/03L-0:on 810522,emergency Feedwater Ultrasonic Flowrate Indicator FW-313-FT Was Discovered in Fault Condition & Would Not Reset.Caused by Failed Power Supply Board in Transmitter.Board Replaced
ML20005A302
Person / Time
Site: Crystal River Duke Energy icon.png
Issue date: 06/23/1981
From: Hernandez V
FLORIDA POWER CORP.
To:
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II)
Shared Package
ML20005A299 List:
References
LER-81-029-03L, NUDOCS 8106300172
Download: ML20005A302 (2)


LER-1981-029, /03L-0:on 810522,emergency Feedwater Ultrasonic Flowrate Indicator FW-313-FT Was Discovered in Fault Condition & Would Not Reset.Caused by Failed Power Supply Board in Transmitter.Board Replaced
Event date:
Report date:
3021981029R03 - NRC Website

text

{{#Wiki_filter:(~ -- ss tn ' t.lCENSEE EVENT AE.: ORT EXHI3IT /. e@ tr. tA:s sau.r':.o ;v:e n., at:.ints. acawancus courac si.::.te 1 1 I I I I l j e lo e il l? l Li C ?.} ?! 3_gl 0 l 01-l 0 l 0 0 l 0 0 l -l0 l 0 gj !+ l 1l 1l1 l]g; l ig l 1 1 , caua,. us a . :2 a :..s a 4 _. o uciuse::: i. a w C:N"" Josil 3 5 2;2:B i 1 GL ol 6 I2 13 '8 31 !@ 0 ,'f,y l L g! O f SI C i -to i 310 [ 2 gl I M 8 COCa 47 %vsga ed ta

4. g an ; ; a rg
4 r3 age;e?;a;g 3;

r.va:rt:mn:4Ah:smerAst.2::ss1:vtscIs@ (o TT1 l At 0705 during normal operation, it was discovered that Emergency Feedwater Ultra- . [~oTTl [, sonic Flowrate Indicator W-313-FT was in the fault condition and would not reset. 9 Maintenance was initiated and go..,g This created a condition contrary to T.S. 3.7.1.2. There was no effect upon the health or safety of , operability was restored at 1345. This was the first occurrence of this type,and this is the , the general public. ninth event reported under this Specification. i nosil i; 1 8 9 C:v* vasvg ca SI 371 t.u CA ts,, <= c m,=, m...e,,, =, m,,, m. 3=, l3,.i i ci nl@ [Ejg g@ lIl NI Sl Tg Rl U[g g gg o,,c;.~,.m n .T .<.m~ c ce... c=, sc: P ang... l8l1l g l 01219l kl l 013 l W [_ _,1 lyl u c... m., ar _s, zz u u u u a a sa 2,

z

'CN Ms cW5r 5;ni?r ^5,^5c;;;;' t"t,

- l.t.=y

,.,c:;p:2;,, eu.,gI If l@ lAl@ ici6T216lc W@@@ I Zl@ ,1, I I I ( c.aust cas::wncn.An c:matcnvg Acncss @ g l The cause of th'is event is attributed to a failed power supply board in the trans-

,,,jg mitter. The board was replaced. Long term corrective action will be to replace the, M I Ultrasonic [ low Transmitter with a conventional flow transmitter.

This will be p g accomplished concurrently with major Emergency Feedwater System modifications present]y ,,,,3 g scheduled for 1983. ',Iciun n..>: :n.c

..cu..:uw..-,@

o c.~. me-cr.. n., W [_Fj@ [ ll O! Ol@l NA l [Al@i Operator observation l u u .4 n s,a,,,,, eg.,,, 7 aggg43g av;VNT cs a;*1vsfy (gc a? cs ce e g.,3 aj g I' I C L2f @3 C8 AIL!affL21@l NA l l NA _I I .9 la et as es 33 plato, sag tascsbe g3 ervis e t s Tv*t ts:eec, l81,ll 40l0l@lZlgj NA p e =,,,,,,,,r, mci. a vvtte t s ca* **'C E, I a 0-10 l@l NA l u a

  • C5 Ce 04 S ava,*.I **J 8&C uT*

T**% D 6 L;ser*e 181911 3 @l NA ] n u c: iei D j e ;l7,7.... g - s e ei = o ~ NA l ll ll 1Ii iiiii "Name of Preparer: gg

  • css. (90!.

798-%S6 (siz Aruc:En sumen?z Ix? ops.-{cs s=n m es.., es o. I 1 y y

.. m.,

- e 2.

3 SUPPLEMENTARY INFORMATION j Report No.: 50-302/81-029/03L-0 Facility: Crystal River Unit 3 Report Date: June 23, 1981 Occurrence Date: May 22, 1981 Id:ntification of Occurrence: Emergency Feedwater Ultrasonic Flowrate Indicator was inoperable contrary to Technical Specification 3.7.1.2. Conditions Prior to Occurrence: Mode 1 power operation (100%). De:cription of Occurrence: At 0705 during normal opcration, it was discovered that FW-313-FT, Emergency Feedwater Ultrasonic Flow Indicator was in the fault condition and would not reset. Maintenance was initiated,and opera-bility was restored at 1345. Designation of Apparent Cause: The cause of this event is attributed to a failed power supply board in the flow transmitter. An01ysis of Occurrence: There was no effect upon the health or safety of the general public.

Corrective Action

The board was replaced. Long term corrective action will be to replace the ultrasonic flow transmitter with a conventional flow transmitter. This will be accomplished concurrently with major Emergency Feedwater System modifications presently scheduled for 1983. Failure Data: This was the first occurrence of this type,and this is the ninth event reported under this Specification. /rc }}