05000336/LER-1981-017-02, /03L-0:on 810427,during Routine Operations,Safety Injection Tank Level Transmitter Indicated Normal Level W/High Level Alarm Present.Caused by Instrument Drift. Recalibr Restored Proper Level in Indication

From kanterella
(Redirected from ML20004B971)
Jump to navigation Jump to search
/03L-0:on 810427,during Routine Operations,Safety Injection Tank Level Transmitter Indicated Normal Level W/High Level Alarm Present.Caused by Instrument Drift. Recalibr Restored Proper Level in Indication
ML20004B971
Person / Time
Site: Millstone 
Issue date: 05/22/1981
From:
NORTHEAST NUCLEAR ENERGY CO.
To:
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION I)
Shared Package
ML20004B964 List:
References
LER-81-017-02L, LER-81-17-2L, NUDOCS 8106010367
Download: ML20004B971 (1)


LER-1981-017, /03L-0:on 810427,during Routine Operations,Safety Injection Tank Level Transmitter Indicated Normal Level W/High Level Alarm Present.Caused by Instrument Drift. Recalibr Restored Proper Level in Indication
Event date:
Report date:
3361981017R02 - NRC Website

text

u. s. nuut L e.n n L ouua mv w....w.v.,

.m LICENSEE EVENT REPORT ONTROL BLOCK: l l

l l

l l

lh (PLEASE PRINT OR TYPE ALL REQUIRED INFORMATION) l 6

@ C lT l Ml Nl Sl 2 l@l 0 l 0 l - l 0 l0 l0 l0 l0 l-l0 l0 ]@l 4 l 1 l 1 l 1l 1 l@

l l@

8 9 LICENSEE CODE 14 15 LICENSE NUVBER 25 26 LICENSE TYPE JO 57 CAT 58

@]

SO I Li@l0 5 l 0 l 0 l 0 l 3 l 3 l 6 l@l0 l4 l2 17 18 11 l@[0151212

. O'4* T 68 69 EVENT DATE 74 75 REPOHT o ATE 80 60 61 DOCKET NUMBER 8

EVENT OESCRIPTION AND PROB ABLE CONSEQUENCES h I

gg l During routine operations, the A Safety Injection Tank (SIT) Level transmitter was A calibration check and l

g l indicating normal level with a high level alarm present.

In j

g l t-eadjustment of the transmitter revealed actual level to be 58.3 percent.

o g i accordance with Technical Specificaticas section 3.5.1, action a, the tank was I

Time in the action statement was approximately 1

gg i mmediately drained to 57.7% level.

i TTO l 15 minutes.

Similiar Events:

LER's 77-48, 79-26, 81-13.

[

l a l8) I Su' ESC 70'ESEOE C0Se' 58e#"$oE COuPONENT COor C

g lS lF j@ gg l E l@ lI lN lS lT lR j U j@ [T j@ [Z j @

COOE 8

9 10 11 12 f3 18 19 20 REVISION SEQUENTIAL OCCURRENCE REPORT EVENT YE A R REPORT NO.

COOE TYPE N O.

O lEE R/RO 1811 l l--J 10 11 17 1 M

1013J LL_J l-1 LOJ jgj

_ 21

??

23 24 26 27 28 29 30 38 32 KE A

ON ON PLANT ET HOURS SUB IT D FOR [UB.

SU PLI MANUFA TURER LE_j@[Z_J@

LZ_J@

LZ_j@

10 1 01 01 01 lNJ@

LYj@

[Nj@

lG l 0 l 8 l 0 l@

33 34 35 36 37 40 41 42 43 44 47 CAUSE DESCRIPTION AND CORRECTIVE ACTIONS i

121011 The cause of the erroneous level indication was found to be instrument drift i li J l causing indicated level to be lowet than actual.

Recalibration restored oroner I

1 I

(, i2) I level indication.

L I

, Is) I I

.1 I 4 I l 80 STA S

% POWE R OTHE R STATUS OISCO A DISCOVERY CESCRIPTION 1 ls j [Ej@ l1 l 0 l 0 l@l NA l

U @l Operator Observation j

8

'8 A!TiviTY 8

CO TENT LOCATION OF RE'.E ASE li lc l [Zj @ [Zj@l NA l

l NA l

f. ELE ASED OF RELE ASE AMOUNT OF ACTIVITY PERSONNEL EXPOS ES NOURER TYPE OFSCRIPTION l

- 2171101 I

l@LZJ@l NA 80 PE f tSONNE L INJUHIES Nu

DESCRIPTION

y i lR i l 0 gun 10l@l NA 80 2

8 9 31 12 Wn '

",SC,, Slo '^c'" @

  • "^

p Io f Lzj@l NA 8 C to 9

NRQE Pun.ca r

,iOipfj'g"i L

810 6 010Jo7 69 69 go. ;