copy i;f LER)

Office of Inspection and Enforcement Nuclear Regulatory Commission f.1. Ryan Plaza Drive Suite 1000 Arling.on, Texas 76012 Director - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -

1 (P Letter, LER)

Office of Management information and Program Control U. S. Nuclear Regulatory Commission Washington, D.C.

20555 Mr. Richard ?halps - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 10 (Original of FPLO 1etter iSV, CA, Site plus Two Copies One Representative Copy of P letter, One Ceneral Atomic Company Copy of LER)

P. O. Box 426 Platteville, Colorado 80651 P r. B il l Lava lee - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -

1 (P !.etter, LER)

Nuclear Safety Analysis Center 3412 'fillview Avenue P. O. Box 10412 Palo Alto, California 94Y 1

(P Letter, LER)

JRC Resident Site Inspe cto r Y

~

REPORT DATE:

July 2, 1981 REPORTABLE OCCURRENCE 81-040 ISSUE O OCCURRENCE DATE:

June 4, 1981 Page 1 of 3 FORT ST. VRAIN NUCLEAR GENERATING STATION PUBLIC SERVICE COMPANY OF COLORADO 16805 WELD COUNTY ROAD 19 1/2 PLATTEVILLE, COLORADO 80651 REPORT NO. 50-267/81-040/03-L-0 Final

DENTIFICATION OF OCCURRENCE

Between June 4 and June 9, 1981, eight hydraulic shock suppressors (snubbers) were found to be out of oil and therefore, inoperable.

Since reactor operation had occurred during the surveillance interval, this is reportable as a degraded mode of LCO 4.3.10 per Fort St. Vrain Technical Specification AC 7.5.2(b)2.

EVENT

DESCRIPTION

The following is a table of events for the situation:

Date Event June 4, 1981 Snubbers HRS-104, HRS-357, and MSS-118 found to be out of oil and inoperable.

June 5, 1981 Snubbers BFS-142 and BFS-405E found out of oil and inoperable.

i June 9, 1981 Snubbers BFS-142E, BFS-532, and BFS-556 found out I

of oil and inoperable.

l l

CAUSE

DESCRIPTION:

The loss of oil from the snubber reservoirs was found to be due to leaky seals and 0-rings.

REPORTABLE OCCURRENCE 81-040 ISSUE O Page 2 of 3 CORRECTIVE ACTION:

The corrective actions for the eight snubbers is as follows:

BFS-142 - Replaced reservoir gaskets, tested, and filled with oil.

BFS-532 - Cleaned, replaced seals and 0-rings, tested, and filled with oil.

BFS-556 - Cleaned and replaced seals, 0-rings, and gaskets. Filled with oil.

BFS-142E - Cleaned and replaced seals and 0-rings.

Filled with oil.

BFS-405E - Replaced reservoir seal gaskets and filled with oil.

HRS-104 - Replaced 0-rings anc filled with oil.

HRS-357 - Filled with oil.

MSS-118 - Cleaned and replaced seals and 0-rings. Filled with oil.

Because eight snubbars were found inoperable, the surveillance interval was adjusted to 31 days per SR 5.3.8(a).

No further corrective action is anticipated or required for the eight snubbers described in this report.

REPORTABLE OCCURRENCE 81-040 ISSUE 0 Page 3 of 3 Prepared By:

Asa B. Reed g Technical Services Technician Reviewed By: I M1Wa.td i

L. M. McBride l

Technical Servicas Manager

/

/

Reviewed By:

- E6 Jib /D."Rfi l Operatior.. Manager Approved By:

a b W a x_e M Don Warembourg g

Manager, Nuclear Production