05000339/LER-1981-010-03, /03L-0:on 810113,w/unit at 100% Power,Overspeed Trip of Turbine Driven Auxiliary Feedwater Pump Occurred During Surveillance Testing.Caused by Failure of Turbine Governor to Control Speed.Governor Was Replaced

From kanterella
(Redirected from ML19343C052)
Jump to navigation Jump to search
/03L-0:on 810113,w/unit at 100% Power,Overspeed Trip of Turbine Driven Auxiliary Feedwater Pump Occurred During Surveillance Testing.Caused by Failure of Turbine Governor to Control Speed.Governor Was Replaced
ML19343C052
Person / Time
Site: North Anna Dominion icon.png
Issue date: 02/11/1981
From: Cartwright W
VIRGINIA POWER (VIRGINIA ELECTRIC & POWER CO.)
To:
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II)
Shared Package
ML19343C044 List:
References
LER-81-010-03L, LER-81-10-3L, NUDOCS 8102180530
Download: ML19343C052 (1)


LER-1981-010, /03L-0:on 810113,w/unit at 100% Power,Overspeed Trip of Turbine Driven Auxiliary Feedwater Pump Occurred During Surveillance Testing.Caused by Failure of Turbine Governor to Control Speed.Governor Was Replaced
Event date:
Report date:
3391981010R03 - NRC Website

text

..

LICENSEE EVENT REPORT CONTROL BLOCK / / / / / / / (1)

(PLEASE PRINT OR TYPE ALL REQUIRED INFORMATION)

/0/1/

/V/A/N/A/S/2/ (2)

/0/0/-/0/0/0/0/0/-/0/0/ (3)

/4/1/1/1/1/ (4)

/ / / (5)

LICENSEE CODE LICENSE NUMBER LICENSE TYPE CAT LL/ (6)

/0/5/0/0/0/3/3/9/

(7)

/0/1/1/3/8/1/ (8) /0/2/1/1/8/1/ (9)

E DOCKET NUMBER EVENT DATE REPORT DATE EVENT DESCRIPTION AND PROBABLE CONSEQUENCES (10)

/0/2/

/

On January 13, 1981, with Unit 2 at 100 percent power, an overspeed trip of

/

/0/3/

/

the turbine driven auxiliary feedwater pump occurred during surveillance

/

/0/4/

/

testing. This event is reportable pursuant to T.S. 6.9.1.9.b.

Two redundant /

/0/5/

/

motor driven auxiliary feedwater pumps were operable. The action statement of /

/0/6/

/

the LC0 was met.

The public health and safety were not affected.

/

I

/0/7/

/

/

/0/8/

/

/

SYSTEM

CAUSE

CAUSE COMP.

VALVE CODE CODE SUBCODE COMPONENT CODE SUBCODE SUBCODE

/0/9/

/H/H/ (11) LE/ (12) LB/ (13) /M/E/C/F/U/N/ (14) LZ/ (15)

/Z/ (16)

SEQUENTIAL OCCURRENCE REPORT REVISION LER/R0 EVENT YEAR REPORT NO.

CODE TYPE NO.

(17) REPORT NUMBER

/8/1/

/-/ /0/1/0/

/\\/

/0/3/

/L/

/-/

[0/

ACTION FUTURE EFFECT SHUTDOWN ATTACHMENT NPRD-4 PRIME COMP. COMPONENT TAKEN ACTION ON PLANT METHOD HOURS SUBMITTED FORM SUB. SUPPLIER MANUFACTURER LC/ (18) LZ/ (19) LZ/ (20) LZ/ (21) /0/0/0/0/ (22) LY/ (23) LN/ (24) /A/ (25) /W/2/9/0/ (26)

CAUSE DESCRIPTION AND CORRECTIVE ACTIONS (27)

/1/0/

/

The turbine governor failed to control the turbine speed properly. The cause /

/1/1/

/

of the governor failure was not determined.

The governor was replaced and

/

/1/2/

/

the turbine driven auxiliary feedwater pump was returned to operable status

/

/1/3/

/

after being tested in accordance with T.S. and IWP requirements.

/

/1/4/

/

/

FACILITY METHOD OF

/(

} DISCOVERY DISCOVERY DESCRIPTION (32)

STATUS

% POWER OTHER STATUS

/1/5/

LE/ (28)

/1/0/0/ (29) /

NA

/B/ (31)

/ SURVEILLANCE TEST

/

ACTIVITY CONTENT RELEASED OF RELEASE AMOUNT OF ACTIVITY (35)

LOCATION OF RELEASE (36)

/1/6/

[Z/ (33)

LZ/ (34) /

NA

/

/

NA

/

PERSONNEL EXPOSURES NUMBER TYPE DESCRIPTION (39)

/1/7/ /0/0/0/ (37) /Z[ (38) /

NA

/

PERSONNEL INJURIES NUMBER DESCRIPTION (41)

/1/8/ /0/0/0/ (40) /

NA

/

LOSS OF OR DAMAGE TO FACILITY TYPE

DESCRIPTION

/1/9/

/Z/ (42) /

NA

/

PUBLICITY ISSUED DESCRIPTION (45)

NRC USE ONLY

/2/0/

/N/ (44) /

NA

/////////////

NAME OF PREPARER W. R. CARTWRIGHT PHONE (703) 894-5151 810 2 J.806 3 0