4-O ATTACHMENT I PROPOSED TECHNICAL SPECIFICATION CHANGE RELATED TO SAFETY / RELIEF VALVE SETPOINTS 4

s 4

i I

i i

POWER AUTHORITY OF THE STATE OF~NEW YORK JAMES A..FITZPATRICK NUCLEAR POWER PLANT DOCKET NO. 50-333 MARCH-26, 1981 P

810.4030 % 9i

JAFNPP 1.2 ItEACTOR COOLANT SYSTEM 2.2 REACTOR C00LAffr SYSTEM APPLICABILITT:

. APPLICABILITY:

Applies to limits on reactor coolant Applies to trip settings of the instru-ments and devices which are provided to system pressure.

prevent the reactor coolant system safety limits from being exceeded.

ORJECTIVE:

OBJECTIVE:

To establish a limit below which the To define the level of the process variables at which automatic protective integrity of the Reactor Coolant System action is initiated to prevent the safety is not threatened due to an overpressure limits from being exceeded.

condition.

SPECIFICATION:

SPECIFICATION:

1.

The Limiting Safety System setting 1.

The reactor coolant system pressure shall not exceed 1.325 psig at any shall be specified below:

time when irradiated fuel is present A.

Reactor coolant high pressuit scram in the reactor vessel.

shall be 5 1,045 psig.

B.

Reactor coolant system safety / relief valve nominal settings shall be as follows:

Safety / Relief Valves l

3 valves at 1090 psig 2 valves at 1105 usig l

6 valves at 1140 osia The allowable setpoint error for each safety / relief valve shall be + 1 percent.

l 27 Amendment No. N, /l, 43

-