Text

'Af M

e4izi4ss-sooo f,U,$lT"*

February 23, 1981 f 5719 Director of Nuclear Reactor Regulation United States Nuclear Regulatory Commission Attn:

Mr. Steven A. Varga, Chief Operating Reactcrs Branch No. 1 Division of Licensic.g Washington, DC 20555

Reference:

Beaver Valley Power Station, Unit No. 1 Docket No. 50-334, License No. DPR-66 ESF Reset - Additional Information Gentlemen:

In recent discussions with Messrs. J. T. Beard and D. Chaney of your staff, Duquesne Light Company has agreed to the following actions concerning resetting of the main feedwater and bypass regulating valves after a feed-water isolation signal. As a short term action, procedures will be reviewed and revised, as necessary, to require placing the controllers in manual and resetting the valves to the closed position. On-shift training will be provided to the operators for the procedure changes. The permanent corrective action will be to revise the control circuitry to prevent the valves from returning to their pre-trip position on resetting the ESF signal. This modification will be installed at the next scheduled refueling outage.

If you have any questions, please contact my office.

Very truly yours,

/

l -

C. N. Dunn Vice President, Operations cc:

D. A. Beckman, Resident Inspector g

U.S. Nuclear Regulatory Commission

.s

{Q{\\l Beaver Valley Power Station g

Shippingport, PA 15077 U.S. Nuclear Regulatory Commission gpy,Q 3 'nb

~

,- )

Washington, DC 20555 8d' p*35#ocavo" Q g/

c/o Document Management Branch co n

g y

3 N

d

/s ai\\

g o

81os o s

$61

~

-